Table 17: Entity concept parameters for 2-channel MTL787SP barriers with
diode return (figures 29, 30 and 31 and notes 6 to 9)
Table 18: Entity concept parameters for two-channel MTL700P barriers with an
optional ground return (figure 31 and notes 6 to 9)
Table 19: Entity concept parameters for two-channel MTL700P barriers with separate ground returns (figure 30 and notes 6 to 9)
19
INM700-10 June 2005
Barrier Groups Voc Isc Each channel Each channel
model No. (V) (mA) Ca (µF) La (mH)
MTL
707P+ (return) C, E 14.1 0 2.85 1000
707P+ (return) D, F, G 14.1 0 7.62 1000
707P+ (signal) C, E 26.4 160 0.49 6.21
707P+ (signal) D, F, G 26.4 160 1.31 11.5
761Pac A, B 9.0 25 4.89 54.8
761Pac C, E 9.0 25 14.6 194.0
761Pac D, F, G 9.0 25 39.1 475.0
766Pac A, B 11.5 149 1.87 1.25
766Pac C, E 11.5 149 5.63 7.16
766Pac D, F, G 11.5 149 15.0 13.4
Figure 29 Figure 30 Figure 31
Model
No. Groups Voc Isc Ca La Voc Isc Ca La Voc Isc Ca La
(MTL) (V) (mA) (µF) (mH) (V) (mA) (µF) (mH) (V) (mA) (µF) (mH)
787SP A, B 28.9 115 0.13 2.70 25.9 110 0.17 2.93 28.9 115 0.13 2.70
(28V ch) C, E 28.9 115 0.39 11.52 25.9 110 0.51 12.3 28.9 115 0.39 11.52
D, F, G 28.9 115 1.06 22.57 25.9 110 1.38 24.3 28.9 115 1.06 22.57
787SP A, B – – – – 25.9 0 0.17 1000 – – – –
(diode ch) C, E – – – – 25.9 0 0.51 1000 – – – –
D, F, G – – – – 25.9 0 1.38 1000 – – – –
Barrier Groups Voc Isc Ca La
model No. (V) (mA) (µF) (mH)
MTL
707P+ C, E 27.4 160 0.45 6.21
707P+ D, F, G 27.4 160 1.20 11.5
761Pac A, B 18.0 50 0.43 14.4
761Pac C, E 18.0 50 1.29 53.0
761Pac D, F, G 18.0 50 3.46 119.0
766Pac A, B 23.0 297 0.22 0.20
766Pac C, E 23.0 297 0.66 1.72
766Pac D, F, G 23.0 297 1.77 3.39
Note 1: The hazardous-location-mounted equipment may be switches or ther-
mocouples. Other apparatus such as RTDs, LEDs, non-inductive
resistors, (and strain-gauge load cells for the systems shown in figures 32 and 33), may be used if the auto-ignition temperature of the
hazardous location is greater than T4 (275°F, 135°C). For the systems shown in figures 28, 29 and 30, certified devices with the correct entity concept parameters can also be used.
Note 2: The non-hazardous location or control-room mounted equipment
should not use nor generate more than 250V rms.
Note 3: For guidance on the installation see ANSI/SA RP 12.6.
Note 4: Five MTL700 Series barriers are approved for installation in Group F:
MTL705, 707, 708, 787S and 758. All MTL700P Series barriers
are approved for Group F.
Note 5: Full details of all approved combinations are available on MTL
drawing No. SCI-88
Notes 6 to 9 inclusive relate to tables 16 to 19 inclusive
Note 6: The barriers are associated apparatus and, when mounted in an
appropriate enclosure can be installed in the following areas:
a) Non-hazardous locations
b) Class 1, Division 2, Groups A, B, C, and D hazardous locations
c) Class II, Division 2, Groups F and G hazardous locations
d) Class III, Division 2 hazardous locations
Note 7: Barriers must be installed in enclosures meeting the requirements of
ANSI/ISA–S82
Note 8: Use Factory Mutual Research Corporation approved dust-tight enclosures
appropriate for environmental protection for the following locations:–
a) Class II, Division 2, Groups F and G hazardous locations
b) Class III, Division 2 hazardous locations
Note 9: For installation guidance see ANSI/ISA 12.6 and the National
Electrical Code. See also Installation drawing SCI–326
Notes 10 to 14 inclusive relate to table 15
Note 10: The non-hazardous (safe) location equipment must not generate or
use voltages in excess of 250V rms. or dc
Note 11: The hazardous location equipment. Any number of FMRC approved
devices which meet the power and entity parameter requirements
below may be connected to the Fieldbus:a) All device's electronic circuitry which interface directly to the
fieldbus must be powered from fieldbus power. Other power
sources in the devices (if any) must be galvanically isolated from the
fieldbus power.
b) Vmax of all devices must be equal to or greater than 22V.
c) Imax of all devices must be equal to or greater than 233mA.
d) Pmax of all devices must be equal to or greater than 1.18W.
e) The sum of all devices unprotected input capacitance Ci, plus
the cable capacitance must be equal to or less than Ca for the applicable Gas Group in Table 15.
f) The sum of all devices unprotected input inductance Li, plus the
cable inductance must be equal to or less than La for the applicable
Gas Group in Table 15.
Note 12: For guidance on installation see ANSI/ISA RP12.6 and the USA
National Electric Code.
Note 13: The barrier must be installed in enclosures meeting the requirements
of ANSI/ISA – S82
and the USA National Electric Code.
Note 14: Use FMRC – approved, or NRTL – listed, dust – ignition proof enclo-
sures appropriate for environmental protection in Class II, Division
2, Groups F and G, and Class III Hazardous Locations.
7.9 Final check
After completing the installation, each item contained in the checklist
(table 8) should again be checked out by a competent person,
preferably someone who has not been involved in the work.
8 MAINTENANCE
Since the MTL700/700P Series barriers are encapsulated they cannot
be repaired, but provided they are connected correctly to the circuits
they are intended to protect, and provided those circuits are not
themselves defective, barrier defects are unlikely to occur. For these
reasons, servicing of barrier installations consists principally of the
routine inspection and earth testing described in this section.
If replacements do have to be fitted however it is worth checking, in the
case of barriers connected directly to power supplies, if one of the new
overvolt-protected models can be substituted. These models can
tolerate supply voltages up to 35V dc without blowing their fuses, and
can therefore eliminate the problem of poorly regulated supplies.
Further information about the maintenance of barrier installations is
given in BS 5345: Part 4: 1977, Section 4.
8.1 Routine inspection
At intervals of not more than two years (more frequently for particular
environments), visually check the barrier installation to check the
following points.
When undertaking these checks, personnel should comply with all the
regulations relating to the safety of the plant and personnel. Great care
must be taken to prevent any direct interconnection between hazardous
and non-hazardous (safe) area circuits. The instructions given in section
4 of this manual should be observed at all times.