MTL Instruments MTL5099 Specifications

MTL5099 DUMMY
Unused hazardous­area cores
3 2 1
6 5 4
7 8 9
10 11 12
13 14
Unused safe-area cores
ISOLATOR
The MTL5099 is used with other MTL5000 Series units to provide termination and earthing facilities for, unused cable cores from hazardous areas.
Safe areaHazardous
Terminal Function
1 Hazardous-area core 2 Hazardous-area core 3 Hazardous-area core 4 Hazardous-area core 5 Hazardous-area core 6 Earth 7 Safe-area core 8 Safe-area core 9 Safe-area core 10 Safe-area core 11 Safe-area core 12 Safe-area core
MTL5000 SERIES COMMON SPECIFICATION
Connectors
Each MTL5000 unit is supplied with signal and power connectors, as applicable. When using crimp ferrules for the hazardous and non-hazardous (safe) signal connectors the metal tube length should be 12mm and the wire trim length 14mm. For the power connectors the metal tube length should be 10mm and the wire trim length 12m m. See INM5000 for recommended ferrules.
Isolation
250V rms between input, output and power supply terminals, tested at 1500V rms minimum between safe- and hazardous-area terminals. MTL5073, output and power supply not isolated.
Location of units
Safe area
Terminals
Accommodate conductors of up to 2.5mm2 stranded or single­core
Mounting
On 35mm (top hat) rail to : EN 50022–35 x 7.5; BS 5584; 35 x 27 x 7.3 DIN 46277
Ambient temperature limits
–20 to +60°C (–6 to +140°F) operating –40 to +80°C (–40 to +176°F) storage
Humidity
5 to 95% relative humidity
Weight
110g approx (except where indicated)