The MTL2215 enables either one or two separate IS circuits in a
hazardous area to be relay-contact controlled by a single on/off
switch or logic signal in a safe area. Applications include the
calibration of strain-gauge bridges, changing the tone of an IS
sounder, the testing of IS fire alarms, and the transfer of safe-area
signals into an annunciator with IS input terminals not segregated from
each other. The output-relay contacts are certified as ‘non-energystoring’ apparatus, and can be connected to any IS circuit without
further certification, provided that separate IS circuits are such that
they would still remain safe if connected together.
MTL2215 SWITCHOPERATED RELAY
IS-output
All contacts shown in alarm condition (relay de-energised)
Changing tone of IS sounder
MTL2215
MTL2215
MTL2241
Inputting IS annunciator from safe area
Sound
alarm
SPECIFICATION
See also ‘Common specification’
Number of channels
One, fully floating
Location of control circuit
Safe area
Input/output characteristics
Relay energised if <27kΩ or <1V applied
Relay de-energised if >54kΩ or >2V applied (50V maximum)
Hysteresis, nominal: 16kΩ or 0.6V
Power supply failure protection
Relay de-energised if supply fails
Response time
50ms, nominal
Contacts (suitable for connection to IS circuits)
2-pole changeover
Contact rating (non-IS applications)
250V,5A,500VA (ac), resistive loads, reactive loads must be
suppressed
250V,5A,250W (dc), resistive loads, reactive loads must be
suppressed
Contact life expectancy (non-IS applications)
2 x 105operations at maximum load
LED indicator
ON when relay energised
Consumption
0.9 to 1.4W (ac versions)
60mA (24V dc version)
Ambient temperature limits
–20 to +55°C (all versions, close packed)
–20 to +60°C (all versions, at least 5mm apart)
–40 to +80°C (all versions, storage)
Safety description (each channel)
Non-energy-storing apparatus: relay contacts may be
connected to any certified IS circuit in Zone 0 without further
certification
Note: The 2-pole changeover contacts may be used to switch separate IS
circuits only if these remain intrinsically safe when interconnected, since the
two sets of relay contacts are not segregated from each other.
Change
tone
Annunciator
with IS
inputs
Switch
+
1
2
IS
sounder
L
N
L
N
L
N
Hazardous area
Safe area