MTL Instruments MTL2215 Data sheet

EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283 AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899 ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997 E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com
June 2004
The MTL2215 enables either one or two separate IS circuits in a hazardous area to be relay-contact controlled by a single on/off switch or logic signal in a safe area. Applications include the calibration of strain-gauge bridges, changing the tone of an IS sounder, the testing of IS fire alarms, and the transfer of safe-area signals into an annunciator with IS input terminals not segregated from each other. The output-relay contacts are certified as ‘non-energy­storing’ apparatus, and can be connected to any IS circuit without further certification, provided that separate IS circuits are such that they would still remain safe if connected together.
MTL2215 SWITCH­OPERATED RELAY
IS-output
All contacts shown in alarm condition (relay de-energised)
Changing tone of IS sounder
MTL2215
MTL2215
MTL2241
Inputting IS annunciator from safe area
Sound alarm
SPECIFICATION
See also ‘Common specification’
Number of channels
One, fully floating
Location of control circuit
Safe area
Input/output characteristics
Relay energised if <27kor <1V applied Relay de-energised if >54kor >2V applied (50V maximum) Hysteresis, nominal: 16kor 0.6V
Power supply failure protection
Relay de-energised if supply fails
Response time
50ms, nominal
Contacts (suitable for connection to IS circuits)
2-pole changeover
Contact rating (non-IS applications)
250V,5A,500VA (ac), resistive loads, reactive loads must be suppressed 250V,5A,250W (dc), resistive loads, reactive loads must be suppressed
Contact life expectancy (non-IS applications)
2 x 105operations at maximum load
LED indicator
ON when relay energised
Consumption
0.9 to 1.4W (ac versions) 60mA (24V dc version)
Ambient temperature limits
–20 to +55°C (all versions, close packed) –20 to +60°C (all versions, at least 5mm apart) –40 to +80°C (all versions, storage)
Safety description (each channel)
Non-energy-storing apparatus: relay contacts may be connected to any certified IS circuit in Zone 0 without further certification
Note: The 2-pole changeover contacts may be used to switch separate IS circuits only if these remain intrinsically safe when interconnected, since the two sets of relay contacts are not segregated from each other.
Change tone
Annunciator with IS inputs
Switch
+
1
2
IS sounder
L
N
L
N
L
N
Hazardous area
Safe area
1 2 3 4
5 6
+ 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+
IS relayIS relay
10 11 12 13 14 15 16
10 11 12 13 14 15 16
10 11 12 13 14 15 16
+
9
+
9
+
9
+
+
+