MTL Instruments MTL1211 Data sheet

DRAFT - 03 August 2017
Technical data
MTL signal conditioners
MTL1211 switch / proximity detector
with line fault detection
The MTL1211 is a single channel switch or proximity detector isolator with the option to select line fault detection or a repeat output. Switches are used to select phase reversal or the repeat output.
Power for this module is supplied via the power bus embedded in the DIN rail in conjunction with the power bus accessories.
Terminals Function
1 Input (+)
2 Input (-)
5 Output
6 Output
August 2017 EPS1211 rev 3
Terminals Function
680Ω
22kΩ
7 Repeat Output / LFD alarm
8 Repeat Output / LFD alarm
D Power supply -ve
E Power supply +ve
MTL1211
+
_
On
LFD PR
+24V
Output
Repeat/LFD
SPECIFICATION
See also common specification
Number of channels
Location of equipment
Input signal
Voltage to sensor
Input/output characteristics
Relay characteristics
Response time
Line fault detection (LFD) when used
LED indicators
Power supply voltage.
Maximum current consumption
Power dissipation within unit
Isolation
One, with fully floating input and outputs
Safe area
Dry contact or inputs conforming to BS EN60947-5-6:2001, standards for proximity detectors (NAMUR)
7-9V dc from 1kΩ ±10%
Normal Phase - Output closed if input >2.1mA (<2kΩ in input circuit), Output open if input <1.2mA (>10kΩ in input circuit). Hysteresis 200µA (650Ω nominal)
Contact rating: 250V ac, 2A cosØ >0.7, 340V dc, 2A resistive load
20mS
User selectable via switches on the side of the unit. Line faults are indicated by an LED. The Output relay is
de-energised if an input line fault is detected.
Open-circuit alarm on if Iin <50uA, Open-circuit alarm off if Iin >250uA
Short-circuit alarm on if Rin <100Ω, Short circuit alarm off if Rin >360Ω
Note: resistor must be fitted when using LFD with contact inputs 500Ω to 1kΩ in series with the switch and
20kΩ to 25kΩ in parallel with the switch.
Green: power indication, Yellow: Channel status, on when relay energised Red: LFD status, on when line fault detected
18V to 32V DC
16mA at 24V dc
0.4W at 24V
250V ac or dc functional isolation between power, field and system circuits. (Tested to 1100Vac) 1500V between relay contacts and other circuits
Eaton Electric Limited, Great Marlings, Butterfield, Luton Beds, LU2 8DL, UK. Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283 E-mail: mtlenquiry@eaton.com www.mtl-inst.com
© 2017 Eaton All Rights Reserved Publication No. EPS 1211 rev 3 030817 August 2017
1