MTL Instruments MTL1000 Operating Manual

DRAFT - 08 August 2017
Instruction manual
MTL signal conditioners
November 2018 INM 1000 Rev 8
MTL1000 range
Signal conditioning interfaces
DRAFT - 08 August 2017 DRAFT - 08 August 2017
DECLARATION OF CONFORMITY
A printed version of the Declaration of Conformity has been provided separately within the original shipment of goods. However, you can find a copy of the latest version at http://www.mtl-inst.com/certificates
ii
DRAFT - 08 August 2017 DRAFT - 08 August 2017
CONTENTS
DECLARATION OF CONFORMITY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
1 INTRODUCTION. . ...................................................................1
1.1 General .................................................................................1
2 MTL1000 RANGE DESCRIPTION .......................................................1
2.1 Modules ................................................................................1
2.2 Accessories .............................................................................2
3 INSTALLATION PRECAUTIONS ........................................................3
3.1 General .................................................................................3
3.2 Installation ..............................................................................3
3.2.1 Modules ...........................................................................3
3.2.2 Cabinet and enclosure mounting .........................................................3
4 COMMON SPECIFICATIONS ..........................................................4
5 MODULES .........................................................................5
5.1 MTL1991 Power feed and alarm module .......................................................5
5.2 Current repeaters .........................................................................5
5.2.1 MTL1141 Transmitter repeater power supply ..................................................5
5.2.2 MTL1142 Transmitter repeater power supply with HART .........................................6
5.2.3 MTL1143 Transmitter repeater power supply with HART and repeat output ..........................6
5.2.4 MTL1144 voltage/current input, loop powered isolator ...........................................7
Table 1 MTL1144 switch settings
5.2.5 MTL1145 loop powered current repeater .....................................................7
5.3 MTL1171, 1172 Temperature and MTL1173 Potentiometer converters ................................8
Table 2 Configuration and DIP switch settings
Table 3 MTL1171 and MTL1172 range DIP switch setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
5.3.1 MTL1171 thermocouple input converter .....................................................10
5.3.2 MTL1172 RTD input converter .............................................................10
5.3.3 MTL1173 Potentiometer input converter .....................................................10
5.4 MTL1211 Switch / Proximity Detector input ....................................................11
5.5 MTL1249 Current / Voltage input/output repeater ...............................................11
Table 4 MTL1249 Dip Switch settings
5.6 MTL1271 loop powered thermocouple input converter ...........................................13
5.7 MTL1272 loop powered RTD temperature converter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6 MTL13XX TRIP AMPLIFIERS .........................................................14
6.1 Introduction ............................................................................14
6.2 Trip level Setting .........................................................................14
6.3 Label Indicators / Switches .................................................................14
6.4 Switch settings ..........................................................................15
Table 1 Trip switch settings . . . . . . . . . . . . . . . . . . . . . .
Table 2 Trip switch MTL137x Configuration and DIP switch settings . . . . . . . . . . . . . . . . . . . . . .
Table 3 MTL1371 and MTL1372 range DIP switch settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5 MTL1321 trip amplifier with voltage/current input and 4-20mA output ...............................15
Table 4 MTL1321 SW101 range switch settings . . . . . . . . . . . . . . . . . . . . . .
6.6 MTL1321 trip amplifier with voltage/current input and 4-20mA output . . . . . . . . . . . . . . . . . . . . . .
6.7 MTL1371 trip amplifier converter, thermocouple input/4-20mA output
6.8 MTL1372 trip amplifier converter, RTD input/4-20mA output
6.9 MTL1373 trip amplifier converter, Potentiometer input/4-20mA output
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
. . . . . 15
. . . . . 15
. . . . . . . . . . . . . . . . . . . . 16
. . . . . . . 17
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 17
. . . . . . . 17
. . . . . . . .17
iii
DRAFT - 08 August 2017 DRAFT - 08 August 2017
7 MAINTENANCE ...................................................................14
7.1 Routine Maintenance .....................................................................14
7.2 Enclosures .............................................................................14
8 APPENDIX A ......................................................................14
Table 1 Isolator current consumption for MTL1991 calculation @ 24V . . . . . . . . . . . . . . . . . . . . . . . . . . 15
iv
DRAFT - 08 August 2017 DRAFT - 08 August 2017
IMPORTANT NOTE
This manual describes the installation and use of:
• MTL1000 range of isolating interfaces and accessories.
The MTL1000 products are designed to provide signal isolation and signal conversion between equipment and areas of a process plant.
WARNING!
This equipment must be installed, operated and maintained only by trained
competent personnel and in accordance with all appropriate international, national
and local standard codes of practice and site regulations for process connected
apparatus and in accordance with the instructions contained here.
The following methods are used on the product and in this manual to alert the user to important information:-
Caution - read the instructions
Caution - hot surface
v
DRAFT - 08 August 2017 DRAFT - 08 August 2017
MTL1000 range - signal conditioning interfaces
1 INTRODUCTION
1.1 General
This instruction manual describes the procedures for installing, connecting, checking and maintaining MTL1000 range of isolating interfaces and accessories. The MTL1000 products are designed to provide signal isolation and signal conversion between equipment and areas of a process plant.
Signal isolation eliminates or reduces the risk of earth loops, surges and noise, all of which can result in loss of signal integrity or damage to equipment. In addition, some modules offer the ability to convert signal types to provide level compatibility between system components.
2 MTL1000 RANGE DESCRIPTION
The MTL1000 range of modules and accessories is designed for use with process connected systems. It consists of compact isolating interface modules mounted on 35mm DIN rail. Power is provided through a DIN rail mounted power bus, to which, the isolator module is plugged into when clipped onto the DIN rail. Power is supplied to the isolators via a dedicated power feed module which also provides current limit protection in the event of a fault.
The MTL1000 range modules provide power and status information via LEDs on the top of the module. Where
module configuration is required, then switches are accessed by the user through the side cover.
2.1 Modules
The table below lists the modules in the MTL1000 range:
MTL1991 Power feed and alarm module
MTL1141 Transmitter repeater power supply
MTL1142 Transmitter repeater power supply with HART passthrough
MTL1143 Transmitter repeater power supply with HART passthrough and repeat output
MTL1144 V/I to current repeater, loop powered
MTL1171 Thermocouple input converter
MTL1172 Resistance temperature device (RTD) converter
MTL1173 Potentiometer input converter
MTL1271 Thermocouple input converter, loop powered
MTL1272 RTD converter, loop powered
MTL1211 Switch / Proximity detector input
MTL1249 Signal converter, V/I to V/I
MTL1341 Transmitter repeater with 2ch trip
MTL1321 Trip amplifier with voltage/current input
MTL1371 Trip amplifier with Thermocouple input
MTL1372 Trip amplifier with RTD input
MTL1373 Trip amplifier with Potentiometer input
1
DRAFT - 08 August 2017 DRAFT - 08 August 2017
2.2 Accessories
PBUS6.2 DIN rail power bus connector for 2
module positions (pack of 10)
PBUS6.2
PBUS17.5 DIN power rail bus connector for 1 module position
(pack of 10)
PBUS17.5
PBUS02
PBUS03 Module end stop
PBUS03
TH1000
TH1300
THR2
2
DRAFT - 08 August 2017 DRAFT - 08 August 2017
3 INSTALLATION PRECAUTIONS
3.1 General
This equipment must be installed, operated and maintained only by trained competent personnel
and in accordance with all appropriate international, national and local standard codes of practice
and site regulations for apparatus and in accordance with the instructions contained here.
3.2 Installation
3.2.1 Modules
All modules are DIN rail mounted in conjunction with the power bus connector. The power bus
must be installed on the DIN first with the required number of slots for the modules that will be
fitted. Each power bus connector powers 2 isolators. The MTL1991 power feed module, if used,
will occupy one position. This may be located in any position. Power may be connected directly
to the bus using the PBUS02 connector set. These are screw terminals that plug directly into the
power bus at either end of the bus. The power supply should be of the transformer isolated type
to obtain the secondary isolation required for SELV.
Modules are mounted on the DIN rail by clipping the foot, furthest from the release clip,
on to the DINrail first. Rotate the module down onto the DIN rail and clip into place (Fig.1).
To release, use a flatbladed screwdriver to release the module clip (Fig 2), hold module and
rotate clip upwards. (Fig.3)
Fitting module to DIN rail Release clip Module removal
Fig. 1 Fig. 2 Fig. 3
3.2.2 Cabinet and enclosure mounting
The MTL1000 modules must be installed in a cabinet or enclosure with an impact rating of
at least 6.5J. Consideration must be given to the management of the internal temperatures.
Space must be provided around the modules to allow airflow. The optimum transfer of heat
is attained when the DIN rail is mounted horizontally but vertical DIN rails may also be
used where adequate space is available, especially in larger cabinets. Principle sources of
heat, such as power supplies, should be located above the modules. An enclosure depth,
measured from the base of the DIN rail, of at least 150mm is recommended. The absolute
minimum is 115mm.
CAUTION
Exercise care when removing modules in operation from the middle of a
group as the surface temperature on the side faces may be hot.
3
DRAFT - 08 August 2017 DRAFT - 08 August 2017
4 COMMON SPECIFICATIONS
For individual product specifications please refer to individual product specification sheets.
Terminals
Screw clamp. Conductors of up to 13AWG / 1.8mm dia. stranded or single-core copper.
Max torque 0.4Nm to 0.6Nm. Cable insulation strip /ferrule length 6-8mm
PBUS02 use wire type Solid / Stranded, 28 – 16 AWG / 0.14-1.3mm dia, – copper
Power supply voltage
18V to 32V DC SELV (UL listed where UL is applicable)
Isolation
250V ac or dc between power, field and system circuits.
tested to 1100Vac)
Mounting
T-section 35mm DIN rail (7.5mm or 15mm) to EN 50022
Ambient temperature limits
-20 to +60°C (-6 to +140°F) operating
-40 to +80°C (-40 to +176°F) storage
Humidity
5 to 95% relative humidity
Altitude
<2000m
Weight
6.2mm modules 120g
17.5mm modules 130g
EMC
EN61326 and NE21* Class A equipment
* For 20mS power interruption compliance, a suitable power supply must be used.
Dimensions
100 mm
112 mm
111 mm
6.2 mm
Fig. 1 MTL1000
4
112 mm
111 mm
Fig. 2 MTL1300
100 mm
17.5 mm
DRAFT - 08 August 2017 DRAFT - 08 August 2017
¾
5 MODULES
5.1 MTL1991 power feed and alarm module
The MTL1991 module is required to feed power to a group of MTL1000 range modules via the DIN rail power bus. Each power feed module provides reverse voltage protection and power monitoring. The power monitor relay provides a dry contact output which may be used for connection into a monitoring system or local indicator.
The number of isolators connected to any one power feed module must be assessed for power consumption. The maximum load current when feeding power via terminal 5 is 1A. If redundant power inputs are not required then terminal 6 may be used and a maximum load current of 2 A is acceptable. Check current consumption table in Appendix A for details. If power is fed directly into terminal 6 and external 3A time delay fuse must be fitted. Alarm relay contact rating is 40Vrms ac/dc 0.5A, resistive.
Where redundant power feeds are required, two MTL1991 modules are fitted with one power feed on each. The maximum load current is 1A.
MTL1991
ALARM
1
2
D E
5
6
2A
7
Vs+
Bus supply output
Vs-
V+ supply input 19-32V dc 1A
Direct V+ supply input (max 2A)
V- supply input
5.2 Current repeaters
5.2.1 MTL1141 transmitter repeater power supply
Before installing this modules check the connection requirements on the ‘system’ side of the module. The output may be configured to source or sink current. Current source is used when the input to the system is passive, ie there is no power supply present and it presents a resistive load. Current sink is used mainly with a ‘2 wire’ transmitter input to the system where ‘loop power’ and ‘input’ terminals are provided. Terminal 6 on the MTL1141 is connected to the transmitter supply, and terminal 5 to the input. See Fig.4. Switch SW1 on the module must be set prior to installation. The module is supplied with the switch set in ‘source’ mode.
MTL1141
SW1
Source output
5 +
4-20mA
6
-
Sink output
5
-
6
+
Load
­Power
+
turn
SW1
Source - Sink
Label side of module
Fig. 4 Fig. 5
5
DRAFT - 08 August 2017 DRAFT - 08 August 2017
5.2.2 MTL1142 transmitter repeater power supply with HART
Before installing this modules check the connection requirements on the ‘system’ side
of the module. The output may be configured to source or sink current. Current source
is used when the input to the system is passive, i.e. there is no power supply present
and it presents a resistive load. Current sink is used mainly with a ‘2 wire’ transmitter
input to the system where ‘loop power’ and ‘input’ terminals are provided. Terminal
6 on the MTL1142 is connected to the transmitter supply, and terminal 5 to the input.
Switch SW1 on the module must be set prior to installation. The module is supplied
with the switch set in ‘source’ mode. HART communications are passed with both
settings. In source mode the input impedance on the system input must be >240Ω for
HART compliance.
SW1
Source - Sink
Load
Output
PWR
+
-
MTL1142
Tx+
1
+
­Input
2
Com
3
D E
Vs- Vs+
5
6
+
4-20mA
-
5.2.3 MTL1143 transmitter repeater power supply with HART and repeat output
Before installing this modules check the connection requirements on the ‘system’ side
of the module. Output 1 is configured to source current into a load and provide HART
communications passthrough.
Output 2 on terminals 7 and 8 generates a repeat 4-20mA signal to another device. This
output provides a 4-20mA ‘source’ current to the system input. HART communication
is not provided via this output.
An active current source may also be applied via terminals 2 and 3. HART
communications are not provided when operating in this mode.
Load
-
+
MTL1143
PWR
+
-
6
Tx+
1
+
­Input
2
Com
3
D E
Vs- Vs+
5
+
4-20mA
6
-
7
+
4-20mA
8
-
Load
Load
Output 1
Output 2
DRAFT - 08 August 2017 DRAFT - 08 August 2017
5.2.4 MTL1144 voltage/current input, loop powered isolator
The MTL1144 provides an interface to convert voltage or current signals into 4-20mA for connection to a system analogue input. Switches are used to select the required input range. The input terminals are chosen depending on signal type, 1 and 2 for voltage input and 2 and 4 for current input.
The maximum load resistance is dependent on the available power supply voltage. Max load = 50(Vs-17)
System AI
2 wire Tx
system input
MTL1144
V
1
2
I
I
V/I
4-20mA
I
+
5
I
-
6
Limit
Load
+24V Tx Power
-ve
Return
CAUTION
Do not connect a low impedance voltage source to terminals 2 and 4, damage
may result.
Note: Signal source must be isolated from mains supply.
Table 1
MTL1144 switch settings
DS1 DS2 DS3 Input Output
OFF OFF OFF 0-1V
ON OFF OFF 0-5V
OFF ON OFF 0-10V
ON ON OFF 1-5V
OFF OFF ON 0-20mA
ON OFF ON 4-20mA
OFF ON ON 0-100mV
4-20mA
7
DRAFT - 08 August 2017 DRAFT - 08 August 2017
5.2.5 MTL1145 loop powered current repeate2
The MTL1145 can be used for both input and output applications. It is primarily
designed for use with analogue outputs and loop powered from the system
output. Power is taken from the analogue output signal to power the isolator. HART
communication passthrough is not provided by this module.
Current Source
(Analogue Outpt /Input)
I/P converter
/ AI Load
MTL1145
System AO
O/P+
O/P-
System AI
+
-
Alternatively the module can be used in a current sink mode where an analogue output
in the field can be connected to pass a signal into a system input. Power is taken from
the Transmitter power connection on the system and the signal is fed back through the
system input load to 0V.
Current Sink
(Analogue Input)
2 wire
Tx
MTL1145
Input
Power
Input +
System AI
V source
Channel
0V / Return
(24V)
Input
Notes: Greater accuracy is provided when operating in Current Source mode.
Signal source must be isolated from mains supply.
8
DRAFT - 08 August 2017 DRAFT - 08 August 2017
5.3 MTL1171, 1172 temperature and MTL1173 potentiometer converters
MTL117x
DS1
SW1
DS10
The MTL1171, for thermocouples and MTL1172, for RTD, convert low level temperature inputs to 4-20mA. The MTL1173 is for a potentiometer input. Input type and range setting is performed using switches on the side of the module.
The sensor types and wire break detection are selected using switches DS 1-4 and a selection of popular ranges is available using switches DS 6-9. See tables 1 and 2.
Current output, voltage output or current sink output is available on the system terminals by wiring to the appropriate terminals as shown and setting SW1 to the appropriate position.
Source Sink
SW1
LED indicators show the power and field input status
Condition Green (PWR) Red (STS)
Power ON/ Normal ON OFF Power Low Voltage OFF OFF
Field Open circuit ON Flashing
Module failure ON ON
Configuration and DIP switch settings
Model Input type DS1 DS2 DS3 DS4 DS5
Type Wire Break Wire Break Drive Trip 1 Trip 2
MTL1x71 THC J Off / K On
ON/OFF
MTL1173 POT -
ON = Upscale
OFF = Downscale
N/A N/AMTL1x72 RTD 4W Off 3W On
Table 3
MTL1171 and MTL1172 range DIP switch setting
Range THC/RTD DS6 DS7 DS8 DS9 DS10 0 to 100°C 0 0 0 0 - 0 to 150°C 0 0 0 1 - 0 to 200°C 0 0 1 0 - 0 to 350°C 0 0 1 1 - 0 to 500°C 0 1 0 0 - 0 to 650°C 0 1 0 1 -
0 to 800°C 0 1 1 0 - 0 to 1000°C
0 1 1 1 -
(RTD max 850°C)
-10 to 50°C 1 0 0 0 -
-50 to 50°C 1 0 0 1 -
-50 to 100°C 1 0 1 0 -
-50 to 150°C 1 0 1 1 -
-50 to 250°C 1 1 0 0 -
-50 to 350°C 1 1 0 1 -
-200 to 600°C 1 1 1 0 - Special (Reserved) 1 1 1 1 -
Note: Cycle power supply after setting switched
9
DRAFT - 08 August 2017 DRAFT - 08 August 2017
5.3.1 MTL1171 thermocouple input converter
For Type J or K thermocouples. Cold junction compensation is provided by the MTL1171.
Switch settings select open wire detection and up/down scale drive.
MTL1171
5.3.2 MTL1172 RTD input converter
For PT100 RTD sensors. Switch settings select 3 or 4 wire connection and open wire
detection with up/down scale drive.
MTL1172
5.3.3 MTL1173 potentiometer input converter
Potentiometer Input. Switch settings select open wire detection with up/down scale drive.
Potentiometer
input
MTL1173
1
3
4-20mA
1-5V
System AI
Current
2 wire Tx
system input
input
Source Sink
+
5
-
62
+
7
-
8
+
-
+
Channel
-
Load
Voltage
input
SW1
Load
Limit
-ve
Return
+24V Tx
Power
ED
+24V
10
DRAFT - 08 August 2017 DRAFT - 08 August 2017
MTL1211
Output
Repeat/LFD
+24V
+
_
680Ω
22kΩ
On
LFD PR
MTL1249
ED
5
6
2
1
7
8
+
-
+
-
Load
System AI
+
-
Current
input
Voltage
Channel
input
+24V Tx Power
Limit
2 wire Tx
system input
-
+
SW1
Source Sink
Load
-ve
Return
+24V
V/I
V/I
I
V
V
I
I
5.4 MTL1211 Switch / Proximity Detector input
Switch or proximity detector isolator with the option to select line fault detection or a
repeat output Switches are used to select phase reversal and the repeat output or LFD
alarm output .
5.5 MTL1249 Current / Voltage input/output repeater
The MTL1249 is a single channel signal conditioner which can accept voltage or current
inputs and provide a voltage or current output. The signal levels are selected by the user
using switches on the module as shown in the table 3.
11
DRAFT - 08 August 2017 DRAFT - 08 August 2017
Table 4 MTL1249 Dip Switch settings
INPUT DS1 DS2 DS3 DS4 DS5 DS6 INPUT
OFF OFF OFF OFF OFF OFF 0-1V
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
Current
Voltage
ON OFF OFF OFF OFF OFF 0-5V
OFF ON OFF OFF OFF OFF 0-10V
ON ON OFF OFF OFF OFF 1-5V
OFF OFF ON OFF OFF OFF 0-20mA
ON OFF ON OFF OFF OFF 4-20mA
OFF ON ON OFF OFF OFF 0-1V
ON ON ON OFF OFF OFF 0-5V
OFF OFF OFF ON OFF OFF 0-10V
ON OFF OFF ON OFF OFF 1-5V
OFF ON OFF ON OFF OFF 0-20mA
ON ON OFF ON OFF OFF 4-20mA
OFF OFF ON ON OFF OFF 0-1V
ON OFF ON ON OFF OFF 0-5V
OFF ON ON ON OFF OFF 0-10V
ON ON ON ON OFF OFF 1-5V
OFF OFF OFF OFF ON OFF 0-20mA
ON OFF OFF OFF ON OFF 4-20mA
OFF ON OFF OFF ON OFF 0-1V
ON ON OFF OFF ON OFF 0-5V
OFF OFF ON OFF ON OFF 0-10V
ON OFF ON OFF ON OFF 1-5V
OFF ON ON OFF ON OFF 0-20mA
ON ON ON OFF ON OFF 4-20mA
OFF OFF OFF ON ON OFF 0-1V
ON OFF OFF ON ON OFF 0-5V
OFF ON OFF ON ON OFF 0-10V
ON ON OFF ON ON OFF 1-5V
OFF OFF ON ON ON OFF 0-20mA
ON OFF ON ON ON OFF 4-20mA
OFF ON ON ON ON OFF 0-1V
ON ON ON ON ON OFF 0-5V
OFF OFF OFF OFF OFF ON 0-10V
ON OFF OFF OFF OFF ON 1-5V
OFF ON OFF OFF OFF ON 0-20mA
ON ON OFF OFF OFF ON 4-20mA
OFF OFF ON OFF OFF ON 0-100mV
ON OFF ON OFF OFF ON 0-100mV
OFF ON ON OFF OFF ON 0-100mV
ON ON ON OFF OFF ON 0-100mV
OFF OFF OFF ON OFF ON 0-100mV
ON OFF OFF ON OFF ON 0-100mV
OUTPUT
4-20mA
0-20mA
0-5V
1-5V
0-10V
2-10V
4-20mA
0-20mA
0-5V
1-5V
0-10V
2-10 V
12
DRAFT - 08 August 2017 DRAFT - 08 August 2017
Input+
MTL1271
5
6
2
1
+
-
System AI
2 wire Tx
system input
Input-
Load
-ve
Return
+24V Tx
Power
Limit
4-20mA
Type J or K
thermocouple
Input+
MTL1272
5
6
2
1
+
-
System AI
2 wire Tx
system input
Input-
Load
-ve
Return
+24V Tx Power
Limit
4-20mA
3
3 wire
PT100 RTD
4 wire
PT100 RTD
Input+
Input-
5.6 MTL1271 loop powered thermocouple input converter
For use with Type J or K thermocouples. Range and thermocouple type are set by use
of DP switches on the module. The maximum load resistance is dependent on the
available power supply voltage. Max load = 50(Vs-17)
For range settings please refer to Table 1 for MTL1171/2. Note, no LED indicators are
fitted on the loop powered modules.
Note: Signal source must be isolated from mains supply.
5.7 MTL1272 loop powered RTD temperature converter
For use with PT100 type sensors. Range is set by use of DP switches on the module.
The maximum load resistance is dependent on the available power supply voltage.Max
load = 50(Vs-17)
For range settings please refer to Table 1 for MTL1171/2. Note, no LED indicators are
fitted on the loop powered modules.
Note: Signal source must be isolated from mains supply.
13
DRAFT - 08 August 2017 DRAFT - 08 August 2017
High Trip
Low Trip
Relay O – Contacts open
Relay On – Contacts Closed
Relay On – Contacts Closed
Relay O – Contacts open
Set point
Set point
6 MTL13XX TRIP AMPLIFIERS
6.1 Introduction
The trip amplifier modules all use the 17.5mm wide housing with up to 16 terminals available
for field and system connections. Power can be supplied via the DIN rail power bus, using the
PBUS17.5 power connectors, or directly into the module via screw terminals 15 and 16. Where the
power bus is being used it is recommended power is fed directly to the bus using the PBUS02
or MTL1991 power feed connections. Two trip points may be set with high or low level switching
6.2 Trip level Setting
Setting the trip level the relay switching action
must be set to High Trip or Low Trip using
the switches on the side of the module. It is
normal to set the relay so that under non-alarm
conditions the relay contacts are Before closed.
When in alarm, the relay contacts would normally
be set to open, this will also be the state when
the module is unpowered (failsafe operation).
DS4 / DS5 Off – High trip, On – Low trip
Set these switches with the module off the DIN rail.
The yellow Trip LEDs are illuminated when the relays are energised.
The switching point for either trip is set by feeding the required process trip level into the input
of the module and pressing one of the two small ‘SET’ buttons on the top of the module for the
appropriate trip. The Power and STS light will flash 5 times. The level is digitally stored in the
module and retained in the event of power loss. Pressing the SET button again will overwrite the
previous setting to the current input level that is being applied at the time.
All models also provide a 4-20mA output which can be set for current source (active) or current
sink (passive) operation as required
6.3 Label Indicators / Switches
STS RED Off normal operation. On fault. Flashing - temperature input open circuit
PWR GREEN on when power applied
Trip 1 YELLOW on when relay 1 energised
Trip 2 YELLOW on when relay 2 energised
DSx DIP switches for mode setting
SW1 Current output Sink / Source setting
STS PWR
TRIP 1 TRIP 2
MTL13xx
SET O/PSET O/P
SW1
¾ turn
14
DRAFT - 08 August 2017 DRAFT - 08 August 2017
6.4 Switch settings
Table 1 Trip switch settings
MTL13xx
DS4 (trip 1) DS5 (trip 2) Status
ON ON Trip alarm low
OFF OFF Trip Alarm high
Table 2
MTL137x Configuration and DIP switch settings
Model Input type DS1 DS2 DS3 DS4 DS5
Type Wire Break Wire Break Drive Trip 1 Trip 2 MTL1371 THC J Off / K On MTL1372 RTD 4W Off 3W On MTL1373 POT -
Table 3 MTL1371 and MTL1372 range DIP switch setting
ON/OFF
ON = Upscale
OFF = Downscale
Off High
On Low
Off High
On Low
Range THC/RTD DS6 DS7 DS8 DS9 DS10 0 to 100°C 0 0 0 0 - 0 to 150°C 0 0 0 1 - 0 to 200°C 0 0 1 0 - 0 to 350°C 0 0 1 1 - 0 to 500°C 0 1 0 0 - 0 to 650°C 0 1 0 1 -
0 to 800°C 0 1 1 0 - 0 to 1000°C (RTD max 850°C) 0 1 1 1 -
-10 to 50°C 1 0 0 0 -
-50 to 50°C 1 0 0 1 -
-50 to 100°C 1 0 1 0 -
-50 to 150°C 1 0 1 1 -
-50 to 250°C 1 1 0 0 -
-50 to 350°C 1 1 0 1 -
-200 to 600°C 1 1 1 0 - Special (Reserved) 1 1 1 1 -
Note: Cycle power supply after setting switched
15
DRAFT - 08 August 2017 DRAFT - 08 August 2017
6.5 MTL1321 trip amplifier with voltage/current input and 4-20mA output
For use with 0-10V voltage or active 0-20mA current source inputs.
SW1 used to set current source or current sink 4-20mA output.
+
V Input+
V
V/I Input-
I Input+
MTL1321
1
2
4
V/I
T1 T2
D
0V +24V
I
E
4-20mA
13
-
14
+24V
15
0V
16
9
Trip 1
10
11
Trip 2
12
Source Sink
Load
-
Table 4
MTL1321 SW101 range switch settings
Input Output DS1 DS2 DS3 DS6
0-1V
OFF OFF OFF OFF
0-5V ON OFF OFF OFF
0-10V OFF ON OFF OFF
1-5V ON ON OFF OFF
4-20mA
0-20mA OFF OFF ON OFF
4-20mA ON OFF ON OFF
0-1V
OFF ON ON OFF
0-5V ON ON ON OFF
0-10V OFF OFF OFF ON
1-5V ON OFF OFF ON
0-20mA
0-20mA OFF ON OFF ON
4-20mA ON ON OFF ON
0-100mV 4-20mA OFF OFF ON ON
0-100mV 0-20mA ON OFF ON ON
2 wire Tx
system input
SW1
Load
+24V Tx
Power
Switches DS4 and DS5 set the trip action as previously described
16
DRAFT - 08 August 2017 DRAFT - 08 August 2017
6.6 MTL1341 trip amplifier with 4-20mA input/output
For use with 2 wire 4-20mA transmitter and 4 wire transmitters or 0-20mA current sources.
0-20mA isolated current repeat with 2 trip points. SW1 used to set current source or
current sink 4-20mA output.
4 wire
Tx
Tx+
Input
Com
MTL1341
1
2
3
+
13
4-20mA
V/I
I
T1 T2
D
E
0V +24V
-
14
+24V
15
0V
16
9
Trip 1
10
11
Trip 2
12
Source Sink
-
Load
2 wire Tx
system input
SW1
Load
+24V Tx
Power
For testing a resistance may be fitted between terminals 1 and 2 to simulate an input.
Use a resistance decade box or a current simulator if precise setting is required.
Resistance Approx. Output current
25KΩ 1mA
6KΩ 4mA
1k9KΩ 12mA
1KΩ 20mA
6.7 MTL1371 trip amplifier converter, thermocouple input/4-20mA output
For use with Type J or K thermocouples. Range set using DIP switches on the side of the module.
4-20mA current output with sink or source setting and two trip points. SW1 used to set current
source or current sink 4-20mA output
Input+
Input-
Type J or K
thermocouple
MTL1371
1
2
THC
T1 T2
D
+
13
4-20mA
I
E
-
14
+24V
15
0V
16
9
Trip 1
10
11
Trip 2
Source Sink
-
12
Load
2 wire Tx
system input
SW1
Load
+24V Tx
Power
0V +24V
17
DRAFT - 08 August 2017 DRAFT - 08 August 2017
6.8 MTL1372 trip amplifier converter, RTD input/4-20mA output
For use with PT100 RTDs. Range set using DIP switches on the side of the module.
4-20mA current output with sink or source setting and two trip points. SW1 used to set
current source or current sink 4-20mA output.
3 wire
PT100 RTD
Input+
Input-
4 wire
PT100 RTD
Input+
Input-
MTL1372
1
2
3
4
RTD
T1 T2
D
4-20mA
I
E
13
14
15
16
10
11
12
9
+24V
0V
+
-
Trip 1
Trip 2
wire Tx
2
system input
Source Sink
SW
1
Load
-
Load
24V Tx
+
Power
0V +24V
6.9 MTL1373 trip amplifier converter, Potentiometer input/4-20mA output
For use with 3 wire potentiometers with an end to end resistance between 100Ω and 100KΩ.
To minimise the effect of wiring resistance between the module and the potentiometer a higher value
potentiometer resistance is recommended. SW1 used to set current source or current sink 4-20mA output.
3 wire
Potenometer
input
+
Input
-
MTL
1
2
3
1373
POT
T
D
0
V +24V
1 T2
E
+
13
20
mA
4
-
I
-
14
24V
+
15
0
V
16
9
Trip
Trip
1
2
10
11
12
System AI
wire Tx
2
system input
Source Sink
SW
1
Load
-
Load
24V Tx
+
Power
18
DRAFT - 08 August 2017 DRAFT - 08 August 2017
7 MAINTENANCE
Note: Return any isolator identified as faulty to the Eaton’s MTL product line or representative
from which it was purchased, for repair or replacement.
7.1 Routine maintenance
Occasionally check the general condition of the installation to make sure that no deterioration has
occurred. At least once every two years (and more frequently for particularly harsh environments),
check that:
isolators are of the types specified in the relevant documentation.
isolators are legibly tagged and tag details given comply with the relevant
documentation.
isolators are securely clipped to the DIN rail.
all cable connections are properly made to the isolators.
all connecting cables are of the specified type and rating, are correctly routed
(particularly when fitted in enclosures), and are not frayed or otherwise damaged.
all cable screens are properly earthed.
there is no sign of damage or corrosion.
to clean use water based damp cloth.
7.2 Enclosures
The only enclosure maintenance required is cleaning and periodic visual inspections. Clean
external surfaces only, using soap and water, do not use chemical solvents or proprietary cleaning
fluids. Every year (more frequently in harsh environments), inspect enclosures and check that:
they are attached securely to their mountings.
any accumulation of water inside has been removed (using the drain plug, if fitted).
cable gland nuts are tight.
there are no signs of any damage.
all connections are properly made.
8 APPENDIX A
Table 1 Isolator current consumption for MTL1991 calculation @ 24V.
Isolator Typical load current Maximum load current
MTL1141 33mA @16mA output 45mA
MTL1142 35mA @16mA output 51mA
MTL1143 50mA @16mA output 71mA
MTL1171 15mA voltage out
35mA current out
MTL1172 15mA voltage out
35mA current out
MTL1173 15mA voltage out
35mA current out
MTL1211 25mA 35mA
MTL1249 38mA 38mA
MTL13xx 55mA 80mA
40mA
40mA
40mA
19
DRAFT - 08 August 2017 DRAFT - 08 August 2017
THIS PAGE IS LEFT INTENTIONALLY BLANK
20
DRAFT - 08 August 2017
AUSTRALIA
MTL Instruments Pty Ltd, 10 Kent Road, Mascot, New South Wales, 2020, Australia
Tel: +61 1300 308 374 Fax: +61 1300 308 463 E-mail: mtlsalesanz@eaton.com
BeNeLux
MTL Instruments BV Ambacht 6, 5301 KW Zaltbommel The Netherlands
Tel: +31 (0)418 570290 Fax: +31 (0)418 541044 E-mail: mtl.benelux@eaton.com
CHINA
Cooper Electric (Shanghai) Co. Ltd 955 Shengli Road, Heqing Industrial Park Pudong New Area, Shanghai 201201
Tel: +86 21 2899 3817 Fax: +86 21 2899 3992 E-mail: mtl-cn@eaton.com
FRANCE
MTL Instruments sarl, 7 rue des Rosiéristes, 69410 Champagne au Mont d’Or France
Tel: +33 (0)4 37 46 16 53 Fax: +33 (0)4 37 46 17 20 E-mail: mtlfrance@eaton.com
GERMANY
MTL Instruments GmbH, Heinrich-Hertz-Str. 12, 50170 Kerpen, Germany
Tel: +49 (0)22 73 98 12 - 0 Fax: +49 (0)22 73 98 12 - 2 00 E-mail: csckerpen@eaton.com
INDIA
MTL India, No.36, Nehru Street, Off Old Mahabalipuram Road Sholinganallur, Chennai - 600 119, India
Tel: +91 (0) 44 24501660 /24501857 Fax: +91 (0) 44 24501463 E-mail: mtlindiasales@eaton.com
ITALY
MTL Italia srl, Via San Bovio, 3, 20090 Segrate, Milano, Italy
Tel: +39 02 959501 Fax: +39 02 95950759 E-mail: chmninfo@eaton.com
JAPAN
Cooper Crouse-Hinds Japan KK, MT Building 3F, 2-7-5 Shiba Daimon, Minato-ku, Tok yo, Japan 105-0012
Tel: +81 (0)3 6430 3128 Fax: +81 (0)3 6430 3129 E-mail: mtl-jp@eaton.com
NORWAY
Norex AS Fekjan 7c, Postboks 147, N-1378 Nesbru, Norway
Tel: +47 66 77 43 80 Fax: +47 66 84 55 33 E-mail: info@norex.no
RUSSIA
Cooper Industries Russia LLC Elektrozavodskaya Str 33 Building 4 Moscow 107076, Russia
Tel: +7 (495) 981 3770 Fax: +7 (495) 981 3771 E-mail: mtlrussia@eaton.com
SINGAPORE
Cooper Crouse-Hinds Pte Ltd 100G Pasir Panjang Road, Interlocal Centre #07-08 Singapore 118523
Tel: +65 6645 9888 Fax: +65 6645 9811 E-mail: sales.mtlsing@eaton.com
SOUTH KOREA
Cooper Crouse-Hinds Korea 7F. Parkland Building 237-11 Nonhyun-dong Gangnam-gu, Seoul 135-546, South Korea.
Tel: +82 6380 4805 Fax: +82 6380 4839 E-mail: mtl-korea@eaton.com
UNITED ARAB EMIRATES
Cooper Industries/Eaton Corporation Office 205/206, 2nd Floor SJ Towers, off. Old Airport Road, Abu Dhabi, United Arab Emirates
Tel: +971 2 44 66 840 Fax: +971 2 44 66 841 E-mail: mtlgulf@eaton.com
UNITED KINGDOM
Eaton Electric Ltd, Great Marlings, Butterfield, Luton Beds LU2 8DL
Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283 E-mail: mtlenquiry@eaton.com
AMERICAS
Cooper Crouse-Hinds MTL Inc. 3413 N. Sam Houston Parkway W. Suite 200, Houston TX 77086, USA
Tel: +1 281-571-8065 Fax: +1 281-571-8069 E-mail: mtl-us-info@eaton.com
Eaton Electric Limited, Great Marlings, Butterfield, Luton Beds, LU2 8DL, UK. Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283 E-mail: mtlenquiry@eaton.com www.mtl-inst.com
© 2018 Eaton All Rights Reserved Publication No. INM 1000 Rev 8 051118 November 2018
EUROPE (EMEA):
+44 (0)1582 723633 mtlenquiry@eaton.com
THE AMERICAS:
+1 800 835 7075 mtl-us-info@eaton.com
ASIA-PACIFIC:
+65 6645 9888 sales.mtlsing@eaton.com
The given d ata is only intended as a p roduct descrip tion and should not be re garded as a legal warrant y of properties or gu arantee. In the interest of further technical developments, we reserve the right to make de sign changes.
Loading...