MTL Instruments LS Operating Manual

Instruction sheet
MTL surge protection
MTL LS Range
Operating Instructions for LED Lighting Type 2 SPD
January 2017 INS 801-745 Rev B
Do not attempt to open or tamper with the SPD in any way as this will
CAUTION
compromise performance and will void the warranty.
Megger and hi-pot tests will damage this device. Disconnect all power
supplying the equipment and isolate the SPD unit before testing.
Prior to installation, confirm the SPD is rated for the correct voltage,
and frequency equivalent to the application.
Installation
1) Turn off all power supplying this equipment.
2) Mount the SPD using the enclosure flanges to a flat surface.
3) Connect the wire leads as per the wiring diagrams below.
4) For optimal device performance, use shortest length of wire possible and avoid sharp or unnecessary bends.
Product Characteristics
Model Volta ge Conn Modes Freq In Diagram
LS10 - 347V-S
LS10 N-347 V-S2
LS10 - 4 80V-S
LS10 N-480V-S2
LS12-347V-P
LS12N-347V-P2
LS12- 4 8 0 V-P
LS12N - 4 8 0 V-P2
12 0 -3 4 7, 5A SERIES L-N , L- G , N - G 50/60 3 kA A
480, 5A SERIES L- G , L- L 50/60 3 kA B
120 - 3 47 PARALLEL L- N , L- G , N - G 50/60 3 kA C
480 PARA LLEL L- G, L- L 50/60 3 kA D
Eaton Electric Limited,
© 2017 Eaton All Rights Reserved Publication No. INS 801-745 Rev B 060117
1
January 2017
MTL LS range
January 2017
Wiring Diagrams
SERIES CONNECTED SPDs: Units designed to be connected in series with the LED driver for
protection of the modes as listed in the table above. Refer to the connection diagrams to ensure that the SPD you have chosen is appropriate for the application it is being installed into. These range versions have internal protection that will disconnect the surge protective components and will not maintain power to the load. If this situation is undesirable for the application, replace the unit with a parallel connected type.
PARALLEL CONNECTED SPDs: Units designed to be connected in parallel with the LED driver for protection of the modes as listed in the table above. Refer to the connection diagrams to ensure that the SPD you have chosen is appropriate for the application it is being installed into. These parallel versions have internal protection that will disconnect the surge protective components but will maintain power to the load – now unprotected. If this situation is undesirable for the application, replace the unit with a series connected type.
Eaton Electric Limited,
© 2017 Eaton All Rights Reserved Publication No. INS 8012-745 rev B 060117 January 2017
EUROPE (EMEA):
+44 (0)1582 723633 mtlenquiry@eaton.com
THE AMERICAS:
+1 800 835 7075 mtl-us-info@eaton.com
ASIA-PACIFIC:
+65 6645 9864 / 9865 sales.mtlsing@eaton.com
The given dat a is only intended as a prod uct descriptio n and should not be regard ed as a legal warranty of pr operties or guara ntee. In the interest of further technical developments, we reserve the right to make desig n changes.
2
Loading...