MTL Instruments FS32 Specifications

Technical data
MTL surge protection
MTL FS32 range
Surge protection for fieldbus components
Protects intrinsically safe spurs on
MTL 937x-FB range fieldbus
20kA maximum surge current per line
Plug connectors for quick and easy
connection or rewiring
Meets the requirements of IEC61158-2:2004
Can be used on MTL Megablocks or
other fieldbus equipment
10 year product warranty
February 2016 EPS 901-169 Rev C
The FS32 surge protection device prevents surges and transient over-voltages conducted along the Trunk or Spurs of fieldbus systems from damaging the associated electronics such as terminators, spur blocks and the bus control equipment. Designed to fit Eaton’s latest MTL fieldbus barrier product to protect spurs the FS32 can also be used to protect spurs on Megablock wiring hubs. This space saving design helps to reduce the size of junction boxes and ease installation.
The multi-stage hybrid surge protection network at the heart of the FS32 uses a combination of solid state electronics and a gas-filled discharge tube (GDT) to provide surge protection up to 20k A. This impressive surge protection circuit is design to exhibit exceptionally low line resistance and has negligible voltage drop to the spurs.
In operation the FS32 does not adversely affect the performance or operation of the fieldbus or connected equipment, it allows signals to pass with little attenuation while diverting surge currents safely to earth (ground) and clamping output voltages to safe levels.
Fully automatic in operation the FS32 devices react immediately to make sure that the equipment is never exposed to damaging surges between lines or the lines to earth (ground). Reacting instantaneously the FS32 redirects surges safely to earth (ground) and then resets automatically.
The FS32 represents the next generation of surge protection to be fitted on F allows the FS32 to be connected directly to the terminal receptacle on the module carrier of the 9370 fieldbus barrier. The earth (ground) is connected through the mounting screw in one simple operation. The field spur cable termination block plugs directly into the FS32 allowing fast and effective retro fitting if desired with no additional hardware being required.
For general purpose Megablock wiring hubs FCS-MBx, FCS -MBx­SG, FCS-MBx-SG-T, F300 Range and Intrinsically Safe Megablock wiring hubs F24 0 - F273 the FS 32 represents a simple solution for the fitting of surge protection with the addition of the FS32- BAR earthing (grounding) arrangement. Furthermore the FS32 can also be used on fieldbus power supplies such as the F800 to protect the trunk.
A 10 year no fuss warranty is available as standard for the FS32, so if a correctly connected device should fail for any reason simply return it for a free replacement.
oundatio n™ fieldbus Systems. The space saving form factor
Measurement Technology Limited, Great Marlings, Butterfield, Luton Beds, LU2 8DL, UK. Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283 E-mail: mtlenquiry@eaton.com www.mtl-inst.com
© 2016 MTL All Rights Reserved Publication No. EPS 901-169 Rev C 180216 February 2016
1
MTL FS32 range
February 2016
SPECIFICATION
All figures typical at 25°C (77°F) unless otherwise stated
Maximum surge current
20k A (8/20µs waveform) per line
Leakage current
0.1µA @ working voltage
Working voltage
±32Vdc
Maximum continuous operating voltage
±36V peak normal mode ±225 V peak common mode
Limiting voltage
62V @ 3kA 8/20µs
Line resistance
0.1 Ohm per line
Capacitance
Line — Line — 40pF Line — Ear th (Ground) — 80pF
Attenuation
-1dB — 7kHz to 7.5MHz
Ambient temperature limits
-40°C to +75°C (- 40°F to +167°F) (working)
-40°C to +80°C (- 40°F to +176°F) (storage)
Humidity
5% to 95% RH (non-condensing)
Electrical connections
Plug/header screw terminal
Weight
40g
Dimensions
See figure 1
EMC compliance
BS EN 61326-1:2013
Electrical Safety
BS EN 61643-21:2001
INSTALLATION
Directly plugs into MTL 934x-FB and Relcom mega-blocks.
ORDERING INFORMATION
FS32 FS32-BAR
Figure 1 Dimensions (as supplied)
Unprotected ve+
Unprotected ve-
Shield
Ground/Earth Screw
Figure 2 AC and DC connections
Protected ve+
Protected ve-
Shield
M3 threaded
hole, X8
M4 threaded hole, X8
Part No. FS32-BAR
Scored to break for shorter applications
Ground bar for Megablocks
TO ORDER SPECIFY - Order by module, as listed in the specification table below.
Model FS32
Nominal voltage U Rated voltage (MCOV) U Nominal current I Nominal discharge current (8/20µs) i Max discharge current (8/20µs) I Lightning impulse current (10/350µs) I Residual voltage @ i Voltage protection level @ 1kV/µs U Bandwidth f Capacitance C 40pF Series resistance R 0.1 Operating temperature range -40°C to +75°C Category tested A2, B2, C1, C2, C3, D1 Overstressed fault mode in=3kA 22kA Impulse durability (8/20µs) 10kA Degree of protection IP20 AC durability 1A Service conditions 80kPa - 160kPa 5% - 95% RH
sn
U
n c
n
sn max imp
p p
G
32V 36V
1.6A 3kA 20kA
2.5kA 62V <45V 73MHz
rms
, 5T
Tested in accordance to IEC 61643-21
HAZARDOUS AREA APPROVALS
Standard/Authority Certificate/File No. Approved for
ATEX Directive 94/9/EC FISCO (Baseefa)
IECEx IECEx BAS 09.0083X Ex ia IIB T3 Ga
Test Specification No. 1, 2002 Marine (Lloyds Register)
2
Baseefa09ATEX0180X Ex ia IIB T3 Ga
14/60004 Environmental Category ENV3 FS32
Measurement Technology Limited, Great Marlings, Butterfield, Luton Beds, LU2 8DL, UK. Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283 E-mail: mtlenquiry@eaton.com www.mtl-inst.com
© 2016 MTL All Rights Reserved Publication No. EPS 901-169 Rev C 180216 February 2016
Product
Ex ia IIC T4 Ga (-40°C<Ta<75°C) see schedule All
Ex ia IIC T4 Ga (-40°C<Ta<70°C) see schedule
EUROPE (EMEA):
+44 (0)1582 723633 mtlenquiry@eaton.com
THE AMERICAS:
+1 800 835 7075 mtl-us-info@eaton.com
ASIA-PACIFIC:
+65 6 645 9888 sales.mtlsing@eaton.com
The given d ata is only intended as a p roduct descrip tion and shou ld not be regarded as a le gal warrant y of properties or gu arantee. In th e interest of further technical developments, we reserve the right to make de sign changes.
All
Loading...