Calculating Maximum Current Draw and Battery Backup Requirements
13
2.4
Mounting the Enclosure /Door Label
14
2.4.1
Connecting the AC Power
16
2.4.2
Battery Installation
17
2.4.3
Output (NAC) Installation
18
2.4.4
Relay Installation
19
3 Programming
3.1
Menu System
20
3.1.1
Power-up Screen
21
3.1.2
Idle Screen
21
3.1.3
Alarm Screen
21
3.1.4
Trouble Screen
22
3.1.5
Supervisory Screen
23
3.1.6
Login Screen
23
3.2
Main Menu
24
3.2.1
General Menu Setup
24
3.2.1.1
Default Setup
24
3.2.1.2
Time/Date Setup
25
3.2.2
SLC Setup
26
3.2.2.1
CDR(Customer data record)
26
3.2.2.2
Walk Test
27
3.2.2.3
Maintenance Menu
28
3.2.3
Output Setup
30
3.2.3.1
Nac Setup
30
3.2.3.2
Cadence Setup
31
3.2.3.3
Relay Setup
32
3.2.4
History Display
33
3.2.5
PC Menu
34
3.2.6
Device Enable/Disable
34
3.2.7
Network
36
3.2.8
Remote Annunciator
37
3.2.9
Booster 38
3.3
Gas Release
39
Page 5
4
4 Appendix
4.1
Data Sheet for FSUTLC(Loop Card)
41
4.2
Installation Instructions for 3 Channel I/O Unit FSUTCIOU
42
4.3
Installation Instructions for Mini Input Monitor FSUMIM
45
4.4
Installation Instructions for Output Monitor FSUOM
47
4.5
Installation Instructions for T-tap FSUSIU
49
4.6
Installation Instructions for Remote Annunciator FSURA
51
4.7
Installation Instructions for Mini Output Monitor FSUMOM
54
4.8
Installation Instructions for Mini Zone Monitor FSUMZM
56
4.9
MA-1000 Site Installer User Manual (PC program)
58
4.10
Networking
98
4.11
Operating Instructions
100
4.12
Detectors UL Certifications
101
4.13
Basic Operating Instructions
103
Notes:
1. For maintenance recommendations refer to NFPA 72 National Fire Alarm Code, 2007.
2. Compatibility identifier number: 0409008
3. Software release: Dec 2008 Version 08
4. Install in accordance to NFPA 72 (2007).
5. All circuits inherently power limited except AC wiring and battery cabling.
6. UL 864 9th Edition does not permit the disabling of all zones.
7. UL864 9th Edition does not permit the use of Auto Silence.
Page 6
5
CAUTIONS
1. BATTERY MAINTENANCE INSTALLATION CAUTIONS
Initial preparation before installation:Verify no abnormalities on battery case (like crack or leakage)
Free air space must be provided between each battery. Recommended minimum space is 5~10mm
(0.02~0.04 inches).
Set the batteries firmly in the equipment. Otherwise, batteries may be damaged, or connection
conductivity may be decreased due to shock. When batteries are used in vibration conditions, they
shall be mounted in upright position and with proper cushion for protecting vibration.
Avoid mixed usage of batteries differing in capacity, manufacturer, storage or charge/discharge
conditions. Batteries may be damaged after cycles due to difference in electrical characteristics.
2. REGULAR CHECK AND REPLACE PRECAUTIONS
Measure the total voltage of the batteries during float charge to see whether there is any abnormal
deviation and investigate the situation.
TRANSPORTATION PRECAUTIONS
Handle the batteries carefully to avoid injuries.
Avoid moisture or rain on the batteries and cartons.
Transport the batteries in the upright position and avoid abnormally strong shock / vibration.
Do not lift a battery by its terminal. Otherwise, internal construction may be damaged and leakage
may occur.
3. OTHER PRECAUTIONS
Clean battery with wet soft cloth. Never apply oil, polyvinyl chloride or organic solvents (like gasoline
and paint thinner) to the battery. Otherwise, battery cover may be cracked / deform and acid leakage
will result.
Do not disassemble the battery. Otherwise, sulphuric acid will flow out.
If sulphuric acid deposit on to skin or cloth, wash immediately with water. If splashed into eyes, wash
with a large amount of water and consult medical physician immediately.
Avoid dusting by cloth duster or dry cloth (particularly chemical textile), as they will generate static
electricity which is dangerous.
Wash your hands after handling battery.
Do not short the battery terminals.
Never dispose battery into fire.
Page 7
6
MA-1000 FACP
1 General
The MA-1000 provides all of the sophisticated features required of a leading edge analog fire
system along with the simple operation and neat installation demanded by both installers and
building users.
The panel can be flush or surface mounted and the generously sized metal back box allows ample
facilities for rear or top cable entries.
A comprehensive range of ancillary devices is available to operate with MA-1000, including Optical,
Ionization, photo-thermal and heat detectors.
Each of the MA-1000 system components has been specifically designed to operate as part of a
MA-1000 system, this provides an assurance that the panel, the detectors, the interfaces and the
ancillaries are all fully compatible with one another and that the full range of system functionality is
supported by each device.
1.1 Product Features
The Panel has the following features:
Built-in four-line (16 Characters each line) LCD display provides easy to read readouts.
15 key keypad for programming, reset and silencing.
2 SLC loops (optional 4 loops).
Real time clock.
Event History Buffer (256 events) with Date/Time stamp. Events can be displayed on LCD.
8 selectable/programmable output patterns for notification appliance (outputs) circuits.
4 Notification appliance circuits (NAC's) outputs.
3 programmable general purpose relays.
Built-in walk test.
Switchable 6 amp power supply INPUT 110-120 3.2A, 220-240VAC 1.6A 50/60Hz
OUTPUT +24V 6.5A
Dedicated alarm and trouble relays.
Housed in a 37.0cmW x 39.5 cm H x 11.5 D metal cabinet.
Cabinet supports two 12V, 7Ah backup batteries.
Page 8
7
1.2 Specifications
AC Power
6.5A POWER SUPPLY AC Input max 3.2A (120VAC) 1.6A (220VAC) model number S-150-24.
Battery (sealed lead acid only)
Maximum charging circuit – 0.98A&22VDC
Maximum charger capacity: 18 amp hour battery (two 7 amp hour batteries can be housed in the
enclosure. Larger batteries require a separate Battery Cabinet MBC “Mini Battery Cabinet”
manufactured by space age.
SLC Circuits
The MA-1000 Panel comes with two SLCs loops (optional 4 SLC loop card) which has the following
parameters:
Supply voltage: 24 VDC nominal, 27.6 VDC maximum.
Addressable Loops
Max Number: 2
Max Load per loop: 60 mA
Maximum loop current is 150 mA (short circuit)
Max Number of Addressable Devices per loop: 200
The total number of addresses per loop is 200; this includes detectors, manual pulls and all other
addressable items. When designing systems it’s recommended that allowances are made for future
expansion, Short circuit isolators are incorporated into every MA-1000 loop device, including Smoke
detectors, heat detectors, sounders, manual pulls and interfaces. Therefore, no further fault
protection is required, in the event of a single fault; none of the devices connected to the loop will fail
to operate as the fault will be isolated by the two adjacent devices.
T-tap connected devices downstream of a cable fault will cease to function.
Notification Appliance Circuit(s)
4 NACs Regulated
Supervised for ground faults impedance value 1KΏ
1.2 ampere per NAC
Operation: Style Y (Class B Style Y)
Power-limited Circuitry
Normal Operating Voltage: Nominal 24 VDC, Maximum 27 VDC
Maximum Signaling Current: 4.2 amps total with 6.5AMP power supply P/N 08.009.
Maximum Line Impedance: 1.5 volt drop end-of-line
End-of-Line Resistor: 10KΩ 1/5 5% (part number 06.006)
NAC Specification
Four programmable outputs are Notification Appliance Circuit (NAC).
Page 9
8
The NAC provide the following programmable modes:
NAC Steady – 24 VDC at alarm condition
NAC Temporal Code – 24 VDC at alarm condition (on, off, on, off)
NAC March Time – 24 VDC at alarm condition (on, on, off, off, on, on, off, off)
Synchronization - Cooper Wheelock DSM-12/24 p/n 06.012 is for per NAC MAX 20 devices can be
connected.
Max arms current 70mA
ANSI S-3-41
Single stroke BI
California code
Form C Relays
Trouble Relay is common working when Trouble condition.
Alarm Relay is common working when Alarm condition.
Relay 1 is programmable relay.
Relay 2 is programmable relay.
Relay 3 is programmable relay.
All relays have same rating: 2A, 30VAC, resistive
The FACP provides 3 programmable Form-C relays and one fixed fail-safe Form-C trouble relay, all
with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive).
Note: that the relay connections must be power-limited. Refer to UL Power-limited wiring
requirements.
Loop lengths
The maximum permitted loop length is 2 km measured from the near to the far terminals on the MA1000 Loop Card PCB. There is no minimum limit to loop length. Any wiring spurs off the loop must
be included within the 2 km limit. On long loop runs, the lengths of wiring rises and falls (between
floors, down to manual call points) must be included. Remember to include these especially when
taking loop lengths from plan drawings.
Page 10
9
1.3 Controls and Indicators
Front Panel Membrane User Buttons
Acknowledge
This function, also abbreviated to "ACK", is used to acknowledge an abnormal situation such as an
alarm or trouble condition. The acknowledge function tells the panel that building personnel or
emergency responders are aware of the alarm, trouble, or supervisory condition. Acknowledging the
alarm or trouble condition also normally silences the panel's own sounder.
Alarm Silence
Also known as "audible silence". Depending on the configuration of the alarm system, this function
will either silence the system's notification appliances completely, or will silence only the audible
alarm, with strobe lights continuing to flash. Audible silence allows for easier communication
amongst emergency responders while responding to an alarm. This can also be used during
construction as a means of a preliminary test, before the final full test.
Reset
This resets the panel after an alarm condition. All initiating devices are reset, and the panel is
cleared of any alarm conditions. If an initiating device is still in alarm after the system is reset, such
as a smoke detector continuing to sense smoke, or a manual pull station still in an activated
position, another alarm will be initiated.
LED Indicators
AC Green LED
AC power (green light) when this indicator is lit, power is being provided to the system from the
building's electrical system, and not from the backup battery. When an AC power condition changes,
the Trouble indicator comes on and the AC power indicator goes off and the screen alerts building
personnel of a power failure. If the AC power indicator is lit without any other indicators also lit, then
the system is in a normal condition. If no LEDs are lit, there is no power source feeding the panel.
ALARM Red LED
Alarm (red light) This indicator is lit when an alarm condition exists in the system, initiated by smoke
detectors, heat detectors, sprinkler flow switches, manual pull stations, manual call points, or
otherwise. Along with the indicator on the panel, notification appliances, such as horns and strobes,
are also activated, signaling a need to evacuate to building occupants. In an alarm condition, the fire
alarm panel indicates where the alarm originated. The alarm panel can be reset once the device
which initiated the alarm is reset, such as returning the handle of a manual pull station to its normal
position.
TROUBLE Yellow LED
Trouble/Fault (yellow light) When held steady or flashing, it means that a trouble condition exists on
the panel. Trouble conditions are often activated by a contaminated smoke detector or an electrical
problem within the system. Trouble conditions are also activated by a zone being disabled
(disconnected from the system), a circuit being disabled, low power on the backup battery, the
disabling of a notification appliance, the ground faults, or short or open circuits. The alarm panel's
sounder will activate if a trouble condition exists. In a trouble condition, the panel displays the zone
or devices causing the condition. The "Trouble" indicator goes out automatically when the situation
causing the trouble condition is rectified.
Page 11
10
SILENCE Yellow LED
Also known as "audible silence". Depending on the configuration of the alarm system, this function
will either silence the system's notification appliances completely, or will silence only the audible
alarm, with strobe lights continuing to flash. Audible silence allows for easier communication
amongst emergency responders while responding to an alarm. This can also be used during
construction as a means of a preliminary test, before the final full test.
SUPERVISORY Yellow LED
Supervisory (yellow light) This signal indicates that a portion of the building's fire protection system
has been disabled (such as a fire sprinkler control valve being closed and, consequentially, a
sprinkler tamper switch being activated), or, less frequently, that a lower priority initiating device has
been triggered (such as a duct smoke detector). The "Supervisory" indicator requires a "Reset" to
clear.
Local Piezo Sounder
A Piezo sounder provides separate and distinct sounds for alarm, trouble, and supervisory
conditions as follows:
Alarm - on steady
Trouble - pulse 1 second on and 1 second off
Supervisory - pulse ½ second on and ½ second off
Page 12
11
2 Installations
Essential please read before proceeding!
The equipment described in this manual is listed by ETL TESTING LABORATORIES, for use in fire
alarm signaling systems, only when installed in accordance with this manual and the latest National
Fire Protection Association Standards NFPA 72; the National Electrical Code (NFPA 70); the Life
Safety Code (NFPA 101); and/or the local authority having jurisdiction (AHJ).
It is possible to apply system components incorrectly or arrange system components and installation
wiring so that required life safety functions are NOT performed. As a result, lives may be lost.
To minimize this possibility:
DO NOT deviate from any installation instructions contained in this manual.
DO NOT assume any installation details not shown in this manual.
DO NOT alter any mechanical or electrical features of the equipment supplied
BE FAMILIAR with the building code, fire prevention code, and/or requirements of the Authority
Having Jurisdiction (AHJ) in the locale of the installation.
!Caution!
Under normal and fault conditions, AC line voltages may be present on any terminal. Touching any
component could be hazardous and result in loss of life. A short circuit can result in arcing that could
cause molten metal injuries to testing personal.
To minimize this possibility, only qualified electrical technicians familiar with electrical hazards
should perform these checkout procedures. Safety glasses should be worn by such personnel, and
instruments used for voltage measurement should be designed for the purpose and should be in
good mechanical and working order.
If there is application or installation information that is not clear or not covered in this manual, please
contact us at: MTECH Technical Support at +972-4-6000610 or by email:
technicalsupport@mtech.com
2.1Agency Requirements
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
The PANEL is listed by ETL TESTING LABORATORIES to UL 864 9th edition as a FACP control
unit for use in NFPA 72 systems.
Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the
specific section of the manual for additional requirements.
All field wiring must be installed in accordance with NFPA 70 National Electric Code.
Use UL listed smoke detectors and notification appliances compatible with the PANEL
Page 13
12
from those specified in the Appendix to this manual.
A full system checkout must be performed every time the panel is programmed.
The MA-1000 range of analog fire alarm control panels are designed in accordance UL864 9th Fire
Detection and Fire Alarm systems Control and Indicating Equipment.
This product has been certified to comply with the requirements in the Standard for Control Units
and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864,
9th Edition has not been evaluated. Such operation requires the approval of the local Authority
Having Jurisdiction (AHJ).
2.2 Calculating Current Draw and Standby Battery
This section is to determine the current draw and standby battery needs for your installation.
Maximum Battery Standby Load
It is recommended to use the battery of Diamec Company (www.diamec.com). The required nominal
batteries capacity as versus standby current system is shown in the table bellow (1-1). For chosen
battery order the compatible wire set model
Make sure that for the system configuration the standby is not more than 0,270 A for 8Ah battery
and 0.4287 A for 12 Ah battery.
Table 1-1
LWH24 h60 h
DMU12-7715165101
0.2393 --
06.014
DMU12-121215199101
0.4287 --
06.015
Battery wires
model
Battery
Model
Capacity,
Ah
Size , mm
Max.permissible System
Standby current during
Page 14
13
2.3 Calculating Maximum Current Draw and Battery Backup Requirements
This section will assist you in determining the maximum system current draw and standby battery
needs for your installation. Follow the steps below to determine the current draw and standby
battery requirements. Appendix B—MA-1000 Current Draw/Battery Backup lists the standby and
alarm current draw for the panel. Total standby and alarm Current is determined by multiplying the
quantity of items by its current draw. To quickly determine maximum system current draw, perform
the following computations:
Download the “Backup Calculation.xls” file from www..biz
Fill in the quantities of conventional detectors, addressable detectors and devices.
Fill in the quantities and current draw of the Notification Appliances or auxiliary-powered devices for
each output from the manual for each specific device.
Fill in the total quantities of detectors and modules. The detectors and modules total alarm current
is determinate by estimation method, under the hypothesis that 5% LED will be ON.
The required battery capacity is determined according to equation
Cb >= (Isb* Tsb + Ia*Ta)*1.1
Where:
Cb- required battery capacity, Ah
Isb – standby current, A
Tsb – supervisory time, 24 or 60 hours
Ia – alarm current, A
Ta – alrm time, 5 min (0.0833 hours)
1.1 – safety factor.
Make sure the total alarm current you calculated (including current for the panel itself) does not
exceed 4.5 Amps. This is the maximum alarm current allowable.
Calculation example is shown in the following table (1-2).
Page 15
14
MA-1000
Page 16
15
2.4 Mounting the Enclosure
Install the Enclosure as follows:
1. Carefully unpack the system components and inspect for any damage due to shipping.
2. Mount the enclosure in a clean, dry, vibration-free area where extreme temperatures are not
encountered. The location should be readily accessible with sufficient room for easy installation and
maintenance.
3. Mount by using the two mounting holes located in the upper back of the cabinet. After the panel
has been properly located using the mounting holes, the panel can be secured.
4. Complete all conduit connections to the cabinet. Use the knockouts provided in the top and the
sides.
Wire must NOT enter the bottom of the cabinet, since this area is intended for batteries only.
Page 17
16
Peripheral Devices
Page 18
17
2.4.1 Connecting the AC Power
WARNING!
To reduce the risk of electrical shock, make sure that all power has been turned off or disconnected
prior to attempting to connect power to the Power Supply.
Apply the AC Power BEFORE connecting the batteries to the Panel!
Provide the Fire Alarm Control Panel with a dedicated AC Circuit rated 15 Amps.
Refer to Figure 2.1 for wiring diagram.
1. Enter Power Cable into Cabinet via left side knock out hole.
2. Attach the brown (live) wire from the source to terminal “Line” (USA use color black wire).
3. Attach the blue (neutral) wire from the source to the “Neutral” terminal (USA use color white wire).
4. Attach the ground wire from the source to the “GD” terminal block (USA use color green wire).
Figure 2.1
P1
Battery
Fault
GND wire
NEUTRAL
LIVE
Normal
+ -
GND
Factory fitted
NO NOT REMOVE
The GND cable must
be connected to this
point
+-
Page 19
18
2.4.2 Battery Installation
The batteries are placed at the bottom of the enclosure by removing the four nuts holding the battery
plate. The MA-1000 is fully protected if the batteries are connected in the opposite direction the
battery fault yellow led will show steady in such a condition. When green battery LED is in a steady
condition to shows that the battery connection is normal.
Page 20
19
2.4.3 Output (NAC) Installation
Each NAC can be programmed to operate for a limited amount of time or continuously, stay on
during operation or operate using one of several on/off patterns as well as start operation due to
various conditions happening.
Page 21
Contact rating
3A @ 30VDC (PF=1)
NO NC C
NO NC CNO NC C
RELAY 1
ALARM
RELAY 3
TROUBLE
NO NC C
NO NC C
RELAY 2
Dry Contact outputs
must be connected
to a power limited
source.
Normal Closed
Normal Open
COMMON ALARM RELAY
COMMON TROUBLE RELAY
PROGRAMMABLE RELAY 1
PROGRAMMABLE RELAY 2
PROGRAMMABLE RELAY 3
ALARM
TROUBLE
P G RELAY
P G RELAY
P G RELAY
2.4.6 Panel Relay Outputs
Relay outputs (Alarm, Trouble, and programmable) carry the same ratings.
Dry contact relays voltage free power factor 0.4.
Technical Specifications
Page 22
5
jkl
6
mno
7
pqrs
8
tuv
9
wxyz
Esc
0
Ack
RESET
*
NoYes
Backward
Foward
#
NextEnter
1
abc
2
def
3
4
ghi
Silence
NAMES
3 Programming
The MA-1000 has 15 digit keys, as well as Esc, Enter, Next, Silence and Reset keys:
Some of the keys have additional functions, which are activated depending on the
screen being displayed.
3.1 Menu System
The user interface is organized into a menu tree leading to specific programming item or
an action to be performed.
There are two types of menus:
Tree menu – the first two selections of the menu are presented and labeled as 1
and 2. Pressing the corresponding key will activate that item. If more than 2 items
on the menu, pressing the Next key will show the next 2 items on the menu, which
will be labeled 3 and 4.
21
Page 23
Programming menu – the top line displays screen function. The bottom line scrolls
MA-1000 FACP
Initialization
Please wait
07/08 12:35:36
System OK
MA-1000 FACP
By MTECH
between options when user presses the right or left arrow keys (6 and 4 keys
respectively). Pressing the Enter causes the system to accept new selection.
Pressing the up or down keys will cause system to skip this item and go back or
forth to adjacent items.
3.1.1 Power-up Screen
The MA-1000 1200 will display the following screen for 70 seconds following powering
up of the system or by pressing the ACK key a few times while in idle mode:
Initialization screen
After reset the panel has a 1 minute waiting time for the isolator’s to settle
3.1.2 Idle Screens
When the panel doesn’t detect any troubles or alarms, it displays the following screen:
By pressing 5 key the screen will change between Date and Time or year time. The
green LED indicates a normal condition & that the AC power is connected.
22
Page 24
3.1.3 Alarm (Fire) Screens
FIRE: 001/010
P64L2a200s123z96
Description Line 1
Description Line 2
To view alarm events select the or button.
3.1.4 Trouble Screens
When a trouble condition is detected, with-out an Alarm condition the trouble screen will appear.
The first row indicates a TROUBLE condition showing the number of devices.
The second row shows the panel number, loop and point number, sub-address number
(if exist) and zone number. Third & Forth rows indicate the point descriptions.
TROUBLES 008
Description Line 1
Description Line 2
P64L2a200s123z96
The display will indicate the initial status change for the highest priority type signal.
Alarm condition is the highest priority type signal no other condition will be displayed
when there is an Alarm condition
When an alarm condition is detected, the panel changes to the following screen.
The first row indicates a FIRE condition showing the number of devices in an alarm
condition. The second row shows the panel number, loop and point number, subaddress number (if exist) and zone number.
Third & Forth row is the area description.
23
Page 25
The first row indicates this trouble from a list of all the troubles.
Second - type of trouble.
NO BATTERY
TROUBLE 003/008
NO BATTERY
TROUBLE 003/008
System TROUBLE Conditions
The following list contains the system-wide and NAC trouble conditions:
NO BATTERYBattery removed
LOW BATTERYDischarged battery less than 22VDC
AC FAULTAC Voltage not present
CHARGER FAULTEither a condition stopping the charger to operate or a
failure with the charger has occurred.
GROUND FAULT Level 9VDC
NAC TROUBLE 1.2.3.4Open condition, short & ground conditions.
RS485 TROUBLE Connection to Annunciator or Booster is lost.
This screen is activated when ever one or more of the following condition(s) exist.
The panel buzzer will activate if a trouble condition exists. In a trouble condition, the
panel displays the zone or devices causing that condition. The “Trouble” indicator goes
away automatically when the situation causing the trouble condition has been rectified.
To view trouble events by pressing the keys you are able to manually read the
trouble conditions.
24
Page 26
3.1.5 Supervisory Screen
Supervisory 2
Description Line 1
Description Line 2
P64L2a200s123z96
ENTER PASSWORD:
****
If password is not found, the message "ACCESS DENIED" will be displayed for 2 seconds and
the system will go back to idle mode. The default password code is 1967, enter the code may
be changed by entering the USER screen.
You can program each input device as a supervisory by the PC program. When a
supervisory alarm is detected, you will see the following screen.
The first row indicates the alarm type SUPERVISORY and its number of devices.
The second row shows the panel no’, loop no’, point no’, sub-address no’ (if exist) and
zone no’. Third & Forth rows indicate the point descriptions.
3.1.6 Login screen
The login screen is activated whenever the user presses the Enter key while system is
in idle mode Following the pressing of 4 numeric keys, the system will search for the
password and enter with appropriate access level.
To log out of the system, press Esc, the system will time if not used after 30 minutes.
The MA-1000 can remember up to 16 separate user codes. Each user code can be
assigned one of two access levels:
Installer
Manager / User
Only installers may change the system setup.
25
Page 27
Manager/User is not allowed to change the system setup, they are to use walk test, time
MAIN MENU
1.Set 2.SLC
3.History 4.PC
5.Device En/Dis
1.SET General Setup
2.SLC Manage Loop
3.History Event Display
4.PC PC program
5.Device Enable/Disable
GENERAL SETUP
2.Date/Time
1.Defaults
1. Defaults defaults setup
2. Date/Timesetup date/time
LOAD DEFAULTS ?
NO
Reload manufacturer default settings.
Select Yes or No and press Enter to execute.
Default factory settings:
All settings are Fire.
All NACs & Relay are enabled as steady code.
and date & view history.
3.2 Main Menu
First screen to appear following login is the main menu:
3.2.1 SET (General Setup Menu)
Pressing 1 in main menu will enter general setup menu.
3.2.1.1 Defaults Setup
The Default setup allows the user to reset the panel to its manufacture default condition.
26
Page 28
All devices configuration has been deleted.
The default password code is 1967.
3.2.1.2 Date/Time Setup
DATE / TIME TYPE
1 . Amer 2 . Euro
Chooses between American or European date formats.
DATE: 10 / 03 / 10
TIME: 11 : 28
Adjust the date & time.
Press Enter to execute
LOOP MENU SETUP
1.CDR 2.Walk Test
3.Maintenance
1.CDR
2.Walk
3.Maintenance
This setup allows user to select date and time display types, set the date and time.
3.2.2 SLC Setup
The MA-1000 comes standard with 2 SLC loops (4 loops optional), with up to 200 points
on each loop. The loop Setup screens allows the user to define the behavior of each
loop.
3.2.2.1 CDR (Customer Data Record)
27
Page 29
CDR MENU SETUP
1.Veiw
2.SCAN DEVICES
1. View devices connected to SLC
2. Get addresses from SLC
L : 1 Addr : 001
Z:01 OPTICAL
Room 123
Floor 3
L : 2 is Empty
Scan Devices
(Erase CDR) Y/N
No
Caution :
Scan devices delete CDR!
Yes /No
Condor FACP
Ver 3.1000225.A.2
Scan Devices
Please Wait . . .
1. View
To view the desired loop press the right arrow key (number 6) presses the left arrow key
(number 4) to return to the first loop. Press the up & down arrow keys to view other
devices in the loop.
2. Scan devices Scan devices scans the loop for Pre-Programmed points used with the FS100 hand-
held programmer. Which was designed to program addresses of detectors & Interfaces
used with the MA-1000 fire panel? Although this programmer is not required to program
the detectors/interfaces, many installers find it easy and more convenient than the
standard empty base to the control panel programming method.
28
Page 30
Walk Test OFF
Alarms : 000
Sound:Yes
Loop:1
Walk Test ON
Loop:1
Alarms : 005
Sound:Yes
2. Walk test
Press Yes/No To activate Sounder (Must be connected
to NAC 1) option, then press Next to activate test.
During walk test, the display will show the number of
alarms. Each alarm will cause NAC 1 to fire up for 1
second and then the loop will be reset.
3.2.2.2 One Man Walk Test
Walk test mode allows a single engineer to test the various detectors and call points on
a system without always having to return to the panel either to reset the system or
silence the alarms.
When in WALK TEST MODE, the system operates as normal except that when a
detector or call point goes into alarm, the alarms only operate for a few seconds and
then will silence. The panel then tries to reset the device automatically and, if
successful, the alarms are operated again for a few seconds and the installation
engineer can move on to the next detector. After a full test has been carried out the
engineer can check the order in which the detectors/call points were operated using the
DISPLAY LOG mode. This information can also be printed on the optional printer.
When the panel is in “Walk Test Mode” the control panel inserts a different code into the
log and also onto the print-out. This is to distinguish between when a device has been
tested in “Walk Test Mode” and when a device has been triggered while in normal
operation.
The following differences will occur:
a) When in the LOG mode, "One man walk test”" will appear on the display followed by
the address text and device type.
b) On the printout a “One man walk test” message will appear will appear followed by
the address text and device type.
29
Page 31
To exit walk test mode, press Esc.
MAINTENANCE MENU
1.Learn 2.Flash
3.Point Flash
Autolearn will
Erase CDR Y/N
No
Caution :
Auto Learn delete data from Loop Card & from
devices
Yes /No
Commissioning.....
Self addressing features of system.
First device that physically connected to the loop
obtains the 1 address , second address 2,and etc.
Condor FACP
Ver 3.100225.A.2
Commissioning
Please Wait . . .
Erase CDR
Erase data from Loop Card
3.2.2.3 Maintenance Menu
1. Learn - Commissioning
2. Flash
If global LED flashing is set to on, all device LED’s will pulse intermittently to confirm
correct communication. Select (Global Flashing LED On/Off) from the Maintenance
Menu Screen.
Point flash will flash the chosen device LED.
30
Page 32
MAINTENANCEMENU
1.AnValue
2.GlobalFlash+
3.PointFlash
MAINTENANCE MENU
1.Learn 2.Flash+
3.Point Flash
By Pressing 2. Flash will flash all SLC devices (which
have an LED) + indicates that the function is on.
Point Flash
LOOP : 1
ADDR Device: 1
Test: OFF
Press NEXT TO Start/Stop TESTS(Led ON)
Press ←→ to change number and ↑↓ to change Loop
3. Point Flash
31
Page 33
1.2.3 Output Setup
SILENCE
When the Silence key is pressed the NAC will change state.
FIRE
NAC to turn on when a fire alarm condition exists
AUX Continuous
Power supply 24VDC.
AUX Resettable
Power supply 24VDC resettable (lost power for 2 sec after reset) .
Door Magnets
A steady 24VDC in an ALARM condition the AUX changes state to
OFF until RESET.
SUPERVISORY
NAC turns on when a supervisory condition exists.
CADENCE
NAC Cadence is where you choose the NAC type ON, March code,
ANSI S-3-41, Single stroke BI, California code, Wheelock.
Delay
Delay time 0-120 sec to trigger Nac On when a FIRE NAC is
selected. Each step 10 – sec.
Timer
Timer 0-120 sec to trigger Nac Off when a FIRE NAC is selected.
Each step 10 – sec.
Configured with MA-1000 Site Installer software.
Each NAC can be programmed to operate for a limited amount of time or continuously,
stay on during operation or operate using one of several on/off patterns as well as start
operation due to various conditions happening.
1.2.3.1 NAC Setup
! To advanced options please refer to appendix 4.9.
32
Page 34
3.2.3.2 CADENCE Setup
5 sec
on
5 sec
off
March Code Output
ANSI Code Output
Single Stroke BI
California Code
Wheelock Sync
5 sec on
5 sec off
1.5 sec off
1.9 sec off
5 sec off10 sec off
Synchronization for Wheelock audio devices
5 sec off5 sec on
5 sec on5 sec on5 sec on
5 sec off5 sec off
NAMEPattern Description
Cadence Patterns
The cadence patterns shown in the following table can be selected for NAC outputs. Each NAC can select an output
pattern.
33
Page 35
3.2.3.3 Relay Setup
SILENCE
When the Silence key is pressed the Relay will change state.
FIRE
Relays to turn on when a fire condition exists
SUPERVISORY
Relays to turn on when a supervisory condition exists.
TROUBLE
Relays to turn on when in trouble mode
Delay
Delay time 0-120 sec to trigger Relay On when a FIRE RELAY is
selected.
Each step 10 – sec.
Timer
Timer 0-120 sec to trigger Relay Off when a FIRE RELAY is selected.
Each step 10 – sec.
Each relay can be programmed to operate for a limited amount of time or continuously,
stay on during operation or operate using one of several on/off patterns as well as start
operation due to various conditions happening.
! To advanced options please refer to appendix 4.9.
34
Page 36
3.2.4 History Display
05/07 08:23:55
NO BATTERY
06/09 08:29:14
ALARM
CALLPOINT 2:001
Zone : 1
Press 3 In Main Menu.
06/09 08:29:14
SLC TROUBLE
ZONE MONT 1:011
Z: 1 SubAdr: --3
Press ↓ to next event.
Events will be displayed from newest to oldest, first screen will show date / time and
event type and ID:
35
Page 37
3.2.5 PC MENU
MAIN MENU
1.Set 2.SLC
3.History 4.PC
5.Device En/Dis
Press 4 In Main Menu
Initialization
Communication
with PC
Press Enter
Press Enter to start communication with PC.
Refer to Appendix 4.9 (PC user manual) for setup information.
Panel
Communication
with PC ...
Communication Screen
To Exit Press “End Communication” on PC program.
MAIN MENU
1.Set 2.SLC
3.History 4.PC
5.Device En/Dis
Press 5 In Main Menu
Loop Number
1
Press 1 or 2 to change Loop, then Enter
3.2.6 Device enable/disable
36
Page 38
Device Number
001
Press 0-9 to change device number , then Enter
L:1 Addr:001
Z: 01 CALLPOINT
ENABLE
Press NEXT TO ENABLE/DISABLE device
Then function is activated system going in to the trouble condition.
Up to 30 devices per loop can be disabling with "PC Program".
*** Not use "Scan Device" function, if chosen a "Disable Device” option.
! To advanced enable/disable options please refer to appendix 4.9
37
Page 39
3.2.7 NETWORK
Panel Name
Set Panel
Number (The
panel ID number)
Set Number of Panels in
the Network ( The amount
of panels in the
NETWORK)
Condor Panel N34
Ver 3.100225.A.1
Loop ver 3.0209
slave ver 0225B2
For checking current number of panel in the network
press Ack key.
N34 – Panel number 34.
Enable Network
Reset
This option enables the panel to be reset by the
network. If this option is not chosen the panel will
not be able to be reset by the network.
Enable Network
Silence
This option enables the panel to be silenced by
the network. If this option is not chosen the panel
will not be able to be silenced by the network.
!IMPORTANT! The NETWORK features have not been tested by ETL to UL864 until a
future date.
Refer to Appendix 4.10 for set-up information.
38
Page 40
ENTER PASSWORD:
****
INSERT PANEL
NUMBER: 1
3.2.8 Remote Annunciator
The remote Annunciator unit developed in order to give allowance users supervision
and control on the MA-1000 fire system from remote places. The unit connected to the
MA-1000 by RS485 communication port. You can connect up to 8 units per panel on
this port. The units have 4 lines display similar to the MA-1000 display and data
transferred from the MA-1000 to units show the same messages.
The Remote Annunciators enable/disable by PC program software FS MA-1000 Site
Installer running on PC and connected to MA-1000 by RS232 communication port.
You can silence or reset the MA-1000 from each unit.
The following describe how to program and control the MA-1000 from the Annunciator.
Press the ENTER key on Annunciator keyboard to enter your 4 digits password and
press ENTER. The default password is 1967.
Insert the Annunciator number [1: 8] and press ENTER.
Insert new USER access code and press ENTER. The default code is 1234.
39
Page 41
ACCESS CODE:
1234
ACCESS LEVEL: 1
1. Silence
2. Reset
3. Reset+Silence
ACCESS DENIED
There are 3 options of access levels for USERS silence, reset or both. Select
One of the options and press ENTER.
Now the Remote Annunciator is programmed and ready to use by the USERS.
In an alarm or trouble condition the USER press ENTER key and insert his access code
The USER can select Silence or Reset according to his selected options. If the USER
select reset when he allow to enter only silence the access would denied
Note: For more details refer to Appendix 4.6.
3.2.9 Booster
The Booster integrated to the system in order to enlarge the number of NAC’s and
RELAY’s output to the building and enable connection of more units to building than the
MA-1000 panel is permitted.
40
Page 42
The Booster has 4 programmable NAC’s, 3 programmable RELAY and common fire
alarm & trouble relay. Up to 8 boosters / annunciators can be connected per panel.
The Booster enable/disable by PC program software FS MA-1000 Site Installer running
on PC and connected to MA-1000 by RS232 communication port. Pressing on
Boosters/Annunciator tab will pop up the following window than mark the booster you
want to configure.
By pressing the Setting Booster tab you get the following pop up window.
41
Page 43
Screen
Description
BoostPan trb 1
1
Nac 1 Trouble on Booster 1
BoostPan trb 1
2
Nac 2 Trouble on Booster 1
BoostPan trb 1
3
Nac 3 Trouble on Booster 1
BoostPan trb 1
4
Nac 4 Trouble on Booster 1
BoostPan trb 1
5
Charger Fault on Booster 1
BoostPan trb 1
6
Ground Fault on Booster 1
BoostPan trb 1
7
AC Fault on Booster 1
BoostPan trb 1
8
No Battery on Booster 1
RS485 trbl
AB----- 1
No RS485 Connection to Boosters 1
Move the RS232 cable to Booster and press check connection tab. If OK than configure
the NACs and Relay. Write the data to the Booster and press the End connection tab.
Return the RS232 cable to MA-1000, check communication and press the End
communication tab. This will insert hardware reset to MA-1000 and system initialization.
TROUBLES DESCRIPTION
Refer to Appendix 4.9 for more information
3.3 GAS Releasing
Gas A
GAS A is used for releasing operation for a room.
The following set-up of the panel parameters:
1. FSUOM-G= >Output double knock & MCP Override .Trigger by
address only = Must only be connected to sounder 1 the FSUOM-G
module has built in timers for the use of releasing gas with a 30 second
delay ON and a 15 second delay off to prevent the solenoid
overheating.
42
Page 44
2. FSUOM-S=> The FSUOM-S is used for the Internal Horn and external
lamp according to its usage as stated below. The sounders are nonsilenceable both sounders 1& 2 may be used for this operation.
Two or more detectors and a call-point (manual pull) must be grouped ( by address),
when one detector detects an alarm the panel will go into a normal alarm condition the
alarm relay will change state, the alarm led will activate including the nac ‘s.
When the second detector detects an alarm condition the global alarm nac will activate
(silenceable), output of the FSUOM-S will activate the internal horn and the external
lamp after 30 seconds the output of the FSUOM-G (Solenoid) will activate. FSUOM-G
and will deactivate after 12 seconds.
When operating the call-point (manual pull) at any-time will activate the solenoid as an
xzone.
An example of GAS release screen
GAS B
GASB is used for releasing operation “Aerosol usage”.
The following set-up of the panel parameters and FSUOM-G occur:
FSUOM-G => Output = Double knock & MCP Override, trigger by zone. Release time
30 seconds.
43
Page 45
Two or more detectors and a call-point must be grouped( by zone), when one detector
detects an alarm condition the panel treats that alarm condition as a normal alarm
condition the alarm relay will change state, the alarm led will activate, nac will activate
(silenceable).
When the second detector detects an alarm condition the common alarm nac will
activate (silenceable), output of FSUOM-G will activate after 30 seconds and will
deactivate after 12 seconds.
When operating the call-point at any-time will activate the solenoid
A example of GAS release screen
3.4 Remote Annunciator
The remote Annunciator device developed in order to give allowance users supervision
and control on the MA-1000 fire system from remote places. The unit connected by
RS485 communication port to the MA-1000. You can connect up to 8 units on this port.
The unit has 4 lines display similar to the MA-1000 display and show the same
messages.
44
Page 46
SLC Installation
LED FS251/D
Class A Style D
1
2
1
1
2
1
-VE COM IN
Class A ONLY
Loop1
Loop2
S
+
S
+
S-
S-
F-
F
+
F
+
F-
2
2
4
4
3
3
+ -
E
E
E
E
+VIN
-VE COM OUT
-VE COM IN
SECTION 4 Appendixes
Appendix 4.1
Data Sheet for FSUTLC
Version# 001
SLC Circuits
The MA-1000 Panel comes with two SLCs (one loop card) which have the following
parameters:
Supply voltage: 24VDC
Addressable Loops
Max Number: 2
Max Loop Load per loop: 60 mA
Max Number of Addressable Devices per loop: 200
Loop lengths: The maximum permitted loop length is 2 km measured from the near to
the far terminals.
The total number of addresses per loop is 200; this includes detectors, manual pulls and
all other addressable items. When designing systems it’s recommended that
allowances are made for future expansion, Short circuit isolators are incorporated into
every MA-1000 loop device, including Smoke detectors, heat detectors, manual pulls
and interfaces. Therefore, no further fault protection is required, in the event of a single
fault; none of the devices connected to the loop will fail to operate as the fault will be
isolated by the two adjacent devices.
45
Page 47
Appendix 4.2
UL864 9th Edition
Installation Instructions for:
3 Channel I/O Unit MA-3I3O
Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface mounting back-box.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according to the diagram below.
Notes: No addressing of the interface is required. See control panel operation for details.
Standard Connections
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistor must always be fitted, even if the inputs are unused.
3. Monitored inputs can detect open or short circuit faults.
4. Output relays are volt-free contacts and are not monitored..
46
Page 48
Specifications
Loop Load
Min
Nom
Max
Units
Quiescent Current
310
A
Operating Voltage
18 30
V DC
Inputs
Trigger Resistance
5.6
k
End Of Line Resistor
22
k
Short Circuit Fault Threshold Resistance
1
k
Open Circuit Fault Threshold Resistance
33
k
Output Relays
Switching Voltage
24
30
VDC
Contact Rating
1
A
Switching Power
30 W
Environmental
Operating Temperature
-10 +60
°C
Humidity (Non Condensing)
95
%RH
Standards
UL864 9th Edition
Compatibility
Suitable for use with MA-1000 Analog Addressable Fire
Panels
Physical
Dimensions 147 x 88 x 57 (mm)
Weight 0.25kg
Ingress Protection IP40
Short Circuit Isolator
This addressable device contains an integral short circuit isolator, which operates between the – IN
terminal and the
– OUT terminal. The isolator operates in conjunction with the MA-1000 Analog Addressable Fire Panel
when a low parallel resistance fault of typically 200Ω is present between the +VE and –VE of the loop
wiring.
47
Page 49
Short Circuit Isolation Data
(Integral with each device)
Total Loop Resistance for correct
operation of short circuit isolator
50Ω (max)
Continuous Current allowable through
isolator
700mA (max)
Isolator Resistance in closed state0.13Ω (max)
Leakage Current into direct short
circuit with isolator open
13mA (max)
Parallel Fault Resistance to be seen at
the Control Panel for isolators to open
200Ω (typ)
48
Page 50
Appendix 4.3
35 mm
18.5 mm
63 mm
Dimensions
Mounting Details (Drilling positions, template over leaf)
37.5mm
20 mm
Approved to UL864
Installation Instructions for:
Mini Input Monitor MA-IN
Installation
1. Fit the box in position using the mounting details below.
2. Connect the unit according to the diagram below.
Notes:
No addressing of the interface is required. See control panel operation for details.
This needs to be programmed as a call point on site installed PC software.
Standard Connections
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistor provided must always be fitted, even if the input is unused.
3. Monitored inputs can detect open or short circuit faults.
49
Page 51
Specifications
Loop Load
Min
Nom
Max
Units
Quiescent Current
310 mA
Operating Voltage
18 30
VDC
Inputs
Trigger Resistance
5.6
End Of Line Resistor
22
Short Circuit Fault Threshold Resistance
1
Open Circuit Fault Threshold Resistance
33
Environmental
Operating Temperature
-10 +60
°C
Humidity (Non Condensing)
95
%RH
Standards
UL864 9th Edition
Compatibility
Suitable for use with analog addressable panels
Physical
Dimensions 63mm x 35mm x 18.5mm
Weight > 0.1gm
Ingress Protection IP40
Short Circuit Isolation Data
(Integral with each device)
Total Loop Resistance for correct
operation of short circuit isolator
50Ω (max)
Continuous Current allowable through
isolator
700mA (max)
Isolator Resistance in closed state0.13Ω (max)
Leakage Current into direct short
circuit with isolator open
13mA (max)
Parallel Fault Resistance to be seen at
the Control Panel for isolators to open
200Ω (typ)
Short Circuit Isolator
This addressable device contains an integral short circuit isolator, which operates between the – IN
terminal and the
– OUT terminal. The isolator operates in conjunction MA-1000 Control Panel when a low parallel
resistance fault of typically 200Ω is present between the +VE and –VE of the loop wiring.
50
Page 52
Appendix 4.4
+ -
+ -
- +
UL864 9th Edition
Installation Instructions for:
Output Monitor MA-2120
Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface mounting back-box.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according to the diagram below.
Notes:
No addressing of the interface is required. See control panel operation for details.
Standard Connections
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistor must always be fitted, even if the spur is unused.
51
Page 53
Specifications
Loop Load
Min
Nom
Max
Units
Quiescent Current
300 mA Sounder Circuits
External PSU Input Voltage
20
24
30 V External PSU Current Rating
1 A Sounder Load (Each Channel)
300
mA
End Of Line Resistance
12±5%
k External PSU Monitor Input
End Of Line Resistance
12±5%
k
Fault Input Trigger Resistance
100
Environmental
Operating Temperature
-10 +60
°C
Humidity (Non Condensing)
95
%rh
Standards
UL864 9th Edition
Compatibility
Suitable for use with MA-1000 Analog Addressable Fire Panels
Physical
Dimensions 147 x 88 x 57 (mm)
Weight 0.25kg
Ingress Protection IP40
Short Circuit Isolation Data
(Integral with each device)
Total Loop Resistance for correct
operation of short circuit isolator
50Ω (max)
Continuous Current allowable through
isolator
700mA (max)
Isolator Resistance in closed state0.13Ω (max)
Leakage Current into direct short
circuit with isolator open
13mA (max)
Parallel Fault Resistance to be seen at
the Control Panel for isolators to open
200Ω (typ)
Short Circuit Isolator
This addressable device contains an integral short circuit isolator, which operates between the – IN
terminal and the
– OUT terminal. The isolator operates in conjunction with Analog Addressable Control Panels when a
low parallel resistance fault of typically 200Ω is present between the +VE and –VE of the loop wiring.
Appendix 4.5
52
Page 54
Installation Instructions for:
UL864 9th Edition
T-tap MA-TA
Installation
1. Fit the unit in position.
2. Connect the unit according to the diagram below.
Notes:
A T-tap Isolator must be used when making T-taps (Class B) from the SLC loop. Without this unit, the self
addressing features of the system will not function correctly.
No addressing of the interface is required. See control panel operation for details.
Standard Connections
Notes:
53
Page 55
1. Only connect cable screen to its adjacent earth terminal.
Loop Load
Min
Nom
Max
Units
Quiescent Current
170
A
Operating Voltage
18 30
VDC
Environmental
Operating Temperature
-10 +60
°C
Humidity
95
%RH
Standards
UL864 9th Edition
Compatibility
Suitable for use with MA-1000 Analog Addressable Fire Panels
Physical
Dimensions 98 x 42 x 32
Weight 0.05kg
Ingress Protection IP30
Short Circuit Isolation Data
(Integral with each device)
Total Loop Resistance for correct
operation of short circuit isolator
50Ω (max)
Continuous Current allowable through
isolator
700mA (max)
Isolator Resistance in closed state0.13Ω (max)
Leakage Current into direct short
circuit with isolator open
13mA (max)
Parallel Fault Resistance to be seen at
the Control Panel for isolators to open
200Ω (typ)
2. This unit can only be used FS analog range of detector bases and compatible detectors.
Specifications
Short Circuit Isolator
This addressable device contains an integral short circuit isolator, which operates between the – IN
terminal and the
– OUT terminal. The isolator operates in conjunction with MA-1000 Control Panel when a low parallel
resistance fault of typically 200Ω is present between the +VE and –VE of the loop wiring.
Appendix 4.6
54
Page 56
Installation Instructions for:
UL864 9th Edition
Remote Annunciator MA-1050
Installation
1. Connect the unit according to the diagram below.
Notes:
No addressing of the interface is required. See control panel operation for details.
Standard Connections
Electrical Specifications
OperatingVoltage: 16-26VDC
55
Page 57
Standby Current: 12 mA max
Alarm Current: 30 mA
Wiring Distance: 3,300ft max from FACP (depending on wire gauge and number of devices on the RS
Compatibility: Suitable for use with analog addressable panels.
Physical Dimensions: 160mm x 160mm x 44 mm
Engineering Specifications
The fire system should contain a built-in annunciator and should support up to eight remote annunciators.
Remote annunciators will have the identical control & display layout to match the appearance of the builtin annunciator.
The Remote annunciators shall have the same functionality and operation as the built-in annunciator. All
annunciators have a 64-character LCD display and have five LEDs for: Alarm, Supervisory, System
Trouble, System Silence, and System Power.
The annunciator will be able to silence and reset alarms through the use of a code entered on the
annunciator keypad or by using a firefighter’s key. The annunciator has two levels of user codes that will
limit the operating system programming to authorized persons.
Description
The Remote annunciators include an4 line with 64-character backlit LCD providing easy-to understand
messages. The annunciator has an easy friendly membrane keypad. The most used keys Reset and
Silence are larger and colored. In addition to status messages displayed on the LCD, there are five LEDs
for alarm, supervisory, trouble, silence, and AC power status. The annunciator enclosure can be surface
or flush mounted.
Features
• 64-character backlit LCD display (4 lines with 16 characters on each line)
• Membrane Keypad
• Accepts user codes or fire fighter’s key
• Larger keypad buttons for system reset and silence
• Five status LEDs for alarm, supervisory, trouble, silence
and AC power conditions
• Wiring lengths up to 3300 ft. from the FACP
(Depending on wire gauge and number of devices on RS485)
• ETL listed, complies with NFPA 72
Appendix 4.7
56
Page 58
Installation Instructions for:
Loop In
Loop Out
Analogue Addressable Loop
35 mm
18.5 mm
63 mm
Dimensions
Mounting Details (Drilling positions, template over leaf)
37.5mm
20 mm
UL864 9th Edition
Mini Output Monitor MA-OR
Installation
1. Fit the box in position using the mounting details below.
2. Connect the unit according to the diagram below.
3. Recommended cable Type FPLP (plenum cable), Type FPLR (riser cable), or Type FPL
Standard Connections
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. Output relay are volt-free contacts and are not monitored.
Specification
57
Page 59
Loop Load
Min
Nom
Max
Units
Quiescent Current
310
A
Operating Voltage
18 30
V DC
Output Relay
Switching Voltage
24
30
V DC
Contact Rating
1 A Switching Power
30
W
Environmental
Operating Temperature
-10 +60
°C
Humidity (Non Condensing)
95
%RH
Standards
UL864 9th Edition
Compatibility
Suitable for use with FS Analog Addressable Fire
Systems
Physical
Dimensions 63mm x 35mm x 18.5mm
Weight >0.1kg
Ingress Protection IP40
Short Circuit Isolation Data
(Integral with each device)
Total Loop Resistance for correct
operation of short circuit isolator
50Ω (max)
Continuous Current allowable through
isolator
700mA (max)
Isolator Resistance in closed state0.13Ω (max)
Leakage Current into direct short
circuit with isolator open
13mA (max)
Parallel Fault Resistance to be seen at
the Control Panel for isolators to open
200Ω (typ)
Short Circuit Isolator
This addressable device contains an integral short circuit isolator, which operates between the – IN terminal and the
– OUT terminal. The isolator operates in conjunction with MA-1000 Control Panel when a low parallel resistance
fault of typically 200Ω is present between the +VE and –VE of the loop wiring.
58
Page 60
Appendix 4.8
35 mm
18.5 mm
63 mm
Dimensions
Mounting Details
(Drilling positions, template over leaf)
37.5mm
20 mm
UL864 9th Edition
Installation Instructions for:
Mini Zone Monitor MA-ZONE
Installation
1. Fit the box in position using the mounting details below.
2. Connect the unit according to the diagram below.
3. Recommended cable Type FPLP (plenum cable), Type FPLR (riser cable), or Type FPL
Standard Connections
Notes:
1. The FSUMZM can only be used with FS Conventional range.
2. Only connect cable screen to its adjacent earth terminal.
3. The end of line device is EOLM-1 (supplied) must always be fitted.
59
Page 61
Specifications
Loop Load
Min
Nom
Max
Units
Quiescent Current
2.6 mA
Load With 20 FS Detectors
3.2 mA
Alarm Condition Load, with 20 Conventional Detectors
8
mA
Supply Voltage
18 30 V
Detector Zone
18 30
VDC
Number of Detectors per Zone
0 20 End of Line Monitor EOLM
ACTIVE END OF LINE DEVICE
Fire Input Trigger Resistance
680
Short Circuit Fault Threshold Resistance
100 Open Circuit Fault Threshold Resistance
39
Environmental
Operating Temperature
-10 +60
°C
Humidity
95
%RH
Standards
UL864 9th Edition
Compatibility
Suitable for use with MA-1000 Analog Addressable Fire
Panels
Physical
Dimensions 63 x 35 x 18.5 (mm)
Weight 0.28kg
Ingress Protection IP30
Short Circuit Isolation Data
(Integral with each device)
Total Loop Resistance for correct
operation of short circuit isolator
50Ω (max)
Continuous Current allowable through
isolator
700mA (max)
Isolator Resistance in closed state0.13Ω (max)
Leakage Current into direct short
circuit with isolator open
13mA (max)
Parallel Fault Resistance to be seen at
the Control Panel for isolators to open
200Ω (typ)
Short Circuit Isolator
This addressable device contains an integral short circuit isolator, which operates between the – IN terminal and the
– OUT terminal. The isolator operates in conjunction with MA-1000 Control Panel when a low parallel resistance
fault of typically 200Ω is present between the +VE and –VE of the loop wiring.
60
Page 62
Appendix 4.9
MA-1000
Site Installer
User Manual
61
Page 63
62
Page 64
63
1. Installation
1.1 Removing Previous Versions
Before the new software can be installed, it is recommended to uninstall any previous versions. This can be done
by following the steps shown below: -
1. Open the Start Menu and select Control Panel.
2. On Windows 2000/XP/Vista/7 select Add/Remove Programs, or if using Windows Vista/7, select
Uninstall a Program.
3. Find MA-1000SI application in the items displayed and select it.
4. Now select the Remove or Uninstall option to remove the software.
5. Windows may now ask permission to continue. If this is the case, simply confirm the action by selecting
Yes / Continue.
6. The old version of the software will now be removed.
1.2 Installing the Software
To install the software, do the following: -
1 The software requires that Microsoft Office Excel is installed
2 Locate the file Setup_MA-1000.exe and launch it. If the software was supplied on CD, this can be found by
browsing the CD using Windows Explorer (shortcut is Windows Key + E).
3 The software will now install.
4 Please follow any instructions displayed on the screen.
Page 65
64
2 Using Site Installer
2.1 Starting the Application
The software can either be launched from the desktop, via the MA-1000 shortcut or by opening the Start Menu |
Programs | folder and selecting MA-1000.
2.1.1 Software License Key
The first time the software is started and at specific intervals (usually every 12 months), a screen similar to the
one shown in Figure 1 will be displayed.
FIGURE 1 - License Key Dialog
When this appears, it will be necessary to contact , quote the code displayed and a license key will be provided,
which will unlock the functionality of the software.
The purpose of licensing the software is to prevent unauthorized use of the software and to ensure that it is
updated at regular intervals.
Page 66
65
2.2 Configuring a Panel
2.2.1 Creating a Panel Configuration File
To start a new site configuration, it is first necessary to create a site configuration file. This can be done by
following these steps: -
1. Using the File menu select New Panel.
2. Enter a name for the panel file (it is good practice to use the same name as the site to be configured).
3. Select a location where the file will be stored.
4. Now select Open to create the panel file.
5. A screen similar to the one shown in FIGURE 2 will be displayed: -
FIGURE 2 - The screen displayed when a new panel has been created.
Page 67
66
2.2.2 Retrieving a New Panel Configuration
To retrieve a new panel configuration, follow the steps below: -
1. Open the panel file if not already open (if this has not been created, refer to 2.2.1).
2. Ensure the panel has been auto-learned.
3. Connect the computer to the display card of the fire panel using a 9-way serial cable. This cable must
include the connections shown below in FIGURE 3. If the computer does not have a serial port, a USB to
RS232 adaptor will also be needed (see below): -
Converter
USB RS232
Pin Name
3
Rx
2 Tx
5 Signal GND
Pin Name
2
Tx
3 Rx
5 Signal GND
Optional
9 pin connector on
display card
FIGURE 3 - Shows the connection between the PC and panel.
4. Go to the Setting menu and choose Com Port. A screen like the one shown below will be displayed:
FIGURE 4 - Serial Communications Dialog
Page 68
67
5. Using the drop down box, select the communications port (1-9) that will be used to physically connect to the
panel and then select Ok.
6. Place the panel into SLC menu setup - CDR and select the Learn or SCAN Devices menu options from the
menu choices displayed on the panel.
7. Select PC from the menu choices displayed on the panel and then select ENTER.
8. This must be done BEFORE the next step; otherwise communications will not be possible.
9. Select the Check Connection button on the PC software.
10. Select the Read from Panel button on the PC software (see FIGURE 2).
11. The panel configuration will now be transferred to the PC. If this does not occur, double check the connections
using Check Connection button and repeat these steps again.
Page 69
68
2.2.3 Moving Devices to a Different Zone
Once a new panel configuration has been retrieved, the next thing to do is to define the zones. To do this, follow
the steps below: -
1. Select the first loop of the panel in the overview window. A screen similar to the one shown below will
be displayed: -
FIGURE 5 - Loop Editor
2. Select the devices to move, which are displayed below the Source Zone control.
(Shift + LEFT MOUSE BUTTON can be used to select multiple devices)
Page 70
69
3. Choose the Change Zone button to display a window similar to the one shown below: -
FIGURE 6 - Change Zone Screen
3. Select the zone the device(s) are to be moved to, using the Zone drop down control.
4. Select Change button to move the devices to the new zone.
5. Repeat as required, then choose the Close button
Page 71
70
Page 72
71
2.2.4 Configuring Device Location Text
To configure the text of devices, select the Descriptions button, then choose the Loop devices button as
shown below in FIGURE 7: -
FIGURE 7 – Configuring location text using the Device Description
You can view/edit current text of selected device as shown below in FIGURE 8a:
FIGURE 8a
Page 73
72
2.2.5 Configuring Zone Location Text
To configure the text of zones, select the Descriptions button, and then choose the Zone button.
Page 74
73
2.2.6 Configuring Device Input Settings
To configure the input settings of a device, left click on the device and then select DeviceInputs.
This will bring up the screen shown below in FIGURE 9: -
FIGURE 9 - Device Input Settings
FIGURE 10 - Device Input Settings
To select which input to configure, set the input number at the top of the window.
For single input devices, such as detectors, this will always be set to one.
Page 75
74
2.2.7 Configuring Device Output Settings
To configure the output settings of a device, left click on the device and then select Device Outputs.
The screen shown below in FIGURE 11 will then appear: -
FIGURE 11 - Device Output Settings
For a multi-output device, the output number can be changed at the top of the window, to allow settings to be
defined for each individual output.
1. Each output can be trigger by:
Address – Any point address from the list (allocated devices) up to 16 may be chosen.
Zone – Any zone from the list (allocated devices) up to 16 may be chosen.
Global – Any address or zone will trigger the output.
2. Double-knock – Any two devices from the allocated list, when the two devices from the
list enter an Alarm condition, the chosen output will enable. For the Global settings any 2
devices in alarm condition.
MCP Override – When any manual pull from the allocated list will trigger the chosen
output will enable even in an X-cross situation.
3. Delay time- from 1 to 10 minutes.
Additional setting for the loop sounders.
Sounder Volume: low, medium or high
Sounder Tone: Continuous, Two tone, Slow whoop.
Page 76
75
FIGURE 12 – Allocated devices list
Page 77
76
2.2.8 Configuring MA-1000 Onboard Outputs
To set the operating condition of onboard output circuits, select the NACs or Relays button, as indicated below in
FIGURE 13: -
SILENCE
When the Silence key is pressed the NAC turn off.
FIRE
NAC to turn on when a fire alarm condition exists
AUX Continuous
Power supply 24VDC.
AUX Resettable
Power supply 24VDC resettable (lost power for 2 sec after reset).
Door Magnets
A steady 24VDC in an ALARM condition the AUX changes state to OFF until
RESET.
SUPERVISORY
NAC turns on when a supervisory condition exists.
CADENCE
NAC Cadence is where you choose the NAC type ON, March code,
ANSI S-3-41, Single stroke BI, California code, Wheelock.
Delay
Delay time 0-120 sec to trigger Nac On when FIRE NAC is selected.
Each step 10 –sec.
Timer
Timer 0-120 sec to trigger Nac Off when FIRE NAC is selected.
Each step 10 –sec.
Page 78
77
Nac Cadence Setup
5 sec
on
5 sec
off
March Code Output
ANSI Code Output
Single Stroke BI
California Code
Wheelock Sync
5 sec on
5 sec off
1.5 sec off
1.9 sec off
5 sec off10 sec off
Synchronization for Wheelock audio devices
5 sec off5 sec on
5 sec on5 sec on5 sec on
5 sec off5 sec off
NAMEPattern Description
Cadence Patterns
The cadence patterns shown in the following table can be selected for NAC outputs. Each NAC can select an output
pattern.
Page 79
78
FIGURE 13 - Panel Outputs
SILENCE
When the Silence key is pressed the Relay turn off.
FIRE
Relays to turn on when a fire condition exists
TROUBLE
Relays to turn on when in trouble mode
SUPERVISORY
Relays to turn on when a supervisory condition exists.
Delay
Delay time 0-120 sec to trigger Relay On when FIRE RELAY is selected.
Each step 10 –sec.
Timer
Timer 0-120 sec to trigger Relay Off when FIRE RELAY is selected.
Each step 10 –sec.
Each Nac or Relay can be trigger by:
Global – Any address or zone will trigger the output.
Double Knock – Any 2 alarms from any address or zone will trigger the output.
Address – Any point address from the list (allocated devices) up to 16, may be chosen.
Zone – Any zone from the list (allocated devices) up to 16 may be chosen.
XAddress - Any devices from the allocated list up to 16, when all of them from the list enter
an Alarm condition the chosen Nac (Relay) will enable.
XZone - Any zone from the allocated list up to 16, when all of them from the list enter an Alarm
condition the chosen Nac (Relay) will enable.
MCP Override – When any manual pull from the allocated list will trigger the chosen
Nac (Relay) will enable even in an X-cross situation.
Alarms in one zone - Up to 8 alarms together from the one chosen zone can trigger the Nac
(Relay).
Page 80
79
FIGURE 14 – Allocated List
Page 81
80
2.2.9 Configuring the Remote Annunciators and Power Boosters
1.To set the operating condition of Remote Annunciators and Power Boosters, select the Boosters/Annunciators
button, as indicated below in FIGURE 13: -
FIGURE 15 – Boosters/Annunciators
4. To enable the Remote Annunciators or Power Boosters, select the checkbox.
5. To configuring the Power Booster selects the Setting Booster Panel button as indicated below in FIGURE
13.
6. Configuration of Nac’s and Relays is same as the MA-1000 Panel.
Page 82
81
FIGURE 16 – Power Booster Settings.
7. To send or retrieve configurations connect the computer to the Booster panel.
8. Select the Check Connection button
9. This must be done BEFORE the next step; otherwise communications will not be possible.
10. Select the Write data or Read data button on the PC software (see FIGURE 2).
11. Select End communications button to reset panel.
Page 83
82
2.2.10 Add / Remove devices from PC software
1. Select the empty place to add, as displayed below.
(Shift + LEFT MOUSE BUTTON can be used to select multiple places)
FIGURE 17 – Select empty place.
2. Select Add device button.
3. Choose device from the list, as displayed below.
4. Select Add Device button.
FIGURE 18 – Select Device.
5. Select the devices to remove, as displayed below.
(Shift + LEFT MOUSE BUTTON can be used to select multiple places)
Page 84
83
6. Select Delete Device button.
FIGURE 19 – Select Device.
Page 85
84
2.2.11 Replace Device
1. Select the device to replace, as displayed below.
FIGURE 20 – Select device.
7. Select Replace Device button.
8. Choose device from the list, as displayed below.
9. Select Apply button.
Page 86
85
2.2.12 Report
1. Select Report button.
FIGURE 21 – Report.
2. Choose report type.
1. Full html report.
2. Loop outputs.
3. Nac/Relay/Booster.
Page 87
86
FIGURE 20 – Save Report as.
FIGURE 21 – View report.
3. Report will display automatically in the default browser.
Loop outputs:
Page 88
87
Save as TXT format:
Page 89
88
Panel outputs:
Save as EXEL format
Page 90
89
2.2.13 History (Events)
1. Select Read History button.
FIGURE 23 – Read History
FIGURE 23 – Save Event list
Page 91
90
FIGURE 21 – View Event
2. History will display automatically in the default browser.
Page 92
91
2.2.14 Networking
Up to sixty three MA-1000 panels can be networked together to operate as a single networked
system. To achieve this each panel must be fitted with a network card.
When operating as a networked system all fire and fault information is displayed at every panel,
silencing and resetting of alarms can also be carried out from any panel on a networked system if
panels are suitably configured.
The PC Software enables the address, location text, device type and any comments to be
downloaded to the MA-1000 panels.
The software can download to all 63 networkable Panels.
The PC is connected to each Panel on the network in turn. All data for the Panel is downloaded.
For networked systems, panels are identified by panel number, P1, P2 etc.
NETWORK SETUP
1. From PC program set panel id number.
2. Set number of panels in the network (amount of panels)
3. Write Panel name.
Panel Name
Set Panel
Number (The
panel ID
number)
Set Number of Panels in the
Network ( The amount of
panels in the NETWORK)
To create the network project:
1. Select project button.
2. Choose ‘New/Open file project’ from the list, as displayed below.
3. Select Management Panels button.
Enable Network
Reset
This option enables the panel to be reset by the
network. If this option is not chosen the panel
will not be able to be reset by the network.
Enable Network
Silence
This option enables the panel to be silenced by
the network. If this option is not chosen the
panel will not be able to be silenced by the
network.
Page 93
92
4. Select Add panel or Delete panel
5. Select/Close to apply
Page 94
93
2.2.15 Disable/Enable Device
1. Select the devices to disable, as displayed below.
2. Select Disable/Enable Device button.
3. Select Yes/No to permit.
** Up to 30 devices per loop can be disabling.
*** Not use "Scan Device" function, if chosen a "Disable Device” option.
Page 95
94
2.2.16 Monitoring
Monitoring - this is an events in real time.
1. Connect the computer to the MA-1000 fire panel as previously described in Figure 3.
2. Go to the Setting menu and choose Com Port.
3. Select Monitoring button.
FIGURE – Monitoring window
a. Select "Silence" or "Reset" button, to send same commands to the MA-1000 Panel.
b. Switch between main and monitoring window.
c. Check connections of the panels in the network
d. Options to lock or unlock the monitoring window. (To unlock, use the password for user 1 in current
project).
Page 96
95
2.2.17 Sending Configuration data to the Panel
To send a configuration data to the panel, follow the steps below: -
1. Open the panel file, if not already open.
2. Connect the computer to the MA-1000 fire panel as previously described in Figure 3.
3. Go to the Setting menu and choose Com Port. A screen like the one shown below will be displayed:
FIGURE - Communications Port Window
4. Select PC from the menu choices displayed on the panel and then select ENTER.
5. This must be done BEFORE the next step; otherwise communications will not be possible.
6. Select the Check Connection button on the PC software (see FIGURE 2).
7. Select the Write to Panel button on the PC software.
8. The information configured in the PC software will then be transmitted.
9. Select End Communications button to reset panel.
10.
e. Events can be filtered by: Alarms or Troubles.
f. Save or erase the events.
Page 97
96
2.2.18 Get Analog value of photo detectors
1. Connect the computer to the MA-1000 fire panel as previously described in Figure 3.
2. Go to the Setting menu and choose Com Port.
3. Select Detector analog value button.
Page 98
97
Page 99
98
2.2.19 User Passwords
The MA-1000 can remember up to 16 separate user codes. Each user code can be assigned one of two access
levels:
Installer
Manager / User
Only installers may change the system setup.
Manager/User is not allowed to change the system setup, they are to use walk test, time and date & view history.
Go to the Setting menu and choose User Passwords.
A screen like the one shown below will be displayed:
1. Select the User number to change (1-16).
Page 100
99
2. Select User type button to change user type (INSTALLER or USER).
3. Enter a password (4 digits), then choose the Apply button. If code already exists, system will display
"Code already exist" .The system will not allow for simple codes such as 1111, 4444 or 1234.
4. To ERASE a User Number select User type- NONE.
Note: example of USER screen.
MAIN USER MENU
1. Date/Time
2.Walk test
3.History
2. Allows changes for the times and date.
3. Walk test
4. History
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.