MTE RL-00231, RL-00214, RL-00413, RL-00403, RL-00234 Technical Reference Manual

...
Page 1
RL Line/Load Reactors
208V – 690V
TECHNICAL REFERENCE MANUAL
WARNING
High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.
Quick Reference
Performance Data
Pages 5 - 7
Selection Guide
Pages 8 - 35
Installation Guide
Pages 36 - 42
Start-up/Troubleshooting
Pages 43 - 45
Page 2
This page intentionally left blank
Page 3
RL Reactors Technical Reference Manual 208V – 690V
Form: RL-TRM-E April 2019 REV. 001 III
TABLE OF CONTENTS
RL LINE/LOAD REACTORS ...................................................................................................................... III
1. SAFETY .................................................................................................................................................... 1
WARNINGS AND CAUTIONS ........................................................................................................ 1
GENERAL SAFETY INSTRUCTIONS .............................................................................................. 2
2. GENERAL INFORMATION ...................................................................................................................... 3
RECEIPT & REPAIR STATEMENT ................................................................................................. 3
ENCLOSURES ........................................................................................................................... 4
AGENCY APPROVALS ................................................................................................................ 4
WARRANTY .............................................................................................................................. 4
3. RL LINE/LOAD REACTORS PERFORMANCE DATA ........................................................................... 5
PERFORMANCE SPECIFICATIONS ............................................................................................... 5
AUDIBLE NOISE......................................................................................................................... 6
SERVICE FACTOR ..................................................................................................................... 6
PWM / IGBT PROTECTION ........................................................................................................ 6
HARMONIC ATTENUATION .......................................................................................................... 6
ALTITUDE DERATING ................................................................................................................. 7
TEMPERATURE DERATING ......................................................................................................... 7
4. HOW TO SELECT .................................................................................................................................... 8
SELECTION GUIDE .................................................................................................................... 8
UNDERSTANDING THE RL LINE/LOAD REACTOR PART NUMBER: .................................................. 9
RL LINE/LOAD REACTOR OPTIONS: ....................................................................................... 10
Lug Option Details: ............................................................................................................................. 10
RL LINE/LOAD REACTORS 120V600V SINGLE PHASE ........................................................... 11
Part Number Selection Tables ........................................................................................................... 11
RL LINE/LOAD REACTORS 208 VOLTS, 60HZ ............................................................................ 12
Part Number Selection Tables ........................................................................................................... 12
RL LINE/LOAD REACTORS 208 VOLTS, 60HZ ............................................................................ 13
Part Number Selection Tables ........................................................................................................... 13
RL LINE/LOAD REACTORS 240 VOLTS, 60HZ ............................................................................ 14
Part Number Selection Tables ........................................................................................................... 14
RL LINE/LOAD REACTORS 240 VOLTS, 60HZ ............................................................................ 15
Part Number Selection Tables ........................................................................................................... 15
RL LINE/LOAD REACTORS 400 VOLTS, 50HZ ............................................................................ 16
Part Number Selection Tables ........................................................................................................... 16
RL LINE/LOAD REACTORS 400 VOLTS, 50HZ ............................................................................ 17
Part Number Selection Tables ........................................................................................................... 17
RL LINE/LOAD REACTORS 480 VOLTS, 60HZ ............................................................................ 18
Part Number Selection Tables ........................................................................................................... 18
RL LINE/LOAD REACTORS 480 VOLTS, 60HZ ............................................................................ 19
Part Number Selection Tables ........................................................................................................... 19
RL LINE/LOAD REACTORS 600 VOLTS, 60HZ ............................................................................ 20
Part Number Selection Tables ........................................................................................................... 20
RL LINE/LOAD REACTORS 600 VOLTS, 60HZ ............................................................................ 21
Part Number Selection Tables ........................................................................................................... 21
RL LINE/LOAD REACTORS 690 VOLTS, 50HZ ............................................................................ 22
Part Number Selection Tables ........................................................................................................... 22
RL LINE/LOAD REACTORS 690 VOLTS, 50HZ ............................................................................ 23
Part Number Selection Tables ........................................................................................................... 23
RL LINE/LOAD REACTORS ....................................................................................................... 24
Page 4
RL Reactors Technical Reference Manual 208V 690V
IV Form: RL-TRM-E April 2019 REV. 001
Open Dimension Reference ............................................................................................................... 24
RL LINE/LOAD REACTORS ....................................................................................................... 25
Technical and Mechanical Specifications ........................................................................................... 25
RL LINE/LOAD REACTORS ....................................................................................................... 26
Technical and Mechanical Specifications ........................................................................................... 26
RL LINE/LOAD REACTORS ....................................................................................................... 27
Technical and Mechanical Specifications ........................................................................................... 27
RL LINE/LOAD REACTORS ....................................................................................................... 28
Technical and Mechanical Specifications ........................................................................................... 28
RL LINE/LOAD REACTORS ....................................................................................................... 29
Technical and Mechanical Specifications ........................................................................................... 29
RL LINE/LOAD REACTORS ....................................................................................................... 30
Technical and Mechanical Specifications ........................................................................................... 30
RL LINE/LOAD REACTORS ....................................................................................................... 31
Technical and Mechanical Specifications ........................................................................................... 31
RL LINE/LOAD REACTORS ....................................................................................................... 32
Technical and Mechanical Specifications ........................................................................................... 32
RL LINE/LOAD REACTORS ....................................................................................................... 33
Technical and Mechanical Specifications ........................................................................................... 33
RL LINE/LOAD REACTORS ....................................................................................................... 34
Technical and Mechanical Specifications ........................................................................................... 34
RL LINE/LOAD REACTORS ....................................................................................................... 35
Technical and Mechanical Specifications ........................................................................................... 35
5. HOW TO INSTALL ................................................................................................................................. 36
INSTALLATION CHECKLIST ....................................................................................................... 36
G
ROUNDING
.......................................................................................................................... 37
POWER WIRING CONNECTION ................................................................................................. 38
TYPICAL CONNECTION DIAGRAMS ................................................................ ............................ 39
TORQUE RATINGS ................................................................................................................... 40
TORQUE RATINGS ................................................................................................................... 41
TORQUE RATINGS ................................................................................................................... 42
6. START-UP .............................................................................................................................................. 43
S
AFETY PRECAUTIONS
.......................................................................................................... 43
7. TROUBLESHOOTING ............................................................................................................................ 44
Page 5
RL Reactors Technical Reference Manual 208V – 690V
Form: RL-TRM-E April 2019 REV. 001 V
List of Figures
Figure 3-1: Altitude Derating Curve ................................ ............................................................ 7
Figure 3-2: Temperature Derating .............................................................................................. 7
Figure 5-1: Line Reactor ...........................................................................................................39
Figure 5-2: Load Reactor ..........................................................................................................39
Figure 5-3: Multiple Line Reactors.............................................................................................39
Figure 5-4: Single Phase Line Reactors ....................................................................................39
List of Tables
Table 3-1: Performance Specifications ....................................................................................... 5
Table 4-1: RL Reactors 120V – 600V – Single Phase ...............................................................11
Table 4-2: RL Reactors 208V – 3-Phase ...................................................................................12
Table 4-3: RL Reactors 208V – 3-Phase ...................................................................................13
Table 4-4: RL Reactors 240V – 3-Phase ...................................................................................14
Table 4-5: RL Reactors 240V – 3-Phase ...................................................................................15
Table 4-6: RL Reactors 400V – 3-Phase ...................................................................................16
Table 4-7: RL Reactors 400V – 3-Phase ...................................................................................17
Table 4-8: RL Reactors 480V – 3-Phase ...................................................................................18
Table 4-9: RL Reactors 480V – 3-Phase ...................................................................................19
Table 4-10: RL Reactors 600V – 3-Phase .................................................................................20
Table 4-11: RL Reactors 600V – 3-Phase .................................................................................21
Table 4-12: RL Reactors 690V – 3-Phase .................................................................................22
Table 4-13: RL Reactors 690V – 3-Phase .................................................................................23
Table 4-14: RL Reactors Open Panel Technical Specifications .................................................25
Table 4-15: RL Reactors NEMA 1/2 Technical Specifications ...................................................30
Table 4-16: RL Reactors NEMA 3R Technical Specifications ....................................................33
Table 5-1: RL Reactors Torque Ratings ....................................................................................40
Table 7-1: Troubleshooting Guide .............................................................................................45
Page 6
RL Reactors Technical Reference Manual 208V 690V
1 Form: RL-TRM-E April 2019 REV. 001
1. SAFETY
Warnings and Cautions
The following symbols are used in this manual:
WARNING
High Voltage Warning: warns of situations that dangerously high voltage is involved. Failure to use proper precautions may lead to serious injury or death.
WARNING
General Warning: warns of situations that can result in serious injury or death if proper precautions are not used.
Caution
General Caution: identifies situations that could lead to malfunction or possible equipment damage.
Page 7
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 2
General Safety Instructions
WARNING
High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.
High voltage is used in the operation of line/load reactors. Use extreme caution to avoid contact with high voltage when operating, installing or repairing line/load reactors.
Injury or death may result if safety
precautions are not observed.
Line/load reactors are used in conjunction with inverters, or other electrical equipment that may feedback lethal voltages. Follow the safety instructions in the equipment used with the reactor in addition to the safety instructions in this manual.
WARNING
The opening of the branch circuit protective device may be an indication that a fault current has been interrupted. To reduce the risk of fire or electrical shock, line/load reactors should be examined and replaced if damaged.
An upstream disconnect/protection device must be used as required by the National Electrical Code (NEC) or governing authority.
Even if the upstream disconnect/protection device is open, the drive downstream of the line/load reactor may feedback high voltage to the reactor. The drive safety instructions must be followed. Injury or death may result if safety precautions are not observed.
Line/load reactors must be grounded with a grounding conductor connected to all grounding terminals. Open panel reactors must have a 2”x2” area cleaned of paint and varnish on the lower mounting bracket.
Only spare parts obtained from MTE Corporation or an authorized MTE distributor can be used.
Caution
Loose or improperly secured connections may damage or degrade reactor performance. Visually inspect and secure all electrical connections before power is applied to the filter.
The user of this reactor must assure that the input voltage and frequency is correct for the reactor rating and that the voltage applied falls within the rated operating tolerance envelop specified for the reactor. For severe power line applications where the power feed is likely to experience surges and transients that exceed the input voltage rating, it is recommended that a TVSS (Transient Voltage Surge Suppression) or SPD (Surge Protection Device) be deployed ahead of the reactor to reduce the possibility of exceeding the reactor’s rated voltage. Consult with TVSS or SPD manufacturer to determine the correct protection requirements for your power line conditions.
Page 8
RL Reactors Technical Reference Manual 208V 690V
3 Form: RL-TRM-E April 2019 REV. 001
2. GENERAL INFORMATION
The purpose of this manual is to properly specify, size, and install the RL Series Line/Load Reactors.
For most current information, please refer to website
https://www.mtecorp.com/products/reactors/rl-reactors/
Receipt & Repair Statement
Upon Receipt of this Filter:
RL Line/Load Reactors have been subjected to demanding factory tests before shipment. Carefully inspect the shipping container for damage that may have occurred in transit. Then unpack the reactor and carefully inspect for any signs of damage. Save the shipping container for future transport of the reactor.
In the event of damage, please contact and file a claim with the freight carrier involved immediately.
If the equipment is not going to be put into service upon receipt, cover and store the reactor in a clean, dry location. After storage, ensure that the equipment is dry and that no condensation or dirt has accumulated on the reactor before applying power.
Repair/Exchange Procedure
MTE Corporation requires a Return Material Authorization Number and form before we can accept any reactors that qualify for return or repair. If problems or questions arise during installation, setup, or operation of the reactor, please contact MTE for assistance at:
Toll Free: 1-800-455-4MTE (1-800-455-4683)
International Tel: (+1)262-253-8200
Fax: (+1)262-253-8222
Page 9
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 4
Enclosures
MTE enclosures are designed to provide a degree of protection for electrical components and prevent incidental personnel contact with the enclosed equipment. Depending on the enclosure selected, these enclosures meet the requirements of NEMA 1/2 or 3R.
An approximate cross reference guide between NEMA, UL, CSA and IEC enclosure follows.
Type 1 NEMA / IEC IP20 Enclosure:
Are designed for indoor use and will provide protection against contact with the enclosed equipment.
Type 2 NEMA / IEC IP20 Enclosure:
Are designed for indoor use and will provide protection against contact with the enclosed equipment and provide a degree of protection against limited amounts of falling water and dirt.
Type 3R NEMA / IEC IP23 Enclosure:
Are designed for outdoor use primarily to provide protection against contact with the enclosed equipment and provide a degree of protection against falling rain sleet and external ice formation.
Agency Approvals
UL-508, File E180243 Component Listed (1 amp – 2400 amps) UL-508, File E180243 UL Listed NEMA 1 units (1 amp – 2400 amps) CSA C22.2, File LR29753-13 CSA Certified (1 amp – 2400 amps) Class N, 200° C, File E66214, Type 200-18, UL Recognized Insulation System CE Marked
Warranty
Five (5) years from the date of shipment. See https://www.mtecorp.com/industry-leading-
warranty/ for details.
Page 10
RL Reactors Technical Reference Manual 208V 690V
5 Form: RL-TRM-E April 2019 REV. 001
3. RL LINE/LOAD REACTORS PERFORMANCE DATA
Performance Specifications
Table 3-1: Performance Specifications
Impedance Levels
1.5%, 2%, 3%, 4%, 5% available
Continuous Service Factor*
Reactors rated 1 to 750 Amps – 150% of rating Reactors rated above 750 Amps – 125% rating
Overload Rating
200% of fundamental for 30 minutes 300% of fundamental for 1 minute
Input Voltage(s)
120V – 600V 1 phase 208V – 690V 3 phase
Current Range
1A – 1,500A
Maximum System Voltage
600 Volts (units with terminal blocks) 690 Volts (units with box lugs or tab terminals)
Maximum Switching Frequency
20 kHz
Ambient Temperature (Operating)
-40 to +50 degrees C Open Panel Reactor
-40 to +40 degrees C Enclosed Reactor
-40 to +90 degrees C Storage
Insulation System
Class N (200° C)
Altitude without derating
3,300 feet above sea level
Fundamental Frequency
50/60 Hz
Inductance Curve
100% at 100% current 100% at 150% current 50% at 350% current (minimum)
Inductance Tolerance
+/- 10%
Notes:
*Select reactor based on fundamental current rating. The Short Circuit Current Rating (SCCR) is not required under Exception No.1 of
UL508A SB4.2.1 effective 4/25/06.
Page 11
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 6
Audible Noise
RL Line/Load Reactors offer low noise operation. Core and coil construction, flux density control, harmonic compensation as well as our epoxy impregnation process assure minimal audible noise
radiation. Although our reactors are typically “quiet”, waveforms vary by drive type and application
and therefore reactor audible noise may vary by application. Noise levels may be affected by type of motor and motor conductor as well as motor conductor length.
Typical audible noise levels for units selected from our catalog by HP rating are:
2 thru 12 amps 55 dBA
18 thru 100 amps 65 dBA
130 thru 400 amps 70 dBA
500 thru 1200 amps 75 dBA
Service Factor
RL Line/Load Reactors are compensated for the additional currents and high frequencies caused by the presence of harmonics. The reactor fundamental current rating indicates the typical full load motor current and is also the basis of impedance rating. Standard reactors rated 1 amps thru 750 amps offer a full 1.5 service factor rating which allows them to carry overload current up to 150% of their fundamental rating when applied as an input line reactor. Since the nameplate ratings of motor drives (ASD) varies widely by manufacturer, this helps to assure that the reactor maximum current rating is compatible with the nameplate current rating on the ASD. The service factor rating compensates for ASD manufacturer variances in motor drive current ratings and for harmonic currents. Nominal inductance is assured all the way up to the service factor current rating.
PWM / IGBT Protection
RL Line/Load Reactors are protected against the high peak voltage and fast rise time voltage pulses associated with PWM waveforms. The dielectric strength is 4000 volts rms and RL reactors meet the ratings of an inverter duty motor (NEMA MG-1, part 31). For convenience, they can be located either at the motor or at the drive.
Harmonic Attenuation
Our unique harmonic compensation assures maximum circuit inductance in the presence of complex waveforms and can be relied upon to minimize input total harmonic current distortion (THID). Additionally, it offers superior absorption of transient voltage spikes. Our standard reactors will typically reduce 6-pulse rectifier input current harmonics to the following levels at full load operating conditions:
3% reactor alone 45% or less THID
5% reactor alone 35% or less THID
3% AC reactor + 3% DC link choke 33% or less THID
5% AC reactor + 3% DC link choke 28% or less THID
(DC link choke inductance is equivalent ac impedance).
Page 12
RL Reactors Technical Reference Manual 208V 690V
7 Form: RL-TRM-E April 2019 REV. 001
Altitude Derating
Figure 3-1: Altitude Derating Curve
Temperature Derating
Figure 3-2: Temperature Derating
Altitude Derating Curve
0.70
0.75
0.80
0.85
0.90
0.95
1.00
1.05
0 3300 6600 9900 13200 16500
Altitude (Feet)
Current De-Rating Factor
Reactor Temperature De-Rating
0.60
0.65
0.70
0.75
0.80
0.85
0.90
0.95
1.00
1.05
40 45 50 55 60 65 70 75 80 85 90
Ambient Temperature Deg. C
Current De-Rating Factor
Page 13
RL Reactors Technical Reference Manual 208V – 690V
Form: RL-TRM-E April 2019 REV. 001 8
4. HOW TO SELECT
Selection Guide
MTE RL Line/Load Reactors are optimized to support global IEC and NEC Drive /motor
applications. RL’s are RMS current rated impedance devices. Selection is based on the choice
of inductance correlated to the application motor full load amps, voltage and frequency and the number of phases. Use the product selection brochure based on input voltage and NEC FLA motor selection table for common voltages. For critical impedance selection based on specific HP or load currents, consult MTE applications engineering.
Choose the impedance level:
3% Reactors rated at 3% are typically sufficient to absorb line spikes and motor current
surges, and help prevent nuisance tripping to the drive and circuit breakers in most applications. 3% is typically specified by most drive manufacturers.
5% Reactors rated at 5% are best for reducing harmonic current and frequencies. Use
them when you must reduce VFD drive generated harmonics, and to reduce motor operating temperature.
Single Phase Applications:
RL reactors may also be sized to protect single phase drives. Please see MTE Application Note: How to Use a 3-Phase Line Reactor for a Single-Phase Application for details.
NOTE: For inverters feeding isolation transformers select a reactor with a current rating equal to or greater than that of the transformer primary current.
Please verify information below for proper selection:
Line Voltage and Frequency: Input voltage 208V-690V 50/60 Hz (3-phase); 120V-
600V 50/60 Hz (1-phase). See Table 3-1: Performance Specifications (p5) for specification.
Current Rating: Support for 1 Amp – 1500 Amps. Performance: See Table 3-1: Performance Specifications (p5) for specification. Altitude: 3,300 feet above sea level without derating. See Figure 3-1: Altitude Derating
Curve (p7) for derating information.
Enclosure Type: Open Panel, NEMA 1/2 & NEMA 3R, see Enclosures (p4) for
enclosure descriptions.
Temperature: See Table 3-1: Performance Specifications (p5) for operating
temperature information and Figure 3-2: Temperature Derating (p7) for derating information.
Refer to Article 430 Table 430.91 of the National Electrical code for the selection of the
appropriate enclosure Type Number for your application.
Page 14
RL Reactors Technical Reference Manual 208V 690V
9 Form: RL-TRM-E April 2019 REV. 001
Understanding the RL Line/Load Reactor Part Number:
RL _ - _ _ _ _ X X X
MOV Options* A = 208 Volts
C = 240 Volts E = 400 Volts G = 480 Volts J = 600 Volts
Current Rating (i.e. 001 is 1 Amp) Mechanical Configurations 0 = Base Mount
1 = NEMA 1
3 = NEMA 3R Reactor Relative Impedance Number 1 - 4 (1) is lowest value
Lug/Terminal Block Options**
B1 = Side Facing B8 = Top Mounted
B14 = Front Facing
Page 15
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 10
RL Line/Load Reactor OPTIONS:
* MOV Option – Adding Metal Oxide Varistors (MOV) can help prevent damage to reactors and variable frequency drives (VFD’s) when large spikes in transient voltage occur.
** B1 & B14 Lug Orientation Option – If the current RL part lug orientation does not work for installation; a modification can be made to adjust the lug to be either Side Facing or Front Facing. To signify the change, add either B1 or B14 to the end of the RL part number.
** B8 Terminal Block Option – If the current RL front mounted terminal block does not work for installation, a modification can be made to adjust a terminal block to be Top Mounted. To signify the change, add B8 to the end of the RL part number. (Note: Terminal blocks are only available
on reactors 45 Amps and below. Contact MTE for additional information.)
Lug Option Details:
“B1” Lug Orientation Option “B14” Lug Orientation Option
“B8” Terminal Block Modification
Page 16
RL Reactors Technical Reference Manual 208V – 690V
11 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors 120V – 600V Single Phase
Part Number Selection Tables
Table 4-1: RL Reactors 120V – 600V – Single Phase
Motor
%
Impedance
Input Voltage & Hz
KW
HP
120V 60Hz
208V 60Hz
240V 60Hz
240V 50Hz
400V 50Hz
480V 60Hz
600V 60Hz
0.18
0.25
5%
RL-01801
RL-00204
RL-00402
RL-00403
RL-00103
RL-00203
RL-00102
0.25
0.33
5%
RL-01801
RL-00803
RL-00402
RL-00402
RL-00203
RL-00202
RL-00103
0.37
0.5
5%
RL-01201
RL-00802
RL-00803
RL-00803
RL-00201
RL-00202
RL-00202
0.55
0.75
5%
RL-01801
RL-01202
RL-00802
RL-00802
RL-00404
RL-00404
RL-00202
0.75 1 5%
RL-01801
RL-00801
RL-01202
RL-00802
RL-00403
RL-00403
RL-00404
1.1
1.5
5%
RL-02501
RL-01201
RL-01201
RL-01802
RL-00803
RL-00803
RL-00403
1.5 2 5%
RL-03501
RL-01201
RL-01201
RL-01802
RL-00803
RL-00803
RL-00804
2.2 3 5%
RL-05501
RL-01801
RL-01801
RL-02502
RL-01203
RL-01203
RL-00803
3.7 5 5%
RL-10001
RL-03501
RL-02501
RL-03502
RL-01803
RL-01803
RL-01203
5
7.5
5%
RL-16001
RL-04501
RL-04501
RL-03501
RL-02503
RL-02503
RL-01803
7.5
10
5%
RL-
20001B14
RL-05501
RL-04501
RL-05502
RL-03502
RL-02502
RL-02503
11
15
5%
-
RL-08001
RL-08001
RL-10002
RL-04502
RL-04502
RL-03503
15
20
5%
-
RL-10001
RL-10001
RL-13002
RL-05502
RL-05503
RL-04503
18.5
25
5%
-
RL-13001
RL-13001
RL-13002
RL-08002
RL-08003
RL-05503
22
30
5%
-
RL-16001
RL-16002
RL-16002
RL-08002
RL-08002
RL-05503
30
40
5%
-
RL-
20001B14
RL-
20002B14
RL-
20002B14
RL-10002
RL-10002
RL-08003
37.5
50
5%
-
RL-
25001B14
RL-
25002B14
RL-
25002B14
RL-13003
RL-13003
RL-10003
45
60
5%
-
RL-
32001B14
RL-
32002B14
RL-
32002B14
RL-16003
RL-16003
RL-13003
55
75
5%
-
RL-
40001B14
RL-
32001B14
RL-
40002B14
RL-
20003B14
RL-
20003B14
RL-13003
75
100
5%
-
RL-
50001B14
RL-
40001B14
RL-50002
RL-
25003B14
RL-
25003B14
RL-
20003B14
93
125
5% - - - -
-
RL-
32003B14
RL-
25003B14
112
150
5% - - - -
-
RL-
40003B14
RL-
25003B14
150
200
5% - - - -
-
RL-
40003B14
RL-
32003B14
See Technical and Mechanical Tables for detailed data.
Page 17
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 12
RL Line/Load Reactors 208 Volts, 60Hz
Part Number Selection Tables
Table 4-2: RL Reactors 208V – 3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
0.18
0.25 3%
RL-00204
RL-00214
RL-00234
5%
RL-00201
RL-00211
RL-00231
0.25
0.33 3%
RL-00204
RL-00214
RL-00234
5%
RL-00403
RL-00413
RL-00433
0.37
0.5 3%
RL-00401
RL-00411
RL-00431
5%
RL-00402
RL-00412
RL-00432
0.55
0.75 3%
RL-00401
RL-00411
RL-00431
5%
RL-00803
RL-00813
RL-00833
0.75
1
3%
RL-00801
RL-00811
RL-00831
5%
RL-00802
RL-00812
RL-00832
1.1
1.5 3%
RL-00801
RL-00811
RL-00831
5%
RL-00802
RL-00812
RL-00832
1.5
2
3%
RL-00801
RL-00811
RL-00831
5%
RL-01202
RL-01212
RL-01232
2.2
3
3%
RL-01801
RL-01811
RL-01831
5%
RL-01802
RL-01812
RL-01832
3.7
5
3%
RL-02501
RL-02511
RL-02531
5%
RL-02502
RL-02512
RL-02532
5
7.5 3%
RL-03501
RL-03511
RL-03531
5%
RL-03502
RL-03512
RL-03532
7.5
10
3%
RL-05501
RL-05511
RL-05531
5%
RL-05502
RL-05512
RL-05532
11
15
3%
RL-05501
RL-05511
RL-05531
5%
RL-04501
RL-04511
RL-04531
15
20
3%
RL-08001
RL-08011
RL-08031
5%
RL-05501
RL-05511
RL-05531
18.5
25
3%
RL-10001
RL-10011
RL-10031
5%
RL-08001
RL-08011
RL-08031
See Technical and Mechanical Tables for detailed data.
Page 18
RL Reactors Technical Reference Manual 208V 690V
13 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors 208 Volts, 60Hz
Part Number Selection Tables
Table 4-3: RL Reactors 208V – 3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
22
30
3%
RL-10001
RL-10011
RL-10031
5%
RL-13002
RL-13012
RL-13032
30
40
3%
RL-13001
RL-13011
RL-13031
5%
RL-16002
RL-16012
RL-16032
37.5
50
3%
RL-16001
RL-16011
RL-16031
5%
RL-20002B14
RL-20012B14
RL-20032B14
45
60
3%
RL-20001B14
RL-20011B14
RL-20031B14
5%
RL-20002B14
RL-20012B14
RL-20032B14
55
75
3%
RL-25001B14
RL-25011B14
RL-25031B14
5%
RL-25002B14
RL-25012B14
RL-25032B14
75
100
3%
RL-32001B14
RL-32011B14
RL-32031B14
5%
RL-32002B14
RL-32012B14
RL-32032B14
93
125
3%
RL-40001B14
RL-40011B14
RL-40031B14
5%
RL-40002B14
RL-40012B14
RL-40032B14
112
150
3%
RL-50001B14
RL-50011B14
RL-50031B14
5%
RL-50002
RL-50012
RL-50032
150
200
3%
RL-60001
RL-60011
RL-60031
5%
RL-75002
RL-75012
RL-75032
187
250
3%
RL-75001
RL-75011
RL-75031
5%
RL-75002
RL-75012
RL-75032
225
300
3%
RL-85001B14
RL-85011B14
RL-85031B14
5%
RL-90002B14
RL-90012B14
RL-90032B14
262
350
3%
RL-100001B14
RL-100011B14
RL-100031B14
5%
RL-100002B14
RL-100012B14
RL-100032B14
300
400
3%
RL-120001B14
RL-120011B14
RL-120031B14
5%
RL-120002B14
RL-120012B14
RL-120032B14
375
500
3%
RL-140001
RL-140011
RL-140031
5%
RL-150002
RL-150012
RL-150032
See Technical and Mechanical Tables for detailed data.
Page 19
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 14
RL Line/Load Reactors 240 Volts, 60Hz
Part Number Selection Tables
Table 4-4: RL Reactors 240V – 3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
0.18
0.25 3%
RL-00204
RL-00214
RL-00234
5%
RL-00201
RL-00211
RL-00231
0.25
0.33 3%
RL-00204
RL-00214
RL-00234
5%
RL-00201
RL-00211
RL-00231
0.37
0.5 3%
RL-00402
RL-00412
RL-00432
5%
RL-00403
RL-00413
RL-00433
0.55
0.75 3%
RL-00401
RL-00411
RL-00431
5%
RL-00402
RL-00412
RL-00432
0.75
1
3%
RL-00802
RL-00812
RL-00832
5%
RL-00803
RL-00813
RL-00833
1.1
1.5 3%
RL-00801
RL-00811
RL-00831
5%
RL-00802
RL-00812
RL-00832
1.5
2
3%
RL-00801
RL-00811
RL-00831
5%
RL-00802
RL-00812
RL-00832
2.2
3
3%
RL-01201
RL-01211
RL-01231
5%
RL-01202
RL-01212
RL-01232
3.7
5
3%
RL-01801
RL-01811
RL-01831
5%
RL-02502
RL-02512
RL-02532
5
7.5 3%
RL-02501
RL-02511
RL-02531
5%
RL-03502
RL-03512
RL-03532
7.5
10
3%
RL-03501
RL-03511
RL-03531
5%
RL-03502
RL-03512
RL-03532
11
15
3%
RL-04501
RL-04511
RL-04531
5%
RL-05502
RL-05512
RL-05532
15
20
3%
RL-05501
RL-05511
RL-05531
5%
RL-08002
RL-08012
RL-08032
18.5
25
3%
RL-08001
RL-08011
RL-08031
5%
RL-10001
RL-10011
RL-10031
See Technical and Mechanical Tables for detailed data.
Page 20
RL Reactors Technical Reference Manual 208V 690V
15 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors 240 Volts, 60Hz
Part Number Selection Tables
Table 4-5: RL Reactors 240V – 3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
22
30
3%
RL-10001
RL-10011
RL-10031
5%
RL-08001
RL-08011
RL-08031
30
40
3%
RL-13001
RL-13011
RL-13031
5%
RL-13002
RL-13012
RL-13032
37.5
50
3%
RL-13001
RL-13011
RL-13031
5%
RL-16002
RL-16012
RL-16032
45
60
3%
RL-16001
RL-16011
RL-16031
5%
RL-16002
RL-16012
RL-16032
55
75
3%
RL-20001B14
RL-20011B14
RL-20031B14
5%
RL-20002B14
RL-20012B14
RL-20032B14
75
100
3%
RL-25001B14
RL-25011B14
RL-25031B14
5%
RL-25002B14
RL-25012B14
RL-25032B14
93
125
3%
RL-32001B14
RL-32011B14
RL-32031B14
5%
RL-40002B14
RL-40012B14
RL-40032B14
112
150
3%
RL-40001B14
RL-40011B14
RL-40031B14
5%
RL-40002B14
RL-40012B14
RL-40032B14
150
200
3%
RL-50001B14
RL-50011B14
RL-50031B14
5%
RL-60002
RL-60012
RL-60032
187
250
3%
RL-60001
RL-60011
RL-60031
5%
RL-75002
RL-75012
RL-75032
225
300
3%
RL-75001
RL-75011
RL-75031
5%
RL-75002
RL-75012
RL-75032
262
350
3%
RL-85001B14
RL-85011B14
RL-85031B14
5%
RL-85002B14
RL-85012B14
RL-85032B14
300
400
3%
RL-100001B14
RL-100011B14
RL-100031B14
5%
RL-100002B14
RL-100012B14
RL-100032B14
375
500
3%
RL-120001B14
RL-120011B14
RL-120031B14
5%
RL-140002
RL-140102
RL-140302
See Technical and Mechanical Tables for detailed data.
Page 21
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 16
RL Line/Load Reactors 400 Volts, 50Hz
Part Number Selection Tables
Table 4-6: RL Reactors 400V – 3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
0.18
0.25 3%
RL-00103
RL-00113
RL-00133
5%
RL-00102
RL-00112
RL-00132
0.25
0.33 3%
RL-00103
RL-00113
RL-00133
5%
RL-00102
RL-00112
RL-00132
0.37
0.5 3%
RL-00202
RL-00212
RL-00232
5%
RL-00203
RL-00213
RL-00233
0.55
0.75 3%
RL-00201
RL-00211
RL-00231
5%
RL-00202
RL-00212
RL-00232
0.75
1
3%
RL-00403
RL-00413
RL-00433
5%
RL-00202
RL-00212
RL-00232
1.1
1.5 3%
RL-00402
RL-00412
RL-00432
5%
RL-00404
RL-00414
RL-00434
1.5
2
3%
RL-00402
RL-00412
RL-00432
5%
RL-00403
RL-00413
RL-00433
2.2
3
3%
RL-00803
RL-00813
RL-00833
5%
RL-00804
RL-00814
RL-00834
3.7
5
3%
RL-00802
RL-00812
RL-00832
5%
RL-00803
RL-00813
RL-00833
5
7.5 3%
RL-01202
RL-01212
RL-01232
5%
RL-01203
RL-01213
RL-01233
7.5
10
3%
RL-01802
RL-01812
RL-01832
5%
RL-01803
RL-01813
RL-01833
11
15
3%
RL-02502
RL-02512
RL-02532
5%
RL-02503
RL-02513
RL-02533
15
20
3%
RL-03502
RL-03512
RL-03532
5%
RL-03503
RL-03513
RL-03533
18.5
25
3%
RL-04502
RL-04512
RL-04532
5%
RL-04503
RL-04513
RL-04533
22
30
3%
RL-04502
RL-04512
RL-04532
5%
RL-05503
RL-05513
RL-05533
30
40
3%
RL-08002
RL-08012
RL-08032
5%
RL-08003
RL-08013
RL-08033
See Technical and Mechanical Tables for detailed data.
Page 22
RL Reactors Technical Reference Manual 208V 690V
17 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors 400 Volts, 50Hz
Part Number Selection Tables
Table 4-7: RL Reactors 400V – 3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
37.5
50
3%
RL-08002
RL-08012
RL-08032
5%
RL-10003
RL-10013
RL-10033
45
60
3%
RL-10002
RL-10012
RL-10032
5%
RL-10003
RL-10013
RL-10033
55
75
3%
RL-13002
RL-13012
RL-13032
5%
RL-13003
RL-13013
RL-13033
75
100
3%
RL-16002
RL-16012
RL-16032
5%
RL-16003
RL-16013
RL-16033
93
125
3%
RL-20002B14
RL-20012B14
RL-20032B14
5%
RL-20003B14
RL-20013B14
RL-20033B14
112
150
3%
RL-20002B14
RL-20012B14
RL-20032B14
5%
RL-20003B14
RL-20013B14
RL-20033B14
150
200
3%
RL-32002B14
RL-32012B14
RL-32032B14
5%
RL-32003B14
RL-32013B14
RL-32033B14
187
250
3%
RL-40002B14
RL-40012B14
RL-40032B14
5%
RL-40003B14
RL-40013B14
RL-40033B14
225
300
3%
RL-40002B14
RL-40012B14
RL-40032B14
5%
RL-40003B14
RL-40013B14
RL-40033B14
262
350
3%
RL-50002
RL-50012
RL-50032
5%
RL-50003
RL-50013
RL-50033
300
400
3%
RL-60002
RL-60012
RL-60032
5%
RL-60003
RL-60013
RL-60033
375
500
3%
RL-75002
RL-75012
RL-75032
5%
RL-75003
RL-75013
RL-75033
450
600
3%
RL-85002B14
RL-85012B14
RL-85032B14
5%
RL-85003B14
RL-85013B14
RL-85033B14
550
700
3%
RL-90002B14
RL-90012B14
RL-90032B14
5%
RL-90003B14
RL-90013B14
RL-90033B14
600
800
3%
RL-120002B14
RL-120012B14
RL-120032B14
5%
RL-120003B14
RL-120013B14
RL-120033B14
See Technical and Mechanical Tables for detailed data.
Page 23
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 18
RL Line/Load Reactors 480 Volts, 60Hz
Part Number Selection Tables
Table 4-8: RL Reactors 480V – 3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
0.18
0.25 3%
RL-00103
RL-00113
RL-00133
5%
RL-00102
RL-00112
RL-00132
0.25
0.33 3%
RL-00103
RL-00113
RL-00133
5%
RL-00102
RL-00112
RL-00132
0.37
0.5 3%
RL-00104
RL-00114
RL-00134
5%
RL-00103
RL-00113
RL-00133
0.55
0.75 3%
RL-00201
RL-00211
RL-00231
5%
RL-00202
RL-00212
RL-00232
0.75
1
3%
RL-00201
RL-00211
RL-00231
5%
RL-00202
RL-00212
RL-00232
1.1
1.5 3%
RL-00402
RL-00412
RL-00432
5%
RL-00404
RL-00414
RL-00434
1.5
2
3%
RL-00402
RL-00412
RL-00432
5%
RL-00403
RL-00413
RL-00433
2.2
3
3%
RL-00803
RL-00813
RL-00833
5%
RL-00804
RL-00814
RL-00834
3.7
5
3%
RL-00802
RL-00812
RL-00832
5%
RL-00803
RL-00813
RL-00833
5
7.5 3%
RL-01202
RL-01212
RL-01232
5%
RL-01203
RL-01213
RL-01233
7.5
10
3%
RL-01802
RL-01812
RL-01832
5%
RL-01803
RL-01813
RL-01833
11
15
3%
RL-02502
RL-02512
RL-02532
5%
RL-02503
RL-02513
RL-02533
15
20
3%
RL-03502
RL-03512
RL-03532
5%
RL-03503
RL-03513
RL-03533
18.5
25
3%
RL-03502
RL-03512
RL-03532
5%
RL-03503
RL-03513
RL-03533
22
30
3%
RL-04502
RL-04512
RL-04532
5%
RL-05503
RL-05513
RL-05533
30
40
3%
RL-05502
RL-05512
RL-05532
5%
RL-05503
RL-05513
RL-05533
See Technical and Mechanical Tables for detailed data.
Page 24
RL Reactors Technical Reference Manual 208V 690V
19 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors 480 Volts, 60Hz
Part Number Selection Tables
Table 4-9: RL Reactors 480V – 3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
37.5
50
3%
RL-08002
RL-08012
RL-08032
5%
RL-08003
RL-08013
RL-08033
45
60
3%
RL-10002
RL-10012
RL-10032
5%
RL-10003
RL-10013
RL-10033
55
75
3%
RL-10002
RL-10012
RL-10032
5%
RL-10003
RL-10013
RL-10033
75
100
3%
RL-13002
RL-13012
RL-13032
5%
RL-13003
RL-13013
RL-13033
93
125
3%
RL-16002
RL-16012
RL-16032
5%
RL-16003
RL-16013
RL-16033
112
150
3%
RL-20002B14
RL-20012B14
RL-20032B14
5%
RL-20003B14
RL-20013B14
RL-20033B14
150
200
3%
RL-25002B14
RL-25012B14
RL-25032B14
5%
RL-25003B14
RL-25013B14
RL-25033B14
187
250
3%
RL-32002B14
RL-32012B14
RL-32032B14
5%
RL-32003B14
RL-32013B14
RL-32033B14
225
300
3%
RL-40002B14
RL-40012B14
RL-40032B14
5%
RL-40003B14
RL-40013B14
RL-40033B14
262
350
3%
RL-50002
RL-50012
RL-50032
5%
RL-50003
RL-50013
RL-50033
300
400
3%
RL-50002
RL-50012
RL-50032
5%
RL-50003
RL-50013
RL-50033
375
500
3%
RL-60002
RL-60012
RL-60032
5%
RL-60003
RL-60013
RL-60033
450
600
3%
RL-75002
RL-75012
RL-75032
5%
RL-75003
RL-75013
RL-75033
550
700
3%
RL-85002B14
RL-85012B14
RL-85032B14
5%
RL-85003B14
RL-85013B14
RL-85033B14
600
800
3%
RL-100002B14
RL-100012B14
RL-100032B14
5%
RL-100003B14
RL-100013B14
RL-100033B14
See Technical and Mechanical Tables for detailed data.
Page 25
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 20
RL Line/Load Reactors 600 Volts, 60Hz
Part Number Selection Tables
Table 4-10: RL Reactors 600V – 3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
0.18
0.25 3%
RL-00102
RL-00112
RL-00132
5%
RL-00101
RL-00111
RL-00131
0.25
0.33 3%
RL-00103
RL-00113
RL-00133
5%
RL-00102
RL-00112
RL-00132
0.37
0.5 3%
RL-00103
RL-00113
RL-00133
5%
RL-00102
RL-00112
RL-00132
0.55
0.75 3%
RL-00202
RL-00212
RL-00232
5%
RL-00203
RL-00213
RL-00233
0.75
1
3%
RL-00202
RL-00212
RL-00232
5%
RL-00203
RL-00213
RL-00233
1.1
1.5 3%
RL-00201
RL-00211
RL-00231
5%
RL-00202
RL-00212
RL-00232
1.5
2
3%
RL-00403
RL-00413
RL-00433
5%
RL-00404
RL-00414
RL-00434
2.2
3
3%
RL-00402
RL-00412
RL-00432
5%
RL-00404
RL-00414
RL-00434
3.7
5
3%
RL-00803
RL-00813
RL-00833
5%
RL-00804
RL-00814
RL-00834
5
7.5 3%
RL-01202
RL-01212
RL-01232
5%
RL-01203
RL-01213
RL-01233
7.5
10
3%
RL-01202
RL-01212
RL-01232
5%
RL-01203
RL-01213
RL-01233
11
15
3%
RL-01802
RL-01812
RL-01832
5%
RL-01803
RL-01813
RL-01833
15
20
3%
RL-02502
RL-02512
RL-02532
5%
RL-02503
RL-02513
RL-02533
18.5
25
3%
RL-02502
RL-02512
RL-02532
5%
RL-02503
RL-02513
RL-02533
22
30
3%
RL-03502
RL-03512
RL-03532
5%
RL-03503
RL-03513
RL-03533
30
40
3%
RL-04502
RL-04512
RL-04532
5%
RL-04503
RL-04513
RL-04533
See Technical and Mechanical Tables for detailed data.
Page 26
RL Reactors Technical Reference Manual 208V 690V
21 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors 600 Volts, 60Hz
Part Number Selection Tables
Table 4-11: RL Reactors 600V – 3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
37.5
50
3%
RL-05502
RL-05512
RL-05532
5%
RL-05503
RL-05513
RL-05533
45
60
3%
RL-08002
RL-08012
RL-08032
5%
RL-08003
RL-08013
RL-08033
55
75
3%
RL-08002
RL-08012
RL-08032
5%
RL-08003
RL-08013
RL-08033
75
100
3%
RL-10002
RL-10012
RL-10032
5%
RL-10003
RL-10013
RL-10033
93
125
3%
RL-13002
RL-13012
RL-13032
5%
RL-13003
RL-13013
RL-13033
112
150
3%
RL-16002
RL-16012
RL-16032
5%
RL-16003
RL-16013
RL-16033
150
200
3%
RL-20002B14
RL-20012B14
RL-20032B14
5%
RL-20003B14
RL-20013B14
RL-20033B14
187
250
3%
RL-25002B14
RL-25012B14
RL-25032B14
5%
RL-25003B14
RL-25013B14
RL-25033B14
225
300
3%
RL-32002B14
RL-32012B14
RL-32032B14
5%
RL-32003B14
RL-32013B14
RL-32033B14
262
350
3%
RL-32002B14
RL-32012B14
RL-32032B14
5%
RL-32003B14
RL-32013B14
RL-32033B14
300
400
3%
RL-40002B14
RL-40012B14
RL-40032B14
5%
RL-40003B14
RL-40013B14
RL-40033B14
375
500
3%
RL-50002
RL-50012
RL-50032
5%
RL-50003
RL-50013
RL-50033
450
600
3%
RL-60002
RL-60012
RL-60032
5%
RL-60003
RL-60013
RL-60033
550
700
3%
RL-75002
RL-75012
RL-75032
5%
RL-75003
RL-75013
RL-75033
600
800
3%
RL-75002
RL-75012
RL-75032
5%
RL-75003
RL-75013
RL-75033
See Technical and Mechanical Tables for detailed data.
Page 27
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 22
RL Line/Load Reactors 690 Volts, 50Hz
Part Number Selection Tables
Table 4-12: RL Reactors 690V – 3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
2.2
3
3%
RL-00403
RL-00413
RL-00433
5%
RL-00404
RL-00414
RL-00434
3.7
5
3%
RL-00803
RL-00813
RL-00833
5%
RL-00804
RL-00814
RL-00834
5
7.5 3%
RL-00803
RL-00813
RL-00833
5%
RL-00804
RL-00814
RL-00834
7.5
10
3%
RL-01202
RL-01212
RL-01232
5%
RL-01203
RL-01213
RL-01233
11
15
3%
RL-01202
RL-01212
RL-01232
5%
RL-01203
RL-01213
RL-01233
15
20
3%
RL-01802
RL-01812
RL-01832
5%
RL-01803
RL-01813
RL-01833
18.5
25
3%
RL-02502
RL-02512
RL-02532
5%
RL-02503
RL-02513
RL-02533
22
30
3%
RL-02502
RL-02512
RL-02532
5%
RL-02503
RL-02513
RL-02533
30
40
3%
RL-03502
RL-03512
RL-03532
5%
RL-03503
RL-03513
RL-03533
37.5
50
3%
RL-04502
RL-04512
RL-04532
5%
RL-04503
RL-04513
RL-04533
45
60
3%
RL-05502
RL-05512
RL-05532
5%
RL-04502
RL-04512
RL-04532
55
75
3%
RL-05502
RL-05512
RL-05532
5%
RL-05503
RL-05513
RL-05533
See Technical and Mechanical Tables for detailed data.
Page 28
RL Reactors Technical Reference Manual 208V 690V
23 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors 690 Volts, 50Hz
Part Number Selection Tables
Table 4-13: RL Reactors 690V – 3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
75
100
3%
RL-08002
RL-08012
RL-08032
5%
RL-08003
RL-08013
RL-08033
93
125
3%
RL-10002
RL-10012
RL-10032
5%
RL-10003
RL-10013
RL-10033
112
150
3%
RL-13002
RL-13012
RL-13032
5%
RL-13003
RL-13013
RL-13033
150
200
3%
RL-16002
RL-16012
RL-16032
5%
RL-16003
RL-16013
RL-16033
187
250
3%
RL-20002B14
RL-20012B14
RL-20032B14
5%
RL-20003B14
RL-20013B14
RL-20033B14
225
300
3%
RL-25002B14
RL-25012B14
RL-25032B14
5%
RL-25003B14
RL-25013B14
RL-25033B14
262
350
3%
RL-25002B14
RL-25012B14
RL-25032B14
5%
RL-25003B14
RL-25013B14
RL-25033B14
300
400
3%
RL-32002B14
RL-32012B14
RL-32032B14
5%
RL-32003B14
RL-32013B14
RL-32033B14
375
500
3%
RL-40002B14
RL-40012B14
RL-40032B14
5%
RL-40003B14
RL-40013B14
RL-40033B14
450
600
3%
RL-40002B14
RL-40012B14
RL-40032B14
5%
RL-50003
RL-50013
RL-50033
550
700
3%
RL-50002
RL-50012
RL-50032
5%
RL-50003
RL-50013
RL-50033
600
800
3%
RL-60002
RL-60012
RL-60032
5%
RL-60003
RL-60013
RL-60033
See Technical and Mechanical Tables for detailed data.
Page 29
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 24
RL Line/Load Reactors
Open Dimension Reference
Use the reactor outline below for reference with the Technical and Mechanical Specification tables on the following pages.
Dimensions A, B, and C show overall Width, Height, and Depth respectively. Dimensions D, E, and F are the mounting pattern.
Page 30
RL Reactors Technical Reference Manual 208V 690V
25 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors
Technical and Mechanical Specifications
Table 4-14: RL Reactors Open Panel Technical Specifications
MTE Part
Number
Amps
Rating
Inductance
mh
Watts
Loss
A B C D E
F
Approx Weight
in./
mm
in./
mm
in./
mm
in./
mm
in./
mm
in./
mm
Lbs./
Kg
RL-00101
1
100
14.1
4.2/
106.7
4/
101.6
3/
76.2
2.4/ 61
1.4/ 37
2.6/ 65
4/
1.8
RL-00102
1
50
14.8
4.4/
111.8
4.1/
104.1
2.8/
7.1
2/ 50
1.4/ 37
2.6/ 65
4/
1.8
RL-00103
1
36
12.0
4.4/
111.8
4.1/
104.1
2.8/
7.1
2/ 50
1.4/ 37
2.6/ 65
4/
1.8
RL-00104
1
18
8.0
4.4/
111.8
4.1/
104.1
2.8/
7.1
2/ 50
1.4/ 37
2.6/ 65
4/
1.8
RL-00201
2
12
7.5
4.2/
106.7
4/
101.6
2.6/ 66
2/ 50
1.4/ 37
2.6/ 65
4/
1.8
RL-00202
2
20
11.3
4.2/
106.7
4/
101.6
2.6/ 66
2/ 50
1.4/ 37
2.6/ 65
4/
1.8
RL-00203
2
32
16
4.2/
106.7
4/
101.6
2.6/ 66
2/ 50
1.4/ 37
2.6/ 65
4/
1.8
RL-00204
2 6 10.7
4.2/
106.7
4/
101.6
2.6/ 66
1.7/ 44
1.4/ 37
2.6/ 65
3/
1.4
RL-00401
4 3 14.5
4.2/
106.7
4/
101.6
2.6/ 66
2/ 50
1.4/ 37
2.6/ 65
4/
1.8
RL-00402
4
6.5
20
4.2/
106.7
4/
101.6
2.6/ 66
2/ 50
1.4/ 37
2.6/ 65
4/
1.8
RL-00403
4 9 20
4.2/
106.7
4/
101.6
3/
76.2
2.4/ 60
1.4/ 37
2.6/ 65
5/
2.3
RL-00404
4
12
21
4.2/
106.7
4/
101.6
3.3/
83.8
2.6/ 66
1.4/ 37
2.6/ 65
6/
2.7
RL-00801
8
1.5
19.5
5.9/
149.9
4.6/
116.8
2.9/
73.7
2.1/ 53
2/ 51
3/
76.2
7/
3.2
RL-00802
8 3 29
5.9/
149.9
4.6/
116.8
2.9/
73.7
2.1/ 53
2/ 51
3/
76.2
8/
3.6
RL-00803
8 5 25.3
5.9/
149.9
4.7/
119.4
3.3/
83.8
2.6/ 67
2/ 51
3/
76.2
11/
5
RL-00804
8
7.5
28
5.9/
149.9
4.7/
119.4
3.3/
83.8
2.5/ 63
2/ 51
3/
76.2
13/
5.9
RL-01201
12
1.25
26
5.9/
149.9
5/
127
3.2/
81.3
2.1/ 53
2/ 51
3/
76.2
9/
4.1
RL-01202
12
2.5
31
5.9/
149.9
5/
127
3.2/
81.3
2.1/ 53
2/ 51
3/
76.2
10/
4.5
RL-01203
12
4.2
41
5.9/
149.9
5/
127
3.8/
96.5
2.8/ 70
2/ 51
3/
76.2
18/
8.2
RL-01801
18
0.8
36
5.9/
149.9
5.1/
129.5
3.2/
81.3
2.1/ 54
2/ 51
3/
76.2
9/
4.1
For detailed drawings of each reactor, click on the “MTE Part Number”.
Page 31
RL Reactors Technical Reference Manual 208V – 690V
Form: RL-TRM-E April 2019 REV. 001 26
RL Line/Load Reactors
Technical and Mechanical Specifications
Table 4-14: RL Reactors Open Panel Technical Specifications (continued)
MTE Part
Number
Amps
Rating
Inductance
mh
Watts
Loss
A B C D E
F
Approx Weight
in./
mm
in./
mm
in./
mm
in./
mm
in./
mm
in./
mm
Lbs./
Kg
RL-01802
18
1.5
43
5.9/
149.9
5.1/
129.5
3.5/
88.9
2.5/ 63
2/ 51
3/
76.2
12/
5.4
RL-01803
18
2.5
43
7.1/
180.3
5.7/
144.8
3.7/ 94
2.6/ 66
3/ 76
3/
76.2
16/
7.3
RL-02501
25
0.5
48
7.1/
180.3
5.7/
144.8
3.4/
86.7
2.4/ 60
3/ 76
3/
76.2
11/
5
RL-02502
25
1.2
52
7.1/
180.3
5.8/
147.3
3.4/
86.7
2.4/ 60
3/ 76
3/
76.2
14/
6.4
RL-02503
25
1.8
61
7.1/
180.3
5.8/
147.3
4.2/
106.7
3.1/ 79
3/ 76
3/
76.2
20/
9.1
RL-03501
35
0.4
49
7.1/
180.3
5.7/
144.8
3.7/ 94
2.6/ 66
3/ 76
3/
76.2
14/
6.4
RL-03502
35
0.8
54
7.1/
180.3
5.8/
147.3
3.7/ 94
2.8/ 70
3/ 76
3/
76.2
16/
7.3
RL-03503
35
1.2
54
8.9/
226.1
7.2/
182.9
4.6/
116.8
3.2/ 80
3/ 76
4.3/
108
26/
11.8
RL-04501
45
0.3
54
8.9/
226.1
7.1/
180.3
4.6/
116.8
3.2/ 80
3/ 76
4.3/
108
22/
10
RL-04502
45
0.7
62
8.9/
226.1
7.2/
182.9
4.6/
116.8
3.2/ 80
3/ 76
4.3/
108
26/
11.8
RL-04503
45
1.2
65
8.9/
226.1
7.3/
185.4
5.1/
129.5
3.7/ 93
3/ 76
4.3/
108
34/
15.4
RL-05501
55
0.25
64
9/
228.6
6.9/
175.3
5.3/
134.6
3.2/ 80
3/ 76
4.3/
108
24/
109.
RL-05502
55
0.5
67
9/
228.6
6.9/
175.3
5.3/
134.6
3.2/ 80
3/ 76
4.3/
108
26/
11.8
RL-05503
55
0.85
71
8.9/
226.1
6.9/
175.3
6.3/
160
3.9/ 99
3/ 76
4.3/
108
34/
15.4
RL-08001
80
0.2
82
8.9/
226.1
6.9/
175.3
5.7/
144.8
3.5/ 88
3.63/ 92
4.3/ 108
25/
11.3
RL-08002
80
0.4
86
8.9/
226.1
7.1/
180.3
5.7/
144.8
3.5/
88
3.63/ 92
4.3/ 108
33/
15
RL-08003
80
0.7
96
10.8/
274.3
8.5/
215.9
6.6/
167.6
4.2/ 106
3.63/ 92
5.6/
141.7
63/
28.6
RL-10001
100
0.15
94
8.9/
226.1
7/
177.8
6/
152.4
3.5/ 88
3.63/ 92
4.3/ 108
29/
13.2
RL-10002
100
0.3
84
8.9/
226.1
7/
177.8
6.6/
167.6
3.7/
93
3.63/ 92
4.3/ 108
37/
16.8
RL-10003
100
0.45
108
10.8/
274.3
8.4/
213.4
7.8/
198.1
4.2/ 106
3.63/ 92
5.6/
141.7
67/
30.4
For detailed drawings of each reactor, click on the “MTE Part Number”.
Page 32
RL Reactors Technical Reference Manual 208V 690V
27 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors
Technical and Mechanical Specifications
Table 4-14: RL Reactors Open Panel Technical Specifications (continued)
MTE Part
Number
Amps
Rating
Inductance
mh
Watts
Loss
A B C D E
F
Approx Weight
in./
mm
in./
mm
in./
mm
in./
mm
in./
mm
in./
mm
Lbs./
Kg
RL-13001
130
0.1
108
9.6/
243.8
7.3/
185.4
5.9/
149.9
3.2/ 80
3/ 76
4.3/
108
29/
13.2
RL-13002
130
0.2
180
9.6/
243.8
7.2/
182.9
6/
152.4
3.7/ 93
3.63/ 92
4.3/ 108
43/
19.5
RL-13003
130
0.3
128
10.8/
274.3
8.5/
215.9
7.3/
185.4
4.2/ 106
3.63/ 92
5.6/
141.7
64/
29
RL-16001
160
0.075
116
9.6/
243.8
7.2/
182.9
6/
152.4
3.2/ 80
3.63/ 92
4.3/ 108
41/
18.6
RL-16002
160
0.15
149
10.8/
274.3
8.4/
213.4
6.7/
170.2
3.5/
88
3.63/ 92
5.6/
141.7
54/
24.5
RL-16003
160
0.23
138
10.8/
274.3
8.5/
215.9
7.4/ 187
4.7/ 118
3.63/ 92
5.6/
141.7
74/
33.6
RL-20001B14
200
0.055
124
9.6/
243.8
7.2/
182.9
7.1/
180.3
4.2/ 106
3.63/ 92
4.3/ 108
38/
17.2
RL-20002B14
200
0.11
168
9.6/
243.8
7.2/
182.9
7.9/
200.7
4.4/ 112
3.63/ 92
4.3/ 108
54/
24.5
RL-20003B14
200
0.185
146
10.8/
274.3
8.3/
210.8
9.1/
231.1
5.9/ 150
3.63/ 92
5.6/
141.7
100/
45.4
RL-25001B14
250
0.045
154
9.6/
243.8
7/
177.8
8.1/
205.7
4.2/ 106
3.63/ 92
4.3/ 108
47/
21.3
RL-25002B14
250
0.09
231
10.8/
274.3
8.5/
215.9
7.6/ 193
5.2/ 131
4.6/ 117
5.6/
141.7
80/
36.3
RL-25003B14
250
0.15
588
14.3/
363.2
11.2/
284.5
8.7/ 221
5.8/ 148
4.6/ 117
7.2/
182.9
125/
56.7
RL-32001B14
320
0.04
224
10.8/
274.3
8.4/
213.4
7.9/
200.7
5.2/ 131
4.6/ 117
5.6/
141.7
80/
36.3
RL-32002B14
320
0.075
264
10.8/
274.3
8.4/
213.4
8.9/
226.1
5.9/ 149
4.6/ 117
5.6/
141.7
102/
46.3
RL-32003B14
320
0.125
642
14.3/
363.2
11.1/
281.9
9.4/
238.8
7.1/ 181
4.6/ 117
7.2/
182.9
160/
72.6
RL-40001B14
400
0.03
213
11/
279.4
8.4/
213.4
8.6/
218.4
5.2/ 131
4.6/ 117
5.6/
141.7
84/
38.1
RL-40002B14
400
0.06
571
14.3/
363.2
11.1/
281.9
9.4/
238.8
6.8/ 172
4.6/ 117
7.2/
182.9
118/
53.5
RL-40003B14
400
0.105
293
14.3/
363.2
11.1/
281.9
10.9/
276.9
7.3/ 184
4.6/ 117
7.2/
182.9
149/
67.6
RL-50001B14
500
0.025
226
10.8/
274.3
8.5/
215.9
9.4/
238.8
5.5/ 140
4.6/ 117
5.6/
141.7
93/
42.2
RL-50002
500
0.05
694
14.3/
363.2
11.1/
281.9
10.6/
269.2
6.8/ 172
4.6/ 117
7.2/
182.9
160/
72.6
For detailed drawings of each reactor, click on the “MTE Part Number”.
Page 33
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 28
RL Line/Load Reactors
Technical and Mechanical Specifications
Table 4-14: RL Reactors Open Panel Technical Specifications (continued)
MTE Part
Number
Amps
Rating
Inductance
mh
Watts
Loss
A B C D E
F
Approx Weight
in./
mm
in./
mm
in./
mm
in./
mm
in./
mm
in./
mm
Lbs./
Kg
RL-50003
500
0.085
985
14.3/
363.2
11.1/
281.9
13/
330.2
9.8/ 248
4.6/ 117
7.2/
182.9
210/
95.3
RL-60001
600
0.02
609
14.3/
363.2
11.1/
281.9
8.8/
223.5
5.3/ 134
4.6/ 117
7.2/
182.9
120/
54.4
RL-60002
600
0.04
689
14.3/
363.2
11.1/
281.9
11/
279.4
8/
203
4.6/ 117
7.2/
182.9
175/
79.4
RL-60003
600
0.065
406
14.3/
363.2
11.1/
281.9
13.5/
342.9
9.3/ 235
4.6/ 117
7.2/
182.9
270/
122.5
RL-75001
750
0.015
713
14.3/
363.2
11.2/
284.5
10.4/
264.2
6.6/ 168
7.2/ 183
7.2/
182.9
140/
63.5
RL-75002
750
0.029
630
14.3/
363.2
11.1/
281.9
11.5/
292.1
8/
204
7.2/ 183
7.2/
182.9
190/
86.2
RL-75003
750
0.048
552
14/
355.6
14.1/
358.1
13/
330.2
9.5/ 242
7.2/ 183
7.2/
182.9
265/
120.2
RL-85001B14
850
0.015
798
17.8/
452.1
15.5/
393.7
14.8/
375.9
7.9/
199.6
7.2/ 183
7.2/
182.9
195/
88.5
RL-85002B14
850
0.027
930
17.8/
452.1
15.5/
393.7
15.5/
393.7
N/A
N/A
7.2/
182.9
215/
97.5
RL-85003B14
850
0.042
1133
17.8/
452.1
15.8/
401.3
17.5/
444.5
N/A
N/A
7.2/
182.9
315/
142.9
RL-90001B14
900
0.014
655
16.2/
411.5
14.4/
365.8
13.8/
350.5
N/A
N/A
7.2/
182.9
195/
88.5
RL-90002B14
900
0.025
1020
17/
431.8
14.6/
370.8
14.7/
373.4
N/A
N/A
7.2/
182.9
215/
97.5
RL-90003B14
900
0.04
1365
17.8/
452.1
15.8/
401.3
17.1/
434.3
N/A
N/A
7.2/
182.9
315/
142.9
RL-100001B14
1000
0.011
810
17/
431.8
14.4/
365.8
12.5/
317.5
N/A
N/A
7.2/
182.9
144/
65.3
RL-100002B14
1000
0.022
1080
17/
431.8
14.6/
370.8
14.7/
373.4
N/A
N/A
7.2/
182.9
215/
97.5
RL-100003B14
1000
0.038
1250
17/
431.8
14.6/
370.8
17.2/
436.9
N/A
N/A
7.2/
182.9
315/
142.9
RL-120001B14
1200
0.009
870
17/
431.8
14.7/
373.4
13.8/
350.5
N/A
N/A
7.2/
182.9
195/
88.5
RL-120002B14
1200
0.019
1270
17/
431.8
14.9/
378.5
16.2/
411.5
N/A
N/A
7.2/
182.9
275/
124.7
RL-120003B14
1200
0.03
1530
17/
431.8
14.7/
373.4
17.7/
449.6
N/A
N/A
7.2/
182.9
390/
176.9
RL-140001
1400
0.008
1235
21/
533.4
16.6/
421.6
15.2/
386.1
N/A
N/A
N/A
500/
226.8
For detailed drawings of each reactor, click on the “MTE Part Number”.
Page 34
RL Reactors Technical Reference Manual 208V 690V
29 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors
Technical and Mechanical Specifications
Table 4-14: RL Reactors Open Panel Technical Specifications (continued)
MTE Part
Number
Amps
Rating
Inductance
mh
Watts
Loss
A B C D E
F
Approx Weight
in./
mm
in./
mm
in./
mm
in./
mm
in./
mm
in./
mm
Lbs./
Kg
RL-140002
1400
0.016
1523
21/
533.4
16.6/
421.6
17.1/
434.3
N/A
N/A
N/A
525/
238.1
RL-140003
1400
0.027
1680
21/
533.4
16.8/
426.7
22/
558.8
N/A
N/A
N/A
850/
385.6
RL-150001
1500
0.008
1432
18/
457.2
16.8/
426.7
15.4/
391.2
N/A
N/A
N/A
635/
288
RL-150002
1500
0.015
1100
18/
457.2
16.8/
426.7
15.5/
393.7
N/A
N/A
N/A
460/
208.7
RL-150003
1500
0.025
2621
21/
533.4
16.6/
421.6
19.9/
505.5
N/A
N/A
N/A
760/
344.7
For detailed drawings of each reactor, click on the “MTE Part Number”.
Page 35
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 30
RL Line/Load Reactors
Technical and Mechanical Specifications
Table 4-15: RL Reactors NEMA 1/2 Technical Specifications
Amps
Rating
MTE Part
Number
Cabinet Part
Number
Cabinet Dimensions
(H x W x D)
Approx.
Weight
Inductance
mH
Inches
Millimeters
Lbs
Kgs 1 RL-00111
CAB-8
8.0 x 8.2 x 6.3
203 x 208 x 160
9 4 100
RL-00112
9 4 50
RL-00113
8 4 36
RL-00114
8 4 18
2
RL-00211
CAB-8
8.0 x 8.2 x 6.3
203 x 208 x 160
9 4 12
RL-00212
9 4 20
RL-00213
9 4 32
RL-00214
8 4 6 4 RL-00411
CAB-8
8.0 x 8.2 x 6.3
203 x 208 x 160
9 4 3
RL-00412
9 4 6.5
RL-00413
10 5 9
RL-00414
11 5 12
8
RL-00811
CAB-8
8.0 x 8.2 x 6.3
203 x 208 x 160
12 5 1.5
RL-00812
13 6 3
RL-00813
16 7 5
RL-00814
18 8 7.5
12
RL-01211
CAB-8
8.0 x 8.2 x 6.3
203 x 208 x 160
14 6 1.25
RL-01212
15 7 2.5
RL-01213
23
10
4.2
18
RL-01811
CAB-8
8.0 x 8.2 x 6.3
203 x 208 x 160
14 6 0.8
RL-01812
17 8 1.5
RL-01813
CAB-13V
13.2 x 13.2 x 13.1
335 x 335 x 333
30
14
2.5
25
RL-02511
CAB-13V
13.2 x 13.2 x 13.1
335 x 335 x 333
25
11
0.5
RL-02512
28
13
1.2
RL-02513
34
15
1.8
35
RL-03511
CAB-13V
13.2 x 13.2 x 13.1
335 x 335 x 333
28
13
0.4
RL-03512
30
14
0.8
RL-03513
40
18
1.2
45
RL-04511
CAB-13V
13.2 x 13.2 x 13.1
335 x 335 x 333
36
16
0.3
RL-04512
40
18
0.7
RL-04513
48
22
1.2
For detailed drawings of each cabinet, click on the “Cabinet Part Number”.
Page 36
RL Reactors Technical Reference Manual 208V 690V
31 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors
Technical and Mechanical Specifications
Table 4-15: RL Reactors NEMA 1/2 Technical Specifications (continued)
Amps
Rating
MTE Part
Number
Cabinet Part
Number
Cabinet Dimensions
(H x W x D)
Approx.
Weight
Inductance
mH
Inches
Millimeters
Lbs
Kgs
55
RL-05511
CAB-13V
13.2 x 13.2 x 13.1
335 x 335 x 333
38
17
0.25
RL-05512
40
18
0.5
RL-05513
48
22
0.85
80
RL-08011
CAB-13V
13.2 x 13.2 x 13.1
335 x 335 x 333
39
18
0.2
RL-08012
47
21
0.4
RL-08013
77
35
0.7
100
RL-10011
CAB-13V
13.2 x 13.2 x 13.1
335 x 335 x 333
43
20
0.15
RL-10012
51
23
0.3
RL-10013
81
37
0.45
130
RL-13011
CAB-13V
13.2 x 13.2 x 13.1
335 x 335 x 333
43
20
0.1
RL-13012
57
26
0.2
RL-13013
78
35
0.3
160
RL-16011
CAB-13V
13.2 x 13.2 x 13.1
335 x 335 x 333
55
25
0.075
RL-16012
68
31
0.15
RL-16013
88
40
0.23
200
RL-20011B14
CAB-13V
13.2 x 13.2 x 13.1
335 x 335 x 333
52
24
0.055
RL-20012B14
68
31
0.11
RL-20013B14
114
52
0.185
250
RL-25011B14
CAB-13V
13.2 x 13.2 x 13.1
335 x 335 x 333
61
28
0.045
RL-25012B14
CAB-17V
24.0 x 17.1 x 18.5
610 x 434 x 470
123
56
0.09
RL-25013B14
168
76
0.15
320
RL-32011B14
CAB-17V
24.0 x 17.1 x 18.5
610 x 434 x 470
123
56
0.04
RL-32012B14
145
66
0.075
RL-32013B14
203
92
0.125
400
RL-40011B14
CAB-17V
24.0 x 17.1 x 18.5
610 x 434 x 470
127
58
0.03
RL-40012B14
161
73
0.06
RL-40013B14
192
87
0.105
500
RL-50011B14
CAB-17V
24.0 x 17.1 x 18.5
610 x 434 x 470
136
62
0.025
RL-50012
CAB-26C2
47.0 x 26.6 x 24.9
1194 x 676 x 632
297
135
0.05
RL-50013
347
157
0.085
For detailed drawings of each cabinet, click on the “Cabinet Part Number”.
Page 37
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 32
RL Line/Load Reactors
Technical and Mechanical Specifications
Table 4-15: RL Reactors NEMA 1/2 Technical Specifications (continued)
Amps
Rating
MTE Part
Number
Cabinet Part
Number
Cabinet Dimensions
(H x W x D)
Approx.
Weight
Inductance
mH
Inches
Millimeters
Lbs
Kgs
600
RL-60011
CAB-26C2
47.0 x 26.6 x 24.9
1194 x 676 x 632
257
117
0.02
RL-60012
312
142
0.04
RL-60013
407
185
0.065
750
RL-75011
CAB-26C2
47.0 x 26.6 x 24.9
1194 x 676 x 632
277
126
0.015
RL-75012
327
148
0.029
RL-75013
402
182
0.048
850
RL-85011B14
CAB-26C2
47.0 x 26.6 x 24.9
1194 x 676 x 632
332
151
0.015
RL-85012B14
352
160
0.027
RL-85013B14
CAB-26C2
47.0 x 26.6 x 24.9
1194 x 676 x 632
481
218
0.042
900
RL-90011B14
CAB-26D2
72.0 x 26.6 x 24.9
1829 x 676 x 632
361
164
0.014
RL-90012B14
381
173
0.025
RL-90013B14
481
218
0.04
1000
RL-100011B14
CAB-26D2
72.0 x 26.6 x 24.9
1829 x 676 x 632
310
141
0.011
RL-100012B14
381
173
0.022
RL-100013B14
481
218
0.038
1200
RL-120011B14
CAB-26D2
72.0 x 26.6 x 24.9
1829 x 676 x 632
361
164
0.009
RL-120012B14
441
200
0.019
RL-120013B14
556
252
0.03
1400
RL-140011
CAB-42C2
72.0 x 42.6 x 30.9
1829 x 1082 x
785
815
370
0.008
RL-140012
840
381
0.016
RL-140013
1165
528
0.027
1500
RL-150011
CAB-42C2
72.0 x 42.6 x 30.9
1829 x 1082 x
785
950
431
0.008
RL-150012
775
352
0.015
RL-150013
1075
488
0.025
For detailed drawings of each cabinet, click on the “Cabinet Part Number”.
Page 38
RL Reactors Technical Reference Manual 208V 690V
33 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors
Technical and Mechanical Specifications
Table 4-16: RL Reactors NEMA 3R Technical Specifications
Amps
Rating
MTE Part
Number
Cabinet Part
Number
Cabinet Dimensions
(H x W x D)
Approx.
Weight
Inductance
mH
Inches
Millimeters
Lbs
Kgs 1 RL-00131
CAB-12C3
24.0 x 12.5 x 17.9
610 x 318 x 455
61
28
100
RL-00132
61
28
50
RL-00133
60
27
36
RL-00134
60
27
18
2
RL-00231
CAB-12C3
24.0 x 12.5 x 17.9
610 x 318 x 455
61
28
12
RL-00232
61
28
20
RL-00233
61
28
32
RL-00234
60
27
6 4 RL-00431
CAB-12C3
24.0 x 12.5 x 17.9
610 x 318 x 455
61
28 3 RL-00432
61
28
6.5
RL-00433
62
28 9 RL-00434
63
29
12
8
RL-00831
CAB-12C3
24.0 x 12.5 x 17.9
610 x 318 x 455
64
29
1.5
RL-00832
65
29 3 RL-00833
68
31 5 RL-00834
70
32
7.5
12
RL-01231
CAB-12C3
24.0 x 12.5 x 17.9
610 x 318 x 455
66
30
1.25
RL-01232
67
30
2.5
RL-01233
75
34
4.2
18
RL-01831
CAB-12C3
24.0 x 12.5 x 17.9
610 x 318 x 455
66
30
0.8
RL-01832
69
31
1.5
RL-01833
73
33
2.5
25
RL-02531
CAB-17C3
31.0 x 17.6 x 26.0
787 x 447 x 660
99
45
0.5
RL-02532
102
46
1.2
RL-02533
108
49
1.8
35
RL-03531
CAB-17C3
31.0 x 17.6 x 26.0
787 x 447 x 660
102
46
0.4
RL-03532
104
47
0.8
RL-03533
114
52
1.2
45
RL-04531
CAB-17C3
31.0 x 17.6 x 26.0
787 x 447 x 660
110
50
0.3
RL-04532
114
52
0.7
RL-04533
122
55
1.2
For detailed drawings of each cabinet, click on the “Cabinet Part Number”.
Page 39
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 34
RL Line/Load Reactors
Technical and Mechanical Specifications
Table 4-16: RL Reactors NEMA 3R Technical Specifications (continued)
Amps
Rating
MTE Part
Number
Cabinet Part
Number
Cabinet Dimensions
(H x W x D)
Approx.
Weight
Inductance
mH
Inches
Millimeters
Lbs
Kgs
55
RL-05531
CAB-17C3
31.0 x 17.6 x 26.0
787 x 447 x 660
112
51
0.25
RL-05532
114
52
0.5
RL-05533
122
55
0.85
80
RL-08031
CAB-17C3
31.0 x 17.6 x 26.0
787 x 447 x 660
113
51
0.2
RL-08032
121
55
0.4
RL-08033
151
68
0.7
100
RL-10031
CAB-17C3
31.0 x 17.6 x 26.0
787 x 447 x 660
117
53
0.15
RL-10032
125
57
0.3
RL-10033
155
70
0.45
130
RL-13031
CAB-17C3
31.0 x 17.6 x 26.0
787 x 447 x 660
117
53
0.1
RL-13032
131
59
0.2
RL-13033
152
69
0.3
160
RL-16031
CAB-17C3
31.0 x 17.6 x 26.0
787 x 447 x 660
129
59
0.075
RL-16032
142
64
0.15
RL-16033
162
73
0.23
200
RL-20031B14
CAB-17C3
31.0 x 17.6 x 26.0
787 x 447 x 660
126
57
0.055
RL-20032B14
142
64
0.11
RL-20033B14
188
85
0.185
250
RL-25031B14
CAB-17C3
31.0 x 17.6 x 26.0
787 x 447 x 660
135
61
0.045
RL-25032B14
168
76
0.09
RL-25033B14
213
97
0.15
320
RL-32031B14
CAB-17C3
31.0 x 17.6 x 26.0
787 x 447 x 660
168
76
0.04
RL-32032B14
190
86
0.075
RL-32033B14
248
112
0.125
400
RL-40031B14
CAB-17C3
31.0 x 17.6 x 26.0
787 x 447 x 660
172
78
0.03
RL-40032B14
206
93
0.06
RL-40033B14
237
108
0.105
500
RL-50031B14
CAB-17C3
31.0 x 17.6 x 26.0
787 x 447 x 660
181
82
0.025
RL-50032
CAB-26C3
47.0 x 26.6 x 30.0
1194 x 676 x 762
319
145
0.05
RL-50033
369
167
0.085
For detailed drawings of each cabinet, click on the “Cabinet Part Number”.
Page 40
RL Reactors Technical Reference Manual 208V – 690V
35 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors
Technical and Mechanical Specifications
Table 4-16: RL Reactors NEMA 3R Technical Specifications (continued)
Amps
Rating
MTE Part
Number
Cabinet Part
Number
Cabinet Dimensions
(H x W x D)
Approx.
Weight
Inductance
mH
Inches
Millimeters
Lbs
Kgs
600
RL-60031
CAB-26C3
47.0 x 26.6 x 30.0
1194 x 676 x 762
279
127
0.02
RL-60032
334
151
0.04
RL-60033
429
195
0.065
750
RL-75031
CAB-26C3
47.0 x 26.6 x 30.0
1194 x 676 x 762
299
136
0.015
RL-75032
349
158
0.029
RL-75033
424
192
0.048
850
RL-85031B14
CAB-26C3
47.0 x 26.6 x 30.0
1194 x 676 x 762
354
161
0.015
RL-85032B14
374
170
0.027
RL-85033B14
CAB-26D3
72.0 x 26.6 x 34.0
1829 x 676 x 864
494
224
0.042
900
RL-90031B14
CAB-26D3
72.0 x 26.6 x 34.0
1829 x 676 x 864
374
170
0.014
RL-90032B14
395
179
0.025
RL-90033B14
494
224
0.04
1000
RL-100031B14
CAB-26D3
72.0 x 26.6 x 34.0
1829 x 676 x 864
323
147
0.011
RL-100032B14
394
179
0.022
RL-100033B14
494
224
0.038
1200
RL-120031B14
CAB-26D3
72.0 x 26.6 x 34.0
1829 x 676 x 864
374
170
0.009
RL-120032B14
454
206
0.019
RL-120033B14
569
258
0.03
1400
RL-140031
CAB-42C3
72.0 x 42.6 x 40.0
1829 x 1082 x
1016
859
390
0.008
RL-140032
884
401
0.016
RL-140033
1209
548
0.027
1500
RL-150031
CAB-42C3
72.0 x 42.6 x 40.0
1829 x 1082 x
1016
994
451
0.008
RL-150032
819
371
0.015
RL-150033
1119
508
0.025
For detailed drawings of each cabinet, click on the “Cabinet Part Number”.
Page 41
RL Reactors Technical Reference Manual 208V – 690V
Form: RL-TRM-E April 2019 REV. 001 36
5. HOW TO INSTALL
Installation Checklist
WARNING
Prior to installation, please refer to all general warnings on pages 1 & 2. Failure to practice this can result in bodily injury!
Input and output wiring to the reactor should be performed by authorized personnel in accordance with NEC and all local electrical codes and regulations.
WARNING
The reactor is designed for use with copper conductors with a minimum temperature rating of 75 degrees C.
MTE NEMA 1 enclosures designed for floor mounting must be mounted with the enclosure base horizontal for proper ventilation. Wall mounting a floor mounted enclosure with the base against the wall will cause the reactor to overheat resulting in equipment damage.
RL Line/Load Reactors are supplied in the following configurations:
Open Reactors: These reactors are designed for mounting within an appropriate electrical equipment enclosure.
NEMA 1/2 & 3R general purpose cabinets: Reactors are supplied in a wall mounted or floor mounted cabinet.
Open Reactors Installation Guidelines:
Reactors rated 300 amperes RMS and under are designed for mounting in both a vertical and horizontal position. Larger reactors must be mounted in a horizontal position typically on the floor of the enclosure. Include the power dissipation of the reactor along with all the other components located in the enclosure to determine the internal temperature rise and cooling requirements of the enclosure. Reactors may be located in any region of the enclosure where the ambient temperature does not exceed 45 degrees C. A general guideline is to allow a side clearance of four (4) inches and a vertical clearance of six (6) inches for proper heat dissipation and access within the enclosure. Clearances may be less if proper ventilation exists. Reactors must operate within temperatures specified in this manual or operating life will be compromised. Also, be aware of minimum electrical clearances as defined by the appropriate system safety standard(s).
NEMA 1/2 & 3R Installation Guidelines:
MTE line/load reactors mounted in CAB-8 and CAB-13V enclosures are designed for wall mounting. All other enclosures are designed for floor mounting. Allow a minimum side, front, and back clearances of twelve (12) inches and vertical clearances of eighteen (18) inches for proper heat dissipation and access.
General Installation Guidelines:
Select a well ventilated, dust-free area away from direct sunlight, rain or moisture. Do not install in or near a corrosive environment. Avoid locations where the reactor will be subjected to excessive vibrations. Do not locate the reactor next to resistors or any other component with operating surface temperatures above 125 degree C.
Page 42
RL Reactors Technical Reference Manual 208V 690V
37 Form: RL-TRM-E April 2019 REV. 001
Grounding
NOTE: For cable shield grounding follow the drive manufacturer’s recommendations.
Grounding and Ground Fault Protection
Due to high leakage currents associated with variable frequency drives, ground fault protective devices do not necessarily operate correctly when placed ahead of a RL Line/Load Reactor feeding a drive. When using this type of device, its function should be tested in the actual installation.
Open reactors must be grounded at the designated grounding terminal or the reactor mounting holes if no designated grounding terminal is provided.
A stud is provided on enclosed reactors for grounding the enclosure. The enclosure must be grounded.
WARNING
The reactor must always be grounded with a grounding conductor connected to ground terminals.
For open reactors, ensure a 2” x 2” area is cleaned of paint and varnish on lower mounting bracket for ground connection.
Page 43
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 38
Power Wiring Connection
Verify that the power source to which the reactor is to be connected is in agreement with the nameplate data on the reactor. A fused disconnect switch or circuit breaker should be installed between the reactor and its source of power in accordance with the requirements of the NEC and all local electrical codes and regulations. Refer to the drive user manual for selection of the correct fuse rating and class.
The reactor is suitable for use on a circuit capable of delivering not more than 65,000 rms symmetrical amperes at 480 volts when protected by Bussman type JJS, KTK, KTK-R, SPP or T class fuses.
Reactor are designed for use with copper conductors with a minimum temperature rating of 75 degrees C. Table 5-1: RL Reactors Torque Ratings (p40) lists the wire range and terminal torque requirements for the power input and output connections by reactor part number.
Refer to Figures 5-1 – 5-4 on page 39 for typical electrical diagrams describing the application of reactors in both line and load applications. For reactors supplied as a component part of a drive system or a component part of power electronic apparatus follow the interconnection diagram supplied by the System Engineer.
Where desirable, a flexible conduit connection to the reactor enclosure should be made to reduce audible noise.
WARNING
Input and output power wiring to the reactor should be performed by authorized personnel in accordance with the NEC and all local electrical codes and regulations. Cable lugs and mounting hardware are provided by the customer.
Any extremely low or high resistance readings indicate a mis-wire and may result in damage to reactor if not corrected.
Page 44
RL Reactors Technical Reference Manual 208V 690V
39 Form: RL-TRM-E April 2019 REV. 001
Typical Connection Diagrams
Figure 5-1: Line Reactor
Connects between power source and VFD
Figure 5-2: Load Reactor
Connects between VFD and load (motor)
Figure 5-3: Multiple Line Reactors
Use individual line reactors for independent start/stop drives connected to a common power source. If inverters are slaved and will always run together, a single reactor sized for total motor current may be used.
Figure 5-4: Single Phase Line Reactors
Standard three phase reactors may be used for single phase applications. Visit the MTE website for more information.
Page 45
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 40
Torque Ratings
Table 5-1: RL Reactors Torque Ratings
Amps
Rating
Max
Amps
MTE Part
Number
Wire Range
(AWG)
Terminal Torque
(in-lbs.)
1
1.5
RL-00101
22 – 10
4.5
RL-00102
22 – 10
4.5
RL-00103
22 – 10
4.5
RL-00104
22 – 10
4.5
2
3
RL-00201
22 – 10
4.5
RL-00202
22 – 10
4.5
RL-00203
22 – 10
4.5
RL-00204
22 – 10
4.5
4
6
RL-00401
22 – 10
4.5
RL-00402
22 – 10
4.5
RL-00403
22 – 10
4.5
RL-00404
22 – 10
4.5
8
12
RL-00801
22 – 10
4.5
RL-00802
22 – 10
4.5
RL-00803
22 – 10
4.5
RL-00804
22 – 10
4.5
12
18
RL-01201
14 – 6
16
RL-01202
14 – 6
16
RL-01203
14 – 6
16
18
27
RL-01801
14 – 6
16
RL-01802
14 – 6
16
RL-01803
14 – 6
16
25
37.5
RL-02501
14 – 6
16
RL-02502
14 – 6
16
RL-02503
14 – 6
16
35
52.5
RL-03501
14 – 6
16
RL-03502
14 – 6
16
RL-03503
18 – 4
16
45
67.5
RL-04501
18 – 4
16
RL-04502
18 – 4
16
RL-04503
18 – 4
16
Page 46
RL Reactors Technical Reference Manual 208V 690V
41 Form: RL-TRM-E April 2019 REV. 001
Torque Ratings
Table 5-1: RL Reactors Torque Ratings (continued)
Amps
Rating
Max
Amps
MTE Part
Number
Wire Range
(AWG)
Terminal Torque
(in-lbs.)
55
82.5
RL-05501
6 – 0
6 – 4 (45) & 2 – 0 (50)
RL-05502
6 – 0
6 – 4 (45) & 2 – 0 (50)
RL-05503
6 – 0
6 – 4 (45) & 2 – 0 (50)
80
120
RL-08001
6 – 0
6 – 4 (45) & 2 – 0 (50)
RL-08002
6 – 0
6 – 4 (45) & 2 – 0 (50)
RL-08003
6 – 0
6 – 4 (45) & 2 – 0 (50)
100
150
RL-10001
6 – 0
6 – 4 (45) & 2 – 0 (50)
RL-10002
6 – 0
6 – 4 (45) & 2 – 0 (50)
RL-10003
6 – 0
6 – 4 (45) & 2 – 0 (50)
130
195
RL-13001
2 – 0000
150
RL-13002
2 – 0000
150
RL-13003
2 – 0000
150
160
240
RL-16001
2 – 0000
150
RL-16002
Copper Tab
Not Applicable
RL-16003
Copper Tab
Not Applicable
200
300
RL-20001B14
Copper Tab
Not Applicable
RL-20002B14
Copper Tab
Not Applicable
RL-20003B14
Copper Tab
Not Applicable
250
375
RL-25001B14
Copper Tab
Not Applicable
RL-25002B14
Copper Tab
Not Applicable
RL-25003B14
Copper Tab
Not Applicable
320
480
RL-32001B14
Copper Tab
Not Applicable
RL-32002B14
Copper Tab
Not Applicable
RL-32003B14
Copper Tab
Not Applicable
400
600
RL-40001B14
Copper Tab
Not Applicable
RL-40002B14
Copper Tab
Not Applicable
RL-40003B14
Copper Tab
Not Applicable
500
750
RL-50001B14
Copper Tab
Not Applicable
RL-50002
Copper Tab
Not Applicable
RL-50003
Copper Tab
Not Applicable
Page 47
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 42
Torque Ratings
Table 5-1: RL Reactors Torque Ratings (continued)
Amps
Rating
Max
Amps
MTE Part
Number
Wire Range
(AWG)
Terminal Torque
(in-lbs.)
600
900
RL-60001
Copper Tab
Not Applicable
RL-60002
Copper Tab
Not Applicable
RL-60003
Copper Tab
Not Applicable
750
1050
RL-75001
Copper Tab
Not Applicable
RL-75002
Copper Tab
Not Applicable
RL-75003
Copper Tab
Not Applicable
850
1275
RL-85001B14
Copper Tab
Not Applicable
RL-85002B14
Copper Tab
Not Applicable
RL-85003B14
Copper Tab
Not Applicable
900
1350
RL-90001B14
Copper Tab
Not Applicable
RL-90002B14
Copper Tab
Not Applicable
RL-90003B14
Copper Tab
Not Applicable
1000
1500
RL-100001B14
Copper Tab
Not Applicable
RL-100002B14
Copper Tab
Not Applicable
RL-100003B14
Copper Tab
Not Applicable
1200
1800
RL-120001B14
Copper Tab
Not Applicable
RL-120002B14
Copper Tab
Not Applicable
RL-120003B14
Copper Tab
Not Applicable
1400
2100
RL-140001
Copper Tab
Not Applicable
RL-140002
Copper Tab
Not Applicable
RL-140003
Copper Tab
Not Applicable
1500
2250
RL-150001
Copper Tab
Not Applicable
RL-150002
Copper Tab
Not Applicable
RL-150003
Copper Tab
Not Applicable
Page 48
RL Reactors Technical Reference Manual 208V 690V
43 Form: RL-TRM-E April 2019 REV. 001
6. START-UP
Safety Precautions
Before start-up, observe the following warnings and instructions:
WARNING
Use extreme caution to avoid contact with line voltage when checking for power.
INJURY OR DEATH MAY RESULT IF SAFETY PRECAUTIONS
ARE NOT OBSERVED.
High voltage is used in the operation of line/load reactors. Use EXTREME caution to avoid contact with high voltage when operating, installing, or repairing equipment containing line/load reactors. Line/load reactors are used in conjunction with inverters, or other electrical equipment that may feedback lethal voltages.
Internal components of the reactor are at line potential when the reactor is connected to the drive. This voltage is extremely dangerous and may cause death or severe injury if you come in contact with it.
Reactors are a component part of an electrical system. Do not proceed with startup until the system startup instructions provided by the System Engineer are understood and followed. Injury, death and damage to equipment may result if the system startup instructions are not followed.
Sequence of Operation
1. Read and follow safety precautions.
2. After installation, ensure that:
All reactor ground terminals are connected to ground.
Power wiring to the utility, drive and motor is in accordance with the power wiring
connection diagrams shown in installation instructions section.
Use the guidelines of Table 5-1: RL Reactors Torque Ratings (p40) for power wire gauges.
3. Check that moisture has not condensed on the reactor. If moisture is present, do not proceed with start-up until the moisture has been removed.
4. Refer to the drive user manual for the drive start-up procedure. Observe all safety instructions in the drive user manual.
Page 49
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 44
7. TROUBLESHOOTING
WARNING
When properly installed, this equipment has been designed to provide maximum safety for operating personnel. However, hazardous voltages and elevated temperatures exist within the confines of the enclosure. Servicing should therefore be performed by qualified personnel only and in accordance with OSHA Regulations.
High voltage is used in the operation of this reactor. Use Extreme caution to avoid contact with high voltage when operating, installing or repairing this filter.
INJURY OR DEATH MAY RESULT IF SAFETY PRECAUTIONS ARE NOT OBSERVED.
To aid in troubleshooting, four typical connection diagrams and a troubleshooting guide that lists potential problems and solutions are included:
Figure 5-1: Line Reactor (p39) Figure 5-2: Load Reactor (p39) Figure 5-3: Multiple Line Reactors (p39) Figure 5-4: Single Phase Line Reactors (p39) Table 7-1: Troubleshooting Guide (p45)
Page 50
RL Reactors Technical Reference Manual 208V 690V
45 Form: RL-TRM-E April 2019 REV. 001
Table 7-1: Troubleshooting Guide
PROBLEM:
Line voltage is not present at the reactor output terminals.
Possible cause:
Power to the reactor is turned off.
Solution:
Turn power on.
Possible cause:
One or more external line fuses are blown.
Solution:
Verify the continuity of line fuses in all phases. Replace as necessary.
PROBLEM:
Filter output voltage is not within specification
Possible cause:
Reactor input voltage is not within specification.
Solution:
Check the AC input line voltage and verify that it is within tolerance. Refer to the reactor service conditions and performance specifications for tolerances.
Possible cause:
Source impedance is out of tolerance.
Solution:
Verify that the source impedance is within tolerance. Refer to the reactor service conditions and performance specifications for tolerances.
Possible cause:
Drive set up parameter does not allow for input reactor.
Solution:
Consult drive manufacturer to update setup to accommodate input reactor.
Possible cause:
Input voltage subject to extreme transients such as switching between two voltage sources. Drive faults on over or under voltage.
Solution:
Source switching is not recommended without proper phase synchronizing or allowing reasonable time delay before transfer to new source.