MTE RL-00231, RL-00214, RL-00413, RL-00403, RL-00234 Technical Reference Manual

...
RL Line/Load Reactors
208V – 690V
TECHNICAL REFERENCE MANUAL
WARNING
High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.
Quick Reference
Performance Data
Pages 5 - 7
Selection Guide
Pages 8 - 35
Installation Guide
Pages 36 - 42
Start-up/Troubleshooting
Pages 43 - 45
This page intentionally left blank
RL Reactors Technical Reference Manual 208V – 690V
Form: RL-TRM-E April 2019 REV. 001 III
TABLE OF CONTENTS
RL LINE/LOAD REACTORS ...................................................................................................................... III
1. SAFETY .................................................................................................................................................... 1
WARNINGS AND CAUTIONS ........................................................................................................ 1
GENERAL SAFETY INSTRUCTIONS .............................................................................................. 2
2. GENERAL INFORMATION ...................................................................................................................... 3
RECEIPT & REPAIR STATEMENT ................................................................................................. 3
ENCLOSURES ........................................................................................................................... 4
AGENCY APPROVALS ................................................................................................................ 4
WARRANTY .............................................................................................................................. 4
3. RL LINE/LOAD REACTORS PERFORMANCE DATA ........................................................................... 5
PERFORMANCE SPECIFICATIONS ............................................................................................... 5
AUDIBLE NOISE......................................................................................................................... 6
SERVICE FACTOR ..................................................................................................................... 6
PWM / IGBT PROTECTION ........................................................................................................ 6
HARMONIC ATTENUATION .......................................................................................................... 6
ALTITUDE DERATING ................................................................................................................. 7
TEMPERATURE DERATING ......................................................................................................... 7
4. HOW TO SELECT .................................................................................................................................... 8
SELECTION GUIDE .................................................................................................................... 8
UNDERSTANDING THE RL LINE/LOAD REACTOR PART NUMBER: .................................................. 9
RL LINE/LOAD REACTOR OPTIONS: ....................................................................................... 10
Lug Option Details: ............................................................................................................................. 10
RL LINE/LOAD REACTORS 120V600V SINGLE PHASE ........................................................... 11
Part Number Selection Tables ........................................................................................................... 11
RL LINE/LOAD REACTORS 208 VOLTS, 60HZ ............................................................................ 12
Part Number Selection Tables ........................................................................................................... 12
RL LINE/LOAD REACTORS 208 VOLTS, 60HZ ............................................................................ 13
Part Number Selection Tables ........................................................................................................... 13
RL LINE/LOAD REACTORS 240 VOLTS, 60HZ ............................................................................ 14
Part Number Selection Tables ........................................................................................................... 14
RL LINE/LOAD REACTORS 240 VOLTS, 60HZ ............................................................................ 15
Part Number Selection Tables ........................................................................................................... 15
RL LINE/LOAD REACTORS 400 VOLTS, 50HZ ............................................................................ 16
Part Number Selection Tables ........................................................................................................... 16
RL LINE/LOAD REACTORS 400 VOLTS, 50HZ ............................................................................ 17
Part Number Selection Tables ........................................................................................................... 17
RL LINE/LOAD REACTORS 480 VOLTS, 60HZ ............................................................................ 18
Part Number Selection Tables ........................................................................................................... 18
RL LINE/LOAD REACTORS 480 VOLTS, 60HZ ............................................................................ 19
Part Number Selection Tables ........................................................................................................... 19
RL LINE/LOAD REACTORS 600 VOLTS, 60HZ ............................................................................ 20
Part Number Selection Tables ........................................................................................................... 20
RL LINE/LOAD REACTORS 600 VOLTS, 60HZ ............................................................................ 21
Part Number Selection Tables ........................................................................................................... 21
RL LINE/LOAD REACTORS 690 VOLTS, 50HZ ............................................................................ 22
Part Number Selection Tables ........................................................................................................... 22
RL LINE/LOAD REACTORS 690 VOLTS, 50HZ ............................................................................ 23
Part Number Selection Tables ........................................................................................................... 23
RL LINE/LOAD REACTORS ....................................................................................................... 24
RL Reactors Technical Reference Manual 208V 690V
IV Form: RL-TRM-E April 2019 REV. 001
Open Dimension Reference ............................................................................................................... 24
RL LINE/LOAD REACTORS ....................................................................................................... 25
Technical and Mechanical Specifications ........................................................................................... 25
RL LINE/LOAD REACTORS ....................................................................................................... 26
Technical and Mechanical Specifications ........................................................................................... 26
RL LINE/LOAD REACTORS ....................................................................................................... 27
Technical and Mechanical Specifications ........................................................................................... 27
RL LINE/LOAD REACTORS ....................................................................................................... 28
Technical and Mechanical Specifications ........................................................................................... 28
RL LINE/LOAD REACTORS ....................................................................................................... 29
Technical and Mechanical Specifications ........................................................................................... 29
RL LINE/LOAD REACTORS ....................................................................................................... 30
Technical and Mechanical Specifications ........................................................................................... 30
RL LINE/LOAD REACTORS ....................................................................................................... 31
Technical and Mechanical Specifications ........................................................................................... 31
RL LINE/LOAD REACTORS ....................................................................................................... 32
Technical and Mechanical Specifications ........................................................................................... 32
RL LINE/LOAD REACTORS ....................................................................................................... 33
Technical and Mechanical Specifications ........................................................................................... 33
RL LINE/LOAD REACTORS ....................................................................................................... 34
Technical and Mechanical Specifications ........................................................................................... 34
RL LINE/LOAD REACTORS ....................................................................................................... 35
Technical and Mechanical Specifications ........................................................................................... 35
5. HOW TO INSTALL ................................................................................................................................. 36
INSTALLATION CHECKLIST ....................................................................................................... 36
G
ROUNDING
.......................................................................................................................... 37
POWER WIRING CONNECTION ................................................................................................. 38
TYPICAL CONNECTION DIAGRAMS ................................................................ ............................ 39
TORQUE RATINGS ................................................................................................................... 40
TORQUE RATINGS ................................................................................................................... 41
TORQUE RATINGS ................................................................................................................... 42
6. START-UP .............................................................................................................................................. 43
S
AFETY PRECAUTIONS
.......................................................................................................... 43
7. TROUBLESHOOTING ............................................................................................................................ 44
RL Reactors Technical Reference Manual 208V – 690V
Form: RL-TRM-E April 2019 REV. 001 V
List of Figures
Figure 3-1: Altitude Derating Curve ................................ ............................................................ 7
Figure 3-2: Temperature Derating .............................................................................................. 7
Figure 5-1: Line Reactor ...........................................................................................................39
Figure 5-2: Load Reactor ..........................................................................................................39
Figure 5-3: Multiple Line Reactors.............................................................................................39
Figure 5-4: Single Phase Line Reactors ....................................................................................39
List of Tables
Table 3-1: Performance Specifications ....................................................................................... 5
Table 4-1: RL Reactors 120V – 600V – Single Phase ...............................................................11
Table 4-2: RL Reactors 208V – 3-Phase ...................................................................................12
Table 4-3: RL Reactors 208V – 3-Phase ...................................................................................13
Table 4-4: RL Reactors 240V – 3-Phase ...................................................................................14
Table 4-5: RL Reactors 240V – 3-Phase ...................................................................................15
Table 4-6: RL Reactors 400V – 3-Phase ...................................................................................16
Table 4-7: RL Reactors 400V – 3-Phase ...................................................................................17
Table 4-8: RL Reactors 480V – 3-Phase ...................................................................................18
Table 4-9: RL Reactors 480V – 3-Phase ...................................................................................19
Table 4-10: RL Reactors 600V – 3-Phase .................................................................................20
Table 4-11: RL Reactors 600V – 3-Phase .................................................................................21
Table 4-12: RL Reactors 690V – 3-Phase .................................................................................22
Table 4-13: RL Reactors 690V – 3-Phase .................................................................................23
Table 4-14: RL Reactors Open Panel Technical Specifications .................................................25
Table 4-15: RL Reactors NEMA 1/2 Technical Specifications ...................................................30
Table 4-16: RL Reactors NEMA 3R Technical Specifications ....................................................33
Table 5-1: RL Reactors Torque Ratings ....................................................................................40
Table 7-1: Troubleshooting Guide .............................................................................................45
RL Reactors Technical Reference Manual 208V 690V
1 Form: RL-TRM-E April 2019 REV. 001
1. SAFETY
Warnings and Cautions
The following symbols are used in this manual:
WARNING
High Voltage Warning: warns of situations that dangerously high voltage is involved. Failure to use proper precautions may lead to serious injury or death.
WARNING
General Warning: warns of situations that can result in serious injury or death if proper precautions are not used.
Caution
General Caution: identifies situations that could lead to malfunction or possible equipment damage.
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 2
General Safety Instructions
WARNING
High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.
High voltage is used in the operation of line/load reactors. Use extreme caution to avoid contact with high voltage when operating, installing or repairing line/load reactors.
Injury or death may result if safety
precautions are not observed.
Line/load reactors are used in conjunction with inverters, or other electrical equipment that may feedback lethal voltages. Follow the safety instructions in the equipment used with the reactor in addition to the safety instructions in this manual.
WARNING
The opening of the branch circuit protective device may be an indication that a fault current has been interrupted. To reduce the risk of fire or electrical shock, line/load reactors should be examined and replaced if damaged.
An upstream disconnect/protection device must be used as required by the National Electrical Code (NEC) or governing authority.
Even if the upstream disconnect/protection device is open, the drive downstream of the line/load reactor may feedback high voltage to the reactor. The drive safety instructions must be followed. Injury or death may result if safety precautions are not observed.
Line/load reactors must be grounded with a grounding conductor connected to all grounding terminals. Open panel reactors must have a 2”x2” area cleaned of paint and varnish on the lower mounting bracket.
Only spare parts obtained from MTE Corporation or an authorized MTE distributor can be used.
Caution
Loose or improperly secured connections may damage or degrade reactor performance. Visually inspect and secure all electrical connections before power is applied to the filter.
The user of this reactor must assure that the input voltage and frequency is correct for the reactor rating and that the voltage applied falls within the rated operating tolerance envelop specified for the reactor. For severe power line applications where the power feed is likely to experience surges and transients that exceed the input voltage rating, it is recommended that a TVSS (Transient Voltage Surge Suppression) or SPD (Surge Protection Device) be deployed ahead of the reactor to reduce the possibility of exceeding the reactor’s rated voltage. Consult with TVSS or SPD manufacturer to determine the correct protection requirements for your power line conditions.
RL Reactors Technical Reference Manual 208V 690V
3 Form: RL-TRM-E April 2019 REV. 001
2. GENERAL INFORMATION
The purpose of this manual is to properly specify, size, and install the RL Series Line/Load Reactors.
For most current information, please refer to website
https://www.mtecorp.com/products/reactors/rl-reactors/
Receipt & Repair Statement
Upon Receipt of this Filter:
RL Line/Load Reactors have been subjected to demanding factory tests before shipment. Carefully inspect the shipping container for damage that may have occurred in transit. Then unpack the reactor and carefully inspect for any signs of damage. Save the shipping container for future transport of the reactor.
In the event of damage, please contact and file a claim with the freight carrier involved immediately.
If the equipment is not going to be put into service upon receipt, cover and store the reactor in a clean, dry location. After storage, ensure that the equipment is dry and that no condensation or dirt has accumulated on the reactor before applying power.
Repair/Exchange Procedure
MTE Corporation requires a Return Material Authorization Number and form before we can accept any reactors that qualify for return or repair. If problems or questions arise during installation, setup, or operation of the reactor, please contact MTE for assistance at:
Toll Free: 1-800-455-4MTE (1-800-455-4683)
International Tel: (+1)262-253-8200
Fax: (+1)262-253-8222
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 4
Enclosures
MTE enclosures are designed to provide a degree of protection for electrical components and prevent incidental personnel contact with the enclosed equipment. Depending on the enclosure selected, these enclosures meet the requirements of NEMA 1/2 or 3R.
An approximate cross reference guide between NEMA, UL, CSA and IEC enclosure follows.
Type 1 NEMA / IEC IP20 Enclosure:
Are designed for indoor use and will provide protection against contact with the enclosed equipment.
Type 2 NEMA / IEC IP20 Enclosure:
Are designed for indoor use and will provide protection against contact with the enclosed equipment and provide a degree of protection against limited amounts of falling water and dirt.
Type 3R NEMA / IEC IP23 Enclosure:
Are designed for outdoor use primarily to provide protection against contact with the enclosed equipment and provide a degree of protection against falling rain sleet and external ice formation.
Agency Approvals
UL-508, File E180243 Component Listed (1 amp – 2400 amps) UL-508, File E180243 UL Listed NEMA 1 units (1 amp – 2400 amps) CSA C22.2, File LR29753-13 CSA Certified (1 amp – 2400 amps) Class N, 200° C, File E66214, Type 200-18, UL Recognized Insulation System CE Marked
Warranty
Five (5) years from the date of shipment. See https://www.mtecorp.com/industry-leading-
warranty/ for details.
RL Reactors Technical Reference Manual 208V 690V
5 Form: RL-TRM-E April 2019 REV. 001
3. RL LINE/LOAD REACTORS PERFORMANCE DATA
Performance Specifications
Table 3-1: Performance Specifications
Impedance Levels
1.5%, 2%, 3%, 4%, 5% available
Continuous Service Factor*
Reactors rated 1 to 750 Amps – 150% of rating Reactors rated above 750 Amps – 125% rating
Overload Rating
200% of fundamental for 30 minutes 300% of fundamental for 1 minute
Input Voltage(s)
120V – 600V 1 phase 208V – 690V 3 phase
Current Range
1A – 1,500A
Maximum System Voltage
600 Volts (units with terminal blocks) 690 Volts (units with box lugs or tab terminals)
Maximum Switching Frequency
20 kHz
Ambient Temperature (Operating)
-40 to +50 degrees C Open Panel Reactor
-40 to +40 degrees C Enclosed Reactor
-40 to +90 degrees C Storage
Insulation System
Class N (200° C)
Altitude without derating
3,300 feet above sea level
Fundamental Frequency
50/60 Hz
Inductance Curve
100% at 100% current 100% at 150% current 50% at 350% current (minimum)
Inductance Tolerance
+/- 10%
Notes:
*Select reactor based on fundamental current rating. The Short Circuit Current Rating (SCCR) is not required under Exception No.1 of
UL508A SB4.2.1 effective 4/25/06.
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 6
Audible Noise
RL Line/Load Reactors offer low noise operation. Core and coil construction, flux density control, harmonic compensation as well as our epoxy impregnation process assure minimal audible noise
radiation. Although our reactors are typically “quiet”, waveforms vary by drive type and application
and therefore reactor audible noise may vary by application. Noise levels may be affected by type of motor and motor conductor as well as motor conductor length.
Typical audible noise levels for units selected from our catalog by HP rating are:
2 thru 12 amps 55 dBA
18 thru 100 amps 65 dBA
130 thru 400 amps 70 dBA
500 thru 1200 amps 75 dBA
Service Factor
RL Line/Load Reactors are compensated for the additional currents and high frequencies caused by the presence of harmonics. The reactor fundamental current rating indicates the typical full load motor current and is also the basis of impedance rating. Standard reactors rated 1 amps thru 750 amps offer a full 1.5 service factor rating which allows them to carry overload current up to 150% of their fundamental rating when applied as an input line reactor. Since the nameplate ratings of motor drives (ASD) varies widely by manufacturer, this helps to assure that the reactor maximum current rating is compatible with the nameplate current rating on the ASD. The service factor rating compensates for ASD manufacturer variances in motor drive current ratings and for harmonic currents. Nominal inductance is assured all the way up to the service factor current rating.
PWM / IGBT Protection
RL Line/Load Reactors are protected against the high peak voltage and fast rise time voltage pulses associated with PWM waveforms. The dielectric strength is 4000 volts rms and RL reactors meet the ratings of an inverter duty motor (NEMA MG-1, part 31). For convenience, they can be located either at the motor or at the drive.
Harmonic Attenuation
Our unique harmonic compensation assures maximum circuit inductance in the presence of complex waveforms and can be relied upon to minimize input total harmonic current distortion (THID). Additionally, it offers superior absorption of transient voltage spikes. Our standard reactors will typically reduce 6-pulse rectifier input current harmonics to the following levels at full load operating conditions:
3% reactor alone 45% or less THID
5% reactor alone 35% or less THID
3% AC reactor + 3% DC link choke 33% or less THID
5% AC reactor + 3% DC link choke 28% or less THID
(DC link choke inductance is equivalent ac impedance).
RL Reactors Technical Reference Manual 208V 690V
7 Form: RL-TRM-E April 2019 REV. 001
Altitude Derating
Figure 3-1: Altitude Derating Curve
Temperature Derating
Figure 3-2: Temperature Derating
Altitude Derating Curve
0.70
0.75
0.80
0.85
0.90
0.95
1.00
1.05
0 3300 6600 9900 13200 16500
Altitude (Feet)
Current De-Rating Factor
Reactor Temperature De-Rating
0.60
0.65
0.70
0.75
0.80
0.85
0.90
0.95
1.00
1.05
40 45 50 55 60 65 70 75 80 85 90
Ambient Temperature Deg. C
Current De-Rating Factor
RL Reactors Technical Reference Manual 208V – 690V
Form: RL-TRM-E April 2019 REV. 001 8
4. HOW TO SELECT
Selection Guide
MTE RL Line/Load Reactors are optimized to support global IEC and NEC Drive /motor
applications. RL’s are RMS current rated impedance devices. Selection is based on the choice
of inductance correlated to the application motor full load amps, voltage and frequency and the number of phases. Use the product selection brochure based on input voltage and NEC FLA motor selection table for common voltages. For critical impedance selection based on specific HP or load currents, consult MTE applications engineering.
Choose the impedance level:
3% Reactors rated at 3% are typically sufficient to absorb line spikes and motor current
surges, and help prevent nuisance tripping to the drive and circuit breakers in most applications. 3% is typically specified by most drive manufacturers.
5% Reactors rated at 5% are best for reducing harmonic current and frequencies. Use
them when you must reduce VFD drive generated harmonics, and to reduce motor operating temperature.
Single Phase Applications:
RL reactors may also be sized to protect single phase drives. Please see MTE Application Note: How to Use a 3-Phase Line Reactor for a Single-Phase Application for details.
NOTE: For inverters feeding isolation transformers select a reactor with a current rating equal to or greater than that of the transformer primary current.
Please verify information below for proper selection:
Line Voltage and Frequency: Input voltage 208V-690V 50/60 Hz (3-phase); 120V-
600V 50/60 Hz (1-phase). See Table 3-1: Performance Specifications (p5) for specification.
Current Rating: Support for 1 Amp – 1500 Amps. Performance: See Table 3-1: Performance Specifications (p5) for specification. Altitude: 3,300 feet above sea level without derating. See Figure 3-1: Altitude Derating
Curve (p7) for derating information.
Enclosure Type: Open Panel, NEMA 1/2 & NEMA 3R, see Enclosures (p4) for
enclosure descriptions.
Temperature: See Table 3-1: Performance Specifications (p5) for operating
temperature information and Figure 3-2: Temperature Derating (p7) for derating information.
Refer to Article 430 Table 430.91 of the National Electrical code for the selection of the
appropriate enclosure Type Number for your application.
RL Reactors Technical Reference Manual 208V 690V
9 Form: RL-TRM-E April 2019 REV. 001
Understanding the RL Line/Load Reactor Part Number:
RL _ - _ _ _ _ X X X
MOV Options* A = 208 Volts
C = 240 Volts E = 400 Volts G = 480 Volts J = 600 Volts
Current Rating (i.e. 001 is 1 Amp) Mechanical Configurations 0 = Base Mount
1 = NEMA 1
3 = NEMA 3R Reactor Relative Impedance Number 1 - 4 (1) is lowest value
Lug/Terminal Block Options**
B1 = Side Facing B8 = Top Mounted
B14 = Front Facing
RL Reactors Technical Reference Manual 208V 690V
Form: RL-TRM-E April 2019 REV. 001 10
RL Line/Load Reactor OPTIONS:
* MOV Option – Adding Metal Oxide Varistors (MOV) can help prevent damage to reactors and variable frequency drives (VFD’s) when large spikes in transient voltage occur.
** B1 & B14 Lug Orientation Option – If the current RL part lug orientation does not work for installation; a modification can be made to adjust the lug to be either Side Facing or Front Facing. To signify the change, add either B1 or B14 to the end of the RL part number.
** B8 Terminal Block Option – If the current RL front mounted terminal block does not work for installation, a modification can be made to adjust a terminal block to be Top Mounted. To signify the change, add B8 to the end of the RL part number. (Note: Terminal blocks are only available
on reactors 45 Amps and below. Contact MTE for additional information.)
Lug Option Details:
“B1” Lug Orientation Option “B14” Lug Orientation Option
“B8” Terminal Block Modification
Loading...
+ 35 hidden pages