MTE RL-00203, RL-00101, RL-00201, RL-00202, RL-00204 User Manual

...
RL Series
Line/ load Reactors
USER MANUAL
PART NO. INSTR -011
REL. 150109 REV. 006
© 2015 MTE Corporation
Data subject to change without notice 2 of 32 INSTR-011 REL. 150109 REV. 006
See www.mtecorp.com for current data and CAD drawings
Important User Information
NOTICE
MTE Series RL Line/Load Reactors are components designed to improve the reliability of adjustable frequency drives, DC drives and a wide variety of other types of power electronic equipment. In addition, they provide limited input line current harmonic mitigation and aid in long lead protection for inverter fed motors. Note: (See MTE harmonic filters and motor protection products for guaranteed results.) MTE reactors are available in a large number of current ratings and a variety of inductance values. The suitability of a line/load reactor for a specific application must therefore be ultimately determined by the customer. In no event will MTE Corporation assume responsibility or liability for any direct or consequential damages resulting from the use or application of reactors. Nor will MTE Corporation assume patent liability with respect to the use of information, circuits or equipment described in this instruction manual.
This manual includes recently redesigned performance enhanced reactors. These reactors are physically smaller and weigh less than the reactors they replace. Enhanced reactors have base mounting brackets with additional slotted holes to accommodate past mounting hole centers. You may use your existing drill pattern or choose the new layout. The tables contained in this manual reflect historical mounting dimensions for previous reactors.
This document supports computer searches and is best viewed with Adobe Acrobat PDF viewer (6 or 7). Click links are incorporated throughout the document to speedup document navigation.
AC Line / Load Reactors
User Manual
Data subject to change without notice 3 of 32 INSTR-011 REL. 150109 Rev.006
See www.mtecorp.com for current data and CAD drawings
Table of Contents
IMPORTANT USER INFORMATION .......................................................................................... 2
TABLE OF CONTENTS ............................................................................................................. 3
IMPORTANT SAFETY INFORMATION ...................................................................................... 4
INTRODUCTION ........................................................................................................................ 5
MODEL NUMBER CODES ......................................................................................................... 6
SPARE PARTS .......................................................................................................................... 7
LUG OPTION DETAILS: ............................................................................................................ 8
PRODUCT SPECIFICATIONS ................................................................................................. 10
DE-RATING CURVES .............................................................................................................. 13
DIMENSION REFERENCE ....................................................................................................... 14
MOUNTING COMPATIBILITY .................................................................................................. 15
MECHANICAL DETAILS OPEN REACTORS .......................................................................... 16
NEMA1 MECHANICAL DATA .................................................................................................. 18
RECOMMENDED CONDUIT ENTRY FOR FLOOR MOUNTED............................................... 20
ENCLOSURE DIMINSIONS ..................................................................................................... 21
TECHNICAL DATA .................................................................................................................. 25
INSTALLATION INSTRUCTIONS ............................................................................................ 27
POWER WIRING CONNECTION ............................................................................................. 28
TYPICAL CONNECTION DIAGRAMS ..................................................................................... 29
SEQUENCE OF OPERATION .................................................................................................. 30
STARTUP ................................................................................................................................. 31
AC Line / Load Reactors
User Manual
Data subject to change without notice 4 of 32 INSTR-011 REL. 150109 REV. 006
See www.mtecorp.com for current data and CAD drawings
IMPORTANT SAFETY INFORMATION
WARNING
ONLY A QUALIFIED ELECTRICIAN CAN CARRY OUT THE ELECTRICAL
INSTALLATION OF LINE/LOAD REACTORS
WARNING
High voltage is used in the operation of line/load reactors. Use Extreme caution to avoid contact with high voltage when operating, installing or repairing equipment containing line/load reactors
INJURY OR DEATH MAY RESULT IF SAFETY PRECAUTIONS ARE NOT OBSERVED.
Line/load reactors are used in conjunction with inverters, or other electrical equipment that may feedback lethal voltages. Follow the safety instructions in the equipment used with the reactor in addition to the safety instruction in this manual.
WARNING
The opening of the branch circuit protective device may be an indication that a fault current has been interrupted. To reduce the risk of fire or electrical shock, line/load reactors should be examined and replaced if damaged.
WARNING
An upstream disconnect/protection device must be used as required by the National Electrical Code (NEC).
WARNING
Even if the upstream disconnect/protection device is open, a drive or inverter down stream of the line/load reactor may feed back high voltage to the reactor. The inverter or drive safety instructions must be followed.
INJURY OR DEATH MAY RESULT IF THE DRIVE SAFETY PRECAUTIONS ARE NOT OBSERVED.
WARNING
The frame of line/load reactors must be grounded at least at one of the reactor’s mounting holes.
WARNING
Only spare parts obtained from MTE Corporation or an authorized MTE distributor can be used
AC Line / Load Reactors
User Manual
Data subject to change without notice 5 of 32 INSTR-011 REL. 150109 REV. 006
See www.mtecorp.com for current data and CAD drawings
INTRODUCTION
This manual was specifically developed to assist in the installation, interconnection and operation of MTE Corporation Series RL Line/Load Reactors
This manual is intended for use by personnel experienced in the operation and maintenance of electronic drives, inverters and similar types of power electronic equipment. Because of the high voltages required by the equipment connected to line/load reactors and the potential dangers presented by rotating machinery, it is essential that all personnel involved in the operation and maintenance of line/load reactors know and practice the necessary safety precautions for this type of equipment. Personnel should read and understand the instructions contained in this manual before installing, operating or servicing line/load reactors and the drive to which the reactor is connected.
Upon Receipt of a Reactor:
MTE Line/load Reactors have been subjected to demanding factory tests before shipment. Carefully inspect the shipping container for damage that may have occurred in transit. Then unpack the filter and carefully inspect for any signs of damage. Save the shipping container for future transport of the reactor.
In the event of damage, please contact and file a claim with the freight carrier involved immediately.
If the equipment is not going to be put into service upon receipt, cover and store the reactor in a clean, dry location. After storage, ensure that the equipment is dry and that no condensation has accumulated on the reactor before applying power.
Repair/Exchange Procedure
MTE Corporation requires a Returned Material Authorization Number before it can accept any reactors that qualify for return or repair. If problems or questions arise during installation, setup, or operation of the filter, please call us for assistance at:
Phone: 1-262-253-8200 FAX: 1-262-253-8222
AC Line / Load Reactors
User Manual
Data subject to change without notice 6 of 32 INSTR-011 REL. 150109 REV.006
See www.mtecorp.com for current data and CAD drawings
MODEL NUMBER CODES
1000 100 10 1
RL -
none blank
1
208 Volts
A
0
2
240 Volts
C 1 3
380 - 415 volts
E 2 4
480 Volts
G 3
600 Volts
J
Custom design
X
Side Facing Lug B1
Top Mounted Terminal B8
Front Facing Lug B14
NEMA 1
OVERSIZE NEMA 1
NEMA 3R
MOV
option
Fundamental Current Amps
Style
Z No.
Option
suffix
Open Frame
AC Line / Load Reactors
User Manual
Data subject to change without notice 7 of 32 INSTR-011 REL. 150109 REV.006
See www.mtecorp.com for current data and CAD drawings
Spare Parts
For standard type “RL” AC Line / Load Reactors
Description Part No.
To adds SLU 225 box lugs on B14 LUGKIT-003 To adds XT 500 box lugs on B14 LUGKIT-002
Terminal Blocks
Description Part No.
For RL-00101 thru RL-00804 36-822-049 For RL-01201 thru RL-03502 36-825-004 For RL-03503 thru RL-04503 TERMBLK-013
AC Line / Load Reactors
User Manual
Data subject to change without notice 8 of 32 INSTR-011 REL. 150109 REV.006
See www.mtecorp.com for current data and CAD drawings
LUG OPTION DETAILS:
“B1” Terminal Modification “B14” Terminal Modification
“B8” Terminal Modification
“SLU” Lug Option
Wire range: 2 - 0000
Wire range: 00 – 500 mcm
AC Line / Load Reactors
User Manual
Data subject to change without notice 9 of 32 INSTR-011 REL. 150109 REV.006
See www.mtecorp.com for current data and CAD drawings
SLU Lug Options cont.
SLU 225 shown on 200 amp Reactor
XT 500 shown on 250 amp Reactor
AC Line / Load Reactors
User Manual
Data subject to change without notice 10 of 32 INSTR-011 REL. 150109 REV.006
See www.mtecorp.com for current data and CAD drawings
PRODUCT SPECIFICATIONS
Standard impedance values 1-1/2%, 2, 3%, 4%, 5% available Impedance basis Reactor fundamental current rating Service Factor
(Continuous)
Reactors rated 1 to 750 Amps 150% of fundamental rating Reactors rated above 750 Amps 125% of fundamental rating minimum Note: Select reactor based on fundamental current
rating
Overload Rating 200% of fundamental for 30 minutes
300% of fundamental for 1 minute Maximum system voltage 600 Volts (units with terminal blocks)
690 Volts (units with box lugs or tab terminals)
Maximum switching frequency 20 KHz Insulation system Class N (200° C)
Temperature rise 135° C (average)
Ambient temperature Full load:
-40 to 50° C Open
-40 to 45° C Enclosed
-40 to 90° C Storage
Altitude (maximum) 1000 meters Fundamental frequency
Line or Load 50/60 Hz
Approvals: CE, UL-508, CSA C22.2 Inductance curve (typical) 100% at 100% current
100% at 150% current 50% at 350% current (minimum)
Inductance tolerance +/- 10% Impregnation: High Bond Strength Solvent less Epoxy, 200° C
UL94HB recognized
Dielectric Strength 3000 volts rms (4243 volts peak) dv/dt Protection Meets NEMA MG-1, part 31 (same as inverter duty
motors) Protection: Open reactors with terminal blocks through 45 amps
meet IP20