MTE Matrix ONE Product Specification

Matrix® ONE Technical Reference Manual 240V & 480V
4. PRODUCT SPECIFICATIONS
Table 4-1: Performance Specifications
Service Conditions Load: Typically a 4-pulse rectifier Input Voltage(s) Maximum THID 12% at full load
Input voltage line distortion 1% maximum to ensure performance guaranty Minimum source impedance 1.5% Service Factor 1.00 Overload 150% for 1 minute duration Ambient Temperature (Operating) Open Panel Filters -40 to +50 degrees C Enclosed Filters -40 to +40 degrees C Storage Temperature -40 to +90 degrees C
Altitude Relative Humidity 0 to 95% non-condensing
Over Voltage Category II Insertion Load
Notes (SCCR):
240 VAC ± 10%, 60 ± 0.75 Hz 1 phase 480 VAC ± 10%, 60 ± 0.75 Hz 1 phase
0 to 3300 Feet above sea level. Refer to Figure 5-4: Altitude Derating Curve
+10% no load
-10% full load
The Short Circuit Current Rating (SCCR) is not required under Exception No.1 of
UL508A SB4.2.1 effective 4/25/06. This exception also applies to all the Contactor Options (002, 009, 012, and similar), where the Contactors are separated from the Main Power path by exempt components (such as Reactors) of sufficient Impedance, which is assured in case of the Reactors that are integral components of our Filter.
Form: MS-TRM-E October 2015 REV. 001 14
Matrix® ONE Technical Reference Manual 240V & 480V
Enclosures
MTE enclosures are designed to provide a degree of protection for electrical components and prevent incidental personnel contact with the enclosed equipment. Depending on the enclosure selected, these enclosures meet the requirements of NEMA 1/2 or 3R.
An approximate cross reference guide between NEMA, UL, CSA and IEC enclosure follows.
Type 1 NEMA / IEC IP20 Enclosure:
Are designed for indoor use and will provide protection against contact with the enclosed equipment.
Type 2 NEMA / IEC IP20 Enclosure:
Are designed for indoor use and will provide protection against contact with the enclosed equipment and provide a degree of protection against limited amounts of falling water and dirt.
Type 3R NEMA / IEC IP23 Enclosure:
Are designed for outdoor use primarily to provide protection against contact with the enclosed equipment and provide a degree of protection against falling rain sleet and external ice formation.
Agency Approvals
UL and cUL listed to UL508 Type MX and CSA-C22.2 No 14-95 File E180243 (1-999 Ampere, 120VAC through 690VAC 50/60Hz 1 or 3 phase).
Warranty
Three years from the date of shipment. See www.mtecorp.com for details.
Over Temperature Switch
Table 4-2: Over Temperature Switch
NC Switch opens at 180 Deg. +/- 5 Deg. C
Current Amps Voltage Contact Load
6 120 AC Resistive Loads 3 120 AC Inductive Loads 3 240 AC Resistive Loads
2.5 240 AC Inductive Loads 8 12 VDC Resistive Loads 4 24 VDC Resistive Loads
MTE highly recommends the use of the over temperature switch to prevent damage to the filter in rare instances of overheating from abnormal operating conditions.
Form: MS-TRM-E October 2015 REV. 001 15