MTE HYDROCAL1005 Installation And Operation Manual

HYDROCAL 1005 Manual for Installation and Operation Edition 01.2011
HYDROCAL1005
Gas-in-Oil Analysis System with
Transformer Monitoring Functions
HYDROCAL 1005 Manual for Installation and Operation Page 2/111
Copyright MTE Meter Test Equipment AG All rights reserved.
The contents of this manual are subject to change without notice.
All efforts have been made to ensure the accuracy of this publication but MTE Meter Test Equipment AG can assume no responsibility for any errors Customs tariff number: or their consequences 9027.1010
HYDROCAL 1005 Manual for Installation and Operation Page 1/111
Summary
1. General ....................................................................................................................................... 4
2. Mounting of HYDROCAL1005 unit ............................................................................................ 5
2.1 Locations for installation of HYDROCAL1005 ....................................................................... 5
2.2 Security precautions for installation ...................................................................................... 6
2.3 Preparation for installation .................................................................................................... 8
2.3.1 Power supply for the unit ............................................................................................... 8
2.3.2 Requested tools: ........................................................................................................... 8
2.4 Installation of the HYDROCAL1005 unit ............................................................................... 8
2.5 Electrical Installation of HYDROCAL1005 unit .................................................................... 11
2.6 Completion of Installation ................................................................................................... 12
3. Hardware components of HYDROCAL 1005 .......................................................................... 14
3.1 Front view of HYDROCAL1005 .......................................................................................... 14
3.2 Rear side of HYDROCAL1005 unit ..................................................................................... 15
3.3 Connections on the measuring and controller card ............................................................. 17
3.4 Measurement and extraction Components ......................................................................... 22
4. Software on HYDROCAL unit ................................................................................................. 24
4.1 General information ............................................................................................................ 24
4.2 Description of Gas measurement Process ......................................................................... 24
4.3. Operation Cycles ................................................................................................................ 25
4.3.1. Zero measurement ...................................................................................................... 25
4.3.1.1 Safety function and error observation for Zero measurement cycle ...................... 25
4.3.2 Depression .................................................................................................................. 26
4.3.2.1. Safety function and error observation for depression cycle .................................. 26
4.3.3. Leak detection ............................................................................................................. 27
4.3.3.1. Safety function and error observation for leak detection cycle .............................. 27
4.3.4. Filling to level 1 ............................................................................................................ 28
4.3.4.1. Safety function and error observation for filling to level 1 cycle............................. 28
4.3.5. Degassing ................................................................................................................... 29
4.3.5.1. Safety function and error observation for degassing cycle .................................... 29
4.3.6. Filling to level 2 ............................................................................................................ 30
4.3.6.1. Safety function and error observation for filling to level 2 cycle............................. 30
4.3.7. Measurement .............................................................................................................. 31
4.3.7.1. Safety function and error observation for measurement cycle .............................. 31
4.3.8. Flushing ....................................................................................................................... 32
4.3.8.1. Safety function and error observation for flushing cycle ....................................... 32
4.3.9. Draining ....................................................................................................................... 33
4.3.9.1. Safety function and error observation for draining cycle ....................................... 33
4.3.10. Wait ......................................................................................................................... 34
4.3.10.1. Safety function and error observation for wait cycle ............................................. 34
4.4 Operation of HYDROCAL1005 by its keyboard .................................................................. 35
4.4.1 Contrast Set-up ........................................................................................................... 35
4.5 Main menu .......................................................................................................................... 36
4.6 Extraction Menu .................................................................................................................. 37
4.7 Display of stored „Gas-in-oil“measuring values................................................................... 37
4.7.1 Graphic display................................................................................................. 37
4.7.2 Table presentation............................................................................................ 38
HYDROCAL 1005 Manual for Installation and Operation Page 2/111
4.8 Status of alarms ...................................................................................................... 39
4.8.1 Acknowledgment of alarms ......................................................................................... 39
4.9 Device set – up ........................................................................................................ 40
4.9.1 Menu Transformer data setup .......................................................................... 41
4.9.1.1. DGA Adjustment: Input of correction factor .............................................................. 41
4.9.1.1 Hot Spot calculation .................................................................................. 42
4.9.1.2 Ageing Rate / Loss of Life ......................................................................... 44
4.9.2 Configuration of analogue outputs.................................................................... 45
4.9.3 Configuration of analogue inputs (external sensors) ........................................ 45
4.9.4 Configuration of alarms and digital outputs ...................................................... 48
4.9.5 Unit Setup ........................................................................................................ 51
4.9.5.1 Digital Output Test..................................................................................... 52
4.9.5.2 Device options .......................................................................................... 52
4.9.5.2.1.
Configuration of user settings ......................................................................... 53
4.9.5.3 Date. Time & Clock Settings ..................................................................... 53
4.9.5.4 Configuration of the communication .......................................................... 55
4.9.5.5 Ethernet setup ........................................................................................... 56
4.9.5.6 Alert SMS setup ........................................................................................ 57
4.9.5.7 Internal modem setup ............................................................................... 58
4.9.5.8 RS 232 / RS 485 setup ......................................................................................... 59
4.9.5.9 MODBUS .............................................................................................................. 66
5. Windows Software HydroSoft ................................................................................................ 76
5.1 Purpose of the program ...................................................................................................... 76
5.2 Remarks for use of this operation handbook ...................................................................... 76
5.3 Requirements to the PC ..................................................................................................... 76
5.4 Installation .......................................................................................................................... 77
5.4.1 Microsoft .NET .NET Framework 1.1 Redistributable .................................................. 77
5.4.2 Microsoft Data Access Components ............................................................................ 77
5.4.3 Adaptation of installation ............................................................................................. 78
5.5 Functions of HydroSoft program ......................................................................................... 78
5.6 Start of program ................................................................................................................. 78
5.7 Preparation / rename of a new customer list....................................................................... 79
5.8 Opening a new transformer station ..................................................................................... 80
5.9 Opening a file for a new transformer .................................................................................. 80
5.9.1 Modem settings ........................................................................................................... 82
5.9.2 RS232 interface settings ............................................................................................. 82
5.10 Settings of HYDROCAL1005 unit ....................................................................................... 82
5.10.1 Alert Setup................................................................................................................... 83
5.10.2 External sensors (see also chapter 4.7.3) ................................................................... 86
HYDROCAL 1005 Manual for Installation and Operation Page 3/111
5.10.3 Alert SMS Setup .......................................................................................................... 87
5.10.4 Input of DGA Level Adjustment ................................................................................... 89
5.10.5 Analog Output Setup ................................................................................................... 90
5.10.6 Digital Output Setup .................................................................................................... 91
5.10.7 Device Setup (Clock settings) ...................................................................................... 91
5.10.5.1. Ethernet ................................................................................................................ 92
5.10.5.2. Modbus-TCP ........................................................................................................ 93
5.10.5.3. MODBUS .............................................................................................................. 93
5.11 Data transmission from / to the HYDROCAL1005 unit ........................................................ 93
5.12 View of results .................................................................................................................... 96
5.12.1 Sensor selection .......................................................................................................... 96
5.12.2 Time range selection ................................................................................................... 96
5.12.3 Result window ............................................................................................................. 97
5.12.4 Print and export of results ............................................................................................ 97
5.13 View of alarm status ........................................................................................................... 98
5.13.1 Alarm selection ............................................................................................................ 98
5.13.2 Time range selection ................................................................................................... 98
5.13.3 Alarm window ................................................................ .............................................. 99
5.13.4 Status of alarms .......................................................................................................... 99
5.13.5 Print and export of results ............................................................................................ 99
5.14 Online Sensors ................................................................................................................. 100
6. RS 485 Wiring ........................................................................................................................ 101
7. HYDROSOFT Scheduler ........................................................................................................ 102
7.1 General ............................................................................................................................ 102
7.2 Scheduler ......................................................................................................................... 102
7.2.1 Configuring a Transformer for automatic History Data Update .................................. 102
7.2.1.1 Connection Scheduler Dialog ............................................................................. 103
7.2.2 Scheduler Status Visualization .................................................................................. 103
7.2.2.1 Status Icons ....................................................................................................... 103
7.2.2.2 Transformer ........................................................................................................ 104
7.2.2.3 Station ................................................................................................................ 104
7.2.2.4 Customer ............................................................................................................ 104
7.2.2.5 Example ............................................................................................................. 104
7.2.3 HydroSoft and the Windows Task Scheduler ............................................................ 105
7.2.3.1 Command Line Options for Windows Task Scheduler ........................................ 106
7.2.3.2 IdleClose ............................................................................................................ 106
7.2.3.3 Minimized ........................................................................................................... 106
7.2.4 Internal Operation ...................................................................................................... 106
7.2.5 Data Directory Lock ................................................................................................... 107
8. Technical data HYDROCAL1005 ........................................................................................... 108
9. Dimensional drawings HYDROCAL1005 .............................................................................. 110
HYDROCAL 1005 Manual for Installation and Operation Page 4/111
1. General
The HYDROCAL 1005 is a permanently-installed multi-gas-in-oil analysis system with transformer monitoring functions. It allows for the individual measurement of moisture and the key gases hydro­gen (H2), carbon monoxide (CO), acetylene (C2H2) and ethylene (C2H4) dissolved in transformer oil.
As hydrogen (H2) is involved in nearly every fault of the isolation system of power transformers and carbon monoxide (CO) is a sign of an involvement of the cellulosic / paper isolation the presence and increase of acetylene (C2H2) and ethylene (C2H4) further classifies the nature of a fault as overheat­ing, partial discharge or high energy arcing. The device can serve as a compact transformer monitor­ing system by the integration / connection of other sensors present on a transformer via its analog inputs:
5 analog outputs 0/4-20mADC 4 analog inputs 0/4-20 mADC (Option) 6 analog inputs 0/4-20 mADC +20% / 0-80 VAC +20% (option)
configurable by jumpers It is further equipped with digital outputs for the transmission of alarms or the execution of control functions (e. g. control of a cooling system of a transformer):
5 digital relay outputs 5 digital opto-coupler outputs (Option)
Key Advantages
Hydrogen (H2), Carbon monoxide (CO), acetylene (C2H2) and ethylene (C2H4) measurement  Moisture-in-oil measurement Communication interfaces ETHERNET 10/100 Mbit/s (copper-wired or fibre-optical) and RS 485
to support proprietary communication protocols and to be open / prepared for substation commu-
nication protocols IEC 61850, MODBUS, DNP 3 etc.
Optional on-board GSM and analog modems for remote communication 6 analog AC current inputs for the connection of capacitive HV bushing sensors for HV bushing
monitoring applications
The present operating instructions are divided in the following sections:
Instructions for mounting the HYDROCAL 1005 unit (chapter 2) Hardware components of HYDROCAL 1005 (chapter 3) Description of software of the HYDROCAL 1005 unit (chapter 4) Description of Windows software HydroSoft (chapter 5) RS 485 Wiring (chapter 6) New HydroSoft Scheduler functions (chapter 7) Technical Data of HYDROCAL 1005 (chapter 8) HYDROCAL 1005 dimensional drawings (chapter 9)
HYDROCAL 1005 Manual for Installation and Operation Page 5/111
2. Mounting of HYDROCAL1005 unit
2.1 Locations for installation of HYDROCAL1005
To ensure the correct function of the HYDROCAL1005 the location of mounting is very important. For a typical transformer, four places are possible:
Pos. 1
On return side of cooling circuit:
Please install the unit on a straight piece of tube on the cooler output between the cooler and the main oil tank. In order to avoid negative pressure, the unit must absolutely be
mounted on the downstream side (after the bend) of the oil circulation pump. Remark: Choose this place only in case of continuous oil flux through the cooler.
Pos. 2
Flange below on the transformer tank:
The flange must be at minimum height of 40 cm in order to allow installation and mounting of HYDROCAL1005 unit.
Pos. 3
Upper filling valve: It is possible to mount the Hydrocal 1005 unit on this position, if the filling level of
the oil is min. 100 cm higher than the mounting position. This position is not rec­ommended, because the filling process is influenced by the hydrostatic pressure of the oil and it may be difficult to operate and read the data of the unit.
Pos. 4
Never install the HYDROCAL1005 unit on top of the cooler or on the suction face of the pump. In this case, filling oil step cannot be carried out in the right way.
HYDROCAL 1005 Manual for Installation and Operation Page 6/111
2.2 Security precautions for installation
The following security precautions must be strictly observed during the installation. Otherwise no warranty claims will be accepted.
Never remove the protection cap from the sensor before you are ready to mount the unit on the valve of the transformer.
The protection cap protects the sensor against dust and other foreign bodies. Additionally it protects the thread of the measuring head and/or adapters.
Note: Use the protection cap also after dismounting of the unit.
Never close the aeration holes for oxygenation. They are situated in bot­tom side of the protection cover and at the back plate of the device
Never use or stock chemicals with hydrocarbon contents near the meas­uring sensor.
Never clean the measuring head with solvents, because its gases will strongly impair the measuring accuracy and the sensitivity of the sensors.
Never apply a negative pressure to the measuring head.
Negative pressure can cause problem during filling process.
Remove the HYDROCAL1005 unit from the valve every time you degas or refill the transformer. You can also close the valve of the transformer
Never install the HYDROCAL unit on a valve that is closed for a long pe­riod of time. Remove the unit if this cannot be avoided. Please refer to De-installation instructions
Never install the HYDROCAL1005 on the suction side of the cooling pump!
The HYDROCAL 1005 should be installed on positions located 100 cm be­low of the oil level inside the transformer
Never install the HYDROCAL1005 unit on an elbow or curve of a tube.
The unit cannot operate by negative pressure produced by turbulences in curves.
HYDROCAL 1005 Manual for Installation and Operation Page 7/111
Never install or remove the HYDROCAL1005 without opening first the aeration screw.
Never use galvanized fittings or valves to mount the HYDROCAL1005 unit.
Galvanized fittings or valves can react with oil; this will produce incorrect measuring values.
Never clean the HYDROCAL1005 unit with high pressure cleaning equipment.
High pressure cleaning equipment used to clean transformers can seriously damage the HYDROCAL1005 unit.
Never use a chaining key tool for mounting.
Use of such tools can damage the surface of the measuring head and the threads. Please use an adjustable thin spanner for 1 ½“.
Attention!!!
Faulty or inappropriate handling of the sensor head like malfunction by
negative pressure, paint or solvent liquids make the warranty invalid.
HYDROCAL 1005 Manual for Installation and Operation Page 8/111
2.3 Preparation for installation
Before installation, a visual inspection of the unit must be carried out. Remove the protection cover and check visually the components. All cables and tubes must be connected.
2.3.1 Power supply for the unit
The HYDROCAL1005 unit requires an auxiliary power supply of 110 / 230V close to the unit. The power needed is max. 350 VA.
2.3.2 Requested tools:
Long Allen key, size 4 for aeration screw Bucket, oil absorber, cleaning rag Teflon-band Drill / screw driver Digital multimeter Tin spanner M55 or adjustable tin spanner of 1 ½“ for valve and fittings
To seal the thread of the measuring head, either Teflon band (minimum 4 to 5 layers must be ap­plied) or an O-Ring must be used.
2.4 Installation of the HYDROCAL1005 unit
Attention!!!
Mount the unit horizontally on the valve. The aeration screw must be in
the 12 o’clock position.
Please mount the HYDROCAL1005 unit on a valve with full opening (full bore valve) or a ball valve with an internal thread of 1½” (DIN ISO 228: G 1½) . The HYDROCAL unit has a 1½’’ thread (Di­mensional drawings, see. chapter 8). As an option a valve with NPT 1½ standard can also be used.
A good oil flux should exist on the mounting location. If necessary, use a reduction piece (adapter). It is recommended to mount the HYDROCAL 1005 unit to valve with a union- or sleeve nut. In this
case the device has not to be turned to fix during the installation. An O-ring should be used as seal­ing.
In case there exist strong vibrations on the mounting valve, the valve should be relieved by a sup­port.
Then mount the unit according to the following steps:
HYDROCAL 1005 Manual for Installation and Operation Page 9/111
Only remove the protection cap (slowly while turning)
when you are ready to mount the measuring head!
Clean the internal side of the installation valve. In case you don’t use a union or sleeve nut as connection point with o-ring, wind 4 to 5 layers of
Teflon band on the Hydrocal 1005 connection thread and mount it either directly into the valve or
into an additional adapter. If you use an adapter it should be mounted to the valve, before the Hy-
drocal 1005 will be mounted to the adapter. Wind 4 to 5 layers of Teflon band on the thread of the
adapter and mount it into the valve. Make sure that everything is fixed mechanically. Turn the unit in order to get 12 o clock position.
HYDROCAL 1005 Manual for Installation and Operation Page 10/111
Attention!!!
The following steps must be done according to the company procedures. Work carefully in order to prevent air entering into the transformer. Use a
bucket to catch oil coming out as described on following drawing.
Unscrew the aeration screw 3 – 4 turns with Allen key No. 4. (Aeration is active).
Open the valve slowly until oil comes of the sample tube. As soon as no air bubbles sort on the sample tube, close the aeration screw. Then fully open the
valve. Remove the oil from the measuring head externally.
Do not use any solvents for cleaning!
HYDROCAL 1005 Manual for Installation and Operation Page 11/111
2.5 Electrical Installation of HYDROCAL1005 unit
Use steel protected cables for power supply, alarm-cables and communication cables and con-
nect them to the appropriate connectors.
Recommendations for main supply cable:
Mains supply cable (3-wire)
(1) Phase 230VAC 20% (2) Neutral (3) Protection Earth Wire : 1,5mm2
If optional GSM Modem is used, GSM antenna must be connected to Hydrocal as above draw-
ing:
Recommendations for alarm and external sensor cables:
Cable Specification (or equivalent) Type: e.g. Ölflex FD855CP Cable : 13,3mm (of external cable) Wire : 0,5mm2 (of 16 intern. wires)
Connect the power supply to the HYDROCAL1005 unit. The display shows the specified condi-
tions confirming that the HYDROCAL1005 is functioning correctly.
o Brown (L) o Blue (N) o Green - yellow (PE)
HYDROCAL 1005 Manual for Installation and Operation Page 12/111
2.6 Completion of Installation
START-SCREEN
At first, date and time must be setup, refer to chapter
4.9.5.3. The HYDROCAL1005 has a sub menu allowing con-
figuration of time, date as well as clock
MOUNT-BUTTON
The Hydrocal is currently not installed. After the mount button is activated, the Detect-Cycle will start.
DETECT-SCREEN
The Hydrocal filled up to level 1. A circulation is made to remove air from the system. Finally system is drained to level 0.
UNMOUNT-BUTTON
The Hydrocal is installed in normal operation. (Currently Sync. Wait)
The selected Button is the unmount button. (Controlled draining and stopping)
HYDROCAL 1005 Manual for Installation and Operation Page 13/111
Then, if everything is working correctly put the housing in correct position and secure it with the
knurled thumbscrews.
The measuring cycle of the HYDROCAL1005 unit is synchronized on the hour mark; this means
the first measuring value is available approx. 2, 22 or 42 min. after the hour mark and can be read
on the display. After first start-up, in all cases date and time have to be checked on the HYDROCAL1005 display and eventually have to be adjusted manually in clock settings (chapter 3.7.5.2) or with HydroSoft (chapter 4.10.7).
HYDROCAL 1005 Manual for Installation and Operation Page 14/111
3. Hardware components of HYDROCAL 1005
3.1 Front view of HYDROCAL1005
On the front side of the HYDROCAL1005 unit the following operating elements are available.
[1]
LCD-display with 240 x 320 pixels
[2]
Screw mounting to mount the cover
[3]
Alphanumeric keyboard to enter numbers and text
[4]
Arrow-buttons to move in the menus, for data input and contrast set-up from the main
display (Up an Down)
[5]
Enter button to confirm and stop functions and data
HYDROCAL 1005 Manual for Installation and Operation Page 15/111
3.2 Rear side of HYDROCAL1005 unit
[1]
Measuring sensor with an internal thread of 1½ (DIN ISO 228: G 1½) or optionally (NPT
1½)
HYDROCAL 1005 Manual for Installation and Operation Page 16/111
[2]
Entrance for power supply 88 VAC
min
276 VAC
max
Optional: 88 VDC
min
… 390 VDC
max
max. 350 VA, 50/60 Hz Then, power supply must be connected as follow :
o Brown (L) o Blue (N) o Green - yellow (PE)
[3]
System outlet for digital and analogue inputs and outputs Communication outlet for communication via analogue or GSM/GPRS-modem
[4]
ETHERNET connector
[5]
Gas Air Outlet
HYDROCAL 1005 Manual for Installation and Operation Page 17/111
3.3 Connections on the measuring and controller card
[1]
Connector ST13: 4 x Valve Control
Connection for valve control
HYDROCAL 1005 Manual for Installation and Operation Page 18/111
[2]
Connector ST14: Pumps Oil Air
Connection for pumps oil air control
[3]
Connector ST11: Oil Level / Oil-Flow
Connection for oil level / oil flow control
[4]
Connector ST3: Humidity Temperature
Connection for humidity temperature control
[5]
Connector KL1: Power supply
Note: The connection [5] is connected to a filter module from where the connection to the power supply 88 VAC
min
276 VAC
max
and PE is made
As showed on picture on the left side, usually you just need to connect cables to the main power supply connector Brown L Blue N Green/yellow PE
HYDROCAL 1005 Manual for Installation and Operation Page 19/111
[6]
Connector ST12: Heating
Connection of the heating resistors, depending from the supply voltage
[7]
Connector KL302: Interface RS485 and Modem
X7:1 (OUT B ) RS485 X7:2 (OUT A ) RS485 X7:3 GNDIO Signal ground not shield X7:4 Phone B X7:5 Phone A
[8]
Connector KL301: Analogue Outputs
4…. 20 mADC
X8:1 (Analogue output 1 ) X8:2 (Analogue output 1 ) X8:3 (Analogue output 2 ) X8:4 (Analogue output 2 ) X8:5 (Analogue output 3 ) X8:6 (Analogue output 3 ) X8:7 (Analogue output 4 ) X8:8 (Analogue output 4 ) X8:9 (Analogue output 5 )
X8:10 (Analogue output 5 )
[9]
Connector KL402: Relay Outputs
12 VDC / 220 VDC/VAC / 2 A / 60 W
X9:1 (Relay output 1 ) X9:2 (Relay output 1 ) X9:3 (Relay output 2 ) X9:4 (Relay output 2 ) X9:5 (Relay output 3 ) X9:6 (Relay output 3 ) X9:7 (Relay output 4 ) X9:8 (Relay output 4 ) X9:9 (Relay output 5 ) X9:10 (Relay output 5 )
HYDROCAL 1005 Manual for Installation and Operation Page 20/111
[10]
Connector KL102: Analogue AC Inputs (in Option)
6 x 0 ... 80V +20% 6 x 0/4 … 20mA +20%
X10:1 (Analogue AC input 1 ) X10:2 (Analogue AC input 1 ) X10:3 (Analogue AC input 2 ) X10:4 (Analogue AC input 2 ) X10:5 (Analogue AC input 3 ) X10:6 (Analogue AC input 3 ) X10:7 (Analogue AC input 4 ) X10:8 (Analogue AC input 4 ) X10:9 (Analogue AC input 5 ) X10:10 (Analogue AC input 5 ) X10:11 (Analogue AC input 5 ) X10:12 (Analogue AC input 5 )
[11]
Connector KL101: Analogue DC Inputs (in Option)
0/4 … 20 mA
X11:1 (Analogue DC input 1 ) X11:2 (Analogue DC input 1 ) X11:3 (Analogue DC input 2 ) X11:4 (Analogue DC input 2 ) X11:5 (Analogue DC input 3 ) X11:6 (Analogue DC input 3 ) X11:7 (Analogue DC input 4 ) X11:8 (Analogue DC input 4 )
[12]
Connector KL301: Opto coupler output (in Option)
5 VDC / UCE: 4 V / UEC: 7 V / UCE: 40 mA
X12:1 (Opto coupler output 1 ) X12:2 (Opto coupler output 1 ) X12:3 (Opto coupler output 2 ) X12:4 (Opto coupler output 2 ) X12:5 (Opto coupler output 3 ) X12:6 (Opto coupler output 3 ) X12:7 (Opto coupler output 4 ) X12:8 (Opto coupler output 4 ) X12:9 (Opto coupler output 5 ) X12:10 (Opto coupler output 5 )
[13]
GSM/GPRS-module / GSM antenna
Connector Mini-BNC
HYDROCAL 1005 Manual for Installation and Operation Page 21/111
[14]
ETHERNET connector
Copper-wired or Fibre-optical These sockets are connected with the back plane. It means that normally only con-
nection on back plane is needed
[15]
Measuring cell connector
HYDROCAL 1005 Manual for Installation and Operation Page 22/111
3.4 Measurement and extraction Components
[1]
Capacitive Sensor F0 (ZERO)
[2]
Capacitive Sensor FI (Level 1)
[3]
Capacitive Sensor FII (Level 2)
[4]
Valve V6 (Safety)
[5]
Flow meter (Flow IN / OUT)
[6]
Valve V1 (Filling / Circulation / Draining)
[7]
Valve V3 (Vacuum Generation / Ventilation)
[8]
Compressor K1
[9]
Valve V4 (Pressure / Ventilation)
[10]
Valve V2 (Oil chamber Connection <-> Gas Chamber / Measuring Cell)
[11]
Pump P1
[12]
Bypass Valve Pump V5
[13]
Oil separator
HYDROCAL 1005 Manual for Installation and Operation Page 23/111
HYDROCAL 1005 Manual for Installation and Operation Page 24/111
4. Software on HYDROCAL unit
4.1 General information
The gas-in-oil analyzer HYDROCAL1005 is based on a microprocessor controlled measuring sys­tem. A 32 Bit „Coldfire“ processor with a clock frequency of 240 MHz (bus clock 80 MHz) is used.
The software has been developed with the language „C“. The system has a flash memory of 16 / 32 / 64 Mbyte for measuring data. This offers approximately 2 / 4 / 8 years time storage capacity for the measuring data.
After this period, the oldest data will be overwritten by the latest values. When using additional exter­nal sensors, the storage capacity depends on the number of sensors and the time interval selected for storage. The following formula can be used to determine the storage capacity (in the example 64 Mbyte is used):
12
1
20
1/288/23000
264
n
n
StdagesSensorstordayBytedayByte
Byte
dayshMemorydept
With one additional sensor with a time interval of 5 minutes the following calculation results:
days
dayByte
Byte
dayBytedayByte
Byte
dayshMemorydept 2500
/26456
264
/3456/23000
264
2020
Also an additional reduction of the storage time takes place by the definition of alarms. Each change of alarm status requires 12 Bytes.
Attention: To avoid any loss of data, it is proposed to read out regularly
the measuring data by the Windows based software “HydroSoft”.
4.2 Description of Gas measurement Process
HYDROCAL 1005 Manual for Installation and Operation Page 25/111
4.3. Operation Cycles
This chapter describes each process steps and provides information in regards to the safety functions as well as how to reset errors. The consequence of all errors is that the cycle will be interrupted immediately and
all valves will be closed.
For all observed errors, you can acknowledged them by pressing button ..
If nothing changes, check status of all components according to actual cycle.Check that all tubes go straight into the FESTO quick screws and any oil/air leakages have appearedCheck that cables and all pins of the plug go straight into their socket; pushing the plug in carefully.
4.3.1. Zero measurement
Step
No.
Status of the components
[1]
Capacitive Sensor F0 “not active”
[2]
Capacitive Sensor FI “not active”
[3]
Capacitive Sensor FII “not active”
[4]
Valve V6 “closed”
[5]
Flow meter “not active”
[6]
Valve V1 “circulating”
[7]
Valve V3 “closed”
[8]
Compressor K1 “not active”
[9]
Valve V4 closed
[10]
Valve V2 “closed”
[11]
Pump P1 “active”
[12]
Valve V5 “open”
4.3.1.1 Safety function and error observation for Zero measurement cycle
Observed Components
Detectable Errors
Filling Sensor 0, 1, 2
Operating in normal parameters
Measurement chamber
Measurement chamber offline
Pressure Sensor
Pressure stability
HYDROCAL 1005 Manual for Installation and Operation Page 26/111
4.3.2 Depression
For pressure compensation of the measurement chamber
Step
No.
Status of the components
[1]
Capacitive Sensor F0 “not active”
[2]
Capacitive Sensor FI “not active”
[3]
Capacitive Sensor FII “not active”
[4]
Valve V6 “closed”
[5]
Flow meter “not active”
[6]
Valve V1 “circulating”
[7]
Valve V3 “open”
[8]
Compressor K1 “active”
[9]
Valve V4 ”closed”
[10]
Valve V2 “closed”
[11]
Pump P1 “not active”
[12]
Valve V5 “open”
4.3.2.1. Safety function and error observation for depression cycle
Observed Components
Detectable Errors
Filling Sensor 0, 1, 2
Operating in normal parameters
Measurement chamber
Measurement chamber offline
Pressure Sensor
Pressure does not decrease
HYDROCAL 1005 Manual for Installation and Operation Page 27/111
4.3.3. Leak detection
During the leak detection cycle the pressure stability of the complete system is checked
Step
No.
Status of the components
[1]
Capacitive Sensor F0 “not active”
[2]
Capacitive Sensor FI “not active”
[3]
Capacitive Sensor FII “not active”
[4]
Valve V6 “closed”
[5]
Flow meter “not active”
[6]
Valve V1 “draining / filling”
[7]
Valve V3 “closed”
[8]
Compressor K1 “not active”
[9]
Valve V4 ”closed”
[10]
Valve V2 “open”
[11]
Pump P1 “not active”
[12]
Valve V5 “open”
4.3.3.1. Safety function and error observation for leak detection cycle
Observed Components
Detectable Errors
Filling Sensor 0, 1, 2
Operating in normal parameters
Measurement chamber
Measurement chamber offline
Pressure Sensor
Leakage
Flow meter
V6 closed
HYDROCAL 1005 Manual for Installation and Operation Page 28/111
4.3.4. Filling to level 1
Step
No.
Status of the components
[1]
Capacitive Sensor F0 “active”
[2]
Capacitive Sensor FI “active”
[3]
Capacitive Sensor FII “not active”
[4]
Valve V6 “open”
[5]
Flow meter “active”
[6]
Valve V1 “draining / filling”
[7]
Valve V3 “closed”
[8]
Compressor K1 “not active”
[9]
Valve V4 ”closed”
[10]
Valve V2 “open”
[11]
Pump P1 “not active”
[12]
Valve V5 “open”
4.3.4.1. Safety function and error observation for filling to level 1 cycle
Observed Components
Detectable Errors
Filling Sensor 0, 1, 2
Operating in normal parameters
Filling Sensor 0, 1 Flow meter Timer
- Filling level 1 lost
- Filling stopped?
- Filling timeout
Measurement chamber
Measurement chamber offline
Pressure Sensor
- leakage
- flow stuck
Filling Sensor 0, 1, 2
Measurement chamber offline
Loading...
+ 83 hidden pages