MTE Guard-AC reactors brochure

Benefits of Using Line/Load Reactors
Guard-AC line/load reactors help keep your equipment running longer by absorbing many of the power line disturbances which otherwise damage or shut down your inverters, variable speed controllers, or other sensitive equipment. They are the modern technology solution to inverter and drive application problems. Guard-AC reactors are harmonic compensated & IGBT protected to assure optimum performance in the presence of harmonics. They are very effective at reducing harmonics produced by inverters and drives, and in most cases will help you to meet IEEE
519. Use our harmonic compensated reactors on either the input or output of an adjustable speed drive/inverter. There is no need to de-rate our "harmonic compensated" reactors for harmonics.
Guard-AC reactors are manufactured to the exacting standards of MIL-1-45208, VDE-0550, are UL recognized & CSA certified. All UL approvals are for USA & Canada.
UL-506 File #E53094 (lamp through 1200 amps)
CSA File #LR29753-13 (1200 amps or less) 9
UL-508 File #El80243 (1 amp through 1200 amps)
All higher current reactors offer UL recognized insulation systems and construction.
Impedance Rating
3% impedance reactors
are typically sufficient
to absorb power line spikes
and motor current surges.
They will prevent nuisance tripping
of drives
or circuit breakers
in most applications.
3-Phase Reactors
Line/Load Reactors
Protect Motors from Long Lead Effects
Reduce Output Voltage dv/dt
Virtually Eliminate Nuisance Tripping
Extend Semiconductor Life
Reduce Harmonic Distortion
Reduce Surge Currents
Reduce Motor Temperature
Reduce Motor Audible Noise
Improve True Power Factor
Helps Meet IEEE 519 or IEC 1000-3-4
5% impedance reactors
are best for
reducing harmonic currents
and frequencies.
Use them when
you must comply with
IEEE 519,
to reduce
motor operating temper at ur e,
or to
reduce motor noise.
Harmonic Reduction
Because all standard Guard-AC reactors are compensated for harmonics (current and frequency), they are extremely effective at reducing the amount of harmonics which are produced by a drive/inverter. Use 5% impedance, harmonic compensated reactors for best reduction of harmonic distortion.
Percent Harmonics vs Total Line Impedance
Total Input Impedance
Harmonic3%4%5%6%7% 8% 9%10%
5th 4034323028 26 24 23
7th 1613121110 9 8.37.5
11th 7.3 6.3 5.8 5.2 5 4.3 4.2 4
13th 4.9 4.2 3.9 3.6 3.3 3.15 3 2.8
17th 3 2.4 2.2 2.1 0.9 0.7 0.5 0.4
19th 2.2 2 0.8 0.7 0.4 0.3 0.25 0.2
%THID 44.13 37.31 34.96 32.65 30.35 28.04 25.92 24.68
TRMS 1.09 1.07 1.06 1.05 1.05 1.04 1.03 1.03
Reactor Linearity
This curve illustrates the linearity of Guard-AC reactors. Even at 150 percent of their current rating, these reactors still have 100% of their nominal inductance. This assures maximum filtering of distortion even in the presence of severe harmonics and best absorption of surges. The typical tolerance on rated inductance is plus-or-minus 5 percent.