M-system R7ML-DC16A, R7ML-DA16 Instruction Manual

R7ML-DC16A
P. 1 / 10
EM-7805-G Rev.2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
NPN TRANSISTOR OUTPUT MODULE, 16 points
(MECHATROLINK-I / -II)
MODEL
R7ML-DC16A
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below. If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Discrete output module .............................................. (1)
■ MODEL NO.
Confirm that the model number described on the product is exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVE
• Use MECHATROLINK-II network cable with core (Yasu­kawa Controls Model JEPEC-W6003-x-E) or equivalent for the network.
• Be sure to earth FG terminal.
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may affect the protection level of this unit when it is integrat­ed in a panel system. The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure CE conformity.
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 85mA
■ GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power supply and input signal for safety.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient ventilation.
• Do not install the unit where it is subjected to continuous vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within 0 to 55°C (32 to 131°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which nois­es are present. Do not install them in the same duct.
• FG terminal is NOT a protective conductor terminal.
■ AND ....
• The unit is designed to function as soon as power is sup­plied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
R7ML-DC16A
P. 2 / 10
EM-7805-G Rev.2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
COMPONENT IDENTIFICATION
5
4
3
2
1
0
9
8
7
6
ERR
RD
RUN SD
PWR
X10 X1
STATION ADD. B. RATE
CNFG.
1 2 3 4 5 6 7 8
0 1 2 3 4 5 6 7 8 9 A B C D E F
4567
123
10 11 12 13
2341
15 16 17 18
7896145
MECHATROLINK Setting Rotary SW
MECHATROLINK Connector
Station Address Setting Rotary SW
Status Indicator LED
Operating Mode Setting DIP SW (SW1)
PC Configurator Jack
Discrete Output Status Indicator LED
Power Supply Terminals
MECHATROLINK Connector
Output Terminals
LEFT SIDE VIEW
FRONT VIEW
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
R7ML-DC16A
P. 3 / 10
EM-7805-G Rev.2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
■ STATUS INDICATOR LED
ID COLOR FUNCTION
PWR Green
Turns on when the internal 5V is supplied normally.
RUN Green Turns on in normal communications
conditions.
ERR Red Turns on in no communication or setting
error.
SD Green Turns on when the module is transmit-
ting.
RD Green Turns on when the module is receiving.
■ STATION ADDRESS
Station Address is selected between 60H and 7FH (Intel­ligent I/O) in hexadecimal. (Certain numbers may not be selectable depending on the master types. Refer to the in­struction manual of the master unit.) The left switch determines the MSD, while the right switch does the LSD of the address. (Factory setting: 60H)
Station Address Setting (LSD)
Station Address Setting (MSD)
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
■ MECHATROLINK MODE
Choose MECHATROLINK-I or -II, and the data size. Posi­tions 2, 4 through 9 are unused. (Factory setting: 1)
5
4
3
2
1
0
9
8
7
6
MECHATROLINK Setting
0 : MECHATROLINK-II (32-byte mode) 1 : MECHATROLINK-II (17- byte mode) 3 : MECHATROLINK-I (17- byte mode)
■ EXTENSION MODULE
Combinations with any extension module is selectable.
■ OPERATING MODE
(*) Factory setting
• Extension (SW1-1, 1-2)
SW1-1 SW1-2 Extension
OFF OFF No extension (*)
ON OFF Discrete input, 8 or 16 points
OFF ON Discrete output, 8 or 16 points
• Output at the loss of communication (SW1-4)
SW1-4 Output at the loss of communication
OFF Reset the output (turned off)
ON Hold the output (*)
(maintains the last data received normally)
Caution ! - SW1-3, 1-5, 1-6, 1-7, 1-8 are unused. Be sure to turn
off unused ones.
■ DISCRETE OUTPUT STATUS INDICATOR LED
Discrete output modules have LED indicators showing out­put signal status. Contact ON : LED ON Contact OFF : LED OFF
■ POWER SUPPLY TERMINAL ASSIGNMENT
4NC5NC6
+24V
1NC2NC3
FG
7
0V
NO. ID FUNCTION, NOTES
1 NC ----
2 NC ----
3 FG FG
4 NC ----
5 NC ----
6 +24V Power input (24V DC)
7 0V Power input (0V)
■ OUTPUT TERMINAL ASSIGNMENT
10 +24 V11Y112Y3
1
0 V2Y03Y2
13
Y5
4
Y4
14
Y7
5
Y6
15
Y9
6
Y8
16
YB
7
YA
17
YD
8YC9
YE
18
YF
NO. ID FUNCTION NO. ID FUNTION
1 0V 0V (common) 10 +24V 24V DC
2 Y0 Output 0 11 Y1 Output 1
3 Y2 Output 2 12 Y3 Output 3
4 Y4 Output 4 13 Y5 Output 5
5 Y6 Output 6 14 Y7 Output 7
6 Y8 Output 8 15 Y9 Output 9
7 YA Output 10 16 YB Output 11
8 YC Output 12 17 YD Output 13
9 YE Output 14 18 YF Output 15