M-system R5T-RS Instruction Manual

Page 1
INSTRUCTION MANUAL
RTD INPUT MODULE
(screw terminal block)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below. If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
RTD input module ...............................................................(1)
■ MODEL NO.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures.
MODEL
R5T-RS
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument panel of a metal enclosure.
• The actual installation environments such as panel con­figurations, connected devices, connected wires, may af­fect the protection level of this unit when it is integrated in a panel system. The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform­ity.
■ HOT INSERTION/REMOVAL OF MODULES
• Removing or replacing modules does not affect other mod­ules on the same backplane. It is possible to replace them without removing the power supply. However, replacing multiple modules at once may greatly change line voltage levels. We recommend that you replace them one by one.
■ GENERAL PRECAUTIONS
• DO NOT set the switches while the power is supplied. The switches are used only for maintenance without the power.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the air, install the unit inside proper housing with sufficient ventilation.
• Do not install the unit where it is subjected to continu­ous vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C (14 to 131°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is sup­plied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
INSTALLATION
Use the Installation Base (model: R5-BS).
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6115 Rev.3 P. 1 / 3
Page 2
COMPONENT IDENTIFICATION
R5T-RS
SIDE VIEW FRONT VIEW
Function
12345678
Burnout
RTD
Temp. Unit
ON
RUN
RUN LED
4
65
1
32
■ STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally; Green when the bus B operates normally; Amber when both buses operate normally.
■ SIDE DIP SW
(*) Factory setting
• RTD Type: SW1, 2, 3, 4
SW
1 2 3 4
RTD
ON OFF ON OFF Cu 10 @ 25°C
OFF OFF OFF OFF Cu 50
OFF OFF OFF ON JPt 100 (JIS ’89)
• Temperature Unit: SW5, 6
SW
5 6
OFF OFF °C (*)
ON OFF °F
OFF ON K (Absolute Temp)
TEMP. UNIT
ON OFF OFF OFF Pt 100 (JIS ’89)
OFF ON OFF OFF Pt 100 (JIS ’97, IEC) (*)
OFF ON ON OFF Pt 1000
ON ON OFF OFF Pt 50 Ω (JIS ’81)
OFF OFF ON OFF Ni 100
ON ON ON OFF Ni 508.4 Ω
• Burnout: SW7, 8
SW
BURNOUT7 8
INPUT 1 INPUT 2
OFF OFF Downscale
ON ON Upscale (*)
PC CONFIGURATOR
With configurator software, settings shown below are available. Refer to the software manual of R5CON for detailed operation.
■ CHANNEL INDIVIDUAL SETTING
PARAMETER AVAILABLE RANGE DEFAULT SETTING
Zero Scale -32000 to +32000 0
Full Scale -32000 to +32000 10000
Bias [Zero Adj.] -320.00 to +320.00 0.00
Gain [Span Adj.] -32000 to +32000 1.0000
Zero Base Depends on sensor type 0.00
Full Base Depends on sensor type 0.00
■ CHANNEL BATCH SETTING
PARAMETER AVAILABLE RANGE DEFAULT SETTING
Limit No check mark: Limits to the scaling values equivalent to -15 % to
+115 %.
Check-marked: Limits within Zero Scale to Full Scale.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
No check mark
EM-6115 Rev.3 P. 2 / 3
Page 3
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■ EXTERNAL DIMENSIONS unit: mm (inch)
R5T-RS
18 (.71)
(.22)
4
90 (3.54) 5.6
65
1
32
■ CONNECTION DIAGRAM
RTD
INPUT 1
RTD
INPUT 2
1
A
2
B
3
B
4
A
5
B
6
B
8.2 (.32)
6–M3.5 TERMINAL SCREWS
7.2 (.28)
38.5 (1.52) 98.5 (3.88)
INTERNAL BUS A
INTERNAL BUS B*
INTERNAL POWER
BUS CONNECTOR
LOCKING CLAMP
TERMINAL COVER
POSITIONING GUIDE
WIRING INSTRUCTIONS
■ SCREW TERMINAL
Torque: 0.8 N·m
*For dual redundant communication. Note: The section enclosed by broken line is with 2-ch. option.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6115 Rev.3 P. 3 / 3