Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ HOT INSERTION/REMOVAL OF MODULES
• Removing or replacing modules does not affect other modules on the same backplane. It is possible to replace them
without removing the power supply. However, replacing
multiple modules at once may greatly change line voltage
levels. We recommend that you replace them one by one.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
COMPONENT IDENTIFICATION
■ FRONT VIEW
RUN LED
ERR LED
CJC SENSOR(2)
RUN1
AUTO1
ERR1
ALM1
RUN2
AUTO2
ERR2
ALM2
1
11
2
12
3
13
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
Loop Status Indicator
■ STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the internal bus operates normally.
ERR indicator: Bi-color (red/green) LED;
Red at device error;
Green in normal operating conditions.
Loop status indicators: Red LED
RUN1: Turns on while loop 1 is in operation.
AUTO1: Turns on during auto mode, turns off during
manual mode with loop 1
ERR1: Turns on at error with loop 1
ALM1: Turns on at alarm with loop 1
RUN2: Turns on while loop 2 is in operation.
AUTO2: Turns on during auto mode, turns off during
manual mode with loop 2
ERR2: Turns on at error with loop 2
ALM2: Turns on at alarm with loop 2
INSTALLATION
Use the Installation Base (model: R3-BSx).
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ UNUSED INPUT CHANNELS
• Unused channels can be specified and set so on the PC
Configurator Software (model: R3CON) without needing
to short at the field terminals.
■ AND ....
• The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solderless terminals with insulation sleeve do not fit.
Applicable wire size: 0.3 – 0.75 mm
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd., Nichifu Co., Ltd.
• Two input points can be assigned respectively to monitor
specific control output status.
• One signal can watch heater wire break, SSR shortcircuit
failure and overload at once.
• Control output must be turned on for at the minimum
of 110 milliseconds to detect a heater wire break; must
be turned off for at the minimum of 200 milliseconds to
detect an SSR shortcircuit failure.
■ COMMUNICATION
• Monitoring and setting can be performed easily with PC
Configurator Software (model: R3CON).
• Various values can be read out via network communication (data allocation mode: 8)
• Modbus interface module (model: R3-NM3) available with
the R3 extension area communication realizes a large capacity data reading/writing.
■ CONTROL LOOP
• Control strategies
1) Standard PID control
2) Heating-cooling PID control
(independent PID operation for heating and cooling)
3) Heating-cooling ON/OFF control
(heating-only or cooling-only output is possible.)
• Two control loops can be assigned respectively to one of
the selections (1) through (3).
• Limit cycle method auto-tuning
• Direct/reverse action selectable for standard PID control
• Input 2 can be cascaded to loop 1 as its SP (remote SP)
• MV tracking function: MV in manual mode is carried on
into auto mode.
• High/low limits selectable for SP and MV values
• Specific MV values applicable at STOP/abnormality.
• Three PV alarm modes selectable for each loop
• Four bank settings available for each loop; Banks can be
switched during operation.
• Bank setting
• SP / SP rise ramp / SP fall ramp / P / I / D / Cooling P /
Cooling I / Cooling D / Heating sensitivity / Cooling sensitivity / Deadband / PV alarm high/low limits
■ GETTING READY WITH PC CONFIGURATOR SOFTWARE (model: R3CON)
The PC Configurator Software is used to set up various parameters for the Temperature Controller Module and to perform
auto-tuning.
Connect the CONFIG port to the PC and start up the R3CON. The flowchart below shows how to move to the Controller’s
setting window. In this example, the R3-TC2 is supposed to be installed in the slot 1.
For setting details, refer to the R3-TC2 instruction manual.
Alternatively press F5 button on the keyboard to reload.
The Controller’s setting window is as shown below.
The trend graph shows real time PV and MV status, and parameters and operation status can be monitored.
(1) MONITOR WINDOW
Trend graph shows PV, SP and MV for loop 1 and 2.
Choose Loop 1 or Loop 2 tub at the top.
Trend data for both loops is continuously stored
1
even though only one loop is chosen at a moment.
(2) SWITCHING OPERATION / MODE
Control operation and mode is set with the buttons.
8
7
6
2
(3) ALARM INDICATORS / RESET BUTTONS
3
Alarm status of the selected loop is indicated.
Various alarm status can be reset by clicking [Reset PV],
[Reset CT] and [Reset All].
5
(4) SETTING ITEMS TREE & LIST
Setting parameters are grouped in the menu tree.
4
Choose a specic group to show a parameter list
to choose from. Modied selections / values are written
9
in the device immediately.
13
(5) CT INPUT INDICATORS
CTx(ON) display shows current value when the relevant
control output is ON; while CTx(OFF) shows current
when it is OFF.
‘ - ’ shows that the control output has not been switched
on or off during the last control cycle.
R3-TC2
10
11
12
(6) BANK
[Switch Bank] dialog box appears when [Bank] button
is clicked.
Choose a bank and click OK to apply the change.
(7) AUTO-TUNING
[Auto-tuning] dialog box appears when [Auto-tuning]
is clicked.
Choose a bank and click OK to start auto-tuning for the
specied bank.
(8) MANUAL MV
[Set MV Manually] dialog box appears when
[Manual MV] button is clicked.
Enter a MV value and click OK to apply the change
(only in MAN mode).
(9) SETTINGS
Graph scales in the trend graph and display language
can be changed.
[Settings] dialog box appears when the button is clicked.
(10) Y axis max / Y axis min
Specify a full-scale temperature range for Y axis.
Selectable from -9999.9999 to +9999.9999.
Minimum span is of 0.2.
(11) X axis time span
Specify a full-scale time span for X axis.
Selectable among:
10 sec. 30 sec. 1 min. 3 min. 5 min.
10 min. 15 min. 30 min. 1 hour 2 hours
In addition to the setting example 1 configuration, the heater’s wire break can be detected using a CT input. Suppose that the
heater has 100V / 1kW rating, driven by an SSR.
(1) Current flowing through the heater is calculated in the equation: 1kW / 100V = 10A. Choose the current sensor model
CLSE-05, for the maximum of 50A rating. Connect the sensor to CT input 1 as in the figure below.
Heater
CLSE-05
SSR
Power Supply
CT Input 1
Control Output 1
R3-TC2
(2) Go to the setting items tree and change the following parameters.
■ SETTING EXAMPLE 3: SWITCHING SETPOINT VALUE BY EVENT INPUT
The Controller has two discrete inputs for event control input.
At the maximum of four sets of temperature setpoints and PID parameters can be predefined and stored in the ‘banks.’ The
external event input can be used to switch among these banks.
In this example, the Controller is set according to the example 1 for the setpoint 40.0°C. By using banks, an additional setting
to switch the setpoint to 50.0°C by an event input is created.
(1) Connect a switch to the discrete input 1 as shown below.
Di 1
R3-TC2
(2) Go to the setting items tree and change the following parameters.
SETTING ITEMS TREEPARAMETERSELECTION
Loop 1, Bank 1SP (setpoint value)50.0
Event inputEvent input 1 function assignmentLoop 1, Bank bit 0
(3) Click Auto-tuning button located below the trend graph to show the Auto-tuning dialog box. Choose Bank 1 and click OK.
The Controller go through auto-tuning and then starts control operations.
Now the setting is complete to switch the temperature setpoint to 50.0°C with the switch closed (ON) and to 40.0°C with the
same opened (OFF).
The Controller functions as an analog input module in the R3 remote I/O system. The following 8 words of analog input data
can be read out at Input Register area.
+0
+1
+2
+3
+4
+5
+6
+7
Loop 1 PV (number of decimal places as specified with the ‘input 1 decimal’)
Loop 1 SP (number of decimal places as specified with the ‘input 1 decimal’)
Loop 1 Heating MV (0.01% increments)
Loop 1 Cooling MV (0.01% increments)
Loop 2 PV (number of decimal places as specified with the ‘input 2 decimal’)
Loop 2 SP (number of decimal places as specified with the ‘input 2 decimal’)
Loop 2 Heating MV (0.01% increments)
Loop 2 Cooling MV (0.01% increments)
■ R3 EXTENSION AREA COMMUNICATION
The Controller is compatible with the R3 extension area communication.
By using the model R3-NM3 Modbus Extension Network Module, a large volume of its data can be read out and written in
from the Modbus host device via Holding Register area.
■ EXTENSION AREA ADDRESS ASSIGNMENTS
A Holding Register area of 3000 words is assigned per I/O module as shown in the table below.
SLOTADDRESS
1 2001 through 5000
2 5001 through 8000
3 8001 through 11000
411001 through 14000
: :
1544001 through 47000
1647001 through 50000
■ READING EXAMPLE
In order to read the MV value in the table below from the R3-TC2 in the slot position 2, read 1 word at the address 5005, slot
2 top address 5001 added with 4.
ADDRESSPARAMETERUNIT
+4Loop 1, Heating MV (control output)0.01%
If 7510 is read, the register value is converted into actual engineering unit value by the following equation:
7510 × 0.01 = 75.10%
■ WRITING EXAMPLE
In order to write 40.0 at the SP value in the table below of the R3-TC2 in the slot position 3, write 400 (when the input 1
decimal is set to ‘1,’ disregard the decimal point) at the address 9153, slot 3 top address 8001 added with 1152.
ADDRESSPARAMETERRANGEDEFAULT
+1152Loop 1, SP (setpoint)-3200.0 to +3200.0
(decimal by input 1 decimal setting)
25.0
With the decimal setting ‘2,’ write in ‘4000’ for ‘40.00.’
With the setting ‘3,’ ‘40000’ cannot be written as the maximum range is limited up to 32000.