M-system R3-NM3, R3-NM4 Instruction Manual

INSTRUCTION MANUAL
MODBUS INTERFACE MODULE
(For temperature control module)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below. If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Network interface module ..................................................(1)
Terminating resistor (110 Ω, 0.25 W) .................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures.
POINTS OF CAUTION
■ HOT INSERTION/REMOVAL OF MODULES
• It is possible to replace the module with the power is sup­plied. Be sure to replace it when the module is not com­municating with a host, as it is possible to affect the sys­tem. However, replacing multiple modules at once may greatly change line voltage levels. We recommend that you replace them one by one.
MODEL
■ AND ....
• The unit is designed to function as soon as power is sup­plied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
R3-NM3
INSTALLATION
Use the Installation Base Model R3-BS, or Model R3-BSW for free I/O address capability.
Before mounting the Network Interface Module onto the Base, be sure to configure the module as explained below.
■ DATA ALLOCATION
The setting determines the data area size assigned to each I/O module mounted on the base. The data sent/received via Modbus is mapped according to this setting. See “COMPONENT IDENTIFICATION” and “MODBUS I/O ASSIGNMENTS”.
■ NODE ADDRESS & BAUD RATE, ETC.
See “COMPONENT IDENTIFICATION”.
■ NETWORK SLOTS ON THE BASE
I/O 1 I/O 2 I/O n
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and confirm its operational range as indicated below:
100 – 120V AC rating: 85 – 132V, 47 – 66 Hz, approx. 20VA 200 – 240V AC rating: 170 – 264V, 47 – 66 Hz, approx. 20VA
24V DC rating: 24V ±10%, approx. 12W
■ GENERAL PRECAUTIONS
• DO NOT set the switches on the module while the power is supplied. The switches are used only for maintenance without the power.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the air, install the unit inside proper housing with sufficient ventilation.
• Do not install the unit where it is subjected to continuous vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C (14 to 131°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
With Model R3-BS base, mount the I/O Modules from the left end (I/O 1) to the right in order that the Network Mod­ule assigns data areas from I/O 1. Network Module(s) and Power Module are mounted basi­cally at the right end though technically they could be mounted in any position.
With Model R3-BSW base, there is no limitation in mount­ing positions as I/O address can be assigned freely to each module using rotary switches equipped on the base.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8330 Rev.3 P. 1 / 9
COMPONENT IDENTIFICATION
FRONT VIEW SIDE VIEW
D
C
E
B
F
A
9
0
8
1
7
2
SA1
3
6
5
4
D
C
E
B
F
A
Node Address (MSD)
9
0
8
1
7
SA2
2
3
6
5
RUN LED
4
R3-NM3
ERR LED
Configuration Jack
Euro Type Connector Terminal
4
5
6
Node Address (LSD)
FG SLD DG DB DA
1
2
3
DIP SW
SW6
8 7 6 5 4 3 2 1
ON
■ FRONT ROTARY SW
• Node Address: SA1, SA2
Set the module’s node address in hexadecimal with SA1 and SA2. (Setpoint adjustment: 01 – F7)
■ FRONT DIP SW
(*) Factory setting
• Baud Rate: SW6-1, 6-2
SW
38.4k (*) 19.2k 9600
BAUD RATE (bps)
4800
SW6-1 OFF ON OFF ON SW6-2 OFF OFF ON ON
• Parity: SW6-3, 6-4*
SW
1
PARITY
NONE (*) ODD EVEN
N/A
SW6-3 OFF ON OFF ON SW6-4 OFF OFF ON ON
• Data Mode: SW6-5*
SW
1
DATA MODE
RTU (Binary) ASCII
SW6-5 OFF ON
*1. Bit assignment according to Parity and Data Mode setting.
MODE STA RT DATA PARITY STOP
RTU
ASCII
1 8 1 1 1 8 None 2 1 7 1 1 1 7 None 2
Note: Be sure to set unused SW6-6 through 6-8 to OFF.
DIP SW
SW3
4 3 2 1
ON
SW2
8 7 6 5 4 3 2 1
ON
SW1
8 7 6 5 4 3 2 1
ON
■ SIDE DIP SW
(*) Factory setting
• Data Allocation: SW1, SW2
2
Data Allocation Type*
must be assigned to each I/O module slot position to specify how many data areas (four types) are to be occupied by each. Two bits from SW1 and SW2 are assigned to each position, and data areas can be specified from the slot No. 1 through
8. Setting for No. 9 and later slots is identical to No. 8.
SW ASSIGNMENT SLOT
SW1-1 SW1-2 1 SW1-3 SW1-4 2 SW1-5 SW1-6 3 SW1-7 SW1-8 4 SW2-1 SW2-2 5 SW2-3 SW2-4 6 SW2-5 SW2-6 7 SW2-7 SW2-8 8
SW SETTING DATA ALLOCATION
OFF OFF 1
ON OFF 4
OFF ON 8
ON ON 16
*2. Refer to the specifications of the related series for the Data
Allocation Type of I/O modules.
• Dual Communication: SW3-1
When two network modules are mounted, one must be ‘Main’ (OFF) network and the other must be ‘Sub’ (ON) net­work. For single communication, the network module must always be set to ‘Main’ (OFF).
SW
DUAL COMMUNICATION
MAIN (*)
SUB
SW3-1 OFF ON
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8330 Rev.3 P. 2 / 9
• Input Error Data: SW3-2
Hold: When the communication from an input module is lost
due to the input module error, the network module holds the signal and stands by until the communication recovers. Set to ‘0’: When the communication from an input module is lost due to the input module error, the network module outputs ‘0.’
SW
SW3-2 OFF ON
INPUT ERROR DATA
HOLD (*)
SET ‘0’
• Main/Sub Switching Control: SW3-3
The host PC or PLC can choose whether ‘Main’ or ‘Sub’ bus is used when the switching control is set to ‘Host.’ In ‘Normal’ mode, ‘Main’ bus is normally used, while ‘Sub’ bus is when the main communication has failed. Be sure to match this control mode for both network mod­ules in dual communication mode.
SW
SW3-3 OFF ON
Note: Set SW3-3 to OFF for use in single communication mode.
MAIN/SUB SWITCHING CONTROL
NORMAL (*)
HOST
• LED Function: SW3-4
Functions assigned to the front RUN and ERR LEDs can be selected.
SW3-4
OFF (*) Green when normal Green when abnormal ON Red when receiving Red when transmitting
LED FUNCTION
RUN ERR
R3-NM3
PC CONFIGURATOR
With configurator software, settings shown below are available. Refer to the software manual of R3CON for detailed operation.
■ NETWORK MODULE SETTING
PARAMETER AVAILABLE RANGE DEFAULT SETTING
Time (no communication time) 0.2 – 3200.0 (sec.) 3.0 (sec.)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp