M-system R3-GD1 Instruction Manual

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8465 Rev.2 P. 1 / 4
INSTRUCTION MANUAL
DeviceNet INTERFACE MODULE
(for 64-point analog signals)
R3-GD1
BEFORE USE ....
Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below. If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Network interface module ..................................................(1)
■ MODEL NO.
Confirm that the model number described on the product is exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures.
■ EDS FILE
EDS files are downloadable at M-System’s web site: http://www.m-system.co.jp
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument panel of a metal enclosure.
• The actual installation environments such as panel con­figurations, connected devices, connected wires, may af­fect the protection level of this unit when it is integrated in a panel system. The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform­ity.
■ HOT INSERTION/REMOVAL OF MODULES
• It is possible to replace the module with the power is sup­plied. Be sure to replace it when the module is not com­municating with a host, as it is possible to affect the sys­tem. However, replacing multiple modules at once may greatly change line voltage levels. We recommend that you replace them one by one.
■ GENERAL PRECAUTIONS
• Do NOT set the switches while the power is supplied. The switches are used only for maintenance without the power.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the air, install the unit inside proper housing with sufficient ventilation.
• Do not install the unit where it is subjected to continuous vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C (14 to 131°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is sup­plied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
INSTALLATION
Use the Installation Base Model R3-BS, or Model R3-BSW for free I/O address capability. Before mounting the Network Interface Module onto the base, be sure to configure the module as explained below.
■ DATA ALLOCATION
Use the side DIP SW1 to set the number of slots which the module is assigned to. See “TRANSMISSION DATA DESCRIPTIONS”.
■ NODE ADDRESS & BAUD RATE
See “COMPONENT IDENTIFICATION”.
■ NETWORK SLOTS ON THE BASE
I/O 1 I/O 2 I/O n
With Model R3-BS base, mount the I/O Modules from the left end (I/O 1) to the right in order that the Network Mod­ule assigns data areas from I/O 1. Network Module(s) and Power Module are mounted basi­cally at the right end though technically they could be mounted in any position.
With Model R3-BSW base, there is no limitation in mount­ing positions as I/O address can be assigned freely to each module using rotary switches equipped on the base.
It is available to assign the module to max. 8 slots. The as­signed slots numbers can not be used again for the real I/O modules which need to be mounted on the same base. Don’t set the interface module for more than 16 slots as it can not read the data for more than 16 modules.
R3-GD1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8465 Rev.2 P. 2 / 4
COMPONENT IDENTIFICATION
1
2
3
4
5
6
7
8
6 5 4 3 2 1
ON
NA0
NA1
NA2
NA3
NA4
NA5
DR0
DR1
SW1
ON
8 7 6 5 4 3 2 1
Baud Rate
FRONT VIEW
SIDE VIEW
Data Allocation
MS LED
NS LED
Configuration Jack
Node Address
Functions
Euro Type Connector Terminal
■ INDICATORS
The following table defines the LED states of the MS, and NS indicators.
ID STATE TO INDICATE
MS
Green Operating in a normal condition
Blinking Green Standby (needs commissioning)
Red Critical failure
Blinking Red Minor failure
OFF No power supplied
NS
Green
Link on-line and connections in the established state
Blinking Green
Link on-line but no connections in the established state
Red Critical link failure
Blinking Red Minor link failure
OFF No power supplied
■ FRONT DIP SW
(*) Factory setting.
• Node Address: 1 – 6 (NA0 – NA5)
SW
1 (NA0) 2 (NA1) 3 (NA2) 4 (NA3) 5 (NA4) 6 (NA5)
2
0
2
1
2
2
2
3
2
4
2
5
A node address is defined in 6-digit binary code. 1 – 6 (NA0 to NA5) correspond to the least to most significant digits.
DIP SW
NODE
ADDRESS
6
NA55NA44NA33NA22NA11NA0
0 0 0 0 0 0 0
0 0 0 0 0 1 1
0 0 0 0 1 0 2
0 0 0 0 1 1 3
: : : : : : :
1 1 1 1 0 0 60
1 1 1 1 0 1 61
1 1 1 1 1 0 62
1 1 1 1 1 1 63
0 = OFF, 1 = ON
• Baud Rate: 7, 8 (DR0, DR1)
BAUD RATE
SW
7 (DR0) 8 (DR1)
125 kbps OFF (*) OFF (*)
250 kbps ON OFF
500 kbps OFF ON
N/A ON ON
■ SIDE DIP SW
• Module Allocation: SW1-1, 1-2, 1-3
MODULE SW1-1 SW1-2 SW1-3
1 OFF (*) OFF (*) OFF (*)
2 ON OFF OFF
3 OFF ON OFF
4 ON ON OFF
Note: Be sure to set unused SW1-4 through 1-8 to OFF.
R3-GD1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8465 Rev.2 P. 3 / 4
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■ EXTERNAL DIMENSIONS unit: mm (inch)
1
2
3
4
5
6
130 (5.12)
27.5 (1.08)
109 (4.29)
POSITIONING GUIDE
TERMINAL
COVER
6–M3 SCREW
6.2
(.24)
■ CONNECTION DIAGRAM
1
4
V+
CAN_H
Drain
CAN_L
V–
RUN +
RUN
CONFIGURATION JACK
BUS CONNECTOR
INTERNAL POWER
INTERNAL BUS
RUN CONTACT OUTPUT
JACK
To Other DeviceNet Devices
WIRING INSTRUCTIONS
■ M3 SCREW TERMINAL (RUN contact output)
Torque: 0.5 N·m
■ SOLDERLESS TERMINAL unit: mm (inch)
Refer to the drawing below for recommended ring tongue terminal size. Spade tongue type is also applicable. Solder­less terminals with insulation sleeve do not fit. Applicable wire size: 0.75 – 1.25 mm
2
Recommended manufacturer: Japan Solderless Terminal MFG. Co.,Ltd., Nichifu Co.,ltd.
3.2 (.13) dia.
4 min.
(.16)
12 (.47) max.
6 max.
(.24)
3 (.12) max.
■ EURO TYPE CONNECTOR TERMINAL (DeviceNet)
Applicable wire size: 0.2 – 2.5 mm
2
Stripped length: 7 mm
R3-GD1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8465 Rev.2 P. 4 / 4
TRANSMISSION DATA DESCRIPTIONS
Use the DIP SW located at the side of the module to specify module allocation. 1 module is equivalent to 1 I/O module with 16 words analog input and 16 words analog output. Max. 4 modules (64 words in­put, 64 words output) transmission is available. R3-GD1 seems as if max. 4 I/O modules are mounted to 4 slots via DeviceNet.
Note: Do not mount any modules in the slots which are occupied by virtual modules. If a real I/O module is mounted in the slot, an
internal bus error occurs and the ERR LED turns on. Max. 16 real I/O modules and virtual modules are available. The interface module can not read the data for more than 16 modules.
■ WHEN R3-GD1 IS MOUNTED TO SLOT 2 (4 modules)
In practice, I/O modules are mounted to slot 1 and slot 2. The R3-NE1 in slot 7 recognizes the R3-SV4 in slot 1 directly. How­ever, the R3-NE1 recognizes the R3-GD1 in slot 2 as if 4 modules are mounted to from slot 2 to 5.
SLOT REAL MODULE VIRTUAL MODULE DATA
Slot 1 R3-SV4 R3-SV4 4 Words
Slot 2 R3-GD1 R3-GD1 (1/4) 16 Words
Slot 3 No module R3-GD1 (2/4) 16 Words
Slot 4 No module R3-GD1 (3/4) 16 Words
Slot 5 No module R3-GD1 (4/4) 16 Words
Slot 6 No module No module
Slot 7 R3-NE1 R3-NE1
Slot 8 R3-PS1 R3-PS1
■ OUTPUT DATA
The figure below shows the allocation of the data sent from the network module to the master.
■ INPUT DATA
The figure below shows the allocation of the data sent from the master to the network module.
015 015
+0
Begin
Address
Module 1
+0
Begin
Address
Module 2
Module 3
Module 4
Module 1
Module 2
Module 3
Module 4
+15
+16
+31
+32
+47
+48
+63
+15
+16
+31
+32
+47
+48
+63
INPUT/OUTPUT DATA
■ ANALOG INPUT/OUTPUT DATA
0
15
16 bits binary data
12345678
R3-
SV4
R3-BS08
R3-
GD1
R3-
NE1
R3­PS1