M-system R3-CZ4 Instruction Manual

R3-CZ4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8447 Rev.2 P. 1 / 3
ZERO-PHASE CURRENT INPUT MODULE
(with noise lter)
MODEL
R3-CZ4
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check the contents of the package you received as outlined below. If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
CT input module .............................................................(1)
■ MODEL NO.
Confirm Model No. marking on the side of the product to be exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures.
POINTS OF CAUTION
■ HOT INSERTION/REMOVAL OF MODULES
•Removing or replacing modules does not affect other mod­ules on the same backplane. It is possible to replace them without removing the power supply. However, replacing multiple modules at once may greatly change line voltage levels. We recommend that you replace them one by one.
■ ENVIRONMENT
•Indoor use
•When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient ventilation.
•Do not install the unit where it is subjected to continuous vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -10 to +55°C (14 to 131°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
■ WIRING
•Do not install cables close to noise sources (relay drive cable, high frequency line, etc.).
•Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■ AND ....
•The unit is designed to function as soon as power is sup­plied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
INSTALLATION
Use the Installation Base (model: R3-BSx).
R3-CZ4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8447 Rev.2 P. 2 / 3
COMPONENT IDENTIFICATION
ON
8 7 6 5 4 3 2 1
SW1SW2
ON
8 7 6 5 4 3 2 1
SW3
ON
4 3 2 1
1
2
3
4
5
6
7
8
9
10
FRONT VIEW
SIDE VIEW
ERR LED
RUN LED
Conv. Rate
Input 2 (SW1) or Input 4 (SW2)
Range
Input 1 (SW1) or Input 3 (SW2)
Functions
■ STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally; Green when the bus B operates normally; Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with the input abnormality; Green in normal operating conditions.
■ SIDE DIP SW
• Input Range: SW1, SW2
INPUT 1 (SW 1) INPUT 2 (SW 1)
RANGEINPUT 3 (SW 2) INPUT 4 (SW 2)
1 2 3 4 5 6 7 8
OFF OFF OFF OFF OFF OFF OFF OFF
0 – 1.5mA (*)
ON
OFF OFF OFF
ON
OFF OFF OFF
0 – 0.1mA
• Conversion Rate: SW3
SW
CONVERSION RATE
80 ms (*)
40 ms 20 ms 10 ms
SW3-1 OFF ON OFF ON
SW3-2 OFF OFF ON ON
(*) Factory setting Note: Be sure to set unused SW3-3 and 3-4 to OFF.
PC CONFIGURATOR
The following parameters can be set with using PC Configurator Software (model: R3CON):
•0% scaling value
•100% scaling value
•0% adjustment value (bias)
•100% adjustment value (gain)
•0% input value
•100% input value
•Disable the unused channel
R3-CZ4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8447 Rev.2 P. 3 / 3
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■ DIMENSIONS mm (inch)
130 (5.12)
27.5 (1.08)
109 (4.29)
7.9 (.31)
POSITIONING GUIDE
TERMINAL
COVER
10–M3.5 SCREW
1
2
3
4
5
6
7
8
9
10
■ CONNECTION DIAGRAM
BUS CONNECTOR
INTERNAL POWER
INTERNAL BUS A
INTERNAL BUS B*
*For dual redundant communication.
INPUT 1
3
4
LOAD
SOURCE
k
l
ZCT
INPUT 2
5
6
LOAD
SOURCE
k
l
ZCT
INPUT 3
7
8
LOAD
SOURCE
k
l
ZCT
INPUT 4
9
10
LOAD
SOURCE
k
l
ZCT
WIRING INSTRUCTIONS
■ SCREW TERMINAL
Torque: 0.5 N·m
■ SOLDERLESS TERMINAL mm (inch)
Refer to the drawing below for recommended ring tongue terminal size. Spade tongue type is also applicable. Solder­less terminals with insulation sleeve do not fit. Applicable wire size: 0.3 – 0.75 mm
2
3.2 (.13) dia.
4 min.
(.16)
12 (.47) max.
6 max.
(.24)
3 (.12) max.
Loading...