DC VOLTAGE INPUT ALARM MODULE
(8 points, isolated)
MODEL
R3-AV8
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check the contents of the package you received as outlined below. If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
DC voltage input alarm module ....................................(1)
■ MODEL NO.
Check that model No. described on the specification label is exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
•The equipment must be mounted inside the instrument panel of a metal enclosure.
•The actual installation environments such as panel con­figurations, connected devices and connected wires may affect the protection level of this unit when it is integrat­ed in a panel system. The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure CE conformity.
■ HOT INSERTION/REMOVAL OF MODULES
•Removing or replacing modules does not affect other mod­ules on the same backplane. It is possible to replace them without removing the power supply. However, replacing multiple modules at once may greatly change line voltage levels. We recommend that you replace them one by one.
■ ENVIRONMENT
•Indoor use
•When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient ventilation.
•Do not install the unit where it is subjected to continuous vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -10 to +55°C (14 to 131°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
■ WIRING
•Do not install cables close to noise sources (relay drive cable, high frequency line, etc.).
•Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■ UNUSED INPUT CHANNELS
•Set the unused input channels to ±10V range. Unused channels left open with other settings may be equal to the input lower than -15%, which sets a data abnormality at the PLC or the host device.
Open circuit with the input range set to ±10V means 50%
of the full-scale. An alarm setpoint must be set to a value that does not trip an unwanted alarm.
•Unused channels can be specified and set so on the PC Configurator Software (model: R3CON) without needing the above mentioned setting.
■ AND ....
•The unit is designed to function as soon as power is sup­plied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
INSTALLATION
Use the Installation Base (model: R3-BSx).
R3-AV8
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8436 Rev.2 P. 2 / 4
COMPONENT IDENTIFICATION
SW2SW1
ON
1 2 3 4 5 6 7 8
ON
ON
1 2 3 4 5 6 7 8
SW3
1 2 3 4
5
19
20
21
22
15
16
17
18
23
24
25
26
27
28
6
7
8
9
10
11
12
13
14
1
2
3
4
FRONT VIEW
ERR LED
RUN LED
SIDE VIEW
Range
Input 1-4 (SW1) or Input 5-8 (SW2)
Conv. Rate
Functions
■ SIDE DIP SW
(*) Factory setting
• Input Range: SW1, SW2 (selectable per 4 channels)
INPUT 1 through INPUT4 (SW1)
RANGEINPUT 5 through INPUT8 (SW2)
1 2 3 4
OFF OFF OFF OFF -10 – +10V (*)
ON OFF OFF OFF -5 – +5V
OFF ON OFF OFF -1 – +1V
ON ON OFF OFF 0 – 10V
OFF OFF ON OFF 0 – 5V
ON OFF ON OFF 1 – 10V
OFF ON ON OFF 0 – 1V
• Conversion Rate: SW3
SW
CONVERSION RATE
160 ms (*)
80 ms 40 ms 20 ms
SW3-1 OFF ON OFF ON SW3-2 OFF OFF ON ON
Note: Be sure to set unused SW1-5 through 1-8, SW2-5 through
2-8, SW3-3 and 3-4 to OFF.
■ STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally; Green when the bus B operates normally; Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with the input abnormality; Green in normal operating conditions.
R3-AV8
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8436 Rev.2 P. 3 / 4
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■ DIMENSIONS mm (inch)
TERMINAL
COVER
5
19
20
21
22
15
16
17
18
23
24
25
26
27
28
6
7
8
9
10
11
12
13
14
1
2
3
4
130 (5.12)
27.5 (1.08)
109 (4.29)
POSITIONING GUIDE
28–M3 SCREW
6.2
(.24)
■ CONNECTION DIAGRAM
1
2
INTERNAL POWER
INTERNAL BUS A
INTERNAL BUS B*
BUS CONNECTOR
9
10
3
4
6
7
8
15
11
16
12
19
17
20
18
21
24
22
25
26
23
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
INPUT 6
INPUT 7
INPUT 8
5
1
*For dual redundant communication. NOTE: Connect either wide or narrow span terminals for each channel.
+
+
NARROW
SPAN
WIDE SPAN
+
+
NARROW
SPAN
WIDE SPAN
+
+
NARROW
SPAN
WIDE SPAN
+
+
NARROW
SPAN
WIDE SPAN
+
+
NARROW
SPAN
WIDE SPAN
+
+
NARROW
SPAN
WIDE SPAN
+
+
NARROW
SPAN
WIDE SPAN
+
+
NARROW
SPAN
WIDE SPAN
Wide span : -10 – +10 V DC, -5 – +5 V DC, 0 – 10 V DC, 0 – 5 V DC, 1 – 5 V DC
Narrow span : -1 – +1 V DC, 0 – 1 V DC
WIRING INSTRUCTIONS
■ SCREW TERMINAL
Torque: 0.5 N·m
■ SOLDERLESS TERMINAL mm (inch)
Refer to the drawing below for recommended ring tongue terminal size. Spade tongue type is also applicable. Solder­less terminals with insulation sleeve do not fit. Applicable wire size: 0.3 – 0.5 mm
2
3.2 (.13) dia.
4 min.
(.16)
12 (.47) max.
6 max.
(.24)
3 (.12) max.
R3-AV8
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8436 Rev.2 P. 4 / 4
OUTPUT DATA DESCRIPTIONS
Four alarm setpoints are selectable per each input. Two (2) word (16 bit × 2) data is transmitterd to the PLC or the host device via the R3 network module.
0
15
Alarm 1 Alarm 2
Input 1
Alarm 3 Alarm 4
Alarm 1 Alarm 2
Input 2
Alarm 3 Alarm 4
Alarm 1 Alarm 2
Input 3
Alarm 3 Alarm 4
Alarm 1 Alarm 2
Input 4
Alarm 3 Alarm 4
0
15
Alarm 1 Alarm 2
Input 5
Alarm 3 Alarm 4
Alarm 1 Alarm 2
Input 6
Alarm 3 Alarm 4
Alarm 1 Alarm 2
Input 7
Alarm 3 Alarm 4
Alarm 1 Alarm 2
Input 8
Alarm 3 Alarm 4
0
+1
0
15
Alarm 1 Alarm 2
Input 5
Alarm 3 Alarm 4
Alarm 1 Alarm 2
Input 6
Alarm 3 Alarm 4
Alarm 1 Alarm 2
Input 7
Alarm 3 Alarm 4
Alarm 1 Alarm 2
Input 8
Alarm 3 Alarm 4
+1
ALARM SETTING
The following parameters are programmable using the PC Configurator Software (model: R3CON).
■ ALARM TRIP POINT (-15.00 to +115.00%)
Four alarm setpoints are selectable per each input.
■ ALARM TYPE (High or Low)
High or Low alarm is selectable for each alarm trip point. High alarm: An alarm is set when the input signal goes
above the setpoint.
Low alarm: An alarm is set when the input signal goes be-
low the setpoint.
■ DEADBAND (HYSTERESIS)
(0.00 to 100.00%; factory set to 5.00)
Deadband (deviation between the points where the alarm is set and reset) is selectable for each alarm trip point.
■ POWER ON DELAY TIME
(0.0 to 99.0 seconds; factory set to 5.0)
The alarm output start functioning in the preset time after the power has been turned on. This setting is common to all four points.
■ ALARM ON DELAY TIME
(0.0 to 99.0 seconds; factory set to 1.0)
The alarm output is set when the preset time elapses after the input has entered in the alarm range. This setting is common to all four points.
■ ALARM HOLD TIME
(0.0 to 99.0 seconds; factory set to 1.0)
The alarm output is held for the preset time even if it is reset in shorter time. This setting is common to all four points.