M-system R1M-P4 Instruction Manual

INSTRUCTION MANUAL
PC RECORDER
(4 totalized counter inputs, 8 contact inputs and outputs)
Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below. If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
This product is for use in general industrial environments, therefore may not be suitable for applications which require higher level of safety (e.g. safety or accident prevention sys­tems) or of reliability (e.g. vehicle control or combustion con­trol systems).
For safety, installation and maintenance of this product must be conducted by qualified personnel.
■ PACKAGE INCLUDES:
PC Recorder .........................................................................(1)
Cable (9-pin D-sub cable, straight type) ............................(1)
CD (software and users manual) ........................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures. Read also the Users Manual for the software included in the CD for maximum use of the PC Recorder.
POINTS OF CAUTION
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V, 47 – 66 Hz, approx. 10VA
24V DC rating: 24V ±10%, approx. 7W
■ GENERAL PRECAUTIONS
• Before you remove the module, turn off the power supply, input signal and output signal for safety.
■ PC RECORDER SOFTWARE
• Use the latest version of PC Recorder Software included in the product package.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the air, install the module inside proper housing with sufficient ventilation.
• Do not install the module where it is subjected to continu­ous vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +60°C (23 to 140°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with ca­bles, etc.
■ WIRING
• Wrong connection may damage the module.
• Do not connect cables to moving parts or pull them tightly.
• Do not install cables close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
MODEL
R1M-P4
■ AND ....
• The module is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5665 Rev.12 P. 1 / 6
PC REQUIREMENTS (provided by the user)
■ MSR128-V6
NORMAL MODE (storing rates ≥ 500 ms) HIGH SPEED MODE (storing rates 100 / 200 ms)
PC IBM PC/AT or compatible Operating system Windows XP SP1, SP2, Windows Vista Business 32-bit, Windows 7 Professional 32-bit or
Windows 10 32-bit, 64-bit
Note: Proper software functions may not be ensured under certain conditions. CPU Pentium III 800 MHz or higher Pentium IV 2.0 GHz or higher Screen area 1024 by 768 pixels or better resolution Display color 65000 colors (16 bits) Video memory 2 MB minimum; 4 MB recommended 4 MB minimum Main memory 256 MB recommended for Windows XP
1 GB recommended for Windows Vista, Windows 7,
Windows 10
1
Hard disk area Use an internal hard disk. *
Max. approx. 100 MB required per day. Printer Use a printer for Windows. The programs use Standard System Fonts used in Windows.
Use a printer driver for Standard System Fonts. CD drive Windows supported CD drive is used to install the software program. Card reader drive Used with devices which save data in a CF Card Communication port RS-232-C port (COM1 through COM5) supported
LAN card
*1. External (e.g. SCSI) devices may impair appropriate performance.
512 MB recommended for Windows XP 1 GB recommended for Windows Vista, Windows 7, Windows 10
Use an internal hard disk. *1 Max. approx. 500 MB required per day.
LAN card by Windows
R1M-P4
■ MSR128LS, MSR128LV
MSR128LS MSR128LV
PC IBM PC/AT or compatible Operating system Windows XP SP1 or SP2.
For High Speed Mode (Group 0, 50 msec. storing cycle), use Windows XP SP1, SP2.
Note: Proper software functions may not be ensured under certain conditions. CPU Pentium II 233 MHz or higher *
2
Screen area 800 by 600 pixels or better resolution 640 by 480 pixels or better resolution Display color 65000 colors (16 bits) Main memory 256 MB for Windows XP Hard disk area 200 MB minimum *
3
Follow the respective OS’s standard for Windows XP. CD drive Windows supported CD drive is used to install the software program.
4
Communication port RS-232-C port (COM1 through COM5) supported by Windows *
or LAN communication card
*2. Alternately, Celeron 300 MHz or higher with the secondary cache.
For High Speed Mode (Group 0, 50 msec. storing cycle), Pentium III 800 MHz or higher. *3. External (e.g. SCSI) devices may impair appropriate performance. *4. The RS-232-C port may be predefined for other purposes than for COM port.
Driver software change or system configuration may be required before using such a port. Note 1: At 50 msec. storing cycle (Group 0), the MSR128LS/LV may not be able to store every bit of data depending upon the PC’s
performance levels. These missing data will be substituted by the last stored data. Only one (1) node is connectable in the high speed mode.
Note 2: Please refer to the hardware data sheet for response time of the module.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5665 Rev.12 P. 2 / 6
COMPONENT IDENTIFICATION
■ TOP VIEW ■ BOTTOM VIEW
Totalized (lower 6 digits) or Momentary Value Display
Contact Input LED
T5 T6T7
T1 T2T3 T4
12345678
12
3456789
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
Channel Selector for Digital Meter
10 11 12 13 14 15 16 17 18
Contact Output LED
SW602 is fixed to the position 3. DO NOT CHANGE.
SW602
SW604
R1M-P4
Totalized or Momentary Display Selector
Momentary
Totalized (factory default)
■ REAR VIEW
RS-232-C
Power Terminals
RS-485 Connector
Node Address Setting Rotary SW
9-pin Connector
Specifications
INSTALLATION
■ DIN RAIL MOUNTING
Set the body so that its DIN rail adaptor is at the bottom. Pull down the DIN rail adaptor. Position the upper hook at the rear side on the DIN rail and push in the lower. Push back the DIN rail adaptor.
RUN Indicator LED
Configurator Jack
DIN Rail
35mm wide
■ WALL MOUNTING
Set the body so that its DIN rail adaptor is at the bottom. Pull down the DIN rail adaptor. Refer to “EXTERNAL DIMENSIONS.”
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
DIN Rail Adaptor
EM-5665 Rev.12 P. 3 / 6
TERMINAL CONNECTIONS
36–M3 I/O TERMINALS
Connect the unit as in the diagram below.
■ EXTERNAL DIMENSIONS unit: mm (inch)
10 (.39)
175 (6.89)
165 (6.50)
T1 T2T3 T4
T5 T6T7
R1M-P4
15.5 (.61) 3–5 (.20) dia. MTG HOLES
46 (1.81)
105 (4.13)
104 (4.09)
14 (.55)
123456789
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35
10 11 12 13 14 15 16 17 18
163 (6.42)
FOR WALL MOUNT.
6.2 (.24)
3 (.12)
40 (1.57)
DIN RAIL 35 mm wide
[6 (.24)]
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5665 Rev.12 P. 4 / 6
■ CONNECTION DIAGRAM
15
69
R1M-P4
TOTALIZED
COUNTER
INPUT
COM (–)
COUNTER RESET
COM (–)
CONTACT
INPUT
COM (–)
CONTACT
OUTPUT
COM (–)
ch.A
ch.B
ch.C
ch.D
ch.1
ch.2
ch.3
ch.4
ch.5
ch.6
ch.7
ch.8
ch.1
ch.2
ch.3
ch.4
ch.5
ch.6
ch.7
ch.8
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
I/O Circuit
Output Circuit
Term.
Resist.
Power Circuit
RS-232-C
D-SUB CONNECTOR
Shielded Twisted-pair Cable
+
T1 T2
– T3 T4
T5 T6 T7
U (+) V (–)
FG
Jumper*
POWER
To Other PC Recorders
When the device is located at the end of a transmission line via twisted-pair cable,
*
(when there is no cross-wiring), close across the terminal T2 –T3 with the attached jumper pin (or with a leadwire). When the device is not at the end, remove the jumper pin.
DO NOT CONNECT to the terminals 5 thr. 8 or 10 thr. 16. Wrong connection may cause failure of the device.
Caution: FG terminal is NOT a protective conductor terminal.
■ RS-232-C INTERFACE
ABBR. PIN NO. EXPLANATION OF FUNCTION
BA (SD)
BB (RD)
AB (SG) CB (CS)
CA (RS)
2
Transmitted Data
3
Received Data
5
Signal Common
7
Clear to Send
8
Request to Send
1
Not Used.
4
DO NOT connect. Connecting may
6
cause malfunctions.
9
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5665 Rev.12 P. 5 / 6
WIRING INSTRUCTIONS
■ M3 SCREW TERMINAL (I/O signal)
Torque: 0.6 N·m
■ SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue terminal size. Spade tongue type is also applicable. Applicable wire size: 0.75 to 1.25 mm Recommended manufacturer: Japan Solderless Terminal MFG.Co.Ltd, Nichifu Co.,ltd
3 (.12) max
(.24)
6 max
■ EURO TYPE CONNECTOR TERMINAL (Power input, Modbus)
Applicable wire size: 0.2 to 2.5 mm2 (AWG24 to 12) Stripped length: 7 mm
2
(AWG19 to 16)
3.2 (.13) dia.
mm (inch)
R1M-P4
COMMUNICATION CABLE CONNECTIONS
R1M
RS-232-C
CONNECTOR
*1. Internal terminating resistor is used when the device is at the end of a transmission line. *2. Install shielded cables to all sections and ground them at single point.
T1 T2 T3 T4
1
*
2
*
FG
CHECKING
1) Terminal wiring: Check that all cables are correctly con­nected according to the connection diagram.
2) Power input: Check supply voltage.
RS-485
R1M
T1 T2 T3 T4
RS-485
R1M
T1 T2 T3 T4
1
*
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp