Remote I/O R1M Series
40
(1.57)
115
(4.53)
mm (inch)
175 (6.89)
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
RUN indicator LED: Green light blinks in normal conditions.
THERMOCOUPLE & DC INPUT MODULE
(16 points)
Functions & Features
• 16-point thermocouple or DC inputs
• Easy system expansion via Modbus RTU
MODEL: R1M-GH2T-[1]
ORDERING INFORMATION
• Code number: R1M-GH2T-[1]
Specify a code from below for [1]
e.g. R1M-GH2T-M2
FIELD TERMINAL TYPE
T: M3 screw terminals
[1] POWER INPUT
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
RELATED PRODUCTS
• Resistor module (model: REM3-250)
• R1X configurator software (model: R1CON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
GENERAL SPECIFICATIONS
Connection
Power input, transmission: Euro type connector terminal
RS-232-C: 9-pin D-sub connector (male)
I/O: M3 screw terminals
Isolation: Input to RS-232-C or RS-485 to power
Address setting: Rotary switch; 1 – F (15 nodes)
COMMUNICATION
Baud rate: 38.4 kbps
Communication: Half-duplex, asynchronous, no procedure
Protocol: Modbus RTU
Protocol: Modbus RTU
Refer to Modbus Protocol Reference Guide (EM-5650) for
supported functions.
■ RS-232-C
Standard: Conforms to RS-232-C, EIA
Transmission distance: 10 meters max.
■ RS-485
Standard: Conforms to RS-485, EIA
Transmission distance: 500 meters max.
Transmission media: Shielded twisted-pair cable (CPEV-S
0.9 dia.)
INPUT SPECIFICATIONS
Input: Thermocouple or DC input, 16 points
(Common negative for DC input)
Measuring Range:
±20 V, ±5 V, ±1 V, ±0.8 V, ±0.2 V, ±50 mV, ±10 mV
Input resistance: 300 kΩ
Thermocouple types: PR, K, E, J, T, B, R, S, C, N, U, L, P
Sampling rate: 100 millisec./16 points
• Trigger input: Dry contact; ON detected at ≤1.5 V
Sensing: Approx. 5 V DC @ 1 mA
INSTALLATION
Power Consumption
•AC: Approx. 10 VA
•DC: Approx. 7 W
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 400 g (0.88 lbs)
PERFORMANCE (% of measuring range)
Accuracy
DC input: ±0.3 %
Thermocouple input: See the table on the end of this
section.
Cold junction compensation error: ±3°C or ±5.4°F max.
(at 20°C ±10°C or 68°F ±18°F)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
±0.05 %/°C (±0.03 %/°F) for 10 mV range
Insulation resistance: ≥100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (input to RS-232C or RS-485 to power to ground)
![](/html/fb/fb4b/fb4b36e7038cafb428d3cd7749b258c0a4aec499c55bd831051c94c70bd2a94c/bg2.png)
Thermocouple Accuracy
T/C
USABLE RANGE
ACCURACY
°C °F (%)
(PR) 0 to 1770 32 to 3218 ±0.5*
1
K (CA) -270 to +1370 -454 to +2498 ±0.3
E (CRC) -270 to +1000 -454 to +1832 ±0.7
J (IC) -210 to +1200 -346 to +2192 ±0.7
T (CC) -270 to +400 -454 to +752 ±1.0
B (RH) 100 to 1820 212 to 3308 ±0.7*
2
R -50 to +1760
-58 to +3200 ±0.7*
1
S -50 to +1760 -58 to +3200
±0.7*
1
C (
WRe 5-26
) 0 to 2320 32 to 4208 ±0.7
N -270 to +1300 -454 to +2372 ±0.5
U -200 to +600 -328 to +1112 ±0.5
L -200 to +900 -328 to +1652 ±0.3
P (
Platinel II
) 0 to 1395 32 to 2543 ±0.5
*1. ≥400°C or ≥752°F
*2. ≥700°C or ≥1292°F
The described accuracy may be partially not satised when
the temperature ranges below 0°C.
STANDARDS & APPROVALS
RS-485
Connector
Power Terminals
Address Setting
Rotary SW
Configurator
Jack
RUN Indicator
LED
RS-232-C
9-pin Connector
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
CE conformity:
EMC Directive (2004/108/EC)
EMI EN 61000-6-4: 2007
EMS EN 61000-6-2: 2005
Low Voltage Directive (2006/95/EC)
EN 61010-1
Installation Category II
Pollution Degree 2
Input or RS-232-C/RS-485 to power: Reinforced insulation
(300 V)
Input to RS-232-C/RS-485: Basic insulation (300 V)
EXTERNAL VIEW
![](/html/fb/fb4b/fb4b36e7038cafb428d3cd7749b258c0a4aec499c55bd831051c94c70bd2a94c/bg3.png)
ABBR. PIN NO. EXPLANATION OF FUNCTION
BA (SD) 2 Transmitted Data
BB (RD) 3 Received Data
AB (SG) 5 Signal Common
CB (CS) 7 Clear to Send
CA (RS) 8 Request to Send
1 Not Used.
4 DO NOT connect. Connecting may
6 cause malfunctions.
9
CONNECTION DIAGRAM
RS-232-C
T3
T4
T2
T1
T7
T6
T5
Term.
Resist.
Output
Circuit
When the device is located at the end of a transmission line via twisted-pair cable,
(when there is no cross-wiring), close across the terminal T2 –T3 with the attached
jumper pin (or with a leadwire).
When the device is not at the end, remove the jumper pin.
Remark 1: This device is not designed to cancel noise included in the input signals.
Be careful to eliminate such noise by using shielded cables.
Remark 2: Be sure to maintain the same potential at all the common negative
terminals for DC input.
*
9
8
7
6
5
4
3
2
1
10
12
11
13
15
14
16
17
18
20
19
21
22
23
24
25
27
26
28
29
30
31
32
33
35
34
36
TRIGGER INPUT
T/C INPUT
–
+
DC INPUT
INPUT 1
+
–
INPUT 2
INPUT 3
INPUT 4
INPUT 5
INPUT 6
INPUT 7
INPUT 8
INPUT 9
INPUT 10
INPUT 11
INPUT 12
INPUT 13
INPUT 14
INPUT 15
INPUT 16
CJC
Sensor
+
ext. wire
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
Power
Circuit
Input
Circuit
+
–
Shielded Twisted-pair Cable
To Other
I/O Modules
Jumper*
FG
U (+)
V (–)
POWER
D-SUB CONNECTOR
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
![](/html/fb/fb4b/fb4b36e7038cafb428d3cd7749b258c0a4aec499c55bd831051c94c70bd2a94c/bg4.png)
MODBUS WIRING CONNECTION
R1M
T1
T2
T3
T4
R1M
T1
T2
T3
T4
T1
T2
T3
T4
R1M
CONNECTO
R
RS-232-C
RS-485
*
1
*
1
*1. Internal terminating resistor is used when the device is at the end of a transmission line.
*2. Install shielded cables to all sections and ground them at single point.
*
2
FG
RS-485
■ COMMUNICATION PARAMETERS
PARAMETER SPECIFICATION
Data Mode RTU
Baud Rate 9600 / 19200 / 38400 (*) bps
Parity None / Odd (*) / Even
Bit Length 8
Stop Bit 1 (*) / 2
Node Address 1 (*) to 15
Floating Point Data N/A
Interface RS-232-C/ RS-485
(*) Ex-factory setting
■ FUNCTION CODES & SUPPORTED CODES
CODE NAME
01 Read Coil Status X Digital output from the slave
02 Read Input Status X Status of digital inputs to the slave
03 Read Holding Registers X General purpose register within the slave
04 Read Input Registers X Collected data from the field by the slave
05 Force Single Coil X Digital output from the slave
06 Preset Single Registers X General purpose register within the slave
07 Read Exception Status
08 Diagnostics
09 Program 484
10 Poll 484
11 Fetch Comm. Event Counter Fetch a status word and an event counter
12 Fetch Comm. Event Log A status word, an event counter, a message count and a field of event bytes
13 Program Controller
14 Poll Controller
15 Force Multiple Coils X Digital output from the slave
16 Preset Multiple Registers X General purpose register within the slave
17 Report Slave ID Slave type / ‘RUN’ status
18 Program 884/M84
19 Reset Comm. Link
20 Read General Reference
21 Write General Reference
22 Mask Write 4X Register
23 Read/Write 4X Register
24 Read FIFO Queue
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
MODBUS COMMUNICATION