INSTRUCTION MANUAL
CONTACT INPUT MODULE
(32 points)
R1M-A1
BEFORE USE ....
Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below. If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
This product is for use in general industrial environments, therefore may not be suitable for applications which require higher level of safety (e.g. safety or accident prevention sys­tems) or of reliability (e.g. vehicle control or combustion con­trol systems).
For safety, installation and maintenance of this product must be conducted by qualified personnel.
■ PACKAGE INCLUDES:
Remote I/O module .............................................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures. For detailed information on Modbus supported functions, refer to Modbus Protocol Reference Guide (EM-5650). The R1M is programmable using the PC configurator soft­ware. For detailed information on the PC configuration, refer to the R1CON instruction manual. The R1CON PC Configurator Software is downloadable at M-System’s web site: http://www.m-system.co.jp.
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
•This equipment is suitable for Pollution Degree 2 and Installation Category II (transient voltage 2500V). Re­inforced insulation (input or RS-232-C/RS-485 to power: 300V) and basic insulation (input to RS-232-C/RS-485: 300V) are maintained. Prior to installation, check that the insulation class of this unit satisfies the system re­quirements.
•Altitude up to 2000 meters.
•The equipment must be mounted inside a panel.
•Insert noise filters. Okaya Electric Industries Model
SUP-E1H or equivalent for the power source connected to the unit, and TDK Model ZCAT 3035-1330 or equivalent for the RS-232-C cable are recommended.
•The equipment must be installed such that appropriate clearance and creepage distances are maintained to con­form to CE requirements. Failure to observe these re­quirements may invalidate the CE conformance.
•The actual installation environments such as panel con­figurations, connected devices, connected wires, may af­fect the protection level of this unit when it is integrated in a panel system. The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform­ity.
•Install lightning surge protectors for those wires connect­ed to remote locations.
■ POWER INPUT RATING & OPERATIONAL RANGE
•Locate the power input rating marked on the product and confirm its operational range as indicated below: 100 – 240V AC rating: 85 – 264V, 47 – 66 Hz, approx. 10VA
24V DC rating: 24V ±10%, approx. 7W
■ GENERAL PRECAUTIONS
•Before you remove the module, turn off the power supply and input signal for safety.
■ ENVIRONMENT
•Indoor use.
•When heavy dust or metal particles are present in the air,
install the module inside proper housing with sufficient ventilation.
•Do not install the module where it is subjected to continu­ous vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -5 to +60°C (23 to 140°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
•Be sure that the ventilation slits are not covered with ca­bles, etc.
■ WIRING
•Wrong connection may damage the module.
•Do not connect cables to moving parts or pull them tightly.
•Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
•Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■ AND ....
•The module is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
R1M-A1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5661 Rev.6 P. 2 / 8
COMPONENT IDENTIFICATION
■ REAR VIEW
RS-485 Connector
Node Address Setting Rotary SW
Configurator Jack
Specifications
Power Terminals
RS-232-C 9-pin Connector
RUN Indicator LED
INSTALLATION
■ DIN RAIL MOUNTING
Set the body so that its DIN rail adaptor is at the bottom. Pull down the DIN rail adaptor. Position the upper hook at the rear side on the DIN rail and push in the lower. Push back the DIN rail adaptor.
■ WALL MOUNTING
Set the body so that its DIN rail adaptor is at the bottom. Pull down the DIN rail adaptor. Refer to “EXTERNAL DIMENSIONS.”
TERMINAL CONNECTIONS
Connect the module referring to the connection diagram.
■ EXTERNAL DIMENSIONS unit: mm (inch)
• M3 SCREW TERMINALS
123456789
10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35
T1 T2T3 T4
T5 T6T7
104 (4.09)
10 (.39)
105 (4.13)
14 (.55)
163 (6.42)
36–M3 INPUT TERMINALS
165 (6.50)
175 (6.89)
3–5 (.20) dia. MTG HOLES
FOR WALL MOUNT.
6.2 (.24)
15.5 (.61)
[6 (.24)]
40 (1.57)
3 (.12)
46 (1.81)
DIN RAIL 35 mm wide
• FCN TYPE CONNECTOR
T1 T2T3 T4
T5 T6T7
104 (4.09)
10 (.39)
105 (4.13)
14 (.55)
163 (6.42)
165 (6.50)
175 (6.89)
3–5 (.20) dia. MTG HOLES
FOR WALL MOUNT.
FCN TYPE INPUT CONNECTOR
[6 (.24)]
40 (1.57)
40 (1.57)
Connector Pin
Assignment
A1 B1
A16 B16
CN1 CN2
See Caution below
Caution: DO NOT APPLY EXCESSIVE FORCE onto the connector. The connector may be destroyed.
15.5 (.61)
3 (.12)
46 (1.81)
DIN RAIL 35 mm wide
DIN Rail Adaptor
DIN Rail
35mm wide
R1M-A1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5661 Rev.6 P. 3 / 8
■ CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal.
RS-232-C
T3 T4
T2
T1
T7
T6
T5
Term.
Resist.
Output Circuit
When the device is located at the end of a transmission line via twisted-pair cable, (when there is no cross-wiring), close across the terminal T2 –T3 with the attached jumper pin (or with a leadwire). When the device is not at the end, remove the jumper pin.
*
Power Circuit
+
Shielded Twisted-pair Cable
To Other I/O Modules
Jumper*
FG
U (+) V (–)
POWER
D-SUB CONNECTOR
9
8
7
6
5
4
3
2
1
10
12
11
13
15
14
16 17 18
20
19
21 22 23 24 25
27
26
28 29 30 31 32 33
35
34
36
ch.1
ch.2
ch.3
ch.4
ch.5
ch.6
ch.7
ch.8
COM (–)
ch.9
ch.10
ch.11
ch.12
ch.13
ch.14
ch.15
ch.16
COM (–)
ch.17
ch.18
ch.19
ch.20
ch.21
ch.22
ch.23
ch.24
COM (–)
ch.25
ch.26
ch.27
ch.28
ch.29
ch.30
ch.31
Count Reset Input
ch.32
COM (–)
Input Circuit
Input Circuit
A9
A8
A7
A6
A5
A4
A3
A2
A1
A10
A12
A11
A13
A15
A14
A16
B1
:
B16
ch.1
ch.2
ch.3
ch.4
ch.5
ch.6
ch.7
ch.8
ch.9
ch.10
ch.11
ch.12
ch.13
ch.14
ch.15
ch.16
COM (–)
A9
A8
A7
A6
A5
A4
A3
A2
A1
A10
A12
A11
A13
A15
A14
A16
ch.17
CN1
ch.18
ch.19
ch.20
ch.21
ch.22
ch.23
ch.24
ch.25
ch.26
ch.27
ch.28
ch.29
ch.30
ch.31
Count Reset Input
ch.32
FCN TYPE CONNECTOR M3 SCREW TERMINALS
CN2
B1
:
B16
COM (–)
■ RS-232-C INTERFACE
15
69
ABBR. PIN NO. EXPLANATION OF FUNCTION
BA (SD)
BB (RD)
AB (SG)
2 3 5
Transmitted Data Received Data Signal Common
CB (CS) CA (RS)
78Clear to Send
Request to Send
1 4 6 9
Not Used. DO NOT connect. Connecting may cause malfunctions.