Thank you for your choosing M-System. Read this manual carefully to ensure that you use the product correctly and safely.
1.1 PACKAGE
Check contents of the package you received as outlined below.
•Signal conditioner
•Accessories
I/O range and tag name label sheetInstruction manualCJC sensor
(mounted on a Euro type connector terminal
block)
*1 Ordering Information Sheet is included when input or output is specied in ordering.
4M3LU2 OPERATING MANUAL EM-2653-B Rev.0
2. SAFETY PRECAUTIONS (Be sure to observe.)
The following signs are used in this manual to provide precautions required to ensure safe usage of the unit. Please understand these signs and graphic symbols, read the manual carefully and observe the description.
The following signs show seriousness of safety hazard or damage occurred when used wrongly with the signs ignored.
Indicates a potentially hazardous situation which, if not avoided, may result in
serious injury or death.
Indicates a potentially hazardous situation which, if not avoided, may result in
injury or in property damage.
Make sure for safety that only qualied personnel
perform the wiring.
• Failure to do so may result in a re, electric
shock or injury.
Do not touch the terminals while the power is on.
•Doing so may result in electric shock.
Check the connection diagram carefully before
wire connection.
• Failure to do so may result in malfunction, a re
or electric shock.
Tighten the terminal screws of the Euro type connector terminal blocks with a specied torque.
• Excessive fastening may result in damage of
the screws and loose screws may occasionally
result in ignition.
Do not operate buttons with a wet hand or nger.
•Doing so may result in electric shock.
Do not splash water on the unit.
• Doing so may result in a re, electric shock or
injury.
Provide safety measures outside of the unit to
ensure safety in the whole system if an abnormality occurs due to malfunction of the unit or another
external factor affecting the unit’s operation.
Stop using the unit immediately if smokes, unusual
smell or abnormal noises come(s) from it.
• Using the unit continuously may result in a re
or electric shock.
Stop using the unit if it is dropped or damaged.
• Using the unit continuously may result in a re
or electric shock.
Do not throw the unit into the re.
• Doing so may result in rupture of the electronic
component.
5M3LU2 OPERATING MANUAL EM-2653-B Rev.0
Never discompose or remodel the unit.
• Doing so may result in electric shock, malfunction or injury.
Do not press buttons with a pointed object.
•Doing so may result in malfunction of the unit.
PROHIBITION
TO CONTACT
Do not connect or remove the unit while its power
is on.
• Doing so may result in, electric shock, malfunction or injury.
Do not allow ne shavings or wire scraps to enter
the unit in machining screws or wiring.
•Doing so may result in malfunction of the unit.
Do not open the housing cover while the power or
the input is applied.
• Doing so may result in electric shock, malfunction or injury.
Do not touch the printed circuit board or the electronic components in opening the cover.
•Doing so may result in malfunction of the unit.
Do not connect other cables to the COMM (congurator jack) port than the dedicated one.
•Doing so may result in malfunction of the unit.
Use a minus screwdriver and tweezers in setting
the switches.
• Failure to do so may result in malfunction of
the unit.
Do not pull the wires to separate the Euro type
connector terminal blocks from the body.
• Doing so may result in damage of the unit or
injury.
Do not use the unit with the cover open.
•Doing so may result in malfunction of the unit.
Do not pull the wires connecting to the unit.
• Doing so may result in electric shock, damage
of the unit or injury.
Do not use the unit in the atmosphere where combustible gas is present.
• Doing so may result in inammation, ignition or
smoke.
Do not cover the ventilation slits with cables, etc.
•Doing so may result in malfunction or heating.
6M3LU2 OPERATING MANUAL EM-2653-B Rev.0
3. POINTS OF CAUTION
3.1 BEFORE USE ....
The unit is for use in general industrial environments, therefore may not be suitable for applications which require higher
level of safety (e.g. safety or accident prevention systems) or of reliability (e.g. vehicle control or combustion control systems).
For safety, installation and maintenance of this unit must be conducted by qualied personnel.
If the unit is not used in a manner not specied by M-System, the protection provided by the equipment may be impaired.
3.2 CONFORMITY WITH EU DIRECTIVES
This product conforms to the following Low Voltage and EMC Directives.
Electromagnetic Compatibility (EMC) Directive (2004/108/EC)
EMI EN 61000-6-4: 2007/A1: 2011
EMS EN 61000-6-2: 2005
Low Voltage Directive (2006/95/EC)
EN 61010-1: 2010
Installation Category II
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
•This equipment is suitable for Pollution Degree 2 and Installation Category II. Reinforced insulation (signal input or output
to power input: 300 V) and basic insulation (signal input to output: 300 V) are maintained. Prior to installation, check that
the insulation class of this unit satises the system requirements.
•Altitude up to 2000 meters.
•The equipment must be mounted inside a panel.
•The actual installation environments such as panel congurations, connected devices, connected wires, may affect the
protection level of this unit when it is integrated in a panel system. The user may have to review the CE requirements in
regard to the whole system and employ additional protective measures to ensure the CE conformity.
This product conforms to the EMC Directive for electrical and electronic apparatus intended for use in industrial environments. If it is used in the residential environments, it may cause radio interference, and the user is requested to take
appropriate measures.
3.3 ENVIRONMENT
Install the unit within the installation specications.
•Indoors use
•Environmental temperature must be within -25 to +60°C (-13 to 140°F) with relative humidity within 30 to 95% RH without
condensing.
•Altitude up to 2000 meters.
•Provide sufficient space around the unit for heat dissipation.
•Install the unit in a well-ventilated place in order to prevent internal temperature rise.
•Refer to “Clustered mounting” to install several units. In mounting the unit with other equipments side by side, provide
sufficient space between them, according to the dimensions in the clustered mounting.
•Do not use the unit under the following environments:
– Where the unit is exposed to direct sunlight, rain or wind. (The unit is not designed for outdoor use.)
– Where condensation may occur due to extreme temperature changes.
– Where corrosive or ammable gas is present.
7M3LU2 OPERATING MANUAL EM-2653-B Rev.0
– Where heavy dust, iron powder or salt is present in the air.
– Where organic solvent such like benzine, thinner, and alcohol, or strong alkaline materials such like ammonia and
caustic soda may attach to the unit, or where such materials are present in the air.
– Where the unit is subject to continuous vibration or physical impact.
– Where there are high-voltage lines, high-voltage equipments, power lines, power equipments, equipments with trans-
mission unit such like a ham radio equipment, or equipments generating large switching surges around the unit.
3.4 WIRING
•In order to prevent potential electric shock, wire the unit after turning off the power supply and making sure that the power
is not supplied to the cable.
•Be sure to conrm the name and polarity of each terminal before wiring to the Euro type connector terminal blocks.
•Do not connect anything to unused terminals.
3.5 HANDLING CAUTIONS
•The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
•Use the unit within the noted supply power voltage and rated load.
•The last measured values are held in mode transition. Take this into consideration when conguring the control system.
•Clean the surface of the unit with wet soft cloth. Do not use organic solvent such like benzine, thinner and alcohol. Doing
so may result in deformation or discoloration of the unit.
•When abnormality is found such like smokes, unusual smell and abnormal noises coming from the unit, immediately cut
the power supply and stop using it.
8M3LU2 OPERATING MANUAL EM-2653-B Rev.0
4. FEATURES AND PREPARATION PROCEDURE OF M3LU2
4.1 FEATURES OF M3LU2
The M3LU2 is a eld congurable signal transmitter using a simulator and an indicator, without a PC or a dedicated setting
unit.
For instance, select an input type and range with the DIP switches on the unit to set input. Then apply a desired minimum
or maximum input from the simulator and press a front button to memorize the value as minimum or maximum value. Easy
and reasonable M-System’s one-step calibration (hereafter called ‘One-Step Cal’) realizes automatic I/O ranging and calibration only by pressing a button once.
4.2 PREPARATION PROCEDURE
Before using the unit, perform the calibration according the following ow. The procedure depends on the conguration
options or modes.
•Two conguration modes are available with the model M3LU2-x/A, eld conguration using the DIP SW / control
buttons (hereafter called ‘DIP SW conguration’) and the PC conguration.
•The model M3LU2-x/B is for the DIP SW conguration only.
CONFIGURING DIP SW & JP2
DIP SW congurationPC conguration
INPUT RANGING
• With front control buttons and a simulator.
OUTPUT RANGING
• With front control buttons, a simulator
and a multimeter.
WIRING & MOUNTING ON DIN RAIL
POWER ON
I/O SETTING AND CALIBRATION
• Using the PC Congurator Software
(model: M3LUCFG).
STARTING OPERATION
9M3LU2 OPERATING MANUAL EM-2653-B Rev.0
5. COMPONENT IDENTIFICATION
5.1 FRONT AND SIDE VIEWS
(1)
(2)
(3)
(4)
(7)
(5)
(9)
(8)
(6)
(1) LED1 (LD1), LED2 (LD2) and LED3 (LD3)
The blinking pattern (ON/blink/OFF) of the tri-color (green/amber/red) LEDs indicates a mode or an operation status of
the transmitter.
(2) MODE, UP and DOWN Buttons
Used for the I/O ranging and ne adjustments by ‘One-Step Cal’, and for reset of the parameters to the default status.
The functions of the buttons are shown in the following table.
BUTTONFUNCTION
MODE
UP
DOWN
Used to move on to the I/O Ranging Mode, Fine Adjustment Mode and RUN Mode, and to reset the
parameters to the default status.
Used to congure 100% input in the Input Ranging Mode and 100% output in the Output Ranging
Mode, and to increase the output in the Fine Adjustment Mode.
Used to congure 0% input in the Input Ranging Mode and 0% output in the Output Ranging Mode, and
to decrease the output in the Fine Adjustment Mode.
(3) Congurator jack
Used to connect with a PC using the PC Congurator Software (model: M3LUCFG) for various settings, I/O ranging
and ne adjustments.
Connect a dedicated cable between the congurator jack and the PC.
(4) Cover for congurator jack
Slide the cover to connect the cable to the congurator jack. Close the cover in the normal operation.
(5) Specication label
The model No., power input and serial No. (SER NO) are printed on the label.
(6) Connection diagram
The connection diagram for each terminal is shown.
(7) DIP SW setting
The DIP switch settings are shown.
(8) I/O range label
When I/O range indication is necessary, write in the congured ranges on the I/O range label included in the product
package and put it on the side of the unit.
(9) Tag name label
When a tag No. is specied, the unit(s) will be shipped with the tag name label put on the above position.
10M3LU2 OPERATING MANUAL EM-2653-B Rev.0
5.1.1 STATUS INDICATOR LED
Combinations of the three front LEDs (LD1, LD2 and LD3) indicates the transmitter’s operating status by different blinking
patterns. The patterns depend on the conguration modes, DIP SW conguration and PC conguration.
Examples are shown below.
LED COLORPATTERN
Red
Amber
Green
R
A
G
ON
Blink
OFF
■ NORMAL OPERATION (RUN) MODE
Combination of the LEDs and their blinking patterns indicate normal or abnormal operation of the unit, and are useful to
identify error modes.
•Normal operation (RUN) mode
DIP SW CONFIGURATIONPC CONFIGURATION
•Error mode
ERRORDIP SW CONFIGURATIONPC CONFIGURATION
Output saturated
Burnout
DIP SW error
System error
The output is below -15% or above +115%. Check the setting and input.
The sensor or the input wiring is disconnected. Check the sensor and wiring.
DIP SW conguration is inappropriate. Check the SW settings.
Indicates the CPU’s communication error.
11M3LU2 OPERATING MANUAL EM-2653-B Rev.0
■ I/O RANGING MODE & FINE ADJUSTMENT MODE
The LED status in the I/O ranging and ne adjustments using the ‘One-Step Cal’ is shown in the following tables.
MODELEDMODELED
Input ranging
Output rangingFine span adjustment
Fine zero adjustment
NOTE
In the I/O ranging and ne adjustments using the PC Congurator Software (model: M3LUCFG), the LEDs are not according to the above tables.
12M3LU2 OPERATING MANUAL EM-2653-B Rev.0
5.2 INTERNAL VIEW
(1) SW1
(2) SW2(3) SW3
(4) JP2
(1) SW1
Sets output type.
(2) SW2
Sets wires, cold junction compensation, burnout, front control button lock and output type.
(3) SW3
Sets input type, sensor type and conguration mode.
(4) JP2
Sets input type.
13M3LU2 OPERATING MANUAL EM-2653-B Rev.0
6. HOW TO OPEN THE COVER
■
Open the housing cover to set the DIP switches and JP2 inside the cover.
■ HOW TO OPEN THE COVER
(1) Hold the locks at the top and bottom of the unit.
(2) Slide the housing cover gently to open until it hits the latching inside the unit (approx. 3.5 cm).
Top
Front
Approx. 3.5 cm
Lock
Lock
Bottom
■
Lock
Lock
•Do not open the cover while the power or the input is applied.
•Do not touch the printed circuit board or the electronic components in opening the cover.
•Do not pull beyond where the cover is latched.
■ HOW TO CLOSE THE COVER
(1) Push the front to close the cover.
Front
•Before closing the cover, make sure that there is not a conductive foreign material attached on the printed cir-cuit board.
•Be sure to close the cover after setting.
•Be careful not to get your hand or nger caught in the cover.
•Do not force the cover closed. Doing so may result in damage of the electronic components.
14M3LU2 OPERATING MANUAL EM-2653-B Rev.0
7. DIP SWITCH CONFIGURATION
SW1
This chapter describes the conguration of the I/O specications and functions using the DIP switches and the JP2.
For the PC conguration, some DIP switch settings are necessary.
7.1 DIFFERENCE BETWEEN DIP SW CONFIGURATION AND PC CONFIGURATION
The following table shows the difference between the DIP SW conguration and PC conguration.
7.2 DIP SWITCH SELECTION PER I/O SPECIFICATION AND FUNCTION
Congure the DIP switches and JP2 according to your I/O specications and functions.
The unit reads the DIP-switch-calibrated conguration only once after the power supply is turned on. Set the switches with
the power supply removed. Some tools are needed to set the DIP switches and JP2.
•Set the switches and JP2 with the power supply removed.
•Use tweezers or longnose pliers to switch the JP2.
•Use a minus screwdriver with the blade edge 0.8 mm (0.03”) to set the DIP switches.
•Do not touch other electronic components except for the JP2 and DIP switches.
SW2SW3
JP2
15M3LU2 OPERATING MANUAL EM-2653-B Rev.0
7.2.1 CONFIGURATION MODE
With the model M3LU2-x/A, select the conguration mode (conguration method of I/O specications), DIP SW conguration or PC conguration, as shown in the following table. With the model M3LU2-x/B, turn the SW3-8 OFF.
DIP SW conguration: sets I/O specications with the DIP switches inside the cover and the front control buttons.
PC conguration: sets I/O specications with the PC Congurator Software (model: M3LUCFG).
MODESW3-8
DIP SWOFF
PCON
7.2.2 INPUT TYPE (JP2)
Switch the JP2 jumper according to the input specications.
Note that the JP2 setting is required with the PC conguration.
DC VOLTAGE [V] RANGE POSITION
[maximum range: -10 to +10 V DC]
Jumper
12
3
Switch the JP2 jumper to the 2-3 position.Switch the JP2 jumper to the 1-2 position.
NORMAL POSITION
(other than DC voltage [V] range)
Jumper
12
3
7.2.3 INPUT (DIP SWITCHES)
Set the DIP switches (SW2-1 through 2-5, SW3-1 through 3-7) according to the input specications. These settings are not
required with the PC conguration.
7.2.3.1 DC current input
SW3-7SW3-6SW3-5SW3-4SW3-3SW3-2SW3-1
OFFOFFOFFOFFOFFOFFOFF
SW2-5SW2-4SW2-3SW2-2SW2-1
OFFOFFOFFOFFOFF
7.2.3.2 DC voltage input (mV) [maximum range: -1000 to +1000 mV DC]
SW3-7SW3-6SW3-5SW3-4SW3-3SW3-2SW3-1
OFFOFFONOFFOFFOFFOFF
SW2-5SW2-4SW2-3SW2-2SW2-1
Refer to Burnout OFFOFFOFF
•Burnout
BURNOUTSW2-5SW2-4
No burnoutOFFOFF
UpscaleOFFON
DownscaleONON
16M3LU2 OPERATING MANUAL EM-2653-B Rev.0
7.2.3.3 DC voltage input (V) [maximum range: -10 to +10 V DC]
SW3-7SW3-6SW3-5SW3-4SW3-3SW3-2SW3-1
OFFONOFFOFFOFFOFFOFF
SW2-5SW2-4SW2-3SW2-2SW2-1
OFFOFFOFFOFFOFF
7.2.3.4 Thermocouple input
SW3-7SW3-6SW3-5SW3-4SW3-3SW3-2SW3-1
OFFONONRefer to Thermocouple type
SW2-5SW2-4SW2-3SW2-2SW2-1
Refer to Burnout Refer to Cold junction compensationOFFOFF
•Thermocouple type
T/CSW3-4SW3-3SW3-2SW3-1
(PR)OFFOFFOFFOFF
K (CA)OFFOFFOFFON
E (CRC)OFFOFFONOFF
J (IC)OFFOFFONON
T (CC)OFFONOFFOFF
B (RH)OFFONOFFON
ROFFONONOFF
SOFFONONON
C (WRe 5-26)ONOFFOFFOFF
NONOFFOFFON
UONOFFONOFF
LONOFFONON
P (Platinel II)ONONOFFOFF
•Burnout
BURNOUTSW2-5SW2-4
No burnoutOFFOFF
UpscaleOFFON
DownscaleONON
•Cold junction compensation
COLD JUNCTION COMPENSATIONSW2-3
EnableOFF
DisableON
17M3LU2 OPERATING MANUAL EM-2653-B Rev.0
7.2.3.5 RTD input
SW3-7SW3-6SW3-5SW3-4SW3-3SW3-2SW3-1
ONOFFOFFRefer to RTD type
SW2-5SW2-4SW2-3SW2-2SW2-1
Refer to Burnout OFFRefer to RTD wires
•RTD type
RTDSW3-4SW3-3SW3-2SW3-1
Pt 100 (JIS ’97, IEC)OFFOFFOFFOFF
Pt 200OFFOFFOFFON
Pt 300OFFOFFONOFF
Pt 400OFFOFFONON
Pt 500OFFONOFFOFF
Pt 1000OFFONOFFON
Pt 50 Ω (JIS ’81)OFFONONOFF
JPt 100 (JIS ’89)OFFONONON
Ni 100ONOFFOFFOFF
Ni 120ONOFFOFFON
Ni 508.4 ΩONOFFONOFF
Ni-Fe 604ONOFFONON
Cu 10 @25°CONONOFFOFF
•Burnout
BURNOUTSW2-5SW2-4
No burnoutOFFOFF
UpscaleOFFON
DownscaleONON
•RTD wires
WIRESSW2-2SW2-1
2-wireOFFOFF
3-wireOFFON
4-wireONON
18M3LU2 OPERATING MANUAL EM-2653-B Rev.0
7.2.3.6 Resistance input
SW3-7SW3-6SW3-5SW3-4SW3-3SW3-2SW3-1
ONONOFFOFFOFFOFFOFF
SW2-5SW2-4SW2-3SW2-2SW2-1
Refer to Burnout OFFRefer to Resistance wires
•Burnout
BURNOUTSW2-5SW2-4
No burnoutOFFOFF
UpscaleOFFON
DownscaleONON
•Resistance wires
WIRESSW2-2SW2-1
2-wireOFFOFF
3-wireOFFON
4-wireONON
7.2.3.7 Potentiometer input
SW3-7SW3-6SW3-5SW3-4SW3-3SW3-2SW3-1
ONOFFONRefer to Potentiometer (total resistance)
SW2-5SW2-4SW2-3SW2-2SW2-1
Refer to Burnout OFFOFFOFF
•Potentiometer (total resistance)
POTENTIOMETER
(TOTAL RESISTANCE)
2500 to 4000 ΩOFFOFFOFFOFF
1200 to 2500 ΩOFFOFFOFFON
600 to 1200 ΩOFFOFFONOFF
300 to 600 ΩOFFOFFONON
150 to 300 ΩOFFONOFFOFF
80 to 150 ΩOFFONOFFON
SW3-4SW3-3SW3-2SW3-1
•Burnout
BURNOUTSW2-5SW2-4
No burnoutOFFOFF
UpscaleOFFON
DownscaleONON
19M3LU2 OPERATING MANUAL EM-2653-B Rev.0
7.2.4 OUTPUT TYPE
Set the DIP switches (SW1-1 through 1-4, SW2-7 and 2-8) according to the output specications.
The DIP switch settings (SW1-1 through 1-4) are required with the PC conguration.
7.2.4.1 DIP SW conguration
•DC current output
SW1-4SW1-3SW1-2SW1-1SW2-8SW2-7
OFFONOFFOFFOFFOFF
•DC voltage output (narrow spans) [maximum range: -2.5 to +2.5 V DC]
SW1-4SW1-3SW1-2SW1-1SW2-8SW2-7
ONOFFOFFONOFFON
•DC voltage output (wide spans) [maximum range: -10 to +10 V DC]
SW1-4SW1-3SW1-2SW1-1SW2-8SW2-7
ONOFFONOFFONOFF
7.2.4.2 PC conguration
•DC current output
SW1-4SW1-3SW1-2SW1-1
OFFONOFFOFF
•DC voltage output (narrow spans) [maximum range: -2.5 to +2.5 V DC]
SW1-4SW1-3SW1-2SW1-1
ONOFFOFFON
•DC voltage output (wide spans) [maximum range: -10 to +10 V DC]
SW1-4SW1-3SW1-2SW1-1
ONOFFONOFF
7.2.5 FRONT CONTROL BUTTON LOCK
You can lock the button operation on the front panel to prevent inadvertent operation.
LOCKSW2-6
UnlockOFF
LockON
20M3LU2 OPERATING MANUAL EM-2653-B Rev.0
8. WIRING
8mm
8mm
8.1 CAUTION IN WIRING
•Make sure for safety that only qualied personnel performs the wiring.
•In order to prevent potential electric shock, wire the unit after turning off the power supply and making sure that the
power is not supplied to the cable.
•Be sure to conrm the name and polarity of each terminal before wiring to the Euro type connector terminal blocks
(hereafter called ‘terminal block(s)’).
•Take measures to reduce noise as much as possible, e.g. by using shielded twisted pair wires for the input signal.
Ground the input shield to the most stable earth to prevent noise troubles.
•Do not connect anything to unused terminals.
•M-System offers a series of lightning surge protectors for protection against induced lightning surges. Please con-
tact M-System to choose appropriate models.
8.2 WIRING INSTRUCTIONS
■ APPLICABLE WIRE SIZE
•Solid: 0.25 to 2.5 mm
•Stranded: 0.25 to 2.5 mm
2
(0.55 to 1.75 dia.)
2
(0.55 to 1.75 dia.)
8mm
•Tinning wire ends may cause contact failure and therefore is not recommended.
•Expose wire conductors by 8 mm (0.31”).
■ RECOMMENDED FERRULE
The following Phoenix Contact terminals are recommended.
•For single-wire•For twin-wire
CROSS-SECTION AREAMODELCROSS-SECTION AREAMODEL
0.2 to 0.25 mm
0.25 to 0.34 mm
0.34 to 0.5 mm
0.5 to 0.75 mm
0.75 to 1.0 mm
1.0 to 1.5 mm
2
2
2
2
2
2
AI 0,25-8 YE0.34 to 0.5 mm
AI 0,34-8 TQ0.5 to 0.75 mm
AI 0,5-8 WH0.75 to 1.0 mm
AI 0,75-8 GY1.0 to 1.5 mm
AI 1,0-8 RD
AI 1,5-8 BK
2
2
2
2
AI-TWIN 2X 0,5-8 WH
AI-TWIN 2X 0,75-8 GY
AI-TWIN 2X 1,0-8 RD
AI-TWIN 2X 1,5-8 BK
Recommended manufacturer: Phoenix Contact GmbH & Co., KG
21M3LU2 OPERATING MANUAL EM-2653-B Rev.0
■ INSTALLATION/SEPARATION OF TERMINAL BLOCK
•Separation
Insert a minus screwdriver between the terminal block and the housing body, pull up the driver and pull out the terminal
block.
•Installation
Push the terminal block until it clicks into place.
NOTE
Match the terminal numbers of the terminal blocks with those indicated on the transmitter body in installing the blocks (gure on the right).
22M3LU2 OPERATING MANUAL EM-2653-B Rev.0
■ WIRING TO TERMINAL BLOCK
Insert a wire into the dead end of a terminal block and x it with a minus screwdriver with the blade edge 0.6 mm (0.02”)
and the blade width 3.5 mm (0.14”) (torque: 0.5 – 0.6 N∙m).
NOTE
•For a thermocouple input, replace the terminal block (4 – 5 – 6)
with the one connected with the CJC sensor included in the
package. Fasten the input wire and the CJC sensor together
on the terminal 5.
•Do not use a ferrule with insulating sleeve.
•Insert a wire under the CJC sensor (gure on the right).
CJC sensor (model: CJM)
8.3 TERMINAL ASSIGNMENT
Power
Output signal
Input signal
23M3LU2 OPERATING MANUAL EM-2653-B Rev.0
8.4 TERMINAL CONNECTIONS
■ DC POWERED TYPE
DC
VOLT
mA
mV
–+–
■ AC POWERED TYPE
DC
VOLT
mA
mV
–+–
+
+
T/C
ext. wire
+
–
*1
CJC
SENSOR
T/C
ext. wire
+
–
*1
CJC
SENSOR
2-wire
RTD
3-wire
RTD
A
4-wire
RTD
A
B
+
–
B
B
POT.
max.
+
1
A
B
3
2
3
4
min.
2
5
1
–
A
B
7
8
11
12
+
OUTPUT
–
+
DC POWER
–
*2
6
CONFIGURATOR
2-wire
RTD
3-wire
RTD
A
4-wire
RTD
A
B
+
POT.
max.
A
B
A
–
B
B
B
min.
JACK
+
1
3
2
3
4
2
5
1
–
7
8
10
12
+
OUTPUT
–
U
AC POWER
V
*2
6
CONFIGURATOR
JACK
*1 Replace the Euro Type Connector Terminal Block (4 – 5 – 6) with the one connected with the CJC Sensor, included in the package.The CJC Sensor is secured to the terminal 6.Loosen only the terminal 4 – 5 and connect the T/C extension wires.
*2Be aware that the AC power and DC power connect to different terminals.
8.4.1 WIRING INPUT
8.4.1.1 DC voltage/current input
Connect DC voltage or current wires.
DC current inputDC voltage input (V)DC voltage input (mV)
Maximum range: 0 to 20 mA DCMaximum range: -10 to +10 V DCMaximum range: -1000 to +1000m V DC
DC current
Ground
(resistance
100 ohms or less)
DC voltage (V)
Ground
(resistance
100 ohms or less)
DC voltage (mV)
Ground
(resistance
100 ohms or less)
24M3LU2 OPERATING MANUAL EM-2653-B Rev.0
8.4.1.2 Thermocouple input
RTD or resistance
RTD or resistance
RTD or resistance
Connect a thermocouple or extension wires.
Thermocouple input
Extension
T/C
Ground
(resistance
100 ohms or less)
CJC sensor (model: CJM)
Wire
•Wire the unit with the thermocouple using the extension wires with
the same characteristics as the thermocouple.
•The CJC sensor is calibrated to a particular unit and not interchangeable with another. Match the serial No. of the unit and the
sensor (gure on the right).
•Be careful not to change the temperature around the terminal block.
Take care that wind from a fan does not hit it directly.
•Be careful not to separate the CJC sensor from the terminal block.
Do not loosen the screw on the terminal 6. If you did, connect the
CJC sensor to the terminals 5 and 6.
Serial No.
CJC sensor (model: CJM)
8.4.1.3 RTD/resistance input
Connect a RTD or a resistance. Connect according to the RTD/resistance wires.
RTD/resistance input
2-wire3-wire4-wire
Ground
(resistance
100 ohms or less)
Ground
(resistance
100 ohms or less)
Ground
(resistance
100 ohms or less)
•The leadwire resistance including internal resistance such like a lightning surge protector and a barrier must be maximum 20 Ω per wire.
•The excitation is 0.3 mA. Use a RTD with excitation 0.3 mA or more.
25M3LU2 OPERATING MANUAL EM-2653-B Rev.0
8.4.1.4 Potentiometer input
Connect a potentiometer.
Potentiometer input
Potentiometer
Max.
Min.
Ground
(resistance
100 ohms or less)
8.4.2 WIRING OUTPUT
Voltage or current output is provided depending on the output setting.
Output
Output
Ground
(resistance
100 ohms or less)
8.4.3 WIRING POWER
Connect power according to the power input code. The power specications are shown in the following table.
CODERATINGALLOWABLE RANGE & POWER CONSUMPTION
M2100 to 240 V AC85 to 264 V AC, 47 to 66 Hz
Approx. 4 VA at 100 V
Approx. 5 VA at 200 V
Approx. 6 VA at 264 V
R410 to 32 V DC9 to 36 V DC, approx. 3 W
DC powerAC power
AC power
DC power
•Be aware that the AC power and DC power connect to different terminals.
•For DC power, conrm the polarity.
26M3LU2 OPERATING MANUAL EM-2653-B Rev.0
9. INSTALLATION
■ DIN RAIL MOUNTING
Set the unit so that its DIN rail adaptor is at the bottom. Position the upper hook at the rear side of the unit on the DIN rail
and push in the lower.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
■ REMOVAL
Push down the DIN rail adaptor utilizing a minus screwdriver and pull.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
27M3LU2 OPERATING MANUAL EM-2653-B Rev.0
10. CALIBRATION
‘Calibration’ means I/O ranging or output ne adjustments using the front control buttons. M-System’s ‘One-Step-Cal’ calibration technique realizes automatic I/O ranging and adjustment.
This chapter describes ow and operation procedure of the calibration.
You can also carry out the calibration using the PC Congurator Software (model: M3LUCFG). For detailed information,
refer to the M3LUCFG users manual.
10.1 CALIBRATION FLOW
The calibration includes I/O Ranging Mode and Fine Adjustment Mode. Hold down the MODE button to shift each mode
from the RUN Mode. The mode to shift depends on the time to hold down the button.
The following chart shows the calibration ow.
Hold down
Press
Press
Fine Adjustment ?
1 – 2 s
FINE ZERO
ADJUSTMENT MODE
or
FINE SPAN
ADJUSTMENT MODE
or
RUN MODE
*1
Hold down
Press
Press
I/O Ranging ?
INPUT
RANGING
MODE
OUTPUT
RANGING
MODE
Amber LED
Green LED
Red LED
≥ 5s
Apply simulated
0% input signal.
Apply simulated
100% input signal.
Adjust simulated
input until the output
meter shows
desired 0% output.
Adjust simulated
input until the output
meter shows
desired 100% output.
OFF
ON
Blink
Hold down
Hold down
Hold down
Hold down
MODE button
UP button
DOWN button
*2
0% INPUT
CONFIGURED
*2
100% INPUT
CONFIGURED
*2
0% OUTPUT
CONFIGURED
*2
100% OUTPUT
CONFIGURED
RUN MODE
*1
*1 In the RUN Mode, the green LD1 blinks (PC conguration), or turns on (DIP SW conguration).
*2 When you set 0% or 100% input/output ranges, keep pressing UP or DOWN button until the LD1 blinks for approx. 2 seconds and
turns off, which indicates the setup is complete. When you release the button, the LD1 is returned to ON. Therefore hold down the
button until the LD1 turns OFF.
28M3LU2 OPERATING MANUAL EM-2653-B Rev.0
10.2 INPUT & OUTPUT RANGING
After the DIP switch setting is complete, set up the precise input and output range using the front control buttons. Be sure
that the front control button function is enabled with the DIP switch setting (SW2-6 OFF).
10.2.1 OUTLINE OF I/O RANGING
■ PREPARATION
Mount the DIP-SW-congured M3LU2 on to a DIN rail.
Connect the M3LU2 to a simulator and a multimeter and to a power source according to the terminal connections.
■ INPUT RANGING
•In the Input Ranging Mode, apply the desired minimum input level from the simulator and hold down DOWN button
until the LD1 blinks and then turns OFF.
•Then apply the desired maximum input level and hold down UP button until the LD1 blinks and then turns OFF.
[Example 1] Setting input to 0 – 5 V DC
Maximum input range: -10 to +10 V DC
0% input ranging: apply 0 V DC and hold down DOWN button
100% input ranging: apply 5 V DC and hold down UP button
-10 V
0% input ranging
0 V
0 V
Max. input range
Input ranging
+5 V
+10 V
100% input ranging
5 V
NOTE
•Input ranging is not needed in using the default value.
•100% input ranging value must be greater than 0% value.
•Set the input within the maximum range with the minimum span or more. With inappropriate input level, the input rang-
ing is not carried out even in holding down UP or DOWN button. (The LD1 does not change.)
•There is no stated order of setting 0% and 100% levels or no limitations of entering values for multiple times within one
step of Ranging Mode.
•Signal level is not stored when UP or DOWN button is released before the LD1 turns OFF.
29M3LU2 OPERATING MANUAL EM-2653-B Rev.0
■ OUTPUT RANGING
•In the Output Ranging Mode, increase or decrease the simulated input until the meter shows the desired minimum
output level. Hold down DOWN button until the LD1 blinks and then turns OFF.
•Then increase or decrease the simulated input until the meter shows the desired maximum output level. Hold down
UP button until the LD1 blinks and then turns OFF.
[Example 2] Setting output to 0 – 16 mA DC (input 0 – 5 V DC [Example 1])
Maximum output range: 0 – 20 mA DC
0% output ranging: increase or decrease a simulated input until the meter shows 0 mA DC and hold down
DOWN button.
100% output ranging: increase or decrease a simulated input until the meter shows 16 mA DC and hold
down UP button.
-10 V
0% input ranging
0% output ranging
0 V
0 mA
0 mA
0 V
Max. input range
Input ranging
Max. output range
Output ranging
+5 V
+10 V
100% input ranging
5 V
16 mA
20 mA
100% output ranging
16 mA
IMPORTANT
•Use a simulator to adjust the desired output.
•A different signal from that in the input ranging may be applied.
•Increase or decrease a simulated input while conrming the output with a multimeter.
•Even if the input ranging is performed after the output ranging, another output ranging is not needed.
NOTE
•Output ranging is not needed in using the default value.
•100% output ranging value must be greater than 0% value.
•Set the output within the maximum range with the minimum span or more. With inappropriate output level, the output
ranging is not carried out even in holding down UP or DOWN button. (The LD1 does not change.)
•There is no stated order of setting 0% and 100% levels or no limitations of entering values for multiple times within one
step of the Ranging Mode.
•Signal level is not stored when UP or DOWN button is released before the LD1 turns OFF.
30M3LU2 OPERATING MANUAL EM-2653-B Rev.0
10.2.2 MAXIMUM RANGE, MINIMUM SPAN AND DEFAULT VALUE OF INPUT
The maximum range, minimum span and default value of the input are shown in the following tables. The default value
means initial 0% and 100% input when the DIP switch setting is changed.
10.2.2.1 DC current input
MAXIMUM RANGEMINIMUM SPANDEFAULT VALUE
0 to 20 mA DC1 mA4 to 20 mA DC
10.2.2.2 DC voltage input (mV)
MAXIMUM RANGEMINIMUM SPANDEFAULT VALUE
-1000 to +1000 mV DC4 mV0 to 1000 mV DC
10.2.2.3 DC voltage input (V)
MAXIMUM RANGEMINIMUM SPANDEFAULT VALUE
-10 to +10 V DC1 V1 to 5 V DC
10.2.2.4 Thermocouple input
Minimum span: 20°C (36°F)
Default value: same as conformance range in °C
THERMOCOUPLE°C°F
MAXIMUM RANGECONFORMANCE RANGE MAXIMUM RANGECONFORMANCE RANGE
(PR)0 to 17600 to 176032 to 320032 to 3200
K (CA)-270 to +1370-150 to +1370-454 to +2498-238 to +2498
E (CRC)-270 to +1000-170 to +1000-454 to +1832-274 to +1832
J (IC)-210 to +1200-180 to +1200-346 to +2192-292 to +2192
T (CC)-270 to +400-170 to +400-454 to +752-274 to +752
B (RH)100 to 1820400 to 1760212 to 3308752 to 3200
R-50 to +1760200 to 1760-58 to +3200392 to 3200
S-50 to +17600 to 1760-58 to +320032 to 3200
C (WRe 5-26)0 to 23150 to 231532 to 419932 to 4199
N-270 to +1300-130 to +1300-454 to +2372-202 to +2372
U-200 to +600-200 to +600-328 to +1112-328 to +1112
L-200 to +900-200 to +900-328 to +1652-328 to +1652
P (Platinel II)0 to 13950 to 139532 to 2543 32 to 2543
31M3LU2 OPERATING MANUAL EM-2653-B Rev.0
10.2.2.5 RTD input
Minimum span: 20°C (36°F)
Default value: same as maximum range in °C
RTD°C°F
MAXIMUM RANGEMAXIMUM RANGE
Pt 100 (JIS ’97, IEC)-200 to +850-328 to +1562
Pt 200-200 to +850-328 to +1562
Pt 300-200 to +850-328 to +1562
Pt 400-200 to +850-328 to +1562
Pt 500-200 to +850-328 to +1562
Pt 1000-200 to +850-328 to +1562
Pt 50 Ω (JIS ’81)-200 to +649-328 to +1200
JPt 100 (JIS ’89)-200 to +510-328 to +950
Ni 100-80 to +260-112 to +500
Ni 120-80 to +260-112 to +500
Ni 508.4 Ω-50 to +200-58 to +392
Ni-Fe 604-200 to +200-328 to +392
Cu 10 @25°C-50 to +250-58 to +482
10.2.2.6 Resistance input
MAXIMUM RANGEMINIMUM SPANDEFAULT VALUE
0 to 4000 Ω10 Ω0 to 4000 Ω
10.2.2.7 Potentiometer input
MAXIMUM RANGE
(TOTAL RESISTANCE)
2500 to 4000 Ω2% of total resistance0 to 100%
1200 to 2500 Ω
600 to 1200 Ω
300 to 600 Ω
150 to 300 Ω
80 to 150 Ω
MINIMUM SPANDEFAULT VALUE
10.2.3 MAXIMUM RANGE, MINIMUM SPAN AND DEFAULT VALUE OF OUTPUT
The maximum range, minimum span and default value of the output are shown in the following tables. The default value
means initial 0% and 100% output when the DIP switch setting is changed.
10.2.3.1 DC current output
MAXIMUM RANGEMINIMUM SPANDEFAULT VALUE
0 to 20 mA DC1 mA4 to 20 mA DC
10.2.3.2 DC voltage output (narrow spans)
MAXIMUM RANGEMINIMUM SPANDEFAULT VALUE
-2.5 to +2.5 V DC250 mV0 to 1 V DC
10.2.3.3 DC voltage output (wide spans)
MAXIMUM RANGEMINIMUM SPANDEFAULT VALUE
-10 to +10 V DC1 V1 to 5 V DC
32M3LU2 OPERATING MANUAL EM-2653-B Rev.0
10.2.4 OPERATION PROCEDURE OF I/O RANGING
Perform the I/O ranging in the following procedure.
In the RUN Mode, hold down MODE button for 5 seconds or more until the LD1 red LED is ON.
1
Green ON
or
blinking
5 sec. or more
•Conrm that the LD1 green LED is ON (DIP SW conguration) or blinking (PC conguration). Then hold down
MODE button for 5 seconds or more until the LD1 red LED is ON.
•The LD2 red LED starts blinking indicating the Input Ranging Mode.
Apply the desired minimum input level and hold down DOWN button until the LD1 turns OFF.
Red ON
Red blinking
2
Red ON
Red blinking
•Hold down DOWN button, and the LD1 red LED blinks in approx. 2 sec. and then turns OFF in approx. 2 sec.
•The LD1 turning OFF means completion of 0% input ranging. Hold down DOWN button until the LD1 turns OFF.
•Skip to the next procedure when 0% input ranging is not necessary.
Apply the desired maximum input level and hold down UP button until the LD1 turns OFF.
Rapid
red blinking
Approx. 2 sec.
OFFRed ON
Approx. 2 sec.
Release button
0% input ranging completed
3
Red ON
Red blinking
Rapid
red blinking
Approx. 2 sec.Approx. 2 sec.
OFF
Red ON
Release button
100% input ranging completed
•Hold down UP button, and the LD1 red LED blinks in approx. 2 sec. and then turns OFF in approx. 2 sec.
•The LD1 turning OFF means completion of 100% input ranging. Hold down UP button until the LD1 turns OFF.
•Skip to the next procedure when 100% input ranging is not necessary.
33M3LU2 OPERATING MANUAL EM-2653-B Rev.0
Press MODE button to go on to the Output Ranging Mode.
4
Red ON
Red blinking
Press once
•Press MODE button once to go on to the Output Ranging Mode.
•The LD2 turns OFF and the LD3 red LED starts blinking indicating the Output Ranging Mode.
Increase or decrease the simulated input until the meter shows the desired minimum output level. Hold
down DOWN button until the LD1 turns OFF.
5
OFF
Red blinking
Red ONRed ONOFF
Red blinking
•Hold down DOWN button, and the LD1 red LED blinks in approx. 2 sec. and then turns OFF in approx. 2 sec.
•The LD1 turning OFF means completion of 0% output ranging. Hold down DOWN button until the LD1 turns OFF.
•Skip to the next procedure when 0% output ranging is not necessary.
Increase or decrease the simulated input until the meter shows the desired maximum output level. Hold
down UP button until the LD1 turns OFF.
6
Red ON
Red blinking
Rapid
red blinking
Approx. 2 sec.Approx. 2 sec.
Rapid
red blinking
Approx. 2 sec.Approx. 2 sec.
OFF
Release button
0% ouput ranging completed
Red ON
Release button
100% ouput ranging completed
•Hold down UP button, and the LD1 red LED blinks in approx. 2 sec. and then turns OFF in approx. 2 sec.
•The LD1 turning OFF means completion of 100% output ranging. Hold down UP button until the LD1 turns OFF.
•Skip to the next procedure when 100% output ranging is not necessary.
34M3LU2 OPERATING MANUAL EM-2653-B Rev.0
Press MODE button to return to the RUN Mode.
7
Green ON
Red ON
Red blinking
Press once
•Press MODE button once to return to the RUN mode.
•The LD3 turns OFF and the LD1 green LED is ON (DIP SW conguration) or blinking (PC conguration).
or
blinking
OFF
35M3LU2 OPERATING MANUAL EM-2653-B Rev.0
10.3 FINE ADJUSTMENT MODE
Perform the ne zero and span adjustments to correct the deviation between the output signal and a device on site. Be
sure that the front control button function is enabled with the DIP switch setting (SW2-6 OFF).
Note that M-System does not warrant the adjustments by the customer.
Each time the adjustment is performed, signal level is overwritten and is stored even when the power is off.
10.3.1 OUTLINE OF FINE ADJUSTMENT
The following owchart shows the ne zero/span adjustments.
POWER ON
Warming up (10 min. or more)
Moving on to output ne zero adjustment
Adjusting output with UP/DOWN buttons
Moving on to output ne span adjustment
Adjusting output with UP/DOWN buttons
Readjustment
Conrming output value
(operation check)
Adjustment completed
Measurement started
NOTE
•Warm up measuring instruments, equipment and other devices on site for the time specied in each manual, and operate the unit in a stable condition.
•Adjustable ranges are as follows:
Fine zero adjustment -15 to +15%
Fine span adjustment 85 to 115%
36M3LU2 OPERATING MANUAL EM-2653-B Rev.0
10.3.2 OPERATION PROCEDURE OF FINE ADJUSTMENT
Perform the ne adjustment in the following procedure.
Hold down MODE button for 1 to 2 seconds and release the button to go on to the Fine Zero Adjustment
Mode.
1
Green ON
or
blinking
•Conrm that the LD1 green LED is ON (DIP SW conguration) or blinking (PC conguration). Then hold down
MODE button for 1 to 2 seconds and release the button. The LD1 red LED will be ON.
•The LD2 green LED starts blinking indicating the Fine Zero Adjustment Mode.
Use UP (increase) and DOWN (decrease) buttons to adjust the output to 0%. Check the output with a multim-
eter.
2
Hold down
for 1 to 2 sec.
Release button
Output
Red ON
Green blinking
Increase output
Decrease output
•Adjust the output value to 0% regardless of the input.
•Increase the output with UP button, and decrease with DOWN.
•Skip to the next procedure when ne zero adjustment is not necessary.
Press MODE button to go on to the Fine Span Adjustment Mode.
UP (increase)
DOWN (decrease)
↑
↓
Input
3
Red ON
Green blinking
Green blinking
Press once
•Press MODE button once to go on to the Fine Span Adjustment Mode.
•The LD2 turns OFF and the LD3 green LED starts blinking indicating the Fine Span Adjustment Mode.
OFF
37M3LU2 OPERATING MANUAL EM-2653-B Rev.0
Use UP (increase) and DOWN (decrease) buttons to adjust the output to 100%. Check the output with a mul-
↑
timeter.
4
Output
Increase output
UP (increase)
DOWN (decrease)
↓
Decrease output
•Adjust the output value to 100% regardless of the input.
•Increase the output with UP button, and decrease with DOWN.
•Skip to the next procedure when ne span adjustment is not necessary.
Press MODE button to return to the RUN mode.
Input
5
Red ON
Green blinking
Press once
•Press MODE button once to return to the RUN Mode.
•The LD3 turns OFF and the LD1 green LED is ON (DIP SW conguration) or blinking (PC conguration).
Green ON
or
bllinking
OFF
38M3LU2 OPERATING MANUAL EM-2653-B Rev.0
11. CHECKING, MAINTENANCE, INITIALIZATION OF PARAMETERS
11.1 CHECKING
(1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
(2) DIP SW setting: Check that the switches are set to appropriate positions.
(3) Power input voltage: Check voltage across the terminal 10 – 12 (AC) or 11 – 12 (DC) with a multimeter.
(4) Input: Check that the input signal is within 0 to 100% of full-scale.
If the DC voltage (mV), thermocouple, RTD, resistance, potentiometer input or their extension wires is/are disconnected, the output goes over 100% (below 0% with downscale protection) due to burnout function. Conrm the status
indicator LED pattern and check leadwires in such a case.
(5) Output: Check that the load resistance meets the described specications.
11.2 MAINTENANCE
Perform the periodic calibration as stated below.
■ CALIBRATION
Warm up the unit for 10 minutes or more, apply 0, 25, 50, 75 and 100% input to the unit, and make sure that the output
is 0, 25, 50, 75 and 100% respectively within the prescribed accuracy. In case the output is deviated from the accuracy,
perform the ne zero/span adjustment.
11.3 INITIALIZATION OF PARAMETERS
You can reset the DIP-SW-congured parameters (I/O ranging and ne adjustments) to the default status. Reset the parameters in the following procedure.
(1) Turn off the power supply to the unit, open the housing cover and set the SW2-1 to OFF and SW2-2 to ON position.
(2) Close the cover and turn on the power while pressing MODE button.
(3) Wait until green LED blinks at the LD1, LD2 and LD3.
(4) Turn off the power, open the cover and reset the SW2-1 and SW2-2 to the previous position.
(5) Close the cover and turn on the power again.
39M3LU2 OPERATING MANUAL EM-2653-B Rev.0
12. APPENDICES
12.1 SPECIFICATIONS
12.1.1 GENERAL SPECIFICATIONS
ConstructionSmall-sized front terminal structure
ConnectionEuro type connector terminal
Housing materialFlame-resistant resin (gray)
IsolationInput to output to power
Overrange output-15 to +115% (negative current output is not available)
Zero adjustment-15 to +15% (front)
Span adjustment85 to 115% (front)
Burnout (other than current or voltage (V) input)Upscale, downscale or no burnout selectable; Also detects wire breakdown and
overrange input exceeding the electrical design limit for DC input.
Linearization (T/C, RTD input)Standard
Cold junction compensation (T/C input)CJC sensor (included) to be attached to the input terminals
Status indicator LEDTri-color (green/amber/red) LED; Blinking patterns indicate operation status of the
RTD (2-wire, 3-wire or 4-wire)Excitation: ≤ 0.3 mA
Maximum range: refer to Table 3
Allowable leadwire resistance: max. 20 Ω per wire
Minimum span: refer to Table 3
Resistance (2-wire, 3-wire or 4-wire)Excitation: ≤ 0.3 mA
Maximum range: 0 to 4000 Ω
Allowable leadwire resistance: max. 20 Ω per wire
Minimum span: 10 Ω
PotentiometerExcitation: ≤ 0.3 mA
Maximum range: refer to Table 5
Allowable leadwire resistance: max. 20 Ω per wire
Minimum span: 2%
40M3LU2 OPERATING MANUAL EM-2653-B Rev.0
12.1.3 OUTPUT SPECIFICATIONS
Output types and ranges are shown in the following table.
DC CurrentMaximum range: 0 – 20 mA DC
Minimum span: 1 mA
Conformance range: 0 – 23 mA DC
Offset: Lower range can be any specic value within the output range provided
that the minimum span is maintained.
Load resistance: Output drive 15 V max. at 20 mA
(Range: Load resistance)
0 – 20 mA : ≤ 750 Ω
DC VoltageNarrow spans
Maximum range: -2.5 – +2.5 V DC
Minimum span: 250 mV
Conformance range: -3 – +3 V DC
Wide spans
Maximum range: -10 – +10 V DC
Minimum span: 1 V
Conformance range: -11.5 – +11.5 V DC
Offset: Lower range can be any specic value within the output range provided
that the minimum span is maintained.
Load resistance: Output drive 10 mA max.; 5 mA for negative output
(Range: Load resistance)
0 – 10 V : ≥ 1 kΩ
-10 – 0 V : ≥ 2 kΩ
0 – 2.5 V : ≥ 250 Ω
-2.5 – 0 V : ≥ 500 Ω
12.1.4 INSTALLATION
Power comsumptionAC powerM2: 100 – 240 V ACOperational voltage range 85 – 264 V AC, 47 – 66 Hz
Approx. 4 VA at 100 V
Approx. 5 VA at 200 V
Approx. 6 VA at 264 V
DC powerR4: 10 – 32 V DCOperational voltage range 9 – 36 V DC
Ripple 10% p-p max.
Approx. 3 W
Operating temperature-25 to +60°C (-13 to +140°F)
Operating humidity30 to 95% RH (non-condensing)
MountingDIN rail
Weight100 g (3.53 oz)
12.1.5 PERFORMANCE
AccuracySee Table 1 to 6.
Cold junction compensation error±1.0°C at 0 – 50°C (±1.8°F at 32 – 122°F)
Temp. coefficient±0.015%/°C [±0.008%/°F] at -5 to +55°C [23 to 131°F] of max. range
±0.03%/°C [±0.016%/°F] for the following conditions:
(With the Option A, the Sync Filter set to the fastest frequency on the PC Congurator Software. Default is set to have 0.5 sec. response.)
Burnout response≤ 10 sec.
Line voltage effect±0.1% over voltage range
Insulation resistance≥ 100 MΩ with 500 V DC
Dielectric strength2000 V AC @ 1 minute (input to output to power to ground)
41M3LU2 OPERATING MANUAL EM-2653-B Rev.0
12.1.6 STANDARDS & APPROVALS
EU conformityEMC Directive (2004/108/EC)
EMI EN 61000-6-4: 2007/A1: 2011
EMS EN 61000-6-2: 2005
Low Voltage Directive (2006/95/EC)
EN 61010-1: 2010
Installation Category II
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
12.1.7 I/O TYPE, MAXIMUM RANGE & ACCURACY
[Table 1] DC input
INPUT TYPEMINIMUM SPANMAXIMUM RANGE
ACCURACY
DC Current1 mA0 to 20 mA DC±0.1%
DC Millivolt4 mV-1000 to +1000 mV DC±10 μV at F.S. input ≤ 50 mV
±40 μV at F.S. input ≤ 200 mV
±60 μV at F.S. input ≤ 500 mV
±80 μV at F.S. input > 500 mV
DC Voltage1 V-10 to +10 V DC±0.1%
*1 Or ±0.1% of span, whichever is greater.
[Table 2] Thermocouple input
T/C°C°F
MIN.
SPAN
MAXIMUM
RANGE
ACCURACY
*2
CONFORMANCE
RANGE
MIN.
SPAN
MAXIMUM
RANGE
(PR)200 to 1760±1.000 to 17603632 to 3200±1.8032 to 3200
K (CA)20-270 to +1370±0.25-150 to +137036-454 to +2498 ±0.45-238 to +2498
E (CRC)20-270 to +1000±0.20-170 to +100036-454 to +1832±0.36-274 to +1832
J (IC)20-210 to +1200±0.25-180 to +120036-346 to +2192±0.45-292 to +2192
T (CC)20-270 to +400±0.25-170 to +40036-454 to +752±0.45-274 to +752
B (RH)20100 to 1820±0.75400 to 176036212 to 3308±1.35752 to 3200
R20-50 to +1760±0.50200 to 176036-58 to +3200±0.90392 to 3200
S20-50 to +1760±0.500 to 176036-58 to +3200±0.9032 to 3200
C (WRe 5-26)200 to 2315±0.250 to 23153632 to 4199±0.4532 to 4199
N20-270 to +1300±0.30-130 to +130036-454 to +2372±0.54-202 to +2372
U20-200 to +600±0.20-200 to +60036-328 to +1112±0.36-328 to +1112
L20-200 to +900±0.25-200 to +90036-328 to +1652±0.45-328 to +1652
P (Platinel II)200 to 1395±0.250 to 13953632 to 2543±0.4532 to 2543
*2 [Accuracy + Cold Junction Compensation Error 1.0°C (1.8°F)] or ±0.1% of span, whichever is greater.
*1
ACCURACY
*2
CONFORMANCE
RANGE
42M3LU2 OPERATING MANUAL EM-2653-B Rev.0
[Table 3] RTD input
RTD°C°F
*3
MIN. SPANMAXIMUM RANGE
ACCURACY
MIN. SPANMAXIMUM RANGE
ACCURACY
Pt 100 (JIS ’97, IEC)20-200 to +850±0.1536-328 to +1562±0.27
Pt 20020-200 to +850±0.1536-328 to +1562±0.27
Pt 30020-200 to +850±0.1536-328 to +1562±0.27
Pt 40020-200 to +850±0.1536-328 to +1562±0.27
Pt 50020-200 to +850±0.1536-328 to +1562±0.27
Pt 100020-200 to +850±0.1536-328 to +1562±0.27
Pt 50 Ω (JIS ’81)20-200 to +649±0.1536-328 to +1200±0.27
JPt 100 (JIS ’89)20-200 to +510±0.1536-328 to +950±0.27
Ni 10020-80 to +260±0.1536-112 to +500±0.27
Ni 12020-80 to +260±0.1536-112 to +500±0.27
Ni 508.4 Ω20-50 to +200±0.1536-58 to +392±0.27
Ni-Fe 60420-200 to +200±0.1536-328 to +392±0.27
Cu 10 @25°C20-50 to +250±0.5036-58 to +482±0.90
*3 Or ±0.1% of span, whichever is greater.
[Table 4] Resistance input
MINIMUM SPANMAXIMUM RANGE
ACCURACY
*4
10 Ω0 to 4000 Ω±0.1 Ω
*4 Or ±0.1% of span, whichever is greater.
*3
[Table 5] Potentiometer input
MINIMUM SPANMAXIMUM RANGE
ACCURACY
*5
(TOTAL RESISTANCE)
2%2500 to 4000 Ω
±0.1 Ω
1200 to 2500 Ω
600 to 1200 Ω
300 to 600 Ω
150 to 300 Ω
80 to 150 Ω
*5 Or ±0.1% of span, whichever is greater.
[Table 6] Output
OUTPUT TYPEMINIMUM SPANMAXIMUM RANGECONFORMANCE RANGE
DC Current
1 mA
*6
0 to 20 mA DC
0 to 23 mA DC
*7
DC Voltage250 mV-2.5 to +2.5 V DC-3 to +3 V DC
1 V-10 to +10 V DC-11.5 to +11.5 V DC
*6 For current output, overall accuracy degrades another 0.1% with spans ≤ 2 mA.
*7 Negative overrange current below 0 mA is not available.
The I/O settings and calibration are congurable with the PC Congurator Software (model: M3LUCFG). It is convenient
to set the same I/O specications to several units or the items which are not available with the DIP SW conguration or
‘One-Step Cal’ calibration. Whether the I/O settings are available or not depends on the conguration option code and
conguration mode.
A dedicated cable is required to connect the unit to the PC.
PORTPC CONFIGURATOR CABLE MODEL NO.
RS-232-CMCN-CON
USBCOP-US
The PC Congurator Software is freely downloadable at M-System’s web site (http://www.m-system.co.jp/).
Software download model No.: M3CFG
■ I/O CONFIGURATION
The following table shows congurable items with the PC Congurator Software. For detailed information on the PC conguration, refer to the M3LUCFG users manual (EM-9197-A).
ITEMM3LU2-x/AM3LU2-x/B
PC CONFIGURATION
(SW3-8 ON)
Input typeX--------
Sensor wiresX--------
PV range (upper, lower)X--------
PV damping (time constant)XX----
BurnoutX--------
Cold junction compensationX--------
Transfer functionXX----
AO typeX--------
AO range (upper, lower)X--------
ADC conversion rateXXX
Custom TCX--------
Custom RTDX--------
Linearization table settingXX----
DIP SW CONFIGURATION
(SW3-8 OFF)
■ CALIBRATION
‘One-Step Cal’ calibration (I/O ranging) and DAC trimming (ne adjustments) are congurable with the PC Congurator
Software regardless of the conguration option code and conguration mode.
■ REMARKS
For detailed information on the PC conguration, refer to the M3LUCFG users manual (EM-9197-A).
45M3LU2 OPERATING MANUAL EM-2653-B Rev.0
12.3 MODEL NUMBERING
Code number: M3LU2–[1]/[2][3]
INPUT – Field-selectable
DC Current & Voltage
Current: 0 – 20 mA DC
Millivolt: -1000 – +1000 mV DC
Voltage: -10 – +10 V DC
Thermocouple
(PR), K, E, J, T, B, R, S, C (WRe 5-26), N, U, L, P (Platinel II)
RTD
Pt 100, Pt 200, Pt 300, Pt 400, Pt 500, Pt 1000, Ni 100, Ni 120, Ni 508.4 Ω, Ni-Fe 604, Cu 10 @25°C,
Pt 50 Ω, JPt 100
Potentiometer
Total resistance 80 – 4000 Ω
Resistance
0 – 4000 Ω
OUTPUT – Field-selectable
Current
0 – 20 mA DC
Voltage
-2.5 – +2.5 V DC
-10 – +10 V DC
[1] POWER INPUT
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz)
DC Power
R4: 10 – 32 V DC (Operational voltage range 9 – 36 V, ripple 10% p-p max.)
[2] CONFIGURATION OPTIONS
A: PC and eld congurable
B: Field congurable
[3] OPTIONS
blank: none
/Q: With options (specify the specication)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System’s web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
46M3LU2 OPERATING MANUAL EM-2653-B Rev.0
12.4 EXTERNAL DIMENSIONS
10 11 12
789
DIN RAIL
35mm wide
mm (inch)
106 (4.17)
123
456
7
CJC SENSOR
(model: CJM)
* Used only with a thermocouple input
*
18 (.71)
62 (2.44)
(.28)
110.5 (4.35)
[5 (.20)]
• When mounting, no extra space is needed between units
47M3LU2 OPERATING MANUAL EM-2653-B Rev.0
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.