M-System KS2V3 Data Sheet

MODEL: KS2V3
http://www.m-system.co.jp/ KS2V3 SPECIFICATIONS ES-3603 Rev.1 Page 1/5

Plug-in Signal Conditioners K-UNIT

50 (1.97)
110 (4.33)
70 (2.76)
mm (inch.)

DC INPUT LIMIT ALARM

(digital adjustments; dual alarm trip; w/o burnout) Functions & Features
• Providing relay contact closures at preset DC input levels
• Front digital displays
• Programmable with front keys
• Alarm relay switching delay time 999 sec. max.
Typical Applications
• Various alarm applications

[2] OPTIONS (multiple selections)

Standards & Approvals
blank: CE marking /UL: UL approval, CE marking
Other Options
blank: none /Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet (No. ESU-3603)

RELATED PRODUCTS

• Resistor module (model: REM) 500 Ω for 2 – 10 mA DC 250 Ω for 4 – 20 mA DC 100 Ω for 10 – 50 mA DC

MODEL: KS2V3–61–[1][2]

ORDERING INFORMATION

• Code number: KS2V3-61-[1][2] Specify a code from below for each [1] and [2]. (e.g. KS2V3-61-R/UL/Q)
• Specify the specification for option code /Q (e.g. /SET)

INPUT

Voltage
6: 1 – 5 V DC (Use a resistor module for current input)

OUTPUT

1: Relay; SPDT or transfer contact

[1] POWER INPUT

AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
MODEL: KS2V3
http://www.m-system.co.jp/ KS2V3 SPECIFICATIONS ES-3603 Rev.1 Page 2/5

GENERAL SPECIFICATIONS

Param.
Code (P-A1) (P-A2)
Trip
Operation
1
Set Value
Latching
Hold
Relay & LED
Behavior in
Tripped Conditions
High
Absolute
Val ue
*
*Without latching hold function, the unit is tripped upon starting
operation when the unit is set to Low alarm. With the function, the unit is NOT tripped until the temperature goes once above and then below the setpoint.
Alarm Modes
0
No alarm
Without
LED ON
Coil energized
2
Low
Absolute
Val ue
Without
LED ON
Coil energized
3
High
Absolute
Val ue
With
LED ON
Coil energized
4
Low
Absolute
Val ue
With
LED ON
Coil energized
5
High
Absolute
Val ue
Without
LED ON
Coil de-energized
6
Low
Absolute
Val ue
Without
LED ON
Coil de-energized
7
High
Absolute
Val ue
With
LED ON
Coil de-energized
8
Low
Absolute
Val ue
With
LED ON
Coil de-energized
Construction: Panel flush mounting, plug-in Connection: M3.5 screw terminals Housing material: Flame-resistant resin (gray) Isolation: Input to SET1 to SET2 to power Time constant for the input filter (P-dF): 0.0 to 900.0 sec. (0 – 63 %) Alarm relay switching delay time (P-d1, P-d2): 1 to 999 sec.; programmable independently for each setpoint Programming: Front key Setpoint adjustment (ST1, ST2): -5 to +105 %; programmable independently for each setpoint Deadband (hysteresis) (HYS1, HYS2): 0 – 102 %; programmable independently for each setpoint Power ON delay (P-d0): 0 to 20 sec. Read rate: 0.5 sec. Alarm mode (P-A1, P-A2): Programmable independently for each setpoint; See Table below.
Power indicator: Green LED turns on while the power is turned on. Measured Value (PV) indicator: Green LED turns on when PV display is set. Alarm SET1 indicator: Red LED turns on when the Alarm SET1 is in tripped conditions. Alarm SET2 Indicator: Red LED turns on when the Alarm SET2 is in tripped conditions. Engineering unit indication: Sticker label attached; DC, AC, W, °C, °F, V, mV, A, mA, %, kW, mW, kV, kA, kvar, Mvar, var, m, mm, kg, kg/h, kPa, MPa, N·m, Nm3/h, m3/h, m3/sec, m/sec, l/min, %RH, l, l/h, t/h, rpm, ppm, pH, Pa.

INPUT SPECIFICATIONS

■ DC Voltage: -5 – +105 % Input resistance: ≥ 1 MΩ

OUTPUT SPECIFICATIONS

■ Relay Contact: SPDT relays 220 V AC @3 A (cos ø = 1) 30 V DC @3 A (resistive load) Caution: N.O. and N.C. contacts could be conductive at the same time. DO NOT connect both contacts at the same time. Maximum switching voltage: 220 V AC or 30 V DC Maximum switching power: 660 VA or 90 W Minimum load: 10 V DC @1 mA Mechanical life: 2 × 107 cycles with no loads For maximum relay life with inductive loads, external protection is recommended.

INSTALLATION

Power consumption
•AC: Approx. 3.1 VA at 100 V Approx. 4.1 VA at 200 V Approx. 4.8 VA at 264 V
•DC: Approx. 1.7 W Operating temperature: -10 to +55°C or 14 to 131°F (-10 to +50°C or 14 to 122°F for UL) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Panel flush mounting with attached mounting bracket, surface or DIN rail Weight: 200 g (0.44 lb)

PERFORMANCE

Display accuracy: ±0.5% FS ±1 digit Setpoint accuracy: Display accuracy ± 0.1 % FS Trip point repeatability: Included in the setpoint accuracy

DISPLAY

Display: 4 digits of 10 mm (.39”) height, 7-segment LED Scaling range: -1999 to 9999 counts Measured Value (PV)/Alarm (SET1) display: Red LEDs Alarm (SET2) parameter display: Green LEDs PV display at abnormal input: Over range or under range displayed Front LEDs
Loading...
+ 3 hidden pages