M-system AYDV Instruction Manual

AYDV
P. 1 / 3 EM-1615 Rev.6
BEFORE USE ....
Thank you for choosing M-System. Before use, check the package you received as below. If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
Signal conditioner (body + base socket + input resistor)
(1)
Input resistor is provided only with current input type.
MODEL NO.
Check that model No. described on specification label is exactly what you ordered.
INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, installation, connection and basic mainte­nance procedures.
COMPONENT IDENTIFICATION
INSTRUCTION MANUAL
MODEL
AYDV
DEVIATION ALARM
Input Resistor
• Explanations
Setpoint 1 and Setpoint 2 Adjustments are used to set the alarm setpoints. A -5 – +5V DC is output at the setpoint monitor jacks across the COM jack, proportional to the setpoint -50 – +50%. The LED lights turn on when the coil for each relay is energized.
• Examples
For setting the setpoint 1 relay to trip above 20% deviation, turn Setpoint 1 Adj. until you read 2.0V at Setpoint 1 Monitor.
INSTALLATION
Detach the yellow clamps lo­cated at the top and bottom of the unit for separating the body from the base socket.
DIN RAIL MOUNTING
Set the base socket so that its DIN rail adaptor is at the bot­tom. Position the upper hook at the rear side of base socket on the DIN rail and push in the lower. When removing the socket, push down the DIN rail adaptor utilizing a screw­driver (–) and pull.
WALL MOUNTING
Refer to the drawings in the following page.
Clamp
(top & bottom)
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
Shape and size of the base socket are slightly different with various socket types.
FRONT PANEL CONFIGURATION
AYDV
M•UNIT
Model
DEVIATION ALARM
SET MONITOR
-5–+5V(-50–+50%) No.1
No.2
COM
No.1 SET
No.2 SET
Body
Specification
Label
Base Socket
Setpoint 1 Adj. & LED
Setpoint 2 Adj. & LED
Setpoint 2 Monitor
Setpoint 1 Monitor
COM.
AYDV
P. 2 / 3 EM-1615 Rev.6
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram label on the front of the unit. When an input resistor is provided with the module, attach it together with input wiring to the input screw terminals.
DIMENSIONS mm (inch)
CONNECTION DIAGRAM TERMINAL ASSIGNMENTS mm (inch)
80 (3.15)
50 (1.97) 103 (4.06)
132 (5.20)
20
(.79)
•When mounting, no extra space is needed between units.
5678
21
1110
[3.3 (.13)]
80 (3.15)
35.4 (1.39)
40 (1.57) 50 (1.97)
7.8 (.31)
CLAMP (top & bottom)
DIN RAIL 35mm wide
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
11–M3.5
SCREW
39
4
78
21
1110
39
4
12 (.47)
INPUT RESISTOR
(model: REM)
56
Input shunt resistor attached for current input.
*
7 8
10
11
9
2
3
1
+ –
INPUT 1 (meas)
5 6
R
+
4
INPUT 2 (ref)
U(+) V(–)
POWER
**
**
* Input shunt resistor attached for current input. ** Rela
y
status for output code “1”, at power OFF.
OUTPUT 2
OUTPUT 1
HI LO COM HI LO COM
AYDV
P. 3 / 3 EM-1615 Rev.6
CHECKING
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal 7 –␣ 8 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of the full-scale.
4) Alarm operations: Check the alarm operations referring to the figure below.
4) Output load: Check that the output load is 380V AC/ 100VA or 125V DC/30W at the maximum. For maximum relay life with inductive load, external protection is recom­mended.
ALARM RELAY OPERATIONS
Trip Operation in Power Failure
Output 1: (9 – 10) turn ON with code 1
(9 – 11) turn ON with code 2
Output 2: (1 – 2) turn ON with code 1
(1 – 3) turn ON with code 2
POINTS OF CAUTION
GENERAL
• Before you remove the unit from its base socket or mount it, turn off the power supply and input signal for safety.
ENVIRONMENT
• When heavy dust or metal particles are present in the air, install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous vibration. Do not apply physical impact to the unit.
• Environmental temperature must be within -5 to +60°C (23 to 140°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
WIRING
• Do not install cables (power supply, input and output) close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
AND ....
• The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
MAINTENANCE
Regular calibration procedure is explained below:
CALIBRATION
Warm up the unit for at least 10 minutes.
• Hi Setpoint Increase the input signal from a value lower than the setpoint and check that the relay trips at the Hi setpoint (Measure the voltage at the Hi setpoint monitor jacks).
• Lo Setpoint Decrease the input signal from a value higher than the setpoint and check that the relay trips at the Lo setpoint (Measure the voltage at the Lo setpoint monitor jacks). When the setpoints are shifted, recalibrate the unit according to the "ADJUSTMENT PROCEDURE" explained earlier.
0 50 100
Input (%)
Output 2 Setpoint
Output 1 Setpoint
Output 1
(9-10)ON
Output 2
(1-2)ON
(1-3)ON
(9-11)ON
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies, under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice. THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES OF ANY KIND WHATSOEVER. M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: info@m-system.co.jp