Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Multi power monitor
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
The 53U is programmable either by using the front control buttons or the PC Configurator Software. For detailed
information on the PC configuration, refer to the PMCFG
users manual. The PMCFG PC Configurator Software is
downloadable at M-System’s web site.
http://www.m-system.co.jp
Availability of certain functions explained in this manual
depends upon hardware options and firmware versions.
Those limited ones are identified with the following markings.
• Do not install the unit where it is directly exposed to rain,
water droplets or sunlight.
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not apply physical impact to the unit.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 90% RH in
order to ensure adequate life span and operation.
• Contrast of the LCD screen depends upon viewing angles.
Choose the height and angle where it is the most legible.
• Do not apply physical impact to the front face.
• To ensure the designated ingress protection, insert the
gasket as shown below before attaching the mounting
brackets.
POINTS OF CAUTION
■ CONFORMITY WITH EC DIRECTIVES
• This equipment is suitable for use in a Pollution Degree
2 environment and in Installation Category III, with the
maximum operating voltage of 550V between signal input and output or power and 300V between output and
power.
Prior to installation, check that the insulation class of this
unit satisfies the system requirements.
• Altitude up to 2000 meters
• The equipment must be mounted inside a panel.
• Insert a noise filter for the power source connected to the
unit. Cosel Noise Filter Model NAC-06-472 or equivalent
is recommended.
■ POWER INPUT RATING & OPERATIONAL RANGE
Locate the power input rating marked on the product and
confirm its operational range as indicated below.
100 – 240V AC rating: 85 – 264V AC, 47 – 66 Hz, <8VA
110 – 240V DC rating: 99 – 264V DC, <4W
■ GENERAL PRECAUTION
Before you remove or mount the unit, turn off the power
supply and input signal for safety.
■ WIRING
• Wiring to the unit must be conducted by qualified service
personnel.
• Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
The unit is designed to function as soon as power is supplied, however, a warm up for 30 minutes is required for satisfying complete performance described in the data sheet.
LIGHTNING SURGE PROTECTION
In order to protect the unit from lightning surges entering
through signal and power supply cables, use of appropriate
lightning surge protectors are recommended. Please contact M-System.
P. 2 / 49EM-6485-B Rev.12
COMPONENT IDENTIFICATION
■ FRONT VIEW■ REAR VIEW
Data Displays
Control Buttons
Current Input
Terminals
Configurator
Jack
Power Input
Terminals
Ext. Interface
Terminals
Voltage Input
Terminals
∑
IUPQSMAX E PRGPF THD
ENTER ESCAPE
■ CONTROL BUTTON OPERATIONS
∑
IU
PQS
MAX
E PRG
PF THD
ENTER
ESCAPE
E PRG ESCAPE
E PRG ESCAPE
∑
∑
IU
+
+
PQS
PF THD
Hold down
IUHold down
Hold down
Hold down
Hold down
Hold down
NORMAL MODE
Indicates ∑ values
Indicates Voltage or Current
Indicates Power
Indicates Power Factor or THD
Switches Energy readings
Switches to My Default mode
Switches to PC Configuration mode
Switches to Setting mode
Indicates Harmonics by degrees
Switches Energy reading units
Indicates the shortcut menu
SETTING MODE
Go Left
Go Right
Go Down
Go Up
Selects menu; Enables setting changes
Cancels setting changes
----
----
----
----
----
----
BUTTON OPERATION
FUNCTIONS
■HOW TO CHANGE VALUES (e.g. 5A --> 150A)
Press 5 times
Press 5 times
Press
Press
Press
PQS
PF THD
∑
∑
PF THD
Press to increase or decrease the value.
Press to move between digits.
Pressing at the leftmost digit shifts the value on display to the right by 1 digit.
The decimal point and unit are also switched to appropriate ones.
IU
PQSPF THD
∑
∑
53U
P. 3 / 49EM-6485-B Rev.12
INSTALLATION
96 (3.78)92 (3.62)
92 (3.62)
80 (3.15)[12 (.47)]23 (.91)
2 (.08)
96 (3.78)3 (.12)3 (.12)
MOUNTING BRACKETGASKET
100 (3.94) d
ia.
92
+
0.8 (3.65)
0 (3.63)
92
+
0.8 (3.65)
0 (3.63)
■ PANEL CUTOUT unit: mm (inch)
Panel thickness : 2 to 15 mm (0.08 to 0.59 inch)
■ EXTERNAL DIMENSIONS unit: mm (inch)
53U
P. 4 / 49EM-6485-B Rev.12
TERMINAL CONNECTIONS
V1 N V2 1S 1L 2S 2L
L1
sourceload
N
L2
u v v u
U V V U
kl
KL
kl
KL
V1 N V2 1S 1L 2S 2L
L1
sourceload
N
L2
kl
KL
kl
KL
V1 N V2 1S 1L 2S 2L
L1
sourceload
N
L2
V1 V2 V3 1S 1L
L1
sourceload
L2
L3
u v v u
U V V U
kl
KL
V1 V2 V3 1S 1L
L1
sourceload
L2
L3
V1 V2 V3 1S 1L 3S 3L
L1
sourceload
L2
L3
u v v u
U V V U
kl
KL
kl
KL
V1 V2 V3 1S 1L 3S 3L
L1
sourceload
L2
L3
kl
KL
kl
KL
V1 V2 V3 1S 1L 3S 3L
L1
sourceload
L2
L3
kl
KL
V1 V2 V3 1S 1L
L1
sourceload
L2
L3
V1 N1S 1L
L1
sourceload
N
kl
KL
u v
UV
V1 N1S 1L
L1
sourceload
N
kl
KL
V1 N1S 1L
L1
sourceload
N
System /
Application
Single phase /
2-wire
Three phase /
3-wire,
balanced load
Single phase /
3-wire
Terminal
1S 1L3S 3L
L1
sourceload
L2
L3
kl
V1
u v
U V
V2
u v
U V
V3
u v
U V
N
KL
kl
KL
V1 V2 V31S 1L3S 3LN
L1
sourceload
L2
L3
kl
KL
kl
KL
2S 2L
kl
KL
V1 V2 V31S 1L3S 3LN2S 2L
L1
sourceload
L2
L3
N
N
N
2S 2L
kl
KL
V1 N1S 1L
L1
sourceload
L2
kl
KL
u v
UV
V1 N1S 1L
L1
sourceload
L2
L3
N
kl
KL
V1 N1S 1L
L1
sourceload
L2
L3
L3
N
N
System /
Application
Three phase /
4-wire,
balanced load
Three phase /
3-wire,
unbalanced load
Three phase /
4-wire,
unbalanced load
Terminal
Configurator Jack
External Interface
DO/PO
+
–
DI
+
– T1T2T3 T4
Input
V1 V2 V3 N
1S 1L 2S 2L 3S 3L
Power Input
U
(+)V(–)
CONFIG
53U
■ CONNECTING CURRENT INPUTS
Applicable wire size: Max. 2.4 (0.09”) dia., 0.5 – 3.5 mm
Expose the tip of wires by 11 mm (0.43”).
2
P. 5 / 49EM-6485-B Rev.12
53U
T3
T4
T2
T1
Term.
Resist.
+
–
Shielded Twisted-pair Cable
Jumper *
1
V(–)
JACK
U(+)
POWER
DO/PO–
DO/PO+
DO/PO–
DO/PO+
DI –
DI +
CONTACT
INPUT
CONTACT
OUTPUT
• Contact Input Connection E.g.
+
-
• Contact Output Connection E.g.
+
-
DI +
DI –
To other
Modbus devices
■ EXTERNAL INTERFACE CODE: 1
T3
T4
T2
T1
Term.
Resist.
+
–
Shielded Twisted-pair Cable
Jumper *
1
V(–)
JACK
U(+)
DO/PO COM
DO/PO3+
DO/PO2+
DO/PO1+
When the device is located at the end of a transmission line via
twisted-pair cable, (when there is no cross-wiring), close across the
terminal T2 –T3 with a leadwire.
When the device is not at the end, no shortcircuit wire is required.
Analog output may momentarily fluctuate while the configurator cable
is left connected.
*1.
*2.
To other
Modbus devices
■ EXTERNAL INTERFACE CODE: 8
V(–)
U(+)
POWER
DO/PO–
DO/PO+
DI –
DI +
CONTACT
INPUT
CONTACT
OUTPUT
AO2 –
AO2 +
AO1 –
AO1 +
ANALOG
OUTPUT 1
ANALOG
OUTPUT 2
■ EXTERNAL INTERFACE CODE: 4, 5
V(–)
U(+)
POWER
DO/PO1–
DO/PO1+
CONTACT
OUTPUT 1
DO/PO2–
DO/PO2+
CONTACT
OUTPUT 2
AO2 –
AO2 +
AO1 –
AO1 +
ANALOG
OUTPUT 1
ANALOG
OUTPUT 2
■ EXTERNAL INTERFACE CODE: 6, 7
V(–)
U(+)
POWER
POWER
CONTACT OUTPUT 3
CONTACT OUTPUT 2
CONTACT OUTPUT 1
DO/PO3–
DO/PO3+
CONTACT
OUTPUT 3
DO/PO4–
DO/PO4+
CONTACT
OUTPUT 4
DO/PO1–
DO/PO1+
CONTACT
OUTPUT 1
DO/PO2–
DO/PO2+
CONTACT
OUTPUT 2
■ EXTERNAL INTERFACE CODE: 9
V(–)
U(+)
POWER
AO4 –
AO4 +
AO3 –
AO3 +
ANALOG
OUTPUT 3
ANALOG
OUTPUT 4
AO2 –
AO2 +
AO1 –
AO1 +
ANALOG
OUTPUT 1
ANALOG
OUTPUT 2
■ EXTERNAL INTERFACE CODE: 2
CONFIGURATOR
CONFIGURATOR *
2
JACK
CONFIGURATOR *
2
JACK
CONFIGURATOR
JACK
CONFIGURATOR *
2
CONFIGURATOR
JACK
P. 6 / 49EM-6485-B Rev.12
MODBUS WIRING CONNECTION
R2K-1
T1
T2
T3
T4
53U
T1
T2
T3
T4
T1
T2
T3
T4
53U
CONNECTOR
RS-232C
RS-485
*
1
*
1
*1. Internal terminating resistor is used when the device is at the end of a transmission line.
*2. Install shield cables to all sections and ground them at single point.
*
2
FG
RS-485
53U
P. 7 / 49EM-6485-B Rev.12
SYSTEM CONFIGURATION EXAMPLES
RS-485 (Modbus RTU)
Multi Power Monitor
(model: 53U)
RS-232C
RS-232C/RS-485
Converter
(model: R2K-1 or LK1)
Lightning Surge Protector
for RS-485/422
(model: MD74R or MDP-4R) *1
A
X
I
N
A
X
I
N
A
X
I
N
■ RS-485 / RS-232C
■ RS-485 / ETHERNET
Ethernet
Communication Adaptor
(model: 72EM-M4 or 72EM2-M4)
E
T
H
E
R
N
E
T
R
U
N
S
E
N
D
F
I
E
L
D
C
N
F
G
Lightning Surge Protector
for RS-485/422
(model: MD74R or MDP-4R) *1
RS-485 (Modbus RTU)
Multi Power Monitor
(model: 53U)
Lightning Surge Protector
for RS-485/422
(model: MD74R or MDP-4R) *1
A
X
I
N
A
X
I
N
A
X
I
N
Lightning Surge Protector
for RS-485/422
(model: MD74R or MDP-4R) *1
*1. Insert lightning surge protectors recommended in this example if necessary.
53U
P. 8 / 49EM-6485-B Rev.12
53U
MODBUS - BASICS
This device conforms with Modbus-RTU protocol (MODBUS APPLICATION PROTOCOL V1.1a / Modbus over Serial Line
Specification & Implementation Guide V1.0).
The following communication parameters are selectable.
T1.5 timer length 0 to 6.0, in 0.1 increments (Modbus protocol standard: 1.5)
T3.5 timer length 0 to 6.0, in 0.1 increments (Modbus protocol standard: 3.5)
(*) Factory setting
When appropriately set, the host PC connected via RS-485 can read measurands from and write configurations (setting) to
the device.
All registers are assigned to Read Holding Registers, can be read out using this command. If reading an address with no assigned register is attempted, ‘0’ is given.
Write Multiple Registers command is used to write registers. If writing an address with no assigned register is attempted,
‘Exception’ is given.
These commands enable reading measurands and writing configurations.
One (1) word registers are represented in 16-bit integers, while two (2) word registers are in 32-bit. All registers are in the
form of integer unless specifically given in the explanations.
The lower digit word in a 32-bit register is assigned to the lower address (n), while the upper digit word is assigned to the
higher address (n+1). The order can be reversed by programming.
The 32-bit register must be read out and written in single command sequence.
CAUTION : DO NOT apply new setting via Modbus and the front control buttons at once.
It is recommended to wait for a time period indicated under ‘recommended time out value’ in the above table to receive a response for a command. If no response is received for these time periods, take appropriate error processing such as retrying.
P. 9 / 49EM-6485-B Rev.12
53U
MODBUS - OPERATIONS
Modbus registers are assigned to program and operate the unit via Modbus network. It can also disable the view switching
control via the front keys to fix the display view to a specific parameter combination.
Writing a preset passcode in this register deactivates the writing protection via Modbus.
When the Modbus passcode set in this register matches the preset one, setting ‘1’ or ‘2’ in the register address
4945 becomes available to enable writing in Modbus registers.
Reading out the register value is not possible. It reads always ‘-1’ regardless of the code setting.
After writing is complete, be sure to set a value other than the passcode (‘0’ is recommended) to activate the
writing protection again.
4945 1 Modbus register access setting
0 : Write disable (*)
1 : Write enable
2 : Write enable the count values
Other : Write disable
This setting is erased when the power supply to the unit is removed. It always starts with ‘0’ (Write disable)
when the power supply is turned on. Set ‘1’ or ‘2’ before starting writing at other registers.
In order to write a count value (e.g. active energy), set ‘2’ at this register address. When it is set, the unit stops
counting so that a new count value can be written in the register address. Be careful to use ‘2’ setting because
no counting will be performed if the unit remains with this setting.
When the Modbus register writing protection is enabled, this register setting cannot be changed from ‘0’ to ‘1’ or
‘2’ unless a correct security code is set in the register address 4943.
1.01
■USER OPERATIONS
User operations include switching the display views and resetting alarm trips.
ADDR. WORD PARAMETER
5201 1 Key operation lock
0 : All key operations available (*)
1 : All key operations locked
2 : Lock the key operation to go to Setting mode only
5202 1 Data reading display
Shows the parameter set displayed on the three data displays. The display can be switched by writing at this
address from the host.
5203 1 Energy reading display
Shows the parameter type displayed on the bottom data display. The display can be switched by writing at this
address from the host.
5204 1 Energy reading display unit
0 : 0.1 kWh, 0.1 kvarh, 0.1 kVA (*)
1 : 0.1 Wh, 0.1 varh, 0.1 VA
Shows the unit (factor) of the parameter on the energy display (k = kilo). The display unit can be switched by
writing at this address from the host.
Exception: Count time (unit: h) is displayed always ‘without kilo’.
5206 1 Automatic ∑ view switching
0 : Disable automatic switching (*)
1 : Enable automatic switching: ∑1 through ∑4 switched in 10 second intervals. Automatic switching is cancelled
when one of the front control buttons are touched.
P. 10 / 49EM-6485-B Rev.12
53U
■SYSTEM OPERATIONS
System operations include switching the tariff or resetting energy counts, and rebooting.
5330 1 Reset energy count
1 : Reset all values
2 : Reset all MAX / MIN values and set the present values.
3 : Reset all average (demand) values
0 : No resetting
Specify the extent of count resetting. The register is automatically set to ‘0’ when the resetting procedure is
complete after one of these values is written at this address. If another value is written before ‘0’ has been set,
the former resetting procedure ends indefinitely.
Specific values can be preset to each register by writing at this address from the host.
5331 1 Reboot system
Write ‘10001’ to reboot the system. (Any other values can be written but invalid.)
5332 1 Backup / restore setting
20002 : Backup the present setting
30003 : Restore the device with the backup setting data
The register is automatically set to ‘0’ when the procedure is complete after one of these values is written at
this address. If another value is written before ‘0’ has been set, the former procedure ends indefinitely.
5333 1 Passcode
0000 to 9999
0000 : Factory setting
Set and read out a passcode used to go into the Setting Mode using the front control keys.
5334 2 Modbus register writing protection passcode
Setting a passcode to control writing registers via Modbus.
1 to 999 999 999
0 : Cancel writing protection (*)
The Modbus passcode must be set to the register address 4943 before setting ‘1’ or ‘2’ in the address 4945 to
deactivate the writing protection.
The value in this register is encripted when it is read out. Only ‘0’ (Cancel protection) is read out as it is.
When a new code is set in this register, the register address 4945 is immediately reset to ‘0’ so that a next com mand will be already limited in access.
1.01
P. 11 / 49EM-6485-B Rev.12
MODBUS - SETTING
■SYSTEM SETTINGADDR. WORD PARAMETERUNIT
5601 1 System configuration
5733 1 T1.5 timer length
1 to 60 : Specified value
Factory setting : 15
5734 1 T3.5 timer length
1 to 60 : Specified value
Factory setting : 35
5735 1 Long register (32-bit words assignments)
0 : Normal (*) Lower digit word at the lower address
1 : Swap Lower digit word at the higher address
× 0.1 character length
× 0.1 character length
P. 12 / 49EM-6485-B Rev.12
■DEMAND SETTINGADDR. WORD PARAMETERUNIT
5857 1 Average (demand) current update interval Minutes
0 : External trigger signal
1 to 60 : Minutes
Factory setting : 30
5858 1 Average (demand) power update interval Minutes
0 : External trigger signal
1 to 60 : Minutes
Factory setting : 30
■STYLE SETTINGADDR. WORD PARAMETER
5985 1 Input line indication
0 : 1 – 2 – 3 (*)
1 : R – S – T
5986 1 Phase difference direction indication
0 : IND / CAP (*)
1 : LEAD / LAG
5987 1 Power factor (PF1 through PF3, PF) sign
0 : Standard (IEC) (*) Identical to the active energy
1 : Special type 1 (IEEE) Positive in LAG, Negative in LEAD
5988 1 Reactive power (Q1 through Q3, Q) sign
0 : Standard (IEC) (*) Positive from [PF = 1.0] to 180° in LAG direction; Negative for the other direction
1 : Special type 1 Positive in LAG, Negative in LEAD
5989 1 Reactive power (Q1 through Q3) calculation (Q = Q1 + Q2 + Q3)
0 : Standard (*) Qn = √ Sn
1
1 : Reactive power meter method Qn = –––––– ∑ (Uni – Nui) I i + (Nsmp / 4)
5990 1 Apparent power (S) calculation
0 : Standard (*) S = √ P
________
2
+ Q
2
__________
2
– Pn2
Nsmp
i = 1
Nsmp
1 : Sum S = S1 + S2 + S3
5991 1 Unit used to indicate power up to 9999
2.000 : With ‘k’ (0.000 k) (*) 1 : Without ‘k’ (0000)
Note: ‘1,’ ‘2,’ ‘3’ in expressions like Q1, Q2, Q3 indicate ‘R,’ ‘S,’ ‘T’ respectively.
6114 1 Discrete output 1 contact type
0 : Normally open contact (*)
1 : Normally closed contact
The contact opens at the power OFF regardless of this setting.
6115 1 Discrete input function
0 : Undefined (*)
1 : Update demand
2 : Reset energy count
6116 1 Discrete input contact type
0 : Normally open contact (*)
1 : Normally closed contact
6117 1 Discrete output 2 function
0 : Undefined (*)
1 : Energy count
2 : Alarm
6118 1 Discrete output 2 contact type
0 : Normally open contact (*)
1 : Normally closed contact
The contact opens at the power OFF regardless of this setting.
P. 13 / 49EM-6485-B Rev.12
ADDR. WORD PARAMETER
6121 1 Discrete output 3 function
0 : Undefined (*)
1 : Energy count
2 : Alarm
6122 1 Discrete output 3 contact type
0 : Normally open contact (*)
1 : Normally closed contact
The contact opens at the power OFF regardless of this setting.
6125 1 Discrete output 4 function
0 : Undefined (*)
1 : Energy count
2 : Alarm
6126 1 Discrete output 4 contact type
0 : Normally open contact (*)
1 : Normally closed contact
The contact opens at the power OFF regardless of this setting.
■ENERGY SETTING DOADDR. WORD PARAMETERUNIT
6241 1 Energy count 1 assigned to the discrete output 1 ----
Refer to the table in the following page.
6242 2 Pulse weight for Energy count 1 kWh
0 : No pulse output (disabled) kvarh
1 to 100 000 : Specified value
Factory setting : 10
6244 1 Pulse duration (width) for Energy count 1 sec / 10
1 to 20 : Specified value
Factory setting : 1
6245 1 Tariff setting for Energy count 1 --- 0 : Disable (*)
1 : Enable
6246 1 Energy count 2 assigned to the discrete output 2 --- Refer to the table in the following page.
6247 2 Pulse weight for Energy count 2 kWh
0 : No pulse output (disabled) kvarh
1 to 100 000 : Specified value
Factory setting : 10
6249 1 Pulse duration (width) for Energy count 2 sec / 10
1 to 20 : Specified value
Factory setting : 1
6250 1 Energy count 3 assigned to the discrete output 3 --- Refer to the table in the following page.
6251 2 Pulse weight for Energy count 3 kWh
0 : No pulse output (disabled) kvarh
1 to 100 000 : Specified value
Factory setting : 10
6253 1 Pulse duration (width) for Energy count 3 sec / 10
1 to 20 : Specified value
Factory setting : 1
6254 1 Energy count 4 assigned to the discrete output 4 --- Refer to the table in the following page.
6255 2 Pulse weight for Energy count 4 kWh
0 : No pulse output (disabled) kvarh
1 to 100 000 : Specified value
Factory setting : 10
6257 1 Pulse duration (width) for Energy count 4 sec / 10
1 to 20 : Specified value
Factory setting : 1
× 0.1 (kWh / kvarh / kVA) kVA
× 100 msec.
× 0.1 (kWh / kvarh / kVA) kVA
× 100 msec.
× 0.1 (kWh / kvarh / kVA) kVA
× 100 msec.
× 0.1 (kWh / kvarh / kVA) kVA
× 100 msec.
53U
P. 14 / 49EM-6485-B Rev.12
Energycounttype
SETVALUEIDPARAMETER
0 T-EP Active energy, incoming (*)
1 T-EQ Reactive energy, LAG
2 T-ES Apparent energy
3 T-EP– Active energy, outgoing
4 T-EQ– Reactive energy, LEAD
5 T-EQ+LAG Reactive energy, incoming, LAG
6 T-EQ+LEAD Reactive energy, incoming, LEAD
7 T-EQ–LAG Reactive energy, outgoing, LAG
8 T-EQ–LEAD Reactive energy, outgoing, LEAD
9 ---- Reserved. DO NOT USE.
10 T-EQ+P Reactive energy, incoming
11 T-EQ–P Reactive energy, outgoing 2.0012 T-EPA Active energy, (incoming – outgoing)
13 T-EQA Reactive energy, (incoming + outgoing)
200 EP Active energy, high tariff, incoming
201 EQ Reactive energy, high tariff, LAG
202 ES Apparent energy, high tariff
203 EP– Active energy, high tariff, outgoing
204 EQ– Reactive energy, high tariff, LEAD
205 EQ+LAG Reactive energy, high tariff, incoming, LAG
206 EQ+LEAD Reactive energy, high tariff, incoming, LEAD
207 EQ–LAG Reactive energy, high tariff, outgoing, LAG
208 EQ–LEAD Reactive energy, high tariff, outgoing, LEAD 2.00209 ---- Reserved. DO NOT USE.
210 EQ+P Reactive energy, high tariff, incoming
211 EQ–P Reactive energy, high tariff, outgoing 2.00212 EPA Active energy, high tariff, (incoming – outgoing)
213 EQA Reactive energy, high tariff, (incoming + outgoing)
300 L-EP Active energy, low tariff, incoming
301 L-EQ Reactive energy, low tariff, LAG
302 L-ES Apparent energy, low tariff 2.00303 L-EP– Active energy, low tariff, outgoing
304 L-EQ– Reactive energy, low tariff, LEAD
305 L-EQ+LAG Reactive energy, low tariff, incoming, LAG
306 L-EQ+LEAD Reactive energy, low tariff, incoming, LEAD 2.00307 L-EQ–LAG Reactive energy, low tariff, outgoing, LAG
308 L-EQ–LEAD Reactive energy, low tariff, outgoing, LEAD
309 ---- Reserved. DO NOT USE.
310 L-EQ+P Reactive energy, low tariff, incoming