M-System 48NV Data Sheet

MODEL: 48NV
http://www.m-system.co.jp/ 48NV SPECIFICATIONS ES-9438 Rev.8 Page 1/7

Bargraph Indicators 48N Series

50
40
30
20
10
0
10
20
30
40
50 m
3
/h
50
40
30
20
10
0
10
20
30
40
50 m
3
/h
144
(5.67)
36 (1.42)
103
(4.06) mm (inch)

BARGRAPH INDICATOR

Functions & Features
• Displays two process variables in dual graphic bargraphs of 101 LED segments
• IP65 front cover
• Scale plate is easily replaced
• Separable terminal block

MODEL: 48NV–[1][2][3][4]–[5][6]

ORDERING INFORMATION

• Code number: 48NV-[1][2][3][4]-[5][6] Specify a code from below for each [1] through [6]. (e.g. 48NV-2BBV4W-R/CE/D)
• Special input range (For codes Z & 0)
• Bargraph scale (e.g. 0 – 100 %) (See ‘Scale Plate.’)
YR: Amber / Red YG: Amber / Green YB: Amber / Blue GR: Green / Red GY: Green / Amber GB: Green / Blue BR: Blue / Red BY: Blue / Amber BG: Blue / Green

[3] MOUNTING DIRECTION

V: Vertical H: Horizontal

[4] INPUT

Current
A: 4 – 20 mA DC (Input resistance 10 Ω) B: 2 – 10 mA DC (Input resistance 20 Ω) C: 1 – 5 mA DC (Input resistance 39 Ω) D: 0 – 20 mA DC (Input resistance 10 Ω) E: 0 – 16 mA DC (Input resistance 12 Ω) F: 0 – 10 mA DC (Input resistance 20 Ω) G: 0 – 1 mA DC (Input resistance 200 Ω) H: 10 – 50 mA DC (Input resistance 5.1 Ω) Z: Specify current (See INPUT SPECIFICATIONS)
Voltage
3: 0 – 1 V DC (Input resistance 1 MΩ min.) 4: 0 – 10 V DC (Input resistance 1 MΩ min.) 5: 0 – 5 V DC (Input resistance 1 MΩ min.) 6: 1 – 5 V DC (Input resistance 1 MΩ min.) 4W: -10 – +10 V DC (Input resistance 1 MΩ min.) 5W: -5 – +5 V DC (Input resistance 1 MΩ min.) 0: Specify voltage (See INPUT SPECIFICATIONS)

[1] BARGRAPHS

1: Single 2: Dual

[2] BAR LED COLOR

R: Red Y: Amber G: Green B: Blue
Dual (left/right)
RR: Red / Red YY: Amber / Amber GG: Green / Green BB: Blue / Blue RY: Red / Amber RG: Red / Green RB: Red / Blue

[5] POWER INPUT

AC Power
M: 85 – 264 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz) (CE not available) M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±15 %, ripple 10 %p-p max.)

[6] OPTIONS (multiple selections)

Standards & Approvals
blank: Without CE /CE: CE marking
Bezels
MODEL: 48NV
http://www.m-system.co.jp/ 48NV SPECIFICATIONS ES-9438 Rev.8 Page 2/7
blank: Bezels for M-System’s 48 Series panel cutout /D: Bezels for DIN panel cutout /F: Bezels for Fuji Electric's PAJ, PAK, PBA panel cutout

BEZEL OPTION

Bezels are used to adapt the 48N Series to an existing panel cutout. In order to replace M-System’s 48 Series products, use the one attached to the 48N Series as standard. When the existing panel is cut according to DIN standard, specify ‘/D’ suffix code. For a new installation, no bezel is required. Please refer to ‘Mounting Requirement’ and mount the 48N directly. Ingress protection is invalid when the 48N is mounted with a bezel, or when multiple modules are stacked side by side.

RELATED PRODUCTS

• Spare scale plate

GENERAL SPECIFICATIONS

Construction: Panel flush mounting Degree of protection: IP65; applicable to the front panel for single unit mounted according to the specified panel cutout Connection: M3 screw terminals (torque 0.6 N·m) Screw terminal: Nickel-plated steel Housing material: Flame-resistant resin (black) Isolation: Input 1 to input 2 to power Scale plate: Flame resistant resin (white scale & characters on black base)

PERFORMANCE in percentage of span

Accuracy: ±1 % ±1 digit Response time: ≤ 0.5 sec. Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @1 minute (input 1 to input 2 to power to ground)

STANDARDS & APPROVALS

CE conformity: EMC Directive (2004/108/EC) EMI EN 61000-6-4: 2007 EMS EN 61000-6-2: 2005 Low Voltage Directive (2006/95/EC) EN 61010-1: 2001 Installation Category II Pollution Degree 2 Input 1 or input 2 to power input: Reinforced insulation (300 V) Input 1 to input 2: Functional insulation

INPUT SPECIFICATIONS

■ DC Current: 0 – 50 mA DC; input resistor incorporated Minimum span: 1 mA When specifying a resistance value, choose from below.
5.1 Ω, 10 Ω, 12 Ω, 20 Ω, 39 Ω, 200 Ω
■ DC Voltage: 0 – 10 V DC Minimum span: 0.1 V Input resistance: ≥ 1 MΩ Offset: Max. 1.5 times span

INSTALLATION

Power Consumption
•AC: Approx. 3 VA (single) or 4 VA (dual)
•DC: Approx. 1.5 W (single) or 2 W (dual) Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Panel flush mounting Weight: 300 g (0.66 lb)
MODEL: 48NV
http://www.m-system.co.jp/ 48NV SPECIFICATIONS ES-9438 Rev.8 Page 3/7

SCALE PLATE

WHAT MUST BE SPECIFIED WHEN ORDERING
Please specify the bargraph scale range and engineering unit. The overvall scale plate design including the number of divisions, division line length, character font is determined by M-System.
[Example] : Bargraph range 0 to 300 cm Bargraph scale range: 0 – 300 Engineering unit for the bargraph: cm
TYPES OF DIVISIONS
Five (5) types of divisions are used depending upon the scale span, which determined by the following equation: Scale Span = (Max. range value – Min. range value) x 10 where n = integer (used to limit the calculated scale span to the minimum of 1.1, below 11.0.) The number of divisions is automatically determined by the scale span.
Type 1: 1.1 Scale Span < 1.3 Number of divisions: 22 to 25.9 Scale: Starts at 0, increments by 0.02 / 0.2 / 2 / 20 /
200. Min. and max. values indicated. 4 digits including negative sign and decimal point. Division lines: Long, Short, Medium, Short, Long (4 divisions repeated)
Type 3: 2.0 Scale Span < 2.6 Number of divisions: 40 to 51.9 Scale: Starts at 0, increments by 0.05 / 0.5 / 5 / 50 /
500. Min. and max. values indicated. 4 digits including negative sign and decimal point. Division lines: Long, Short, Medium, Short, Medium, Short, Medium, Short, Medium, Short, Long (10 divisions repeated)
Minimum Divisions
Maximum
Divisions
Bipolar
Scale
10
11
8
6
4
2
0
600
400
200
0
-200
-400
0.2
0
-600
0.4
0.6
0.8
1.0
1.2
1.29
Minimum Divisions
Maximum
Divisions
Bipolar
Scale
120 100
50
0
-50
-100
-120
0
0
0.5
1
1.5
2
2.59
5
10
15
20
• Type 2: 1.3 Scale Span < 2.0
Number of divisions: 26 to 39.9 Scale: Starts at 0, increments by 0.03 / 0.3 / 3 / 30 /
300. Min. and max. values indicated. 4 digits including negative sign and decimal point. Division lines: Long, Short, Medium, Short, Medium, Short, Long (6 divisions repeated)
n
• Type 4: 2.6 Scale Span < 5.5
Number of divisions: 26 to 54.9 Scale: Starts at 0, increments by 0.05 / 0.5 / 5 / 50 /
500. Min. and max. values indicated. 4 digits including negative sign and decimal point. Division lines: Long, Medium, Medium, Medium, Medium, Long (5 divisions repeated)
Minimum Divisions
Maximum
Divisions
Bipolar
Scale
0
0.3
0.6
0.9
1.2
1.5
1.8
0.6
0.3
0
-0.3
-0.6
-0.8
0.8
1.99
0
30
60
90
120
130
Minimum Divisions
Maximum
Divisions
Bipolar
Scale
250
200
150
100
50
0
-50
-100
-150
-200
-250
0 0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
5.49
50
100
150
200
250
260