M SYSTEM 0000002 User Manual

INSTRUCTION MANUAL
WIRELESS GATEWAY
(
Modbus-RTU Transparent 900MHz Band Wireless Device (Child device)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below. If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Wireless gateway.................................................................(1)
Antenna ...............................................................................(1)
Terminating resistor (110Ω, 0.25W) ...................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly what you ordered.
■ OPERATING MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection, hardware setting, and basic maintenance procedures. For information on the introduction of wireless device, refer to the 900MHz band wireless device operating manual (EM­XXXX-B).
•Attachment of rooftop antenna; There is a magnet on the bottom face which allows you to attach the antenna on a metal box and such. To obtain optimum performance from the antenna, attach on a metal plate (recommended dimension: 500 mm × 500 mm or more). However, in the case of connecting FE1 to a metal plate, the isolation be­tween FE1 and antenna connector will be lost. Tighten the connector with a specified torque (0.9 N∙m). As a guide, finger-tighten it until the connector stops, and then rotate it 10 to 15 degrees with a wrench. Do not force the cable to bend less than acceptable radius of 3 cm.
•Using 7.5 m coaxial cable (model: xxx)(OKI) for extension decreases transmission distance.
MODEL
)
WL40MW1F
Connector
POINTS OF CAUTION
■ POWER INPUT RATING & OPERATIONAL RANGE
•Locate the power input rating marked on the product and confirm its operational range as indicated below:
24 V DC rating: 24 V ±10%, ≤ 70 mA 12 V DC rating: 12 V ±10%, ≤ 130 mA
■ GENERAL PRECAUTIONS
•Before you remove the unit or mount it, turn off the power supply for safety.
■ ENVIRONMENT
•Indoor use.
•When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient ventilation.
•Do not install the unit where it is subjected to continuous vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -20 to +60°C (-4 to 140°F) with relative humidity within 10 to 90% RH in order to ensure adequate life span and operation.
•Attach the antenna to the unit.
•Attachment and adjustment of sleeve antenna; Loosen
the connector (See the top-right figure.), and rotate the antenna. Holding the antenna vertical, tighten the con­nector by hand. Make sure to fix the antenna firmly.
■ WIRING
•Do not install cables close to noise sources (relay drive cable, high frequency line, etc.).
•Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■ AND ....
•The unit is designed to function as soon as power is sup­plied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
CAUTION REGARDING RADIO FREQUENCY
■ FCC NOTICE
•This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, in­cluding interference that may cause undesired operation.
■ FCC CAUTION
•Changes or modifications not expressly approved by the party responsible for compliance could void the user’s au­thority to operate the equipment.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
WL40MW1F
■ NOTE
•This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accord­ance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to cor­rect the interference at his own expense.
•This transmitter must not be co-located or operated in conjunction with any other antenna or transmitter.
COMPONENT IDENTIFICATION
FRONT VIEW
Status Indicator LED
Maintenance Connector
Configuration Jack
Connector for Power Input *
Power
920Link
920Run
920ERR
ERR
24V
0V
NC
NC
FE1
CFG2
CFG1
Antenna Connector
SD RD
DA
DB
DG
SLD FE
■ FCC RF EXPOSURE INFORMATION
•This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment and meets the FCC radio frequency (RF) Exposure Guide­lines. This equipment should be installed and operated keeping the radiator at least 20cm or more away from person’s body.
FCC ID : 2AOTF-0000002 Contains FCC ID: 2AKGW-1TD3016A1
Status Indicator LED
Connector for RS-485 Communication
*Power input defers depending on the power input code you select.
■ STATUS INDICATOR LED
LED STAT U S COLOR FUNCTION
Power ON Green Power is on. 920Link ON Green Wireless: coordinator is connected
0.5 Hz blinking Green Wireless: coordinator connection in process Blinking twice per second Green Wireless: start-up error
920Run ON Green Wireless: normal communication
ON Red No detour
920ERR Blinking Red Network authentication failure
ERR ON Red Modbus communication error
■ STATUS INDICATOR LED
LED S TAT U S COLOR FUNCTION
SD ON Green RS-485 transmission
RD ON Green RS-485 reception
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
■ TERMINAL ASSIGNMENTS
• Connectors for power input
Unit side connector: MSTBV2,5/5-GF-5,08AU (Phoenix Contact) Cable side connector: TFKC2,5/5-STF-5,08AU (Phoenix Contact)
Power input code: R (24 V DC) Power input code: S (12 V DC)
24V
0V NC NC
FE1
ID FUNCTION
24V Power input 24 V 12V Power input 12 V
0V Power input 0 V 0V Power input 0 V
NC Not used NC Not used
12V
NC NC
FE1
0V
ID FUNCTION
NC Not used NC Not used
FE1 Power input earth FE1 Power input earth
• Connector for RS-485 communication
Unit side connector: MC1,5/5-GF-3,5 (Phoenix Contact) Cable side connector: TFMC1,5/5-STF-3,5 (Phoenix Contact)
ID FUNCTION
DA DB DG SLD FE
DA DA DB DB DG DG
SLD Shield
FE Functional earth
WL40MW1F
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
CONFIGURATOR SOFTWARE SETTING
With configurator software, settings shown below are available. Refer to the users manual of W920FCFG for detailed operation.
■ WIRELESS SETTING
ITEM SETTING RANGE DEFAULT
Preferred PAN ID (group number) 0000 – FFFE (hexadecimal, 4 digits) 0000 Radio channel number 1 – 43 (selectable up to 10 channels) None Short address 0000 – FFFD (hexadecimal, 4 digits) 0000 Network name English one-byte characters within 16 characters
(one-byte space, “-”, “_”, “.”, “@” are usable.)
Encryption key 0000...0 – FFFF...F
(hexadecimal, 32 digits) Monitor unit of Tx time 10 – 3600 (sec.) 600 (sec.) Transmitter power output 0.16mW / 1mW / 20mW 20mW Low-speed moving mode No / Yes No Device type in a network,
Number of devices in a network
Set network quality Standard (recommended) /
Network join mode V3-compatible mode / Fast join mode V3-compatible mode Fixed route No / Yes No Destination short address 0000 – FFFD (hexadecimal, 4 digits) 0000 Temporary detour No / Yes Yes Packet filtering None / Yes (polling type) Yes (polling type) Filter timeout on polling 1.0 – 60.0 (sec.) 1.0 (sec.) 920Run timeout 1.0 – 60.0 (sec.) 3.0 (sec.) Retry times before route switching Once / Twice / Three times Three times
Child (fixed), 1 to 30 devices /
Child (fixed), 31 to 60 devices /
Child (fixed), 61 to 100 devices /
Child (fixed) + child (moving)
Frequency of route switching and delay (higher) /
Frequency of route switching and delay (highest)
Blank
0000...0
Child (fixed), 1 to 30 devices
Standard (recommended)
WL40MW1F
■ MODBUS SETTING
ITEM SETTING RANGE DEFAULT
Transfer rate 38400 / 19200 / 9600 / 4800 bps 38400 bps Parity bit Odd / Even / None Odd Stop bit 1 bit / 2 bits 1 bit
INSTALLATION
■ DIN RAIL MOUNTING
A) Hang the upper hook at the back of the unit on the DIN
rail.
B) Push the lower part of the unit to fit in the DIN rail.
B
A
■ DEMOUNTING
A) Pull down the DIN rail adaptor using a minus screw-
driver. B) Pull out the lower part of the unit. C) Remove the upper part from the DIN rail.
C
B
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
A
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■ EXTERNAL DIMENSIONS unit: mm (inch)
With sleeve antenna
[R165 (6.50)]
[260 (10.24)]
WL40MW1F
[155 (6.10)]
DIN RAIL 35mm wide
105 (4.13)
5 (.20)
60 (2.36)
With rooftop antenna
[200 (7.87)]
80 (3.15)
36 (1.42)
(1.06)
ø3 (.12)
ø1.2 (.05)
approx. 2500 (98.4)ø27
45 (1.77)
8 (.31) Hex.
107 (4.21)
3 (.12)
DIN RAIL 35mm wide
20
(.79)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
107 (4.21)
3 (.12)
■ CONNECTION DIAGRAM
WL40MW1F
Antenna Connector
Maintenance Connector
Configuration Jack
Power Input
USB Connector
Jack
24V
*
0V
NC
NC
FE1
* Power input defers depending on the power input code you select.
WIRING INSTRUCTIONS
■ WIRING CONNECTION WITH SLAVE DEVICES
WL40MW1F
TERMINATOR TERMINATOR
DA DB
DG
SLD
*
FE
DA DB
To Other Modbus
DG
Devices
SLD
FE
REMOTE UNIT
DA DB DG
SLD
FE
REMOTE UNIT
DA DB DG
SLD
FE
*
Connect SLD and FE for reducing noise interference if necessary.
Note: Be sure to connect the terminating resistor included in the product package to the unit at both ends of communication line. The terminator must be connected across “DA” and “DB”.
■ TENSION CLAMP (FRONT TWIN CONNECTION) FOR POWER INPUT
Applicable wire size: 0.2 to 2.5 mm
2
Stripped length: 10 mm Recommended terminals:
AI0,25-10YE 0.25 mm AI0,34-10TQ 0.34 mm AI0,5-10WH 0.5 mm AI0,75-10GY 0.75 mm AI1-10RD 1.0 mm AI1,5-10BK 1.5 mm AI2,5-10BU 2.5 mm
2
(Phoenix Contact)
2
(Phoenix Contact)
2
(Phoenix Contact)
2
(Phoenix Contact)
2
(Phoenix Contact)
2
(Phoenix Contact)
2
(Phoenix Contact)
■ TENSION CLAMP (FRONT TWIN CONNECTION) FOR COMMUNICATION
Applicable wire size: 0.2 to 1.5 mm
2
Stripped length: 10 mm Recommended terminals:
AI0,25-10YE 0.25 mm AI0,34-10TQ 0.34 mm AI0,5-10WH 0.5 mm AI0,75-10GY 0.75 mm
2
(Phoenix Contact)
2
(Phoenix Contact)
2
(Phoenix Contact)
2
(Phoenix Contact)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODBUS FUNCTION CODE
Modbus function codes are shown below.
■ DATA AND CONTROL FUNCTION
CODE NAME
01 Read Coil Status Digital output from the slave (read/write) 02 Read Input Status Status of digital inputs to the slave (read only) 03 Read Holding Registers General purpose register within the slave (read/write) 04 Read Input Registers Collected data from the field by the slave (read only) 05 Force Single Coil Digital output from the slave (read/write) 06 Preset Single Registers General purpose register within the slave (read/write) 08 Diagnostics 15 Force Multiple Coils Digital output from the slave (read/write) 16 Preset Multiple Registers General purpose register within the slave (read/write)
■ EXCEPTION CODE
CODE NAME
01 Illegal Function Function code is not allowable for the slave 02 Illegal Data Address Address is not available within the slave 03 Illegal Data Value Data is not valid for the function 04 Slave Device Failure 05 Acknowledge 06 Slave Device Busy 07 Negative Acknowledge
WL40MW1F
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for protection against induced lightning surges. Please contact M-System to choose appropriate models.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp