MS Sedco TDM Installation Instructions Manual

Page 1
The
Commander
Series
TDM
Universal Time Delay Module INSTALLATION INSTRUCTIONS
Section 1
General Description
The TDM is a multipurpose timing module that can be used for a variety of applications. Its unique design and open architecture allows the TDM to be used in any application that requires timing control of up to two outputs with up to four inputs. Common applications include: simple time delay, vestibule door sequencing (only one device required) and electric lock/automatic door operator sequencing.
The four inputs on the TDM allow sequencing or independent operation of the two outputs. Input 1 will sequence Outputs 1 then 2. Input 2 will sequence Outputs 2 then 1. Input 3 will operate Output 1 independently. Input 4 will operate Output 2 independently.
Both outputs on the TDM are fully programmable for "on time" duration as well as the delay time between the two outputs from 0 to 99 seconds.
WARNING: Devices to be controlled by the TDM must be low voltage (12-24V) but can be
!
inductive loads. Surge suppressors are standard on the TDM.
Figure 2: Simple Time Delayed Output
Figure 3: Electric Lock & Door Operator Sequencing Figure 4: Vestibule Door Sequencing
Detailed Operating Display functions for the TDM are shown in Figure 5. For additional technical assistance, contact us toll free at 1-317-842-2545.
Figure 5: TDM Operating Display Function
NOTICE: These instructions are provided for your convenience. Please verify your installation is in
!
compliance with all applicable standards upon completing installation of this device.
Section 3
Technical Data
Model....................................... TDM
Input Power.............................. 12-24V AC or DC
Power Consumption................ 2W Maximum
Output Contacts....................... Form C, Rated at 3 Amps
Relay Contact Rating............... 3A:120V AC; 3A:60V DC
Temperature Rating................ -22°F to 158°F
(-30°C to 70°C)
Weight...................................... <0.25 lbs.
Physical Size............................ 4.75"L x 2.125"W x 0.75"H
WET/DRY CONTACT OPTION:
The TDM has the option to supply power to Relay Output 1 contacts. This is known as having a "Wet" contact instead of the conventional "Dry" contact closure. To use output 1 as a "Wet" contact, change the jumper setting (see Figure 1). The voltage supplied to Output 1 will be the same as the voltage supplied to the input power wires of the TDM.
WARNING: Changing jumper settings to enable the “Wet” Contact option will apply a voltage to
!
the Output 1 relay contact. Please ensure that any device connected to this output is capable of accepting voltage. Failure to do so may result in damage to the device.
Section 2
Basic Installation
1. Mount the TDM in desired location.
2. With power off, make all necessary wiring connections to the wiring harnesses (Fig. 1).
Figure 1: TDM Layout and Wiring Connections
Section 4
Warranty
MS SEDCO guarantees this product to be free from manufacturing defects for 1 year from date of installation. Unless MS SEDCO is notified of the date of installation, the warranty will be in effect for 1 year from the date of shipment from our factory. If, during the first year, this device fails to operate and has not been tampered with or abused, the unit can be returned prepaid to factory and it will be repaired free of charge. After 1 year, the unit will be repaired for a nominal service charge. This limited warranty is in
lieu of all other warranties expressed or implied, including any implied warranty of merchantability, and no representative or person is authorized to assume for MS SEDCO any other liability in connection with the sale of our products. All warranties are limited to the duration of this written warranty. In no event shall MS SEDCO be liable for any special, incidental, consequential or other damages arising from any claimed breach of warranty as to its products or services.
Questions? Call us toll-free at 1-317-842-2545 or
visit us online at www.mssedco.com.
Detailed wiring and programming instructions for three common applications are included.
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
7898 Zionsville Road Indianapolis, Indiana 46268
Page 1
(82A044) TDMv1017
Page 2
The
Commander
Series
TDM
Universal Time Delay Module INSTALLATION INSTRUCTIONS
FIGURE 1—TDM Layout & Wiring Connections
Input Actions
Input 1—Sequences Output 1 then Output 2 Input 2—Sequences Output 2 then Output 1 Input 3—Operates Output 1 only Input 4—Operates Output 2 only
Wht/Gray
Wht/Brown
CO M
INPUT 4
TDM
PROGRAM
MODE BUTTON
io
Wht/Red
Wht/Grn
Wht/V
CO M
INPUT 2
INPUT 3
DISPLAY ADJUSTMENT
Blue
Wht/Blue
INPUT 1
INPUT 1
Input Connections
Green
Green
Blue
Wht/Blue
Wht/Red
Wht/Grn
Wht/Vio
Wht/Gray
Wht/Brown
Green
Green
LED DISPLAY KEY d1 = delay 1
d2 = delay d3 = delay d1 to d2 d4 = delay d2 to d1 i1 = input 1 (n.o. / n.c.) i2 = input 2 (n.o. / n.c.) i3 = input 3 (n.o. / n.c.)
i4 = input 4 (n.o. / n.c.)
o1 = output 1 (n.o. / n.c.) o2 = output 2 (n.o. / n.c.)
12-24V AC/DC
Input Power 12-24V
(AC or DC)
Switch Input #1
Switch Input #2
Switch Input #3
Switch Input #4
2
Output Connections
White
Gray
Violet
Yellow
Brown
Orange
N.O.
COM N.C.
N.O.
COM N.C.
Output #1
Output #2
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
N. O.
Yellow
Output #1
N. C.
Violet
Gray
Output #2
CO M
N. C.
Orange
Brown
7898 Zionsville Road Indianapolis, Indiana 46268
o1= wet
CO M
N. O.
o1= dry
Wet/Dry
Contact Option
White
(Factory Setting = Dry Contact)
Page 2
(82A044) TDMv1017
Page 3
The
Commander
Series
TDM
Universal Time Delay Module INSTALLATION INSTRUCTIONS
FIGURE 2—Simple Time Delayed Output
This separate power source ( & associated wiring) can be eliminated if the jumper is set for "WET" contacts instead of "DRY" contacts. (see page 6)
SPRINKLER
OR FIRE
DETECTION
SYSTEM (IF USED)
Mag Lock
PROTECTION
SIGNALING
SYSTEM
(IF USED)
FIRE
or Electric Exit Device
NOTE: Mag Lock uses N.C. (Gray & Violet)
Electric Exit device uses N.O. (Gray & White)
Wall
Switch
PUSH
OPEN
TO
WHT/VIO
WHT/RED
12-24V
AC / DC
GRN
Input #3
N.C.
Output #1
MS SEDCO
TDM
Timing Control Module
GRN
12-24V
VIO
GRAY
JUMPER INSTALLED FOR "DRY" CONTACTS
PROGRAMMING PROCEDURE
TDM
PROGRAM
MODE BUTTON
N.C.
COM
INPUT 4
DISPLAY ADJUSTMENT
INPUT 2
INPUT 3
COM
Output #2
N.C.
LED DISPLAY KEY d1 = delay 1 d2 = delay 2
Output #1
COM
N. C.
d3 = delay d1 to d2 d4 = delay d2 to d1 i1 = input 1 (n.o. / n.c.) i2 = input 2 (n.o. / n.c.) i3 = input 3 (n.o. / n.c.) i4 = input 4 (n.o. / n.c.) o1 = output 1 (n.o. / n.c.) o2 = output 2 (n.o. / n.c.)
12-24V AC/DC
N. O.
o1= dry
o1= wet
INPUT 1
INPUT 1
COM
N. C.
N. O.
Once the TDM has been wired for the above application, programming of the device is as follows:
1) Apply power to the unit, provided there is no smoke or fire, you can assume that your wiring job must be somewhat successful.
2) Once properly powered, the display will flash double bars (––) indicating that the unit is in its normal operating ready mode.
3) To begin programming, depress the PROGRAM MODE BUTTON one time. The first parameter to be programmed will appear on the display. This is the delay time, or "on time" of the output #1 and is displayed as d1 followed by the time setting (It will flash between the two). To adjust the time setting, use a small screwdriver and rotate the DISPLAY ADJUSTMENT clockwise to increase and counterclockwise to decrease the time setting. After the desired value is displayed, depress the PROGRAM MODE BUTTON again to save the value. The display will now read d2. Now wait 30 seconds until the display again reads double bars (––) indicating that the unit is in its normal operating ready mode.
4) You are now ready to test your installation. If the time delay has to be changed, make the change to the d1 setting, press the PROGRAM MODE BUTTON once and then wait 30 seconds until the double bars (––) appear again.
5) During operation of the unit, the display will indicate its operating status. Please refer to Figure 5 at the end of this installation manual.
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
7898 Zionsville Road Indianapolis, Indiana 46268
Page 3
(82A044) TDMv1017
Page 4
The
Commander
Series
TDM
Universal Time Delay Module INSTALLATION INSTRUCTIONS
FIGURE 3—Electric Lock and Door Operator
12-24V
AC / DC
12-24V
Wall
Switch
PUSH
TO
OPEN
GRN
GRN
BLU
WHT / BLU
input #1
N.C.
Output #1
MS SEDCO
TDM
Timing Control Module
N.O.
Output #2
PROGRAMMING PROCEDURE
VIO
GRAY
Jumper installed for "DRY" contacts
YEL
BROWN
TDM
PROGRAM
MODE BUTTON
COM
INPUT 4
DISPLAY ADJUSTMENT
INPUT 3
Magnetic
Lock
Door
Operator
Control
COM
INPUT 2
Output #2
COM
N. C.
INPUT 1
N. O.
or Electric Exit Device
NOTE: Mag Lock uses N.C. (Gray & Violet)
Electric Exit device uses N.O. (Gray & White)
LED DISPLAY KEY d1 = delay 1 d2 = delay 2
Output #1
COM
N. C.
d3 = delay d1 to d2 d4 = delay d2 to d1 i1 = input 1 (n.o. / n.c.) i2 = input 2 (n.o. / n.c.) i3 = input 3 (n.o. / n.c.) i4 = input 4 (n.o. / n.c.) o1 = output 1 (n.o. / n.c.)
12-24V AC/DC
o2 = output 2 (n.o. / n.c.)
N. O.
INPUT 1
o1= wet
o1= dry
Once the TDM has been wired for the above application, programming of the device is as follows:
1) Apply power to the unit. The display will flash double bars (––) indicating that the unit is in its normal operating ready mode.
2) To begin programming, depress the PROGRAM MODE BUTTON one time. The first parameter to be programmed will appear on the display. This is the delay time, or "on time" of the output #1 and is displayed as d1 followed by the time setting of 2.0 (Factory Setting) which indicates 2.0 seconds (It will flash between the two). This is the time duration that you want the Electric Lock released (It's usually set around 2-3 seconds). To adjust the time setting, use a small screwdriver and rotate the DISPLAY ADJUSTMENT clockwise to increase and counterclockwise to decrease the time setting. After the desired value is displayed, depress the PROGRAM MODE BUTTON again to save the value. The display will now read d2. d2 is the delay time or "on time" of output #2. This is the time setting that you want for the door (operator) to remain open. This is usually set around 3-5 seconds. To adjust the setting, rotate the DISPLAY ADJUSTMENT until the desired value is displayed and then depress the PROGRAM MODE BUTTON. The display should then read d3. This is the setting for the delay time between the release of the Electric Lock and the opening of the door. This time is usually set around
0.5-1 second. Again, adjust the setting and then depress the PROGRAM MODE BUTTON. The display should now read d4. Now wait 30 seconds until the double bars (––) appear, indicating that the unit is in its normal operating ready mode. *NOTE: d1 should be longer than d3.
3) You are now ready to test your installation. If any of the time settings need to be changed, make the change and press the PROGRAM MODE BUTTON once to save the new value. Then wait 30 seconds until the double bars (––) appear again, indicating that the unit is in its normal operating mode.
4) During operation of the unit, the display will indicate its operating status. Please refer to Figure 5 at the end of this installation manual.
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
7898 Zionsville Road Indianapolis, Indiana 46268
Page 4
(82A044) TDMv1017
Page 5
The
Commander
Series
TDM
Universal Time Delay Module INSTALLATION INSTRUCTIONS
These optional switches are mounted inside the vestibule
Interior
Wall
Switch
switch that opens interior door
switch that opens exterior door
Exterior
Wall
Switch
PROGRAMMING PROCEDURE
FIGURE 4—Vestibule Sequencing
PUSH
OPEN
PUSH
OPEN
TO
TO
BLU
WHT / BLU
WHT / VIO
WHT / GRAY
WHT / BROWN
WHT / GRN
WHT / RED
12-24V
AC / DC
GRN
GRN
input #1
N.O.
Output #1
input #3
MS SEDCO
TDM
Timing Control Module
input #4
N.O.
Output #2
input #2
COM
INPUT 4
WHT
GRAY
Jumper installed for "DRY" contacts
YEL
BROWN
COM
INPUT 2
INPUT 3
INPUT 1
INPUT 1
TDM
PROGRAM
MODE BUTTON
DISPLAY ADJUSTMENT
Output #2
COM
N. C.
Output #1
N. O.
12-24V AC/DC
COM
N. C.
N. O.
Interior Door Operator Control
Exterior Door Operator Control
LED DISPLAY KEY d1 = delay 1 d2 = delay 2 d3 = delay d1 to d2 d4 = delay d2 to d1 i1 = input 1 (n.o. / n.c.) i2 = input 2 (n.o. / n.c.) i3 = input 3 (n.o. / n.c.) i4 = input 4 (n.o. / n.c.) o1 = output 1 (n.o. / n.c.) o2 = output 2 (n.o. / n.c.)
o1= wet
o1= dry
Once the TDM has been wired for the above application, programming of the device is as follows:
1) Apply power to the unit. The display will flash double bars (––) indicating that the unit is in its normal operating ready mode.
2) To begin programming, depress the PROGRAM MODE BUTTON one time. The first parameter to be programmed will appear on the display. This is the delay time, or "on time" of the output #1 and is displayed as d1 followed by the time setting of 2.0 (Factory Setting) which indicates 2.0 seconds (It will flash between the two). This is the time duration that you want the interior door to remain open (It's usually set around 4-5 seconds). To adjust the time setting, use a small screwdriver and rotate the DISPLAY ADJUSTMENT clockwise to increase and counterclockwise to decrease the time setting. After the desired value is displayed, depress the PROGRAM MODE BUTTON again to save the value. The display will now read d2. d2 is the delay time or "on time" of output #2. This is the time setting that you want for the exterior door to remain open. This is usually set around 4-5 seconds. To adjust the setting, rotate the DISPLAY ADJUSTMENT until the desired value is displayed and then depress the PROGRAM MODE BUTTON. The display should then read d3. This is the setting for the delay time between the activation of the interior door and the exterior door. This time is usually set around 1-4 seconds. Again, adjust the setting and then depress the PROGRAM MODE BUTTON. The display should now read d4. This is the delay time between the opening of the doors going in the opposite direction. Adjust this value in the same manner as before. When the PROGRAM MODE BUTTON is depressed, i1 will then be displayed. Now wait 30 seconds until the double bars (––) appear, indicating that the unit is in its normal operating ready mode.
3) You are now ready to test your installation. If any of the time settings need to be changed, make the change and press the PROGRAM MODE BUTTON once to save the new value. Then wait 30 seconds until the double bars (––) appear again, indicating that the unit is in its normal operating mode.
4) During operation of the unit, the display will indicate its operating status. Please refer to Figure 5 at the end of this installation manual.
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
7898 Zionsville Road Indianapolis, Indiana 46268
Page 5
(82A044) TDMv1017
Page 6
The
Commander
Series
TDM
Universal Time Delay Module INSTALLATION INSTRUCTIONS
FIGURE 5—Operation Display & Additional Programming Options
When the unit is operating, the display will indicate which output is active for the duration of its programmed time delay. For relay output #1, a 1 will be displayed and 2 will be displayed for relay output #2. If the delays d3 or d4 are used (such as an installation using a Mag Lock or a Vestibule application), the delay will be evident between the displaying of both outputs.
In addition to the settings already described in the previous sections, below is a listing of various options which are programmable on the TDM. The LED display vs. function are as follows:
–– = Ready Mode (flashing) d1 = Time Delay or "ON TIME" of relay output #1—0.0 to 99 seconds d2 = Time Delay or "ON TIME" of relay output #2—0.0 to 99 seconds d3 = Time Delay between d1 and d2—0.0 to 99 seconds d4 = Time Delay between d2 and d1—0.0 to 99 seconds i1 = Switch Input #1—(N.O. or N.C.) i2 = Switch Input #2—(N.O. or N.C.) i3 = Switch Input #3—(N.O. or N.C.) i4 = Switch Input #4—(N.O. or N.C.) o1 = Relay Output #1—(N.O. or N.C.) o2 = Relay Output #2—(N.O. or N.C.)
- - = Error (flashing)
The PUSHBUTTON FAULT INDICATOR is a special feature designed to alert the installer if a pushbutton is "stuck" in the active position or if the wires have shorted. If this occurs, the display will flash double dots ( . . ). Additionally, this could mean that the wiring did not match the programmed parameter. In other
words, the unit may be programmed for use with a normally open switch, but may be wired to a normally closed switch. Normal operation will resume once the fault condition has been cleared.
WET/DRY CONTACT OPTION:
The TDM has the option of supplying power to relay output #1 contacts. This is known as "WET" contacts instead of the conventional "DRY" contacts or simple contact closure. Providing this voltage can simplify the wiring of installations where an Electric Locking device is used. However, the voltage supplied to the output is the same voltage supplied to the input of the TDM and must be compatible with the Locking device to be controlled. Please contact the factory for additional information.
7898 Zionsville Road Indianapolis, Indiana 46268
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
(82A044) TDMv1017
Page 6
Loading...