DH100-CT
Sliding Pedestrian Door Motion & Presence Sensor INSTALLATION INSTRUCTIONS
NOTE: Set up for this sensor should be
performed by an AAADM-certified installer.
Section 1
General Description
The DH100-CT is an active infrared presence sensor that is designed to provide both activation and safety detection for automatic sliding and folding doors in a single device.
• Test Input provides sensor monitoring
capabilities as required by the latest industry standard.
• Pattern depth and width are
adjustable using mounting height,
dip switches, detection area depth, and detection area width adjustments.
• Frequency can be changed to prevent interference
from other sensors in close proximity.
• Self-Diagnostic means the sensor continuously
monitors itself.
• Monitor Mode Switch ensures against false operation caused by snow, leaves, insects, etc.
• Programmable Presence Timer (2 sec., 30 sec.,
60 sec., or infinity).
Section 3
Mounting Information
1. Do not mount higher than 9.84 ft. (3m).
2. Mount within 50mm (1.97”) from bottom of header
cover.
3. Do not leave any objects which may move in the
detection pattern.
4. Avoid steamy environments.
5. Ensure rain or snow will not fall directly on unit.
6. Ensure snow or water can not accumulate on floor.
7. Ensure a minimum of reflected sunlight from the
floor.
8. Use different frequency settings for sensors in close proximity.
1
3.0m
(9.84ft)
Max 50mm
(1.97”)
6
3
32
4
Section 2
Parts Identification
Potentiometer (Sensitivity Volume)
Connector
Depth Adjustment Lever Arm (Inner 3 Rows)
Indicator LED
(Red, Green & Blue)
Accessories
Mounting Template
Installation
Instruction
Dip Switch
Area Mask (Inner 3 Rows)
Cover
Dip Switch
X
Area Mask (Outer 2 Rows)
Detection Window
Cable
Mounting Screws
(2 pcs.)
Depth Adjustment Lever Arm (Outer 2 Rows)
Y
Base
5
7
Use Alternate Frequency.
A B
To maximize the effectiveness of doorway detection, install the DH100-CT outside and inside as shown below.
Side View
A B
Plan View
Moving Door Leaf Moving Door Leaf
A
B
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
7898 Zionsville Road Indianapolis, Indiana 46268
Page 1
(/MANU) DH100-CTv1017
Page 2
DH100-CT
Sliding Pedestrian Door Motion & Presence Sensor INSTALLATION INSTRUCTIONS
Section 4
Mounting and Wiring
1. Using the mounting template provided, drill mounting and
wire holes.
2. If you need to remove the sensor body from its base, lift the sensor body from the base and tilt it forward
to remove as
1
illustrated.
3. Fasten unit with mounting screws provided.
4. When wiring to a door controller that can test the sensor, set “Test input” dip switch setting 6 to “ON”.
Red
Sensors
Cable
OFF
ON
Cable
6
Black
White
Green
Yellow(+)
Blue(-)
Gray(+)
Y
Brown(-)
5. When wiring to a door controller that cannot test the sensor, set “Test input” dip switch setting 6 to “OFF”.
Red
Sensors
Cable
OFF
ON
Cable
6
Black
White
Green
Yellow(+)
Blue(-)
Gray(+)
Y
Brown(-)
6. House connector in receptacle.
50mm
2
AC/DC 12 to 24 [V] ±10%
N.O.
COM
Emitter
Test-N
do not connect
do not connect
Collector
Test-P
AC/DC 12 to 24 [V] ±10%
N.O.
COM
Collector
Emitter
Power Non Pole
R2,3,4,5 Output
R1,2 Output
Test Input
Power Non Pole
R2,3,4,5 Output
R1,2 Output
7. Replace cover.
Depth Adjustment Lever Arm
NOTE: Be careful not to inadvertently move the Depth Adjustment Lever Arms when
!
replacing the cover.
Section 5
Dip Switch Settings
1
1 2 3 4 5 6 7 8
ON
Dip Switch X
Presence Timer: The sensor will detect a stationary object for the preset Presence Timer Setting on the inner 3 rows.
2s
1 2
Number of Rows: The number of active rows can be set to 5, 4, 3 or 2 depending on detection area requirements.
5 Rows ON
R5
3 4
Frequency: When more than two sensors are used in
close proximity to each other select different frequency settings for each sensor to prevent interference.
A
Safety Relay Output: Refer to Timing Chart of events for full details on Safety Output.
Reflection Diagnostics: A low reflected infrared signal is indicated by a slow flashing Red/Green LED. To ignore this low reflection “Low Reflection” (ON).
Normal
5 6
30s
1 2
4 Rows ON
R4
3 4
B
5 6
N.O.
N.O.
N.C.
N.C.
7
Transmitter Receiver
IR Spot
60s
1 2 1 2
3 Rows ON
R3
3 4
C D
5 6 5 6
Safety Output (Opto-Coupler)
Transmitter
Low Ref.
88
2 Rows ON
R2
3 4
Receiver
LED
IR Spot
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
: Default Setting
7898 Zionsville Road Indianapolis, Indiana 46268
Page 2
(/MANU) DH100-CTv1017
Page 3
DH100-CT
Sliding Pedestrian Door Motion & Presence Sensor INSTALLATION INSTRUCTIONS
Test Input Setting from Door Controller: When
connected to a door controller without a TEST input, set
1 2 3 4 5 6
ON
Dip Switch Y
Direction Detection: When set to ON, pedestrians
Moving away from the sensor will not be detected.
NOTE: For pedestrian safety purposes when “Doorway Learn” is set to ON, the
!
1st and 2nd row of detection will detect
pedestrians regardless of direction of movement.
OFF
Activation Relay Output: Refer to Timing Chart of events
for full details on Activation Output.
N.O.
Activation Output (Mechanical Relay)
N.C.
2
Monitor Mode: Snow mode should only be used in exterior environments where heavy snow or other extreme
conditions exist.
Normal
ON
11
Snow
33
to “OFF”. When connected to a door controller with a TEST input, set to “ON”. Refer to Timing Chart of events.
OFF
ON
6
Without TEST
OFF
0v
ON
0v
With TEST
Without TEST
: Default Setting
Section 6
Power
BEFORE APPLYING POWER, READ AND FOLLOW THESE INSTRUCTIONS:
When power is applied, the sensor will read and store the
environmental optical parameters. This is necessary for
Presence Detection to work properly.
1. CLEAR THE AREA OF ANY UNNECESSARY OBJECTS.
2. Apply POWER.
3. Vacate the Detection Pattern immediately. While the sensor sees ANY moving objects in its DETECTION PATTERN, it will not proceed to the following step.
4. DO NOT enter DETECTION PATTERN for 10 seconds (Presence Detection Setting).
5. TEST the presence feature, especially near the door.
When carrying out the following work, TURN OFF THE POWER:
1. When the floor conditions change.
2. Adjusting pattern or sensitivity.
Door Hold: Switch to OPEN to hold the door in the open
position.
Auto
Open
44
Doorway Learn: Doorway Learn allows the 1st row of
detection to be focused inside the door close area
without detecting the door movement.
NOTE: When Doorway Learn is turned ON, the sensitivity level of the inner row of detection is
!
only at maximum when the outer rows of
detection are activated.
OFF
Door
5
ON
5
7898 Zionsville Road Indianapolis, Indiana 46268
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
Door
“DOORWAY LEARN” is OFF
(Ref. Sec. 5-Dip Switch Settings)
Upon power ON, the solid Green LED turns on indicating that the sensor is in standby mode and ready to detect.
Green solid LED
(/MANU) DH100-CTv1017
Y 5
Page 3
Page 4
DH100-CT
Sliding Pedestrian Door Motion & Presence Sensor INSTALLATION INSTRUCTIONS
Presence Detection: It takes 10 seconds after the
sensor powers up for presence detection to be initiated on all rows of detection. If someone enters the detection area before 10 seconds has elapsed, the sensor will
continue to initialize until after 5 seconds with no motion
being detected.
“DOORWAY LEARN” is ON
(Ref. Sec. 5-Dip Switch Settings)
Upon power ON, the Red LED indicates a door open relay output to begin the “Doorway Learn” process.
Red solid LED
• Green LED blinks for about 10 seconds as “Doorway Learn” process is carried out. Door opens/closes.
Green blinking LED
Y 5
After the “Doorway Learn” process is completed, sensor is in standby mode.
Green solid LED
Presence Detection: During the “Doorway Learn” process, the outer 4 rows of detection on the DH100-CT sensor switch from motion detection to presence detection 10 seconds after power ON. The inner “Doorway Learn” row of detection will switch from motion to presence detection after the “Doorway Learn” process is complete.
“Doorway Learn” Failure & Recovery: If a person enters the detection area during the “Doorway Learn” process, it may not be successfully completed. In this case, the sensor will carry out the “Doorway Learn” process on door activation caused by a person in order to build an accurate image of the door open and door close position.
Green blinking LED
NOTE: When “Doorway Learn” is turned ON, the sensitivity level of the inner row of detection is at maximum ONLY when the outer rows of detection are activated.
CAUTION: When carrying out the following work,
turn off sensor power.
!
When the floor condition is changed by placing a mat on the floor, etc.
When the detection area pattern or sensor sensitivity is adjusted.
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
7898 Zionsville Road Indianapolis, Indiana 46268
Page 4
(/MANU) DH100-CTv1017
Page 5
DH100-CT
Sliding Pedestrian Door Motion & Presence Sensor INSTALLATION INSTRUCTIONS
Section 7
Adjusting Detection Pattern
Detection Area Depth Adjustment: Inner 3 Rows
Inner 3 rows adjustment lever arm
3.3’
4.9’ (1.0m)
(1.5m)
[0 degree] setting
3.3’
(1.0m)
[0 degree] setting
1.6’
(0.5m)
3.3’ (1.0m)
Door
6.6’ (2.0m)
7.2’ (2.2m)
9.8’ (3.0m)
1.6’
(0.5m)
3.3’ (1.0m)
Door Door
6.6’ (2.0m)
7.2’ (2.2m)
3.3’
4.9’ (1.0m)
(1.5m)
[-8 degree] setting
3.3’
(1.0m)
[-8 degree] setting
(0.5m)
(0.5m)
1.6’
1.6’
Door
Without
Base
With
Base
Detection Area Depth Adjustment: Outer 2 Rows
Outer 2 rows adjustment lever arm
3.3’
(1.0m)
3.3’
(1.0m)
[m]
[m]
0
3.3’ (1.0m)
6.6’ (2.0m)
7.2’ (2.2m)
9.8’ (3.0m)
0
3.3’ (1.0m)
6.6’ (2.0m)
7.2’ (2.2m)
9.8’ (3.0m)
6.6’
(2.0m)
[0 degree] setting
6.6’
(2.0m)
[0 degree] setting
With
Base
Without
Base
6.6’
9.8’ (2.0m)
(3.0m)
[+10 degree] setting
6.6’
(2.0m)
[+10 degree] setting
3.3’
(1.0m)
3.3’
(1.0m)
[m]
[m]
9.8’ (3.0m)
Detection Area Width Adjustment
Area Mask
(Inner 3 Rows)
3.3’
6.6’ (1.0m)
(2.0m)
Width
Narrow
Wide
0
Area Mask
(Outer 2 Rows)
3.3’
(1.0m)
6.6’
(2.0m)
3.3’ (1.0m)
6.6’ (2.0m)
9.8’ (3.0m)
Optical beams are designed as shown above. Please note that actual detection area is
!
variable, depending on cloths, materials on the
floor and sensitivity adjustment. Please confirm
the actual area after adjustment.
Section 8
Door Maintenance Work
When carrying out door maintenance work with power applied to the sensor, on door controllers that are wired to “test” the sensor, ensure the dip switches are set as shown below:
Dip Switch X
ON
1 2 3 4 5 6 7 8
2s
1 2
NOTE: Be sure to return the dip switch settings
to their original state once door maintenance
!
work is complete.
Low
Ref.
8
Narrow
Wide
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
7898 Zionsville Road Indianapolis, Indiana 46268
Page 5
(/MANU) DH100-CTv1017
Page 6
DH100-CT
Sliding Pedestrian Door Motion & Presence Sensor INSTALLATION INSTRUCTIONS
Section 9
Verification of Operation
1. After mounting, setting parameters and applying
power, walk test unit to verify detection pattern.
2. If the sensor does not function as expected, TURN OFF THE POWER and RECHECK the Depth Adjustment Lever Arms, Dip Switch and Width Mask Knobs as described in Sections 5 and 7.
3. After rechecking, if there is still a problem, adjust the
sensitivity.
*****EXTREMELY IMPORTANT*****
After final set-up, test unit(s) completely to ensure that proper coverage has been achieved (width, depth and location of the pattern must be tested).
After the installation and operational check of the system:
1. Place the proper labels on the door per all applicable
standards.
2. Instruct the owner of the door system operation and how to test it. This should be checked on a daily
basis.
3. Instruct the owner on what to do if the door or any of
its components become damaged.
4. Strongly recommend to the owner that the complete entry be inspected twice a year as part of the service
agreement.
Section 11
Troubleshooting
PROBLEM 1: Door does not open when person enters
the detection area.
LED STATUS: OFF
CAUSE 1: Sensor Connector. SOLUTION 1: Tighten connector or reconnect.
CAUSE 2: Power Supply. SOLUTION 2: Check that the power supply is properly connected and 12V to 24V AC or DC.
CAUSE 3: Sensor Wiring. SOLUTION 3: Double check sensor wiring is accurate.
PROBLEM 2: Door operates by itself (Ghosting). LED STATUS: Door Opens RED, Door Closes GREEN
CAUSE 1: Moving objects in detection area. SOLUTION 1: Remove the moving object from the
detection area.
CAUSE 2: Sensitivity too high. SOLUTION 2: Reduce sensor sensitivity.
CAUSE 3: Dust, frost or water droplet on the
sensor lens.
SOLUTION 3: Wipe the sensor lens clean and install a weather cover if necessary.
Section 10
Self Diagnostics
A flashing Green/Red LED inducates any technical issues with the HR100-CT. The frequency of the flashing indicates the type of issue as explained below:
LEDs Flashing Fast = Please replace the sensor.
Green
Red
LEDs Flashing Slow = Confirm that sensitivity
potentiometer is set to maximum and re-power the sensor. If the error persists, set Dip Switch 8 to “Low Reflection”.
X
Green
Red
7898 Zionsville Road Indianapolis, Indiana 46268
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
CAUSE 4: Detection area overlaps with that of
another sensor.
SOLUTION 4: Ensure different frequency setting for
each sensor.
CAUSE 5: Detection of falling snow, leaves,
insects, etc.
SOLUTION 5: Turn monitor mode Dip Switch “Snow”.
PROBLEM 3: When Door opens or closes - LED ORANGE. LED STATUS: ORANGE
CAUSE 1: Detection row “ROW 1” (”ROW 2” when “Doorway Learn” is turned ON) is
focused too close to the door.
SOLUTION 1: Adjust detection depth of Inner 3 rows away from the door.
(/MANU) DH100-CTv1017
Y
3 to
Page 6
Page 7
PROBLEM 4: Door opens and remains in open position. LED STATUS: RED
CAUSE 1: Detection area changed, while infinity
presence timer setting is in use.
SOLUTION 1: Re-power the sensor or change the presence timer settings to 30 or 60 secs.
CAUSE 2: Incorrect sensor wiring. SOLUTION 2: Double check sensor wiring.
CAUSE 3: Reflected signal saturation. SOLUTION 3: Remove highly reflective objects from the detection area, or lower the sensor
sensitivity.
LED STATUS: GREEN/RED FAST FLASH
CAUSE 4: Internal sensor error. SOLUTION 4: Replace the sensor.
LED STATUS: GREEN/RED SLOW FLASH
CAUSE 5: Reflection of the transmitted infrared signal from the floor is too low. SOLUTION 5: Increase sensor sensitivity or change the “Reflection Diagnostics” Dip switch 8 from “Normal” to “Low Reflection”.
LED STATUS: ORANGE BLINKING (Slow)
CAUSE 6: Door Hold (Dip switch 4 set to Open). SOLUTION 6: Turn “Door Hold” Dip switch 4 to Auto.
Section 12
Technical Data
Model................................ DH100-CT Combination Motion
& Presence Sensor
Detection Method............. Floor Reflection Method (FRM)
Active Infrared
Max. Installed Height....... 9.84 ft. (3.0m)
Pattern Adjustments........ Pattern Depth (2 to 5 rows via
dip switch setting) and Angle Adjustment Levers (Outer 2 Rows 10° in 3 steps; Inner 3 Rows 8° in 3 steps) Pattern Width via 2 Position Mechanical Mask Knobs (Outer 2 Rows = Narrow or Wide Inner 3 Rows = Single or
Double Door)
Sensitivity via potentiometer
Detection Beams..............UP TO 48 BEAMS
Inner 2 Rows: 12 Beams x 2 Rows Outer Rows: 8 Beams x 3 Rows
Presence Detection.......... 1, 2 & 3 Inner Rows (safety)
timer selectable 2, 30, 60 sec.
and infinity
Motion Detection.............. 4 & 5 Outer rows (Approach)
timer selectable 2, 30 sec.
Power Supply.................... 12 to 24 V AC or DC ± 10%
Power Consumption......... AC12V-1.5VA (Max.)
DC12V-80mA (Max.) AC24V-2.0VA (Max.) DC24V-50mA (Max.)
Output Contact................. Form C Relay: DC50V 0.1A
(Resistor Load) Yellow Wire = Normally Open Green Wire = Normally Closed
White Wire = Common
Relay is "driven" when power fails
Output Holding Time........ Approx. 0.5 seconds
Presence Timer................. Outer 2 Rows (2, 30 sec.)
Inner 3 Rows (2, 30, 60 sec. &
infinity)
LED Indication.................. RED = Detecting
GREEN = Standby ORANGE = Detection Row 1 is
too close to the door
Temperature Range......... -4°F to 140°F (-20°C to 60°C)
Weight............................... 0.55 lbs. (0.25kg)
Color.................................. Black
Accessories....................... Cable, Mounting Screws,
Mounting Template, Installation Instructions
Page 7
(/MANU) DH100-CTv1017
Sliding Pedestrian Door Motion & Presence Sensor INSTALLATION INSTRUCTIONS
DH100-CT
7898 Zionsville Road Indianapolis, Indiana 46268
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
X
Y
Y
Page 8
DH100-CT
Sliding Pedestrian Door Motion & Presence Sensor INSTALLATION INSTRUCTIONS
Section 13
External Dimensions
75mm(2.95") = Standard Mounting Pitch
25mm
(0.98")
62")
(2.
mm
5
66.
15mm
(0.59")
(1.37")
230mm(9.06")
33.
5
mm
(1
.
32")
35mm
10mm (0.39")
70.4 mm(2.77")
44mm
(1.73")
Section 14
Warranty
MS SEDCO guarantees this product to be free from manufacturing defects for 3 years from date of installation. Unless MS SEDCO is notified of the date of installation, the warranty will be in effect for 3 years from the date of shipment from our factory. If, during the first 3 years, our motion detector or support device fails to operate and has not been tampered with our abused, the unit can be returned prepaid to factory and it will be repaired free of charge. After 3 years, the unit will be repaired for a nominal service charge.
This limited warranty is in lieu of all other warranties expressed or implied, including any implied warranty of merchantability, and no representative or person is authorized to assume for MS SEDCO any other liability in connection with the sale of our products. All warranties are limited to the duration of this written warranty. In no event shall MS SEDCO be liable for any special, incidental, consequential or other damages arising from any claimed breach of warranty as to its products or services.
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
7898 Zionsville Road Indianapolis, Indiana 46268
Page 8
(/MANU) DH100-CTv1017
Page 9
Page 9
(/MANU) DH100-CTv1017
Sliding Pedestrian Door Motion & Presence Sensor INSTALLATION INSTRUCTIONS
DH100-CT
7898 Zionsville Road Indianapolis, Indiana 46268
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
FIGURE 1: Timing Chart of Events
NON-DETECTION
DE T E C TI O N As
response to TEST
POWER OFF
1234
5
1234
5
1234
5
DETECTION
NON-DETECTION
TEST RESPONSE
1234
5
T1 T2
NON-TEST TESTTEST
Test Input
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Safety Output Row 1, 2 / Test Input
Activation Output Row 2, 3, 4, 5
1234
5
Yellow
Blue
Yellow
Blue
TEST NON-TESTNON-TEST
OFF
6
ON
7
N.C.
Dip Switch X
Dip Switch Y
NON-DETECTION
POWER OFF
1234
5
DETECTION
White
Green
White
Green
White
Green
White
Green
White
Green
White
Green
1234
5
1234
5
2
N.C.
Dip Switch Y
N.O.
N.O.
T1 : 10±1 [mSec] App
T2 : 11±1 [mSec] App
Sensor
Brown
Gray
Break the current
flow on test state.
Supplying DC12 to 24V, make current flow from
Gray to Brown.
Sensor
Brown
Gray
Sensor
Brown
Gray
Activation Output
Test Input setting
Safety Output