Positioning
Figure 3 illustrates the typical detection pattern
of the PIR sensor when the unit is wall-mounted.
Ensure that the proposed mounting position will
offer the required area of detection.
High Sensitivity Zone:
Detects e.g. arm movement.
Low Sensitivity Zone:
Detects e.g. whole body movement.
Tips
• The sensor is most sensitive to motion across
its eld of view, rather than directly towards or
away from the sensor.
• Avoid mounting the unit close to a light or heat
source (the one being switched, or otherwise)
since this may interfere with the detection.
• Multiple units may be wired in parallel to
extend the detection eld – see Using Multiple
Detectors.
Figure 3 PIR sensor detection pattern
Electrical Requirements
Before attempting to install the unit, ensure that the intended load and wiring arrangement
comply with the following requirements. Figure 2 shows a typical wiring example.
• 3-wire (live/neutral + volt-free switch) connection: The unit requires a permanent
live/neutral connection, and as such is not suitable for replacing an existing light switch
with no neutral conductor at the switch location. A volt-free relay output is provided,
which can be used to switch a load on the same mains supply (by connecting across
from L to COM, making N/O a switched ‘Live Out’), or to provide a contact closure to a
separate load or control signal. There is no minimum load requirement.
Also available: WMPD2 / WMPAD2 / WMPAD2-L (2-wire versions) – Suitable for ‘inline’
connection with the load to be switched (no neutral required), such as to replace a
standard light switch. A minimum load of 20W (per detector) applies; a load capacitor is
required for smaller loads.
• Maximum load: The maximum load rating is 16A (4000W), however for high inrush
loads (such as most types of lighting) a lower limit applies: see Technical Specication.