MSA SUPREMA Touch Manual Addendum

Manual Addendum
SUPREMA Touch
Fire and Gas Warning Unit
Addendum to the SUPREMA Touch manual (Rev. 02).
Order No. 10121863/02 Addendum01
2 Addendum SUPREMA Touch
Addendum to chapter 1.4 Software Status
Module
Software version
Flash resp. EPROM
So
ftware version
CPLD
MAO 20 3.01.02 -
Addendum to chapter 5.1 Special Conditions for Safe Use According to EC­type examination certificate DMT 03 ATEX G 003 X
The analogue outputs of the MAO module shall not be used for safety related purposes.
Additional Modules tested according to DMT 03 ATEX G 003 X
Module
Layout Version
Meaning
MAO20 4 Analog Output Unit
Addendum to chapter 6.6 Plug-In Modules – Status LED
Figure 50 also covers the MAO20 (right figure; similar to the MAO10) The LED D400 (red, centre of the board) on the MAO20 indicates an error of the digital to analog conversion system when activated.
Addendum to chapter 8.1 Modules and Accessories
Order No.
Name
10102071 SUPREMA MAO20
Correction of Chapter 9.5 Descriptions of the Modules
MAO Module (Analog Output)
This module is used when analog outputs (max. 256) are installed in the system. Each MAO module has 8 analog signal outputs for 0 ... 24 mA current loops. The assignment between the outputs and the signal inputs can be configured.
0 ... 24 mA output drivers, measurement signal outputs (galvanic isolated from system) Signal for measuring range: 4 ... 20 mA Signal for over flow: 22 mA (Values between 20 and 22mA are still valid measuring values, but out of range) Signal for INHIBIT: 3.0 mA Signal for Signal failure: 3.2 mA Fail dependent of Free A/Free B (see chapter 10)
Values below 3mA and above 22mA must be handled as failure
Maximum load: 500 Ohm
Data transmitted from the MDO module via the CAN bus A
The System Failure Relay is activated when a processor error occurs
Euro card with a 96-way connector