The PrimaX Gas Transmitters are fixed gas transmitters for measuring toxic or combustible gases and
for monitoring oxygen deficiency, excess or inerting. They are suitable for outdoor and indoor applications without limitations, e.g. offshore industry, chemical and petrochemical industry, water and sewage
industry. The signal of the transmitter can be used in combination with MSA control units for further
actions in safety or non safety applications, e. g. MSA SUPREMA, Gasgard XL, 9010/9020.
The two versions of the gas transmitter are delivered either in a flameproof or in a intrinsically safe
enclosure. The electrical parts and interfaces have the same basic functionality.
It is imperative that this operating manual be read and observed when using the device. In particular,
the safety instructions, as well as the information for the use and operation of the device, must be carefully read and observed. Furthermore, the national regulations applicable in the user's country must be
taken into account for a safe use.
WARNING!
This product is supporting life and health. Inappropriate use, maintenance or servicing may affect the
function of the device and thereby seriously compromise the user's life.
Before use the product operability must be verified. The product must not be used if the function test
is unsuccessful, it is damaged, a competent servicing/maintenance has not been made, genuine MSA
spare parts have not been used.
Alternative use, or use outside this specification will be considered as non-compliance. This also
applies especially to unauthorised alterations to the product and to commissioning work that has not
been carried out by MSA or authorised persons.
1.2Liability Information
MSA accepts no liability in cases where the product has been used inappropriately or not as intended.
The selection and use of the product are the exclusive responsibility of the individual operator.
Product liability claims, warranties also as guarantees made by MSA with respect to the product are
voided, if it is not used, serviced or maintained in accordance with the instructions in this manual.
1.3Safety and Precautionary Measures to be Adopted
Safety Regulations
WARNING!
The following safety instructions must be observed implicitly. Only in this way can the safety and health
of the individual operators, and the correct functioning of the device, be guaranteed.
•The device described in this manual must be installed, operated and maintained in strict accordance with their labels, cautions, instructions, and within the limitations stated.
•The device is designed to detect gases or vapours in air.
•If a device with a combustible sensor is exposed to vibrations, calibration shall be done in sufficient
short intervals until it is verified that the device is not affected by the vibration stress.
•Do not mount the sensing head in direct sunlight as this could cause overheating of the sensor.
•The device must be installed with the sensor inlet pointing downwards to avoid clogging of the gas
inlet by particles or liquids.
•Electrochemical sensors are sealed units which contain a corrosive electrolyte. Should a sensor
develop leakage, it must be immediately removed from service and disposed of properly. Caution
PrimaX
GB
5
Safety Regulations
must be exercised so that the electrolyte does not contact skin, clothing or circuitry otherwise
personal injury (burns) and/or equipment damage may result.
•The only absolute method to ensure proper overall operation of the device is to check it with a
known concentration of the gas for which it has been calibrated. Consequently, calibration checks
must be included as part of the routine inspection of the system.
•As with all devices of these types, high levels of, or long exposure to, certain compounds in the
tested atmosphere could contaminate the sensor. In atmospheres where the device may be
exposed to such materials, calibration must be performed frequently to ensure that the operation
is dependable and display indications are accurate.
•The device must not be painted. If painting is done in an area where a device is located, care must
be exercised to ensure that paint is not deposited on the sintered metal flashback arrestor in the
gas sensor inlet, if so equipped. Such paint deposits would interfere with the gas diffusion process.
•Use only genuine MSA replacement parts when performing any maintenance procedures
provided in this manual. Failure to do so may seriously impair instrument performance. Repair or
alteration of the device, beyond the scope of these maintenance instructions or by anyone other
than an authorised MSA service personnel, could cause the product to fail to perform as designed.
•The device is designed for applications in hazardous areas under atmospheric conditions.
•For correct measurements, the combustible gas sensors require an oxygen concentration greater
than 10 Vol%. Oxygen enriched atmospheres, greater then 21 Vol%, can affect the measurement
and the electrical safety of the device.
•The response time of the device will be increased by significant dust deposits on the Sensor.
Checks for dust deposits must be done at regular intervals.
•Catalytic combustible gas sensors may produce low or zero response to combustible gas after
exposure to substances as Silicon, Silane, Silicate, Halide and compounds containing Fluorine,
Chlorine, Iodine or Bromine.
•Catalytic sensor: After exposure of gas above the measuring range, the sensor has to be immediately calibrated / adjusted, independent of the calibration interval. In the case of an adjustment
the sensitivity of the sensor has to be rechecked again after 24 hours.
•In case of very high flammable concentrations >100%LEL the device is able to lock all outputs
(LOC). This function shall be used for standalone applications according to ATEX requirements.
•Catalytic sensor: If the PrimaX is operated in combination with a control unit and (LOC) is deactivated on the PrimaX, the control unit has to ensure the latching after the measuring range was
exceeded.
•Catalytic sensor: Before a reset of an over range (LOC) indication is done it shall be verified that
the gas concentration is below full scale.
•Toxic gases: If the measuring range is exceeded, sensor life time can be reduced or the sensor
might need a recovery phase.
•Used sensors have to be disposed of in an environmentally compatible way.
•At signal underrange between -1.25 % and -10 % of the measuring range the 4 - 20 mA output is
set to 3,8 mA. At signal underrange of more than -10 % of the measuring range the 4 - 20 mA
output is set to the error state (2 mA). To avoid a delayed alarm activation, a calibration should be
done when the output current is set to 3,8 mA and "LO" is shown on the display persistently.
•The lowest range which is suitable for the alarm thresholds should be selected for toxic gases.
•To compensate for possible deviations during measurement of flammable gases a calibration
factor of 1.05 has to be applied when using the CalGard for remote calibration (see chapter 8.3
"Remote Calibration")
GB
PrimaX
6
1.4MSA Permanent Instrument Warranty
Warra nty
Seller warrants that this product will be free from mechanical defect or faulty workmanship for
•Gas Transmitter: eighteen (18) months from date of shipment or one (1) year from installation,
whichever occurs first;
•Oxygen, Toxic or Catalytic Combustible Sensor: eighteen (18) months from date of shipping or one
(1) year from installation, whichever occurs first.
This warranty is applicable provided the product is maintained and used in accordance with Seller's
instructions and/or recommendations. This warranty does not apply to expendable or consumable
parts, whose normal life expectancy is less than one (1) year.
The Seller shall be released from all obligations under this warranty in the event repairs or modifications are made by persons other than its own or authorized service personnel or if the warranty claim
results from physical abuse or misuse of the product. No agent, employee or representative of the
Seller has any authority to bind the Seller to any affirmation, representation or warranty concerning the
goods sold under this contract. Seller makes no warranty concerning components or accessories not
manufactured by the Seller, but will pass onto the Purchaser all warranties of manufacturers of such
components.
Safety Regulations
PrimaX
GB
7
2Description
2.1Identifying the Unit
Description
PrimaX PPrimaX I
flameproof version
Fig. 1 PrimaX Gas Transmitter
PrimaX P
The PrimaX P is a gas transmitter with an aluminum enclosure. This is a flameproof version for the
detection of combustible or toxic gases or oxygen.
PrimaX I
The PrimaX I is a gas transmitter with a plastic enclosure. It is available as a general purpose version
(not intended for hazardous area) or intrisically safe version. Both versions are designed for a detection
of toxic gases or oxygen.
general purpose version, or
intrinsically safe version
2.2Overview
The device is factory-calibrated and delivered ready for installation. Each device is configured and calibrated for only one specific gas or vapor.
The enclosures vary depending on the particular version. The electrical parts and interfaces have the
same basic functionality.
The device has:
•a quick and easy pluggable sensor,
•a four digit liquid crystal display (LCD),
•a key pad with a cover
•a detachable backplate for installation on a wall or on a pipe
The device operates with a 4 – 20 mA output signal.
GB
PrimaX
8
Description
1
2
3
7
8
9
4
6
5
10
Fig. 2 Exploded View (PrimaX P)
1Terminal for power connection6Sensor
2Keypad with cover7Red LED (PrimaX P only)
3Connector for factory use8Yellow LED (PrimaX P only)
4Display9Green LED (PrimaX P only)
5Bayonet joint with interlock10Identification plate
PrimaX
GB
9
Description
Sensors
DescriptionPrimaX PPrimaX I
Detection of toxic gasesXX
Detection of oxygenXX
Detection of combustible gasesX
The device operates with a 4 – 20 mA output signal.
As an optional feature additional modules are available for these configurations of PrimaX transmitter:
ModulesPrimaX PPrimaX I
HART moduleXX
HART + Relays module X-
HART+ Relays module with galvanically isolated analogue
output
For more information on the HART module → chapter 4.7 "Optional HART Module and Relay".
X-
PrimaX
GB
10
3Installation
The device should be installed where gas leaks are expected. The installation position depends on the
gas density, either in the upper area of the room under the ceiling for gases lighter than air or close to
the ground for gases heavier than air. Also consider how air movement may affect the ability of the
device to detect gas. The display on the front of the instrument must always be clearly visible, the view
must not be obstructed.
Before beginning the installation, check that the delivered components are complete
and correct, referring to the shipping documents and the sticker on the shipment carton.
When preparing the assembly, make sure that the mounting arrangement is correct for
the particular device.
3.1Mechanical Installation
Preparation
To install the device, first remove the backplate.
Installation
Undo Screws
(1)Unscrew the device.
Remove Device
(2)Remove the device from the backplate by lifting up
the lower edge as shown.
PrimaX
GB
11
Wall or Pipe Mounting
For pipe mounting a pipe mounting kit is necessary (→ chapter 8.6 "Pipe Mounting Kit").
Install the Backplate
(1)Use the two keyhole slots for attaching the mounting plate
to the wall. Use 6mm diameter screws and suitable
plugs.
(2)For a wall installation use the backplate as a template for
drilling the holes for the two fixing screws, for a pipe
installation use the pipe clip.
(3)Attach the backplate to the wall or the pipe clip with M6 x
20 screws.
a) The hitch should point away from the wall or pipe.
b) The straight edge of the backplate should be at the
bottom.
Attach the Device to the Backplate
(4) Attach the device to the top of the backplate.
(5)Fold down the device, till it is closed to the backplate.
Installation
Fasten Device
(6)Screw the device to the backplate.
PrimaX
GB
12
3.2Electrical Installation
1 2
3 4
1 2
3 4
Instructions for Electrical Connection
WARNING!
The device must be installed only in compliance with the applicable regulations, otherwise the safe
operation of the instrument is not guaranteed.
•Shielded cable for measuring devices is recommended.
•Always observe maximum cable lengths and cross-sections (→ chapter 6.2 "Cable Lengths and
Cross-sections").
•Water or impurities can penetrate the instrument through the cable. In hazardous areas, it is
recommended to install the cable in a loop just before entry into the instrument or to slightly bend
it to prevent water from entering.
The power supply is defined as 24 VDC. If the input supply voltage at the terminal of the
transmitter is less than 10 V, the device will shut down. The 24 V power supply shall fulfill
the requirements for a PELV/SELV of EN 60950.
Operating the PrimaX I version in hazardous areas requires an intrinsically safe power
supply.
Electrical Connection - PrimaX P
Terminal PrimaX P
Installation
Fig. 3 Terminal PrimaX P (3-wire sensor) Fig. 4 Terminal PrimaX P (4-wire sensor)
1Power supply (+), 24 V DC 1Power supply (+), 24 V DC
20 V DC20 V DC
34–20mA (Signal)34–20mA (Signal)
4empty4Isolated ground
PrimaX
GB
13
PrimaX P
Power supply (+) 24 V DC
0 V DC (-)
4–20mA(Signal)
Isolated ground
Fig. 5 3-wire/4-wire connection - PrimaX P
(1)Unscrew the interlock between cover and bayonet joint of sensor.
(2)Unscrew the aluminum lid of the enclosure.
(3)Unplug the 4-way terminal block.
The block is located behind a plastic cover above the display.
(4)Unscrew clamping nut at the cable gland.
(5)Put clamping nut on the cable.
(6)Insert cable for connection into the device.
(7)Connect cable to terminal.
Use a shielded cable with 3 wires for the 3-wire sensor.
Use a shielded cable with 4 wires for the 4-wire sensor.
(8)Tighten cable gland clamping nut, check that cable cannot move within the cable gland.
(9)Replace enclosure lid and secure the interlock.
Electrical Connection - PrimaX I
Terminal PrimaX I
Installation
GB
1 2
Fig. 6 Terminal PrimaX I
1Power supply (+), 24 V DC
24–20mA (Signal)
PrimaX
14
PrimaX I
Power supply (+)
4 – 20 mA (Signal)
Fig. 7 2-wire connection - PrimaX I
(1)Remove plastic cover.
It is bolted with 4 screws.
(2)Remove the 2-way terminal block.
It is located behind a plastic cover above the display.
(3)Unscrew clamping nut at the cable gland.
(4)Put clamping nut on the cable
(5)Insert cable for connection into the device.
(6)Connect cable to terminal.
a) Use a 2-wire shielded cable.
(7)Tighten cable gland clamping nut, check that cable cannot move within the cable gland.
(8)Replace plastic cover, tighten the screws and secure the interlock.
Installation
PrimaX
GB
15
4Operation
1
2
65
3
7
4
The device is factory-calibrated and delivered ready for installation. Each device is
configured and calibrated for only one specific gas or vapor.
During startup a self-test is performed and the output signal is set to the service current (default
3.0 mA). The following information is displayed:
Display Test
The display shows all segments.
Note: The PrimaX P also shows all LEDs and afterwards the yellow LED is flashing during the startup
procedure.
Software Version
The display shows the firmware version.
Sensor
The display shows the configured type of sensor operating with each individual detector, e.g.:
COMB (combustible), CO, H
Range
The display shows the measuring range predefined for the gas detector, e.g.: 100% LEL.
Countdown
The countdown for sensor stability is displayed.
Normal Operation
After countdown, the gas concentration (ppm, Vol%, % LEL, % UEG, mg/m
symbol flashes to indicate alive status.
S.
2
3
4.2Menu Sequence
Operation
) is displayed. The heart
GB
Fig. 9 Keypad - operating buttons
1ESC button3ENTER button
2UP button4DOWN button
To navigate in the menu sequence, 4 buttons are available.
In general:
(1)Press ENTER to get access to a menu sequence.
(2)Press UP or DOWN until the desired menu is displayed.
(3)Press ENTER to get access to a menu.
(4)Press ESC to cancel the process.
PrimaX
17
The following table lists the menu items. Detailed descriptions can be found in the chapters 4.3 "Calibration", 4.4 "Maintenance and Info" and 4.5 "Password".
Menu itemTextPassword?
M-01CalibrationYes
M-02ZERO CalibrationYes
M-03Show Test Gas ConcentrationNo
M-04Setup CalibrationYes
M-05Sensor ExchangeYes
M-06LCD and LED TestNo
M-07Loop TestYes
M-08Device InfoNo
M-09Sensor InfoNo
M-10Changing the RangeYes
M-00Reset AlarmYe s
4.3Calibration
WARNING!
The test gases used for calibration are possibly posing a health risk. Proper ventilation or extraction
has to be ensured.
General
The calibration must be done at regular intervals in accordance with applicable national and regional
regulations.
The device is calibrated at the factory. Nevertheless, it is recommended to recalibrate the device after
installation. The frequency of calibration depends on the duration of use and the chemical exposure of
the sensor. New sensors must be calibrated frequently until it is clear from the calibration data that they
have stabilised. Suitable regulators and pipes for calibration must be used.
Operation
GB
A calibration cap is recommended for sensor calibration,
flow rate 1l/ min (± 20%).
Connect power to the device at least one hour before attempting a calibration.
Carry out the calibration during commissioning as well as at regular intervals. This
ensures optimum operation of the sensor.
It is recommended that all calibration components are connected before starting a calibration as it is necessary to apply test gas to the device during a countdown.
PrimaX
18
Operation
When monitoring flammable gas in safety related applications the PrimaX must be calibrated with a known concentration of the gas being monitored.
The lower explosive limits (LEL) of the gases and vapors in the following example were taken from EN
60079-20-1. Local regulations may specify different LEL values; always ensure the correct values are
used.
It is recommended that the PrimaX zero is calibrated using clean air, free of measuring gas, and calibration gas of approximately 50 % of measuring range (comb. and TOX) in air of the gas being monitored. The recommended calibration gas for oxygen is 50% of measuring range, but for a measuring
range 0-25 vol% O
Calibration example for Methanol
Methanol calibration gas concentration being used= 3,5 Vol%
Methanol volume concentration for 100%LEL= 6,0 Vol%
Methanol calibration gas concentration in %LEL
, the device can be calibrated using 20.9 vol% O2.
2
For oxygen a zero calibration with gas is not required, it is performed internally.
3,5 Vol% CH
Calibration Procedure
The calibration can be performed as a manual or an automatic calibration (→ M-04).
Automatic Calibration (automatic): a countdown is displayed. After the countdown the value is
measured and displayed. When the value is stable the current value is selected automatically.
Manual Calibration (manual): the measuring value is displayed. When the value is stable press
ENTER to select the current value.
Waiting for calibration gas
After starting any calibration step, calibration gas (zero or test gas) must be applied until calibration
step is finished.
4
O x
100% LEL
6,0 Vol% CH
PrimaX
O
4
= 58,3 % LEL
GB
19
Calibration Steps
The calibration procedure can be canceled at any time by pressing ESC. The previous
transmitter calibration will be used.
(M-01) - ZERO and SPAN Gas Calibration
(1)Press ENTER and select menu 1.
(2)Press ENTER button.
(3)Enter password (→ chapter 4.5 "Password").
(4)Apply zero gas (synthetic air).
(5)Wait until countdown is finished (automatic) or press ENTER (manual).
OK is displayed.
(6)Apply test gas.
(7)Wait until calibration is finished (automatic) or press ENTER (manual).
OK is displayed.
Idle time countdown starts, during this time the test gas can be removed and the output
signal remains on service current level.
(8)Remove test gas during the countdown.
(M-01) - Oxygen Calibration
(1)Press ENTER and select menu 1.
(2)Press ENTER button.
(3)Enter password (→ chapter 4.5 "Password").
(4)Apply synthetic air.
(5)Wait until countdown is finished (automatic) or press ENTER (manual).
OK is displayed.
(6)The device goes to measuring mode.
(M-02) - ZERO Gas Calibration
(1)Press ENTER and select menu 2.
(2)Press ENTER button.
(3)Enter password (→ chapter 4.5 "Password").
(4)Apply zero gas (synthetic air).
(5)Wait until calibration is finished (automatic) or press ENTER (manual).
OK is displayed.
(6)The device goes to measuring mode.
4.4Maintenance and Info
(M-03) - Show Test Gas Value
(1)Press ENTER and select menu 3.
(2)Press ENTER button.
Test gas concentration is displayed.
(3)Press ENTER button to go back to Menu or ESC to go back to measuring mode.
(M-04) - Setup Calibration
This menu is used to set the test gas concentration for span calibration and all calibration countdown
times.
(1)Press ENTER and select menu 4.
(2)Press ENTER button.
(3)Enter password (→ chapter 4.5 "Password").
Operation
GB
PrimaX
20
Operation
(4)Set the test gas concentration with the UP or DOWN button.
(5)Press ENTER button.
(6)Set the zero calibration countdown time in seconds with the UP or DOWN button.
a) Note: time = 0 → (manual) zero calibration, otherwise an (automatic) calibration is
performed by the device.
(7)Press ENTER button.
(8)Set the span calibration countdown in seconds with the UP or DOWN button.
a) Note: time = 0 → (manual) span calibration, otherwise an (automatic) calibration is carried
(9)Press ENTER button.
(10) Set the idle time countdown in seconds with the UP or DOWN button.
(11) Press ENTER button.
(M-05) - Sensor Exchange
This menu initiates the initial calibration and resets the sensor lifetime counter.OX/TOX sensors can
be exchanged under power (hot swapped) with this function.
Hot swaps must not be carried out for COMB sensors.
Only OX/TOX sensors can be exchanged with this menu.
For COMB sensors with this menu only the initial calibration is initiated and the sensor life time is reset.
out by the device.
WARNING!
If an (OX/TOX) sensor is connected:If a COMB sensor is connected:
(1)Press ENTER and select menu 5.
(2)Press ENTER button.
(3)Enter password (→ chapter 4.5 "Pass-
word").
•An hourglass symbol is shown to signify the
time span (max. 15 min) during which it is
possible to hot-swap a sensor without triggering an error code
(5)Change the sensor during this time span.
(6)Press ENTER or ESC to start the running-
in time countdown.
(7)(Perform a ZERO and SPAN or Oxygen
calibration (M-01).
(1)Press ENTER and select menu 5.
(2)Press ENTER button.
(3)Enter password (→ chapter 4.5 "Pass-
word").
(4)(Perform a ZERO and SPAN calibration (M-
01).
GB
Sensors that are no longer required have to be disposed of in an environmentally
compatible way.
(M-06) - LCD/LED Test
LCD and LED test (LED only available in PrimaX P). All segments will be displayed and the LEDs will
flash sequentially.
(1)Press ENTER and select menu 6.
(2)Press ENTER button.
PrimaX
21
Loading...
+ 48 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.