MSA FL500 Operating Manual

Operating Manual
FL500 UV/IR Flame Detector
Order No.: 10193213/00
CR 800000028862
MSAsafety.com
WARNING!
Read this manual carefully before using and maintaining the device. The device will perform as designed only if it is used and maintained in accordance with the manufacturer's instructions. Otherwise, it can fail to perform as designed and persons who rely on this device for their safety could sustain serious injury or death.
The warranties made by General Monitors with respect to the product are voided if the product is not installed, used and serviced in accordance with the instructions in this manual. Protect yourself and your employees by following the instructions.
Read and observe the WARNINGS and CAUTIONS inside. For any additional information relative to use or repair, call 1-800-MSA-2222 during regular working hours.
1000 Cranberry Woods Drive Cranberry Township, PA 16066 USA Phone 1-800-MSA-2222 Fax 1-800-967-0398
For your local MSA contacts please go to our website www.MSAsafety.com
©
MSA 2018. All rights reserved
Contents
1 Safety Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Correct Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Liability Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3 Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.1 Limited Express Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.2 Sole Remedy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.3 Exclusion of Consequential Damage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Continuous Optical Path Monitoring (COPM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 LED Operation Mode Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1 Required Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2 Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2.1 Field of View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2.2 Environmental Factors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.4 Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.5 Terminal Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.5.1 TB2, Alarm High Relay Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.5.2 TB2, Alarm Low Relay Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.5.3 TB1, Fault Relay Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.5.4 Alarm Reset Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.5.5 Analog Output, Modbus and HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.6 Cable Lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.7 Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.8 Chassis Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.9 Fire Cards or Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.10 Cable Termination in a Nonhazardous Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
US
4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.1 Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.2 Changing Device Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.2.1 Using the DIP Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.2.2 Using Modbus or HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3 Sensitivity Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.1 TL105 Test Lamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.2 Alarm Test Feature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.1 Regular Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.2 Cleaning the Optical Window. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.3 Annual Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
FL500 UV/IR Flame Detector
3
7 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.1 Troubleshooting Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.2 Returning the Device for Repairs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.3 Removing the Device from Service Permanently . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.4 References and Other Sources of Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
8.1 System Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
8.2 Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
8.3 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
8.4 Environmental Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
9 Approvals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
FL500 UV/IR Flame Detector
US
4
Safety Regulations
1 Safety Regulations
1.1 Correct Use
WARNING!
Do NOT install or operate the device until you read and understand the instructions in this manual.
Only qualified personnel are approved to operate and do maintenance on the device. NE PAS INSTALLER NI UTILISER CET ÉQUIPEMENT SANS AVOIR D'AVOIR LU ET COMPRIS TOUTES LES DIRECTIVES, TOUS LES AVERTISSEMENTS ET TOUTES LES MISES EN GARDE DANS LE MANUEL D’INSTRUCTIONS.
Do NOT remove the cover from the device when the device is in operation or in an explosive atmo-
sphere. NE PAS OUVRIR LORSQUE SOUS TENSION OU EN PRÉSENCE D’UNE ATMOSPHÈRE EXPLOSIVE.
Install a conduit seal within 18 in. (46 cm) of the device enclosure.
INSTALLER LE JOINT DU CONDUIT DANS UN INTERVALLE DE 18 PO DU BOÎTIER.
Repair or alteration of the device beyond the scope of the maintenance instructions in this manual
or by anyone other than General Monitors or General Monitors-approved service personnel can cause incorrect operation of the device and put persons who use this device for their safety at risk of serious injury or death.
An approved electrician must do electrical wiring.All wiring must satisfy the requirements of the applicable National Electrical Code (NEC), Canadian
Electrical Code (CEC), and local electrical safety codes.
Make sure that field connections to the FL500 are applicable for the location and obey the wiring
requirements of the NEC, CEC, and local electrical safety codes.
Do not install or operate a device that is damaged.Install the device in a location away from conditions (such as high-pressure steam) where electro-
static charge can collect on nonconducting surfaces. This equipment uses an external nonmetallic coating. If extreme levels of electrostatic charge collect, ignition can occur.
Make sure that there is no physical blockage from permanent objects such as structures and
equipment or temporary objects such as personnel and vehicles in the sensor's field of view. If there is physical blockage in the sensor's field of view, the device cannot accurately monitor the area for flame.
Make sure that there is no ice, dirt, or debris on the optical window. Blockage of the optical window
can result in a Fault condition.
During a Fault condition, the device does not monitor the area for flame.Keep the device safe from vibration and mechanical shock, which can cause damage.Do NOT connect or disconnect equipment when power is supplied to the device. Doing so can
result in serious damage to the equipment. The warranty does not apply to equipment that is damaged in this way.
The device has components that can be damaged by electrostatic discharge (ESD). When you do
work with the device wiring, be careful to touch only the connection points. The warranty does not supply coverage for components that are damaged by ESD.
Use ONLY a damp cloth to clean the device. Otherwise, electrical shock or ignition from ESD can
occur. Failure to obey these warnings can result in serious injury or death.
US
For dimensional information about the flameproof joints, contact General Monitors.
FL500 UV/IR Flame Detector
5
Safety Regulations
1.2 Liability Information
General Monitors accepts no liability in cases where the product has been used inappropriately or not as intended.
The selection and use of this product must be under the direction of a qualified safety professional who has carefully evaluated the specific hazards of the jobsite where it will be used and who is completely familiar with the product and its limitations. The selection and use of this product and its incorporation into the safety scheme of the jobsite is the exclusive responsibility of the employer.
Changes and modifications not expressly approved by the manufacturer will void the user's authority to operate the equipment.
1.3 Warranty
1.3.1 Limited Express Warranty
General Monitors warrants the product to be free from mechanical defects and faulty workmanship for a period of two (2) years from the date of sale by General Monitors, provided that the product is main­tained and used in accordance with General Monitors' instructions and/or recommendations. General Monitors makes no warranty concerning components or accessories not manufactured by General Monitors, but will pass on to the Purchaser all warranties of manufacturer.
This warranty is valid only if the product is maintained and used in accordance with General Monitors' instructions and/or recommendations. General Monitors shall be released from all obligations under this warranty in the event that repairs or modifications are made by persons other than its own or authorized service personnel, or if the warranty claim results from accident, alteration, misuse, or abuse.
No agent, employee or representative of General Monitors has authority to bind General Monitors to any affirmation, representation or modification of the warranty concerning the product.
THIS WARRANTY IS STRICTLY LIMITED TO THE TERMS HEREOF AND IN LIEU OF ALL OTHER WARRANTEES, EXPRESSED, IMPLIED, OR STATUTORY INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
1.3.2 Sole Remedy
It is expressly agreed that Purchaser's sole and exclusive remedy for breach of the above warranty, for any tortious conduct of General Monitors, or for any other cause of action, shall be the repair or replacement, at General Monitors' option, of any equipment or parts thereof, which after examination by General Monitors is proven to be defective. Replacement equipment and/or parts will be provided at no cost to Purchaser, F.O.B. Seller's Plant. Failure of General Monitors to successfully replace any nonconforming equipment or parts shall not cause the remedy established hereby to fail of its essen­tial purpose.
1.3.3 Exclusion of Consequential Damage
Purchaser specifically understands and agrees that under no circumstances will General Monitors be liable to Purchaser for economic, special, incidental, or consequential damages or losses of any kind whatsoever, including but not limited to, loss of anticipated profits and any other loss caused by reason of non-operation of the goods. This exclusion is applicable to claims for breach of warranty, tortious conduct or any other cause of action against General Monitors.
FL500 UV/IR Flame Detector
US
6
2 Description
2.1 Overview
The FL500 ultraviolet/infrared (UV/IR) flame detector, referred to hereafter as the "FL500" or "device," uses a UV radiation-sensitive phototube and an IR detector to sense specific wavelengths in the UV and IR spectral regions. The UV and IR detectors send signals about changes in the intensity of UV and IR radiation to a microcomputer to activate Alarm Low, Alarm High, and Fault output. A flicker discrimination circuit in the IR circuitry prevents false alarms caused by lightning, arc-welding, hot objects, and other sources of radiation. The inherent flickering of a flame supplies the necessary modulation to activate the IR circuit.
Description
Ultraviolet Region Infrared Region
UV Detector’s
Spectral
Sensitivity
Visible Region
Sun’s Radiation Reaching Earth
IR Detector’s
Spectral
Sensitivity
Relative Energy
185 nm 260 nm
Fig. 1 Spectral Response of UV and IR Radiation Detectors
Wavelength
2.95 μm
(Hydrogen Detector)
If the device senses only UV radiation (such as arc welding) or only IR radiation (such as a large modulating hot object), an alarm does not occur. If the device senses both UV and IR radiation in the correct combination and intensity, as set by an algorithm in the microcomputer, the device identifies a fire and sends the following output:
4 - 20 mA signal
Immediate Alarm Low output
Time-delayed Alarm High output
RS-485 Modbus RTU output
HART communication
4.35 μm
US
The FL500 has the following features:
Compact unitized design
Wide field of view
Continuous optical path monitoring (COPM)
4 - 20 mA source or sink, alarm relays, and Modbus RTU RS-485 standard
HART 7 communication
False alarm prevention
FL500 UV/IR Flame Detector
7
Description
Fig. 2 FL500 UV/IR Flame Detector
The FL500 is compatible with the General Monitors TA402A trip amplifier, FL802 controller, and other equipment that accepts 4 - 20 mA output. The device can be connected directly with alarm and suppression devices or switched input modules through integral relays. If the HART protocol is used with the FL802 controller, it is necessary to use the special HART signal (1.25 - 20 mA).
Because the FL802 controller is not CE marked, it cannot be supplied to the European Union (EU).
2.2 Continuous Optical Path Monitoring (COPM)
COPM does a check of the device's optical path (from the internal UV and IR detectors through an air gap then the optical window) and related electronic circuitry every 2 minutes. If the optical window is blocked by unwanted objects such as ice, dirt, or debris for two consecutive checks, the device acti­vates the following Fault output:
2.0 mA signal
Fault relay de-energizes
Modbus signal
After a COPM Fault occurs, COPM occurs every 30 seconds until the Fault condition is removed. When the Fault condition is removed, COPM continues every 2 minutes.
Because COPM does a check of the optical path every 2 minutes and two consecutive checks must fail before a Fault occurs, it can be up to 3 minutes before the device iden­tifies a blockage.
Refer to Section 5.2 "Cleaning the Optical Window" for maintenance instructions.
US
FL500 UV/IR Flame Detector
8
2.3 LED Operation Mode Definitions
The LEDs show the following modes of operation for the device.
Device Status Alternate Mode Standard Mode
No Power All LEDs OFF Initial Power On All LEDs blink alternately for 10 s
Green LED = ON
Ready/Normal
Fault - COPM
Fault - Other
Alarm Low
Alarm High
Yellow LED = OFF Red LED = OFF Green LED = ON Green LED = OFF Yellow LED = Blinking slowly (1 Hz) Red LED = OFF Green LED = ON Green LED = OFF Yellow LED = ON Red LED = OFF Green LED = ON Green LED = OFF Yellow LED = OFF Red LED = Blinking slowly (1 Hz) Green LED = ON Green LED = OFF Yellow LED = OFF Red LED = ON
Description
Green LED = ON with heartbeat (5 s ON, 0.5 s OFF)
FL500 UV/IR Flame Detector
US
9
3 Installation
WARNING!
Do not install or operate a device that is damaged.Install the device in a location away from conditions (such as high-pressure steam) where electro-
static charge can collect on nonconducting surfaces. This equipment uses an external nonmetallic coating. If extreme levels of electrostatic charge collect, ignition can occur.
Make sure that there is no physical blockage from permanent objects such as structures and
equipment or temporary objects such as personnel and vehicles in the sensor's field of view. If there is physical blockage in the sensor's field of view, the device cannot accurately monitor the area for flame.
Keep the device safe from vibration and mechanical shock, which can cause damage.
Failure to obey these warnings can result in serious injury or death.
3.1 Required Tools
5 mm Allen wrench (included with the device)
Flat-blade screwdriver, maximum 1/8 in. width
No. 2 Philips screwdriver
10 mm Allen wrench
Adjustable wrench
Installation
3.2 Locations
Use the information in Section 3.2.1 "Field of View" and Section 3.2.2 "Environmental Factors" to select the best location to install the device.
US
FL500 UV/IR Flame Detector
10
3.2.1 Field of View
Gas Performance: HEPTANE
65°
60°
55°
45°
30°
15°
20’
25’
30’
35’
40’
45’
50’
55’
60’
65’
70’
75’
80’
85’
90’
15°
30°
45°
55°
60°
65°
65°
60°
55°
45°
30°
15°
20’25’30’35’
40’
45’50’
55’60’
65’70’
75’80’
85’90’
15°
30°
45°
55°
60°
65°
HorizontalHigh MedLow
HorizontalHigh MedLow
Gas Performance: HEPTANE
90’ 55’ 45’
55’ 45’
55’ 45’
90’
90’
75’
0°
± 15°
30°
- 30°
45°
75’- 60°
50’ 40’ 30’65°
50’ 40’ 30’- 65°
- 45°
60°
90’ 55’ 45’
55’ 45’
55’ 45’
90’
90’
75’
0°
± 15°
30°
- 30°
45°
60’- 60°
50’ 40’ 30’65°
50’ 40’ 30’- 65°
- 45°
60°
Installation
Fig. 3 Heptane Field of View
US
FL500 UV/IR Flame Detector
11
Installation
Gas Performance: METHANE
65°
60°
55°
45°
30°
15°
20’
25’
30’
35’
40’
45’
50’
55’
60’
65’
70’
75’
80’
15°
30°
45°
55°
60°
65°
65°
60°
55°
50°
45°
30°
15°
20’
25’
30’
35’
40’45’
50’
55’60’
65’
70’75’
80’
15°
30°
45°
55°
50°
60°
65°
HorizontalHigh MedLow
Gas Performance:
METHANE
VerticalHigh MedLow
80’ 60’ 45’
80’
0°
± 15°
30°
- 30°
40°
80’- 45°
65’ 50’ 45’ 55°
65’ 50’ 45’- 55°
40’ 35’60°
35’ 35’- 60°
- 40°
45°
80’ 60’ 45’
80’ 50’
80’ 50’
35’
35’
65’ 45’
65’ 45’
0°
± 15°
30°
− 30°
40°
− 40°
45°
− 45°
50°
50°
55°
55°
50’ 35’
60°
60’ 35’
− 60°
Fig. 4 Methane Field of View
FL500 UV/IR Flame Detector
US
12
Installation
45°
50°
55°
40’
35’
30’
25’
20’
15’
10’
60°
15°
30°
40°
30°
15°
25’
30’35’40’
15’20’
15°
30°
40°
45°
50°
55°
60°
Fig. 5 Methanol Field of View
15°
30°
40°40°
45°45°
50°50°
55°55°
60°60°
Gas Performance: METHANOL
HorizontalHigh MedLow
40’ 30’ 25’
± 15°
30°
− 30°
± 40°
45°
− 45°
40’ 30’ 25’50°
40’ 30’ 25’50°
20’55°
20’55°
25’ 20’60°
25’ 20’− 60°
Gas Performance: METHANOL
HorizontalHigh MedLow
10’
40’ 30’ 25’0°
± 15°
30°
− 30°
40°
− 40°
50° 40’ 30’ 25’
50° 40’ 30’ 25’
55° 20’
55° 20’
60°
30’ 20’
30’ 20’
− 60°
FL500 UV/IR Flame Detector
US
13
Installation
45°
50°
55°
60’
55’
50’
45’
40’
35’
30’
25’
20’
15’
10’
60°
15°
30°
40°
30°
15°
50’55’60’
25’
30’35’40’45’
15°
30°
40°
45°
50°
55°
60°
Fig. 6 Propane Field of View
15°
30°
40°40°
45°45°
50°50°
55°55°
60°60°
Gas Performance: PROPAN E
HorizontalHigh MedLow
± 15°
30°
− 30°
40°
− 40°
− 45°
55°
60’ 45’ 25’0°
60’ 45’ 20’
60’ 45’ 20’55°
45’ 25’60°
45’ 30’− 60°
25’45°
25’
Gas Performance: PROPAN E
HorizontalHigh MedLow
10’
15’20’
± 15°
− 30°
− 40°
− 45°
60’ 45’ 25’
30°
40°
55°
35’
25’
35’
25’
25’
20’45°
25’
60’
60’55°
50’60°
50’− 60°
20’
FL500 UV/IR Flame Detector
US
14
Installation
45°
50°
55°
60’
55’
50’
45’
40’
35’
30’
25’
20’
15’
10’
60°
15°
30°
40°
30°
15°
15°
30°
40°
45°
50°
55°
60°
Fig. 7 Ethane Field of View
15°
30°
40°40°
45°45°
50°50°
55°55°
60°60°
Gas Performance: ETHANE
HorizontalHigh MedLow
± 15°
− 30°
40°
− 40°
− 45°
50°
− 60°
60’ 40’ 30’
30°
40’ 30’
45°
50°
60°
40’ 30’
30’ 25’
30’ 25’
60’
60’
55’
55’
Gas Performance: ETHANE
HorizontalHigh MedLow
10’15’20’25’30’35’40’45’50’55’60’
± 15°
− 30°
40°
− 40°
− 45°
50°
− 60°
60’ 40’ 30’
30°
40’ 30’
45°
50°
60°
40’ 30’
30’ 25’
30’ 25’
60’
60’
55’
55’
FL500 UV/IR Flame Detector
US
15
Installation
45°
50°
55°
55’
50’
45’
40’
35’
30’
25’
20’
15’
10’
60°
15°
30°
40°
30°
15°
15°
30°
40°
45°
50°
55°
60°
Fig. 8 Butane Field of View
15°
30°
40°40°
45°45°
50°50°
55°55°
60°60°
Gas Performance: BUTAN E
HorizontalHigh MedLow
± 15°
− 30°
40°
− 40°
− 45°
50°
55°
− 60°
55’ 35’ 25’
30°
45°
50°
55°
60°
25’ 20’
25’ 20’
20’
20’
55’
55’
45’
45’
25’
25’
Gas Performance: BUTAN E
HorizontalHigh MedLow
10’15’20’25’30’35’40’45’50’55’
± 15°
− 30°
40°
− 40°
− 45°
55°
− 60°
55’ 35’ 25’
30°
25’
25’
45°
55°
60°
25’ 20’
25’ 20’
55’
55’
45’
45’
FL500 UV/IR Flame Detector
US
16
3.2.2 Environmental Factors
WARNING!
Do NOT install the device in an area where temperatures will be more than 185°F (85°C). Failure to obey this warning can result in serious injury or death.
The operating temperature range for the device is -67°F to 185°F (-55°C to 85°C). For outdoor instal­lations or other areas that are exposed to intense, direct solar radiation, the device may reach temperatures well above specifications.
Make sure that the device is in an area where ice, dirt, or debris cannot collect on the optical window. If ice, dirt, or debris collects on the optical window, a COPM Fault occurs.
To maintain the device enclosure's IP66/IP67 and Type 6P ingress ratings, use a nonhardening sealant to install stopping plugs on conduit/cable entries that are not used.
3.3 Mounting
Use the mounting bracket (PN 71370-1) and hardware to install the device on a wall, pole, or other surface. The design of the mounting bracket lets you adjust optical alignment while keeping the device in a fixed position.
To attach the mounting bracket to drywall, install at least two fasteners to the stud behind the drywall to give support for the weight of the device. The recommended fastener is a 3-in. #12 screw.
Use the dimensions shown in Figures 10 through 14 to install the device correctly. Make sure that the device:
Is in a location where personnel and objects cannot cause a blockage of the field of view
Is in a location that is convenient for visual inspection and cleaning
Is in a location where ice, dirt, or debris cannot collect on the optical window
Points downward to prevent dust and moisture from collecting on the optical window
Installation
General Monitors does not recommend the use of cable shoes or crimps on any junction box or housing wiring terminals. Poor crimping can cause a bad connection when temperature variations occur.
FL500 UV/IR Flame Detector
US
17
Installation
Fig. 9 FL500 Outline Drawing, Front View
Fig. 10 FL500 Outline Drawing, Side View
US
FL500 UV/IR Flame Detector
18
Fig. 11 FL500 and Mounting Bracket, Side View
Installation
Fig. 12 FL500 and Mounting Bracket, Top View
FL500 UV/IR Flame Detector
US
19
Fig. 13 FL500 and Mounting Bracket, Rear View
Installation
3.4 Wiring
WARNING!
An approved electrician must do electrical wiring.All wiring must satisfy the requirements of the applicable NEC, CEC, and local electrical safety
codes.
Install a conduit seal within 18 in. (46 cm) of the device enclosure.Make sure that all wiring is applicable for use at an ambient temperature of 199.6ºF (93.1°C).Before installing the wiring for the device, disconnect the power source.Read all electrical warnings and wiring requirements before connecting power to the device.The device wiring can be damaged by electrostatic discharge (ESD). When you do work with the
device wiring, be careful to touch only the connection points. The warranty does not supply coverage for components that are damaged by ESD.
Do NOT install wiring in a hazardous atmosphere. Otherwise, electrical shock or ignition can occur.
Failure to obey these warnings can result in serious injury or death.
Install all wiring connections through the base entries to the terminal block (TB). The terminal block accepts 14 - 22 AWG (2.1 - 0.3 mm
2
) stranded or solid-core wire.
US
FL500 UV/IR Flame Detector
20
Fig. 14 FL500 Housing and Base
Remove the insulation from each wire to 0.25 in. (0.64 cm). Use the correct cables for the ambient temperature where the device is installed.
Installation
Fault 2 Alarm Reset
Fault C
Fault 1
Data −
RS485
Control Device
PLC, DCS, ETC
COM (24 V-return)
+−
Power Supply
Fig. 15 Wiring Diagram
Data +
No Connection
0-20 mA
+ 24 VDC
Chassis Ground
Protection Circuits for Relay Contacts
WARNING!
12345678910
11 12 13 14 15 16 17 18 19 20
TB2TB1
No Connection
No Connection
Alarm Test
Alarm Low 2
Alarm Low 1 Alarm Low Relay
Alarm Low C
Alarm High C
Alarm High 1
Alarm High 2
Normally
Open Switch
Normally
Open Switch
Alarm High Relay
US
Protect relay contacts from transient and over-voltage conditions. Attach a clamp to all inductive loads (bells, buzzers, relays) on dry relay contacts as shown. Inductive loads that do not have a clamp attached can cause voltage spikes of more than 1000 Volts. Voltage spikes of this magnitude can cause false alarms and damage to the contacts.
Failure to obey this warning can result in serious injury or death.
(1) To connect the wire to the terminal block, install the conductor in the connection space as shown.
(2) Use a flat-blade screwdriver to tighten the related screw terminal.
FL500 UV/IR Flame Detector
21
3.5 Terminal Connections
TERM#TERM#
TB2TB1
11 12 13 14 15 16 17 18 19 20
12345678910
Chassis
COM (24 V - Return)
+ 24 VDC
0-20 mA
No Connection
Data +
Data −
Fault 1
Fault C
Fault 2
Alarm Low 2
Alarm Low 1
Alarm Low C
Alarm High C
Alarm High 1
Alarm High 2
Alarm Test
No Connection
No Connection
Alarm Reset
There are 20 terminal connections. The following sections give descriptions and specifications for each connection.
Installation
3.5.1 TB2, Alarm High Relay Connection
Fig. 16 Field Terminations
The output for the SPDT Alarm High relay has a time delay that can be set for 2, 4, 8, or 10 seconds. Alarm High output can be normally energized or normally de-energized, latching or non-latching.
All options can be set through Modbus, HART, or the DIP switch. Refer to Section 4.2 "Changing Device Settings" for instructions.
TB2 Position
7 C Common Common 6 1 Normally Closed Normally Open 5 2 Normally Open Normally Closed
Alarm High Relay
Relay Contact (De-Energized)
Relay Contact (Energized)
US
FL500 UV/IR Flame Detector
22
3.5.2 TB2, Alarm Low Relay Connection
The output for the SPDT Alarm Low relay is immediate. Alarm Low output can be normally energized or normally de-energized, latching or non-latching.
All options can be set through Modbus, HART, or the DIP switch. Refer to Section 4.2 "Changing Device Settings" for instructions.
Installation
TB2 Position
Alarm Low Relay
Relay Contact (De-Energized)
Relay Contact (Energized)
8 C Common Common 9 1 Normally Closed Normally Open 10 2 Normally Open Normally Closed
3.5.3 TB1, Fault Relay Connection
The standard configuration for the SPDT Fault relay is normally energized and non-latching. This configuration cannot be changed.
The Fault relay is activated during the time-out function, a low-power or loss-of-power condition, and a COPM Fault. For the duration of these conditions, the Fault relay de-energizes and the signal for analog output decreases to 0 mA (2 mA for a COPM Fault).
TB1 Position
Fault Relay
Relay Contact (De-Energized)
Relay Contact (Energized)
9C C C 8 1 Normally Closed Normally Open 10 2 Normally Open Normally Closed
3.5.4 Alarm Reset Switch
Use the Alarm Reset switch to set latched Alarm High or Alarm Low output that is no longer applicable back to its initial condition.
Do the following:
(1) Connect one contact of a normally open momentary switch to TB1 Terminal 3.
(2) Connect the other contact to COM (device Common).
(3) Push and release the Alarm Reset switch.
Position Function
TB2 POS 11 RESET TB2 POS 14 TEST
Multiple devices cannot be put in a daisy-chain configuration to use the Alarm Reset switch. Each latching Alarm Low and Alarm High output must be reset manually.
FL500 UV/IR Flame Detector
US
23
3.5.5 Analog Output, Modbus and HART
The 0 - 20 mA output is equivalent to the following analog output:
Condition Modbus HART (Normal) HART (Special)
Startup 0 - 0.2 mA 3.5 ±0.2 mA 1.25 ±0.2 mA Fault 0 - 0.2 mA 3.5 ±0.2 mA 1.25 ±0.2 mA COPM Fault 2.0 ±0.2 mA 3.5 ±0.2 mA 2.0 ±0.2 mA Ready 4.05 ±0.2 mA 4.05 ±0.2 mA 4.05 ±0.2 mA IR 8.0 ±0.2 mA 8.0 ±0.2 mA 8.0 ±0.2 mA UV 12.0 ±0.2 mA 12.0 ±0.2 mA 12.0 ±0.2 mA Alarm Low 16.0 ±0.2 mA 16.0 ±0.2 mA 16.0 ±0.2 mA Alarm High 20.0 ±0.2 mA 20.0 ±0.2 mA 20.0 ±0.2 mA
The maximum analog output load, including wiring, is 600 ohms.
In normal HART mode, the current output does not go below 3.5 mA. Modbus sends 2.0 mA output for COPM (as if HART was not there) to make a constant Modbus program available. The digital HART protocol sends the actual current output. When the Alarm High or Alarm Low relays are latched, the highest output current is also latched. The output current goes back to 4.0 mA when the Alarm Reset switch relay is activated.
The special HART mode lets the current decrease to 1.25 mA. The HART protocol continues to operate. Use the special HART mode with products that require 2 mA output for COPM, 1.5 mA output when the device is offline, and 0 mA output for a Fault condition.
The Modbus protocol is used to configure the device or to find the status of the device. For information about Modbus, refer to the FL500 Modbus Communication Operating Manual
(PN 10193214). For information about HART, refer to the FL500 HART Communication Operating Manual
(PN 10193215).
TB1 Position Connection
6DATA + 7DATA -
Installation
US
FL500 UV/IR Flame Detector
24
3.6 Cable Lengths
Use the following cable lengths (maximum 50-ohm loop) for interfaces with impedance devices that have 250-ohm input.
Installation
Cable AWG Run (ft) Cable (mm
2
) Run (m)
14 9000 2.50 2750 16 5800 1.50 1770 18 3800 1.00 1160 20 2400 0.75 730 22 1700 0.50 520
Use the following cable lengths (maximum 20-ohm loop) for a 24 Vdc power supply.
Cable AWG Run (ft) Cable (mm
2
) Run (m)
14 6588 2.08 2013 16 4146 1.31 1266 18 2608 0.823 796 20 1642 0.519 501 22 1055 0.33 321
3.7 Power Supply
The voltage range for the power supply is 20 - 36 Vdc at the device. Low voltage occurs at approxi­mately 18.5 Vdc.
TB1 Position Connection
324 Vdc 2COM
3.8 Chassis Ground
Use this connection to ground the device when you do any work with the wiring. General Monitors recommends that the chassis be grounded at all times.
TB1 Position Connection
1 CHAS GND
3.9 Fire Cards or Panels
General Monitors factory-fits end-of-life (EOL) and Alarm High resistors for devices that are wired together to do monitoring through standard fire cards.
When the FL500 is used with a General Monitors Model IN042 card, the Alarm High resistor is set to 470 ohm and the EOL resistor is set to 5.6K. The EOL resistor is onboard the Model IN042 card and can be selected through the DIP switch.
European Union (EU) approved applications: Make sure that interconnecting cables have an overall screen, or screen and armor. Cables BS5308 Part 2, Type 2, or equiv­alent are approved for use. To make a positive electrical connection, make sure that the cable armor connects to an applicable cable gland at the device.
US
FL500 UV/IR Flame Detector
25
3.10 Cable Termination in a Nonhazardous Area
WARNING!
Do NOT connect or disconnect equipment when power is supplied to the device. Doing so can result in serious damage to the equipment. The warranty does not supply coverage for equipment that is damaged in this way.
Failure to obey this warning can result in serious injury or death.
Connect the cable armor to safety earth in a nonhazardous area. Connect the cable screen (drain wire) to instrument earth in a nonhazardous area. Connect the power supply OV return to instrument earth in a nonhazardous area. Keep interconnecting cables isolated from the power cable and other noisy cables, such as cables for
radio transmitters, welders, switch mode power supplies, inverters, battery chargers, ignition systems, generators, switch gear, arc lights, and other high-frequency or high-power switching process equip­ment. Keep a separation of at least 3 ft (1 m) between instrument and other cables. An increased separation is necessary for long, parallel cable runs. Do not put instrument cable trenches close to lightning conductor earthing pits.
Installation
FL500 UV/IR Flame Detector
US
26
4 Operation
WARNING!
Make sure that there is no physical blockage from permanent objects such as structures and
equipment or temporary objects such as personnel and vehicles in the sensor's field of view. If there is physical blockage in the sensor's field of view, the device cannot accurately monitor the area for flame.
Make sure that there is no ice, dirt, or debris on the optical window. Blockage of the optical window
can result in a Fault condition.
During a Fault condition, the device does not monitor the area for flame.
Failure to obey these warnings can result in serious injury or death.
4.1 Start-Up
Before you supply power to the device, do the following:
Replace the red dust cap with an applicable cable gland.
Disconnect external devices such as automatic extinguishing fire suppression systems to prevent activation.
Make sure that the settings for the DIP switch are in the correct configuration. Refer to Section
4.2.1 "Using the DIP Switch" for instructions.
Make sure that the device is mounted and wired correctly.
Make sure that there is no blockage of the field of view for each device.
Make sure that the optical window and reflectors are clean. Refer to Section 5.2 "Cleaning the Optical Window" for cleaning instructions.
Make sure that the power supply is connected correctly.
Apply power to the device. Each device starts a self-test start-up sequence. For the first 10 seconds, the device sends 0 mA output, the Fault relay stays de-energized, and the green, yellow, and red LEDs flash. After this 10-second period, the device sends 4 mA output, the Fault relay is energized, the red LED goes off, and the green LED comes on and flashes every 5 seconds.
After the start-up sequence is complete, do a sensitivity check. Refer to Section 4.3 "Sensitivity Check" for instructions.
Operation
US
4.2 Changing Device Settings
All device settings can be changed through Modbus, HART, or the DIP switch. Settings made through Modbus and HART override settings made through the DIP switch.
4.2.1 Using the DIP Switch
To change device settings through the DIP switch, do the following:
(1) Use a flat-blade screwdriver to remove the screws that attach the detector head to the base
assembly.
(2) Find the DIP switch.
(3) Make the applicable switch assignments.
(4) Cycle power to the device.
FL500 UV/IR Flame Detector
27
Operation
Fig. 17 DIP Switch Location
On the DIP switch, the nomenclature "ON/CLOSED" is used when the switch is pushed in on the side labeled "ON" or "CLOSED" (opposite the side labeled "OPEN"). The nomenclature "OFF/OPEN" is used when the switch is pushed in on the side with the number related to the switch position or the side labeled "OPEN".
The time delay is the amount of time an Alarm Low condition continues before an Alarm High condition occurs.
Option
Position 12345678910
High Sensitivity OFFOFF-------­Medium Sensitivity ONOFF-------­Low Sensitivity OFFON-------­2-second Alarm Time Delay--OFFON-----­4-second Alarm Time Delay--OFFOFF-----­8-second Alarm Time Delay--ONOFF-----­10-second Alarm Time Delay--ONON-----­Alarm High Non-Latching ----OFF----­Alarm High Latching ----ON----­Alarm Low Non-Latching -----OFF---­Alarm Low Latching -----ON---­Alarm High Normal Energized------ON--­Alarm High Normal
De-Energized Alarm Low Normal Energized-------ON-­Alarm Low Normal
De-Energized Alternate LED ---------ON HART Enabled --------ON-
------OFF---
-------OFF--
US
FL500 UV/IR Flame Detector
28
4.2.2 Using Modbus or HART
To use the HART protocol, it is necessary to select the applicable current (1.25 mA or 3.5 mA). The factory default setting is 3.5 - 20 mA. This setting can only be changed through HART or Modbus.
Settings for Modbus and HART can be changed through the DIP switch. For information about changing device settings through Modbus, refer to the FL500 Modbus Commu-
nication Operating Manual (PN 10193214). For information about changing device settings through HART, refer to the FL500 HART Communica-
tion Operating Manual (PN 10193215).
4.3 Sensitivity Check
Use the TL105 Test Lamp or the Alarm Test feature to make sure that each device operates correctly. If the device does not operate correctly, refer to Section 7 "Troubleshooting" for instructions.
4.3.1 TL105 Test Lamp
The TL105 test lamp is a battery operated, rechargeable test source used to make sure that operation of the device is correct. The test lamp has a high-energy broadband radiation source that emits suffi­cient energy in both the UV and IR spectra to activate the UV and IR detectors. To simulate a fire, the TL105 test lamp automatically flashes at the correct rate for different models. When fully charged, the internal batteries operate continuously for 30 minutes. When the battery charge goes below the level necessary to supply the correct intensity, an internal low-voltage circuit stops operation of the test lamp until the batteries are recharged. For recharging instructions, refer to the TL105 Instruction Manual (PN MANTL105).
Operation
Fig. 18 TL105 Test Lamp
(1) Make sure that the batteries are fully charged.
(2) Stand 15 - 20 ft (5 - 6 m) away from the device.
(3) Point the TL105 test lamp directly at the front of the device.
(4) Shake the test lamp from side to side or up and down. Motion increases the simulation of flames
flickering and increases the response of the device to the test lamp. If device operation is correct, after a few flashes of the test lamp, an Alarm Low condition occurs. If the test lamp stays pointed at the device for the period of the time-delay setting, an Alarm High
condition occurs.
To conserve the battery charge, operate the test lamp only as long as necessary to do a test of each device.
FL500 UV/IR Flame Detector
US
29
4.3.2 Alarm Test Feature
To use the Alarm Test feature, do the following:
(1) Connect one contact of a normally open, momentary switch to TB1 Terminal 4.
(2) Connect the other contact to TB1 Terminals 9 and 10 (COM).
(3) Activate the switch for the period set for the time delay (2 - 10 seconds).
If the device senses the source, it immediately sends Alarm Low output, then the time-delayed
Alarm High ouput. After 1 to 8 seconds, the device resets the non-latching Alarm Low and Alarm High conditions. Latching Alarm Low and Alarm High conditions stay latched until they are reset manually. Refer to Section 3.5.4 "Alarm Reset Switch" for instructions.
If the device does not sense the source, it sends Fault output and does the test again every
10 seconds.
The Alarm Test feature can be used through Modbus and HART.
Multiple devices cannot be put in a daisy-chain configuration to do testing for Alarm High output.
Operation
FL500 UV/IR Flame Detector
US
30
5 Maintenance
WARNING!
Repair or alteration of the device beyond the scope of the maintenance instructions in this manual
or by anyone other than General Monitors or General Monitors-approved service personnel can cause incorrect operation of the device and put persons who use this device for their safety at risk of serious injury or death.
The device has components that can be damaged by electrostatic discharge (ESD). When you do
work with the device wiring, be careful to touch only the connection points. The warranty does not supply coverage for components that are damaged by ESD. Failure to obey these warnings can result in serious injury or death.
General Monitors recommends that maintenance intervals be set through a documented procedure that includes a maintenance log kept by plant personnel or third-party testing services.
5.1 Regular Maintenance
WARNING!
Maintenance
Use ONLY a damp cloth to clean the device. Otherwise, electrical shock or ignition from ESD can occur.
Failure to obey this warning can result in serious injury or death.
Clean the optical window every 30 days at a minimum. Refer to Section 5.2 "Cleaning the Optical Window" for instructions. Do sensitivity checks regularly. Refer to Section 4.3 "Sensitivity Check" for instructions.
Examine, clean the optical window, and do sensitivity checks more frequently for devices that are installed in dirty areas.
5.2 Cleaning the Optical Window
WARNING!
Use ONLY Industrial Strength Windex® with Ammonia D (General Monitors PN 10272-1) to clean the optical window. The optical window material is sapphire, not glass. Using any other commercial glass cleaner will cause damage to the optical window. The warranty does not supply coverage for optical windows that are damaged in this way.
Failure to obey this warning can result in serious injury or death.
Remove debris and film buildup on the optical window and reflectors regularly to make sure that the device has the correct sensitivity and to prevent COPM Faults. General Monitors recommends that you clean the optical window and reflectors every 30 days at a minimum. Clean the optical window and reflectors more frequently for devices that are installed in dirty areas.
US
FL500 UV/IR Flame Detector
31
(1) Use a clean, soft, lint-free cloth, tissue, or cotton swab soaked with Industrial Strength Windex
with Ammonia D to clean the optical window.
(2) Use a clean, dry, cloth to rub the optical window until it is clean. Do NOT touch the lens with your
fingers.
(3) Let the optical window air-dry fully.
5.3 Annual Maintenance
Make sure that all wiring and terminal connections are connected correctly. Make sure that the mounting for all integral safety equipment, including but not limited to following
components, is stable:
Power supplies
Control modules
Field detection devices
Signaling devices
Accessories connected to field and signaling devices
Maintenance
FL500 UV/IR Flame Detector
US
32
6Storage
WARNING!
Keep the device safe from vibration and mechanical shock, which can cause damage. Failure to obey this warning can result in serious injury or death.
Keep the device in a clean area with an ambient temperature of -40°F to 185°F (-40°C to 85°C) and a humidity range of 0% to 95% RH noncondensing.
For extended storage, do the following:
(1) If possible, keep the device in the mold as shipped by the manufacturer.
(2) Install the red dust caps in the cable entry holes.
(3) Seal the device and a desiccant in a plastic bag.
(4) Seal the plastic bag inside another plastic bag.
Storage
FL500 UV/IR Flame Detector
US
33
Troubleshooting
7 Troubleshooting
WARNING!
Repair or alteration of the device beyond the scope of the maintenance instructions in this manual or by anyone other than General Monitors or General Monitors-approved service personnel can cause incorrect operation of the device and put persons who use this device for their safety at risk of serious injury or death.
During a Fault condition, the device does not monitor the area for flame.
7.1 Troubleshooting Table
The troubleshooting table gives information about common faults that occur during commissioning and operation. These common faults can be repaired by a competent operator.
Before you do the following corrective actions, inhibit or disconnect the external alarm wiring to prevent an accidental Alarm High condition.
Problem Possible Cause Corrective Action
No output signal and all LEDs are off
2 mA signal, green LED is off, yellow LED is blinking
0 mA, 1.25 mA, or 3.5 mA signal, and yellow LED is on
Constant 8 mA signal with no known radiation to device
Constant 12 mA signal with no known radiation to device
Constant 16 mA or 20 mA signal (Alarm Low or Alarm High) with no known radiation at device
No dc power to the device
Device is in COPM Fault
Low supply voltage or other fault
Background IR radiation at device
Background UV radiation at device
Background UV radiation at device
Make sure that 24 Vdc is applied with the correct polarity.
Clean the optical window and reflectors. Refer to Section 5.2 "Cleaning the Optical Window" for instructions.
Make sure that the supply voltage is 20 Vdc at the device. If it is, cycle the power to see if the fault is removed.
Put a cover over the optical window for 10 seconds. If the device senses background IR, and the analog output still shows 8 mA, contact technical support for more trouble­shooting.
Put a cover over the UV part of the optical window for 10 seconds. If the device senses background UV, and the analog output still shows 12 mA, contact technical support for more troubleshooting.
Put a cover over the optical window for 10 seconds. If the analog output still shows 16 mA or 20 mA, contact tech­nical support for more trouble­shooting.
US
FL500 UV/IR Flame Detector
34
Troubleshooting
If the corrective actions recommended in the troubleshooting table do not correct operation of the device, return the device to General Monitors for repair.
7.2 Returning the Device for Repairs
Use the following contact information to return a device to General Monitors for repair. Include a detailed written description of the problem.
UNITED STATES
26776 Simpatica Circle Lake Forest, CA 92630
IRELAND
Ballybrit Business Park Galway Republic of Ireland
MIDDLE EAST
P.O. Box 54910 Dubai Airport Freezone United Arab Emirates
SINGAPORE
35 Marsiling Industrial Estate, Road 3 #04-01 Singapore 739257
Additional locations are available at www.MSAsafety.com.
7.3 Removing the Device from Service Permanently
EU member states must discard devices in accordance with the Waste Electrical and Electronic Equipment (WEEE) Directive. All other countries or states must discard devices in accordance with existing federal, state, and local environmental control regulations.
Phone: +1-949-581-4464 Email: info.gm@msasafety.com
Phone: +353-91-751175 Email: info.gmil@msasafety.com
Phone: +971-4-294-3640 Email: gmdubai.main@msasafety.com
Phone: +65-6748-3488
US
7.4 References and Other Sources of Help
Look for documentation, white papers, and product literature for our complete line of safety products at http://www.MSAsafety.com/detection.
For more information about the use and performance standards for the device, refer to the following publications:
BS EN 54-10:2002, Fire detection and fire alarm systems - Flame detectors - Point detectors.
British Standards Institute, London, United Kingdom, 2002.
BS EN 50130-4, Electromagnetic compatibility. Product family standard: Immunity requirements
for components of fire, intruder, hold up, CCTV, access control and social alarm systems. British Standards Institute, London, United Kingdom, 2011.
BS EN 61000-6-4:2007+A1:2011, Electromagnetic compatibility (EMC). Generic standards. Emis-
sion standard for industrial environments. British Standards Institute, London, United Kingdom,
2007.
FL500 UV/IR Flame Detector
35
8 Specifications
8.1 System Specifications
Specifications
Application
Device location
Environmental ratings Type 6P, IP66/IP67 UV Detector pass band 185 - 260 nanometers
IR Detector center wave­length
Typical alarm activation response times
Zeta value
Field of view Refer to Section 3.2.1 "Field of View" for information.
UV/IR Flame Detection
Class I, Division 1, Groups A*, B, C, and D Class II, Division 1, Groups E, F, and G Class III Ex db IIC T5 Gb Ex tb IIIC T100°C Db II 2 G D
-50°C to 85°C under FM, -55°C to 85°C under CSA/ATEX/IECEx
4.35 mm
Fuel Distance (ft)
n-Heptane
Methane 80 <10 Methanol 40 12 Propane 60 <7 Ethane 60 <3 Butane 55 <3
Zeta = -0.001 The margin of error in the range measurement is esti-
mated at ±5 ft (±1.5 m) due to wind conditions and flame turbulence.
90 60
Response Time (s)
6 <3
US
* Applicable to FM approvals only.
Notes: Response times and field of view data were derived by testing the device with a 1 ft
cup of heptane on top of a 1-in. layer of water was ignited for each test. These are typical values. The variation of each fire can cause different results.
BS EN 54-10 identifies the limit of the field of view to ±25 degrees because of the requirements of the Directional Dependence test. This result is from indoor benchtop testing with a Bunsen burner as the fire source, rather than the outdoor flame testing used to identify the field of view in Section 3.2.1 "Field of View".
FL500 UV/IR Flame Detector
2
heptane fire. One
36
8.2 Mechanical Specifications
Enclosure material 316 Stainless Steel Color Red Finish TGIC polyester powder coat Height 6.4 in. (16.2 cm) Width 5.0 in. (12.7 cm) Depth 4.3 in. (11.0 cm) Weight 9.4 lb (4.3 kg)
Cable Entry
Earth Terminals
8.3 Electrical Specifications
2 x ¾ in. NPT (M25 adapters included for some config­urations)
8-32 x 3/8 Philips pan-head screw, stainless steel, zinc-plated, green dye; external stainless steel tooth lock washer included. Applicable for connection of
2
4mm
or smaller.
Specifications
Nominal supply voltage 24 Vdc Supply voltage range 20 to 36 Vdc (measured at device) Maximum supply current 200 mA during COPM only Typical current 80 to 150 mA Maximum output signal load 600 ohms Output signal range 0 to 20 mA * Fault signal 0 to 0.2 mA * COPM fault signal 2.0 ±0.2 mA * Ready signal 4.0 ±0.2 mA IR only signal 8.0 ±0.2 mA UV only signal 12.0 ±0.2 mA Alarm Low signal 16.0 ±0.2 mA Alarm High signal 20.0 ±0.2 mA
North American Approved Applications: SPDT, 5A @ 250 Vac, or 5A @ 30 Vdc resistive max.
Relay contact ratings
European Union (EU) Approved Applications: SPDT, 5A 30V RMS/42.4V Peak, or 5A @ 30 Vdc
resistive max. Modbus RTU
RS-485 output
128 devices in series max. (247 devices with repeaters) Baud rate: 2400, 4800, 9600, or 19200 bps Fully HART 7 FieldComm compliant. Refer to the
HART
FL500 HART Communication Operating Manual (PN 10193215).
HART impedance RX = 50 K CX = 5 nF
US
FL500 UV/IR Flame Detector
37
RFI/EMI protection Complies with BS EN 50130-4 and BS EN 61000-6-4 Status indicator Three LEDs identify status, fault, and alarm conditions
8.4 Environmental Specifications
Specifications
Operating temperature range
Storage temperature range -40°F to 185°F (-40°C to 85°C) Humidity range 0% to 95% RH noncondensing
False Alarm Source Distance from FL500 (ft) Trouble / False Alarm Direct sunlight 3N Reflected sunlight 3N
Arc weld dc 190A, 7014 rod
Arc weld ac 90A, 7014 rod 15 N 1500W electrical heater 2N 6000W electrical heater 2N 100W incandescent light 1N 300W incandescent light 1N Two 34W fluorescent light 1N 500W halogen light 2N 100W UV backlight 3N 250W vapor lamp 3N
Two 25W tungsten incan­descent lamps
-67°F to 185°F (-55°C to 85°C)
15 N
3N
FL500 UV/IR Flame Detector
US
38
9 Approvals
CSA (CSA 18.70180732X), FM, ATEX (Sira 18ATEX1073X), IECEx (SIR 18.0026X), HART Regis­tered, SIL 3 suitable.
Approvals
FL500 UV/IR Flame Detector
US
39
For local MSA contacts, please visit us at MSAsafety.com
Because every life has a purpose...
Loading...