Read this manual carefully before using and maintaining the device. The device will perform as designed
only if it is used and maintained in accordance with the manufacturer's instructions. Otherwise, it can fail to
perform as designed and persons who rely on this device for their safety could sustain serious injury or
death.
The warranties made by General Monitors with respect to the product are voided if the product is not
installed, used and serviced in accordance with the instructions in this manual. Protect yourself and your
employees by following the instructions.
Read and observe the WARNINGS and CAUTIONS inside. For any additional information relative to use or
repair, call 1-800-MSA-2222 during regular working hours.
1000 Cranberry Woods Drive
Cranberry Township, PA 16066
USA
Phone 1-800-MSA-2222
Fax 1-800-967-0398
For your local MSA contacts please go to our website www.MSAsafety.com
Do NOT install or operate the device until you read and understand the instructions in this manual.
Only qualified personnel are approved to operate and do maintenance on the device.
NE PAS INSTALLER NI UTILISER CET ÉQUIPEMENT SANS AVOIR D'AVOIR LU ET COMPRIS
TOUTES LES DIRECTIVES, TOUS LES AVERTISSEMENTS ET TOUTES LES MISES EN
GARDE DANS LE MANUEL D’INSTRUCTIONS.
Do NOT remove the cover from the device when the device is in operation or in an explosive atmo-
sphere.
NE PAS OUVRIR LORSQUE SOUS TENSION OU EN PRÉSENCE D’UNE ATMOSPHÈRE
EXPLOSIVE.
Install a conduit seal within 18 in. (46 cm) of the device enclosure.
INSTALLER LE JOINT DU CONDUIT DANS UN INTERVALLE DE 18 PO DU BOÎTIER.
Repair or alteration of the device beyond the scope of the maintenance instructions in this manual
or by anyone other than General Monitors or General Monitors-approved service personnel can
cause incorrect operation of the device and put persons who use this device for their safety at risk
of serious injury or death.
An approved electrician must do electrical wiring.
All wiring must satisfy the requirements of the applicable National Electrical Code (NEC), Canadian
Electrical Code (CEC), and local electrical safety codes.
Make sure that field connections to the FL500 are applicable for the location and obey the wiring
requirements of the NEC, CEC, and local electrical safety codes.
Do not install or operate a device that is damaged.
Install the device in a location away from conditions (such as high-pressure steam) where electro-
static charge can collect on nonconducting surfaces. This equipment uses an external nonmetallic
coating. If extreme levels of electrostatic charge collect, ignition can occur.
Make sure that there is no physical blockage from permanent objects such as structures and
equipment or temporary objects such as personnel and vehicles in the sensor's field of view. If
there is physical blockage in the sensor's field of view, the device cannot accurately monitor the
area for flame.
Make sure that there is no ice, dirt, or debris on the optical window. Blockage of the optical window
can result in a Fault condition.
During a Fault condition, the device does not monitor the area for flame.
Keep the device safe from vibration and mechanical shock, which can cause damage.
Do NOT connect or disconnect equipment when power is supplied to the device. Doing so can
result in serious damage to the equipment. The warranty does not apply to equipment that is
damaged in this way.
The device has components that can be damaged by electrostatic discharge (ESD). When you do
work with the device wiring, be careful to touch only the connection points. The warranty does not
supply coverage for components that are damaged by ESD.
Use ONLY a damp cloth to clean the device. Otherwise, electrical shock or ignition from ESD can
occur.
Failure to obey these warnings can result in serious injury or death.
US
For dimensional information about the flameproof joints, contact General Monitors.
FL500 UV/IR Flame Detector
5
Safety Regulations
1.2Liability Information
General Monitors accepts no liability in cases where the product has been used inappropriately or not
as intended.
The selection and use of this product must be under the direction of a qualified safety professional
who has carefully evaluated the specific hazards of the jobsite where it will be used and who is
completely familiar with the product and its limitations. The selection and use of this product and its
incorporation into the safety scheme of the jobsite is the exclusive responsibility of the employer.
Changes and modifications not expressly approved by the manufacturer will void the user's authority
to operate the equipment.
1.3Warranty
1.3.1 Limited Express Warranty
General Monitors warrants the product to be free from mechanical defects and faulty workmanship for
a period of two (2) years from the date of sale by General Monitors, provided that the product is maintained and used in accordance with General Monitors' instructions and/or recommendations. General
Monitors makes no warranty concerning components or accessories not manufactured by General
Monitors, but will pass on to the Purchaser all warranties of manufacturer.
This warranty is valid only if the product is maintained and used in accordance with General Monitors'
instructions and/or recommendations. General Monitors shall be released from all obligations under
this warranty in the event that repairs or modifications are made by persons other than its own or
authorized service personnel, or if the warranty claim results from accident, alteration, misuse, or
abuse.
No agent, employee or representative of General Monitors has authority to bind General Monitors to
any affirmation, representation or modification of the warranty concerning the product.
THIS WARRANTY IS STRICTLY LIMITED TO THE TERMS HEREOF AND IN LIEU OF ALL OTHER
WARRANTEES, EXPRESSED, IMPLIED, OR STATUTORY INCLUDING, BUT NOT LIMITED TO,
ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE.
1.3.2 Sole Remedy
It is expressly agreed that Purchaser's sole and exclusive remedy for breach of the above warranty,
for any tortious conduct of General Monitors, or for any other cause of action, shall be the repair or
replacement, at General Monitors' option, of any equipment or parts thereof, which after examination
by General Monitors is proven to be defective. Replacement equipment and/or parts will be provided
at no cost to Purchaser, F.O.B. Seller's Plant. Failure of General Monitors to successfully replace any
nonconforming equipment or parts shall not cause the remedy established hereby to fail of its essential purpose.
1.3.3 Exclusion of Consequential Damage
Purchaser specifically understands and agrees that under no circumstances will General Monitors be
liable to Purchaser for economic, special, incidental, or consequential damages or losses of any kind
whatsoever, including but not limited to, loss of anticipated profits and any other loss caused by reason
of non-operation of the goods. This exclusion is applicable to claims for breach of warranty, tortious
conduct or any other cause of action against General Monitors.
FL500 UV/IR Flame Detector
US
6
2Description
2.1Overview
The FL500 ultraviolet/infrared (UV/IR) flame detector, referred to hereafter as the "FL500" or "device,"
uses a UV radiation-sensitive phototube and an IR detector to sense specific wavelengths in the UV
and IR spectral regions. The UV and IR detectors send signals about changes in the intensity of UV
and IR radiation to a microcomputer to activate Alarm Low, Alarm High, and Fault output. A flicker
discrimination circuit in the IR circuitry prevents false alarms caused by lightning, arc-welding, hot
objects, and other sources of radiation. The inherent flickering of a flame supplies the necessary
modulation to activate the IR circuit.
Description
Ultraviolet RegionInfrared Region
UV Detector’s
Spectral
Sensitivity
Visible Region
Sun’s Radiation
Reaching Earth
IR Detector’s
Spectral
Sensitivity
Relative Energy
185 nm 260 nm
Fig. 1 Spectral Response of UV and IR Radiation Detectors
Wavelength
2.95 μm
(Hydrogen Detector)
If the device senses only UV radiation (such as arc welding) or only IR radiation (such as a large
modulating hot object), an alarm does not occur. If the device senses both UV and IR radiation in the
correct combination and intensity, as set by an algorithm in the microcomputer, the device identifies a
fire and sends the following output:
•4 - 20 mA signal
•Immediate Alarm Low output
•Time-delayed Alarm High output
•RS-485 Modbus RTU output
•HART communication
4.35 μm
US
The FL500 has the following features:
•Compact unitized design
•Wide field of view
•Continuous optical path monitoring (COPM)
•4 - 20 mA source or sink, alarm relays, and Modbus RTU RS-485 standard
•HART 7 communication
•False alarm prevention
FL500 UV/IR Flame Detector
7
Description
Fig. 2 FL500 UV/IR Flame Detector
The FL500 is compatible with the General Monitors TA402A trip amplifier, FL802 controller, and other
equipment that accepts 4 - 20 mA output. The device can be connected directly with alarm and
suppression devices or switched input modules through integral relays. If the HART protocol is used
with the FL802 controller, it is necessary to use the special HART signal (1.25 - 20 mA).
Because the FL802 controller is not CE marked, it cannot be supplied to the European
Union (EU).
2.2Continuous Optical Path Monitoring (COPM)
COPM does a check of the device's optical path (from the internal UV and IR detectors through an air
gap then the optical window) and related electronic circuitry every 2 minutes. If the optical window is
blocked by unwanted objects such as ice, dirt, or debris for two consecutive checks, the device activates the following Fault output:
•2.0 mA signal
•Fault relay de-energizes
•Modbus signal
After a COPM Fault occurs, COPM occurs every 30 seconds until the Fault condition is removed.
When the Fault condition is removed, COPM continues every 2 minutes.
Because COPM does a check of the optical path every 2 minutes and two consecutive
checks must fail before a Fault occurs, it can be up to 3 minutes before the device identifies a blockage.
Refer to Section 5.2 "Cleaning the Optical Window" for maintenance instructions.
US
FL500 UV/IR Flame Detector
8
2.3LED Operation Mode Definitions
The LEDs show the following modes of operation for the device.
Device StatusAlternate ModeStandard Mode
No PowerAll LEDs OFF
Initial Power OnAll LEDs blink alternately for 10 s
Green LED = ON
Ready/Normal
Fault - COPM
Fault - Other
Alarm Low
Alarm High
Yellow LED = OFF
Red LED = OFF
Green LED = ONGreen LED = OFF
Yellow LED = Blinking slowly (1 Hz)
Red LED = OFF
Green LED = ONGreen LED = OFF
Yellow LED = ON
Red LED = OFF
Green LED = ONGreen LED = OFF
Yellow LED = OFF
Red LED = Blinking slowly (1 Hz)
Green LED = ONGreen LED = OFF
Yellow LED = OFF
Red LED = ON
Description
Green LED = ON with heartbeat
(5 s ON, 0.5 s OFF)
FL500 UV/IR Flame Detector
US
9
3Installation
WARNING!
Do not install or operate a device that is damaged.
Install the device in a location away from conditions (such as high-pressure steam) where electro-
static charge can collect on nonconducting surfaces. This equipment uses an external nonmetallic
coating. If extreme levels of electrostatic charge collect, ignition can occur.
Make sure that there is no physical blockage from permanent objects such as structures and
equipment or temporary objects such as personnel and vehicles in the sensor's field of view. If
there is physical blockage in the sensor's field of view, the device cannot accurately monitor the
area for flame.
Keep the device safe from vibration and mechanical shock, which can cause damage.
Failure to obey these warnings can result in serious injury or death.
3.1Required Tools
•5 mm Allen wrench (included with the device)
•Flat-blade screwdriver, maximum 1/8 in. width
•No. 2 Philips screwdriver
•10 mm Allen wrench
•Adjustable wrench
Installation
3.2Locations
Use the information in Section 3.2.1 "Field of View" and Section 3.2.2 "Environmental Factors" to
select the best location to install the device.
US
FL500 UV/IR Flame Detector
10
3.2.1 Field of View
Gas Performance:
HEPTANE
65°
60°
55°
45°
30°
15°
0°
20’
25’
30’
35’
40’
45’
50’
55’
60’
65’
70’
75’
80’
85’
90’
15°
30°
45°
55°
60°
65°
65°
60°
55°
45°
30°
15°
0°
20’25’30’35’
40’
45’50’
55’60’
65’70’
75’80’
85’90’
15°
30°
45°
55°
60°
65°
HorizontalHigh MedLow
HorizontalHigh MedLow
Gas Performance:
HEPTANE
90’55’45’
55’45’
55’45’
90’
90’
75’
0°
± 15°
30°
- 30°
45°
75’- 60°
50’40’30’65°
50’40’30’- 65°
- 45°
60°
90’55’45’
55’45’
55’45’
90’
90’
75’
0°
± 15°
30°
- 30°
45°
60’- 60°
50’40’30’65°
50’40’30’- 65°
- 45°
60°
Installation
Fig. 3 Heptane Field of View
US
FL500 UV/IR Flame Detector
11
Installation
Gas Performance:
METHANE
65°
60°
55°
45°
30°
15°
0°
20’
25’
30’
35’
40’
45’
50’
55’
60’
65’
70’
75’
80’
15°
30°
45°
55°
60°
65°
65°
60°
55°
50°
45°
30°
15°
0°
20’
25’
30’
35’
40’45’
50’
55’60’
65’
70’75’
80’
15°
30°
45°
55°
50°
60°
65°
HorizontalHigh MedLow
Gas Performance:
METHANE
VerticalHigh MedLow
80’60’45’
80’
0°
± 15°
30°
- 30°
40°
80’- 45°
65’50’45’ 55°
65’50’45’- 55°
40’35’60°
35’35’- 60°
- 40°
45°
80’60’45’
80’50’
80’50’
35’
35’
65’45’
65’45’
0°
± 15°
30°
− 30°
40°
− 40°
45°
− 45°
50°
− 50°
55°
− 55°
50’35’
60°
60’35’
− 60°
Fig. 4 Methane Field of View
FL500 UV/IR Flame Detector
US
12
Installation
45°
50°
55°
0°
40’
35’
30’
25’
20’
15’
10’
60°
15°
30°
40°
30°
15°
25’
0°
30’35’40’
15’20’
15°
30°
40°
45°
50°
55°
60°
Fig. 5 Methanol Field of View
15°
30°
40°40°
45°45°
50°50°
55°55°
60°60°
Gas Performance:
METHANOL
HorizontalHigh MedLow
40’30’25’0°
± 15°
30°
− 30°
± 40°
45°
− 45°
40’30’25’50°
40’30’25’− 50°
20’55°
20’− 55°
25’20’60°
25’20’− 60°
Gas Performance:
METHANOL
HorizontalHigh MedLow
10’
40’30’25’0°
± 15°
30°
− 30°
40°
− 40°
50° 40’30’25’
− 50° 40’30’25’
55°20’
− 55°20’
60°
30’20’
30’20’
− 60°
FL500 UV/IR Flame Detector
US
13
Installation
45°
50°
55°
0°
60’
55’
50’
45’
40’
35’
30’
25’
20’
15’
10’
60°
15°
30°
40°
30°
15°
50’55’60’
0°
25’
30’35’40’45’
15°
30°
40°
45°
50°
55°
60°
Fig. 6 Propane Field of View
15°
30°
40°40°
45°45°
50°50°
55°55°
60°60°
Gas Performance:
PROPAN E
HorizontalHigh MedLow
± 15°
30°
− 30°
40°
− 40°
− 45°
55°
60’45’25’0°
60’45’20’
60’45’20’− 55°
45’25’60°
45’30’− 60°
25’45°
25’
Gas Performance:
PROPAN E
HorizontalHigh MedLow
10’
15’20’
± 15°
− 30°
− 40°
− 45°
60’45’25’0°
30°
40°
55°
35’
25’
35’
25’
25’
20’45°
25’
60’
60’− 55°
50’60°
50’− 60°
20’
FL500 UV/IR Flame Detector
US
14
Installation
45°
50°
55°
0°
60’
55’
50’
45’
40’
35’
30’
25’
20’
15’
10’
60°
15°
30°
40°
30°
15°
0°
15°
30°
40°
45°
50°
55°
60°
Fig. 7 Ethane Field of View
15°
30°
40°40°
45°45°
50°50°
55°55°
60°60°
Gas Performance:
ETHANE
HorizontalHigh MedLow
± 15°
− 30°
40°
− 40°
− 45°
− 50°
− 60°
60’40’30’0°
30°
40’30’
45°
50°
60°
40’30’
30’25’
30’25’
60’
60’
55’
55’
Gas Performance:
ETHANE
HorizontalHigh MedLow
10’15’20’25’30’35’40’45’50’55’60’
± 15°
− 30°
40°
− 40°
− 45°
− 50°
− 60°
60’40’30’0°
30°
40’30’
45°
50°
60°
40’30’
30’25’
30’25’
60’
60’
55’
55’
FL500 UV/IR Flame Detector
US
15
Installation
45°
50°
55°
0°
55’
50’
45’
40’
35’
30’
25’
20’
15’
10’
60°
15°
30°
40°
30°
15°
0°
15°
30°
40°
45°
50°
55°
60°
Fig. 8 Butane Field of View
15°
30°
40°40°
45°45°
50°50°
55°55°
60°60°
Gas Performance:
BUTAN E
HorizontalHigh MedLow
± 15°
− 30°
40°
− 40°
− 45°
− 50°
− 55°
− 60°
55’35’25’0°
30°
45°
50°
55°
60°
25’20’
25’20’
20’
20’
55’
55’
45’
45’
25’
25’
Gas Performance:
BUTAN E
HorizontalHigh MedLow
10’15’20’25’30’35’40’45’50’55’
± 15°
− 30°
40°
− 40°
− 45°
− 55°
− 60°
55’35’25’0°
30°
25’
25’
45°
55°
60°
25’20’
25’20’
55’
55’
45’
45’
FL500 UV/IR Flame Detector
US
16
3.2.2 Environmental Factors
WARNING!
Do NOT install the device in an area where temperatures will be more than 185°F (85°C).
Failure to obey this warning can result in serious injury or death.
The operating temperature range for the device is -67°F to 185°F (-55°C to 85°C). For outdoor installations or other areas that are exposed to intense, direct solar radiation, the device may reach
temperatures well above specifications.
Make sure that the device is in an area where ice, dirt, or debris cannot collect on the optical window.
If ice, dirt, or debris collects on the optical window, a COPM Fault occurs.
To maintain the device enclosure's IP66/IP67 and Type 6P ingress ratings, use a nonhardening
sealant to install stopping plugs on conduit/cable entries that are not used.
3.3Mounting
Use the mounting bracket (PN 71370-1) and hardware to install the device on a wall, pole, or other
surface. The design of the mounting bracket lets you adjust optical alignment while keeping the device
in a fixed position.
To attach the mounting bracket to drywall, install at least two fasteners to the stud behind the drywall
to give support for the weight of the device. The recommended fastener is a 3-in. #12 screw.
Use the dimensions shown in Figures 10 through 14 to install the device correctly. Make sure that the
device:
•Is in a location where personnel and objects cannot cause a blockage of the field of view
•Is in a location that is convenient for visual inspection and cleaning
•Is in a location where ice, dirt, or debris cannot collect on the optical window
•Points downward to prevent dust and moisture from collecting on the optical window
Installation
General Monitors does not recommend the use of cable shoes or crimps on any junction
box or housing wiring terminals. Poor crimping can cause a bad connection when
temperature variations occur.
FL500 UV/IR Flame Detector
US
17
Installation
Fig. 9 FL500 Outline Drawing, Front View
Fig. 10 FL500 Outline Drawing, Side View
US
FL500 UV/IR Flame Detector
18
Fig. 11 FL500 and Mounting Bracket, Side View
Installation
Fig. 12 FL500 and Mounting Bracket, Top View
FL500 UV/IR Flame Detector
US
19
Fig. 13 FL500 and Mounting Bracket, Rear View
Installation
3.4Wiring
WARNING!
An approved electrician must do electrical wiring.
All wiring must satisfy the requirements of the applicable NEC, CEC, and local electrical safety
codes.
Install a conduit seal within 18 in. (46 cm) of the device enclosure.
Make sure that all wiring is applicable for use at an ambient temperature of 199.6ºF (93.1°C).
Before installing the wiring for the device, disconnect the power source.
Read all electrical warnings and wiring requirements before connecting power to the device.
The device wiring can be damaged by electrostatic discharge (ESD). When you do work with the
device wiring, be careful to touch only the connection points. The warranty does not supply
coverage for components that are damaged by ESD.
Do NOT install wiring in a hazardous atmosphere. Otherwise, electrical shock or ignition can occur.
Failure to obey these warnings can result in serious injury or death.
Install all wiring connections through the base entries to the terminal block (TB). The terminal block
accepts 14 - 22 AWG (2.1 - 0.3 mm
2
) stranded or solid-core wire.
US
FL500 UV/IR Flame Detector
20
Fig. 14 FL500 Housing and Base
Remove the insulation from each wire to 0.25 in. (0.64 cm).
Use the correct cables for the ambient temperature where the device is installed.
Installation
Fault 2Alarm Reset
Fault C
Fault 1
Data −
RS485
Control Device
PLC, DCS, ETC
COM (24 V-return)
+−
Power Supply
Fig. 15 Wiring Diagram
Data +
No Connection
0-20 mA
+ 24 VDC
Chassis Ground
Protection Circuits for Relay Contacts
WARNING!
12345678910
11 12 13 14 15 16 17 18 19 20
TB2TB1
No Connection
No Connection
Alarm Test
Alarm Low 2
Alarm Low 1Alarm Low Relay
Alarm Low C
Alarm High C
Alarm High 1
Alarm High 2
Normally
Open Switch
Normally
Open Switch
Alarm High Relay
US
Protect relay contacts from transient and over-voltage conditions. Attach a clamp to all inductive loads
(bells, buzzers, relays) on dry relay contacts as shown. Inductive loads that do not have a clamp
attached can cause voltage spikes of more than 1000 Volts. Voltage spikes of this magnitude can
cause false alarms and damage to the contacts.
Failure to obey this warning can result in serious injury or death.
(1)To connect the wire to the terminal block, install the conductor in the connection space as shown.
(2)Use a flat-blade screwdriver to tighten the related screw terminal.
FL500 UV/IR Flame Detector
21
3.5Terminal Connections
TERM#TERM#
TB2TB1
11121314151617181920
12345678910
Chassis
COM (24 V - Return)
+ 24 VDC
0-20 mA
No Connection
Data +
Data −
Fault 1
Fault C
Fault 2
Alarm Low 2
Alarm Low 1
Alarm Low C
Alarm High C
Alarm High 1
Alarm High 2
Alarm Test
No Connection
No Connection
Alarm Reset
There are 20 terminal connections. The following sections give descriptions and specifications for
each connection.
Installation
3.5.1 TB2, Alarm High Relay Connection
Fig. 16 Field Terminations
The output for the SPDT Alarm High relay has a time delay that can be set for 2, 4, 8, or 10 seconds.
Alarm High output can be normally energized or normally de-energized, latching or non-latching.
All options can be set through Modbus, HART, or the DIP switch. Refer to Section 4.2 "Changing
Device Settings" for instructions.
TB2
Position
7CCommonCommon
61Normally ClosedNormally Open
52Normally OpenNormally Closed
Alarm High
Relay
Relay Contact
(De-Energized)
Relay Contact
(Energized)
US
FL500 UV/IR Flame Detector
22
3.5.2 TB2, Alarm Low Relay Connection
The output for the SPDT Alarm Low relay is immediate. Alarm Low output can be normally energized
or normally de-energized, latching or non-latching.
All options can be set through Modbus, HART, or the DIP switch. Refer to Section 4.2 "Changing
Device Settings" for instructions.
Installation
TB2
Position
Alarm Low
Relay
Relay Contact
(De-Energized)
Relay Contact
(Energized)
8CCommonCommon
91Normally ClosedNormally Open
102Normally OpenNormally Closed
3.5.3 TB1, Fault Relay Connection
The standard configuration for the SPDT Fault relay is normally energized and non-latching. This
configuration cannot be changed.
The Fault relay is activated during the time-out function, a low-power or loss-of-power condition, and
a COPM Fault. For the duration of these conditions, the Fault relay de-energizes and the signal for
analog output decreases to 0 mA (2 mA for a COPM Fault).
TB1
Position
Fault Relay
Relay Contact
(De-Energized)
Relay Contact
(Energized)
9C CC
81Normally ClosedNormally Open
102Normally OpenNormally Closed
3.5.4 Alarm Reset Switch
Use the Alarm Reset switch to set latched Alarm High or Alarm Low output that is no longer applicable
back to its initial condition.
Do the following:
(1) Connect one contact of a normally open momentary switch to TB1 Terminal 3.
(2) Connect the other contact to COM (device Common).
(3) Push and release the Alarm Reset switch.
PositionFunction
TB2 POS 11RESET
TB2 POS 14TEST
Multiple devices cannot be put in a daisy-chain configuration to use the Alarm Reset
switch. Each latching Alarm Low and Alarm High output must be reset manually.
FL500 UV/IR Flame Detector
US
23
3.5.5 Analog Output, Modbus and HART
The 0 - 20 mA output is equivalent to the following analog output:
ConditionModbusHART (Normal)HART (Special)
Startup0 - 0.2 mA3.5 ±0.2 mA1.25 ±0.2 mA
Fault0 - 0.2 mA3.5 ±0.2 mA1.25 ±0.2 mA
COPM Fault2.0 ±0.2 mA3.5 ±0.2 mA2.0 ±0.2 mA
Ready4.05 ±0.2 mA 4.05 ±0.2 mA4.05 ±0.2 mA
IR8.0 ±0.2 mA8.0 ±0.2 mA8.0 ±0.2 mA
UV12.0 ±0.2 mA 12.0 ±0.2 mA12.0 ±0.2 mA
Alarm Low16.0 ±0.2 mA 16.0 ±0.2 mA16.0 ±0.2 mA
Alarm High20.0 ±0.2 mA 20.0 ±0.2 mA20.0 ±0.2 mA
The maximum analog output load, including wiring, is 600 ohms.
In normal HART mode, the current output does not go below 3.5 mA. Modbus sends 2.0 mA output
for COPM (as if HART was not there) to make a constant Modbus program available. The digital HART
protocol sends the actual current output. When the Alarm High or Alarm Low relays are latched, the
highest output current is also latched. The output current goes back to 4.0 mA when the Alarm Reset
switch relay is activated.
The special HART mode lets the current decrease to 1.25 mA. The HART protocol continues to
operate. Use the special HART mode with products that require 2 mA output for COPM, 1.5 mA output
when the device is offline, and 0 mA output for a Fault condition.
The Modbus protocol is used to configure the device or to find the status of the device.
For information about Modbus, refer to the FL500 Modbus Communication Operating Manual
(PN 10193214).
For information about HART, refer to the FL500 HART Communication Operating Manual
(PN 10193215).
TB1 Position Connection
6DATA +
7DATA -
Installation
US
FL500 UV/IR Flame Detector
24
3.6Cable Lengths
Use the following cable lengths (maximum 50-ohm loop) for interfaces with impedance devices that
have 250-ohm input.
The voltage range for the power supply is 20 - 36 Vdc at the device. Low voltage occurs at approximately 18.5 Vdc.
TB1 PositionConnection
324 Vdc
2COM
3.8Chassis Ground
Use this connection to ground the device when you do any work with the wiring. General Monitors
recommends that the chassis be grounded at all times.
TB1 PositionConnection
1CHAS GND
3.9Fire Cards or Panels
General Monitors factory-fits end-of-life (EOL) and Alarm High resistors for devices that are wired
together to do monitoring through standard fire cards.
When the FL500 is used with a General Monitors Model IN042 card, the Alarm High resistor is set to
470 ohm and the EOL resistor is set to 5.6K. The EOL resistor is onboard the Model IN042 card and
can be selected through the DIP switch.
European Union (EU) approved applications: Make sure that interconnecting cables
have an overall screen, or screen and armor. Cables BS5308 Part 2, Type 2, or equivalent are approved for use. To make a positive electrical connection, make sure that the
cable armor connects to an applicable cable gland at the device.
US
FL500 UV/IR Flame Detector
25
3.10 Cable Termination in a Nonhazardous Area
WARNING!
Do NOT connect or disconnect equipment when power is supplied to the device. Doing so can result
in serious damage to the equipment. The warranty does not supply coverage for equipment that is
damaged in this way.
Failure to obey this warning can result in serious injury or death.
Connect the cable armor to safety earth in a nonhazardous area.
Connect the cable screen (drain wire) to instrument earth in a nonhazardous area.
Connect the power supply OV return to instrument earth in a nonhazardous area.
Keep interconnecting cables isolated from the power cable and other noisy cables, such as cables for
radio transmitters, welders, switch mode power supplies, inverters, battery chargers, ignition systems,
generators, switch gear, arc lights, and other high-frequency or high-power switching process equipment. Keep a separation of at least 3 ft (1 m) between instrument and other cables. An increased
separation is necessary for long, parallel cable runs. Do not put instrument cable trenches close to
lightning conductor earthing pits.
Installation
FL500 UV/IR Flame Detector
US
26
4Operation
WARNING!
Make sure that there is no physical blockage from permanent objects such as structures and
equipment or temporary objects such as personnel and vehicles in the sensor's field of view. If
there is physical blockage in the sensor's field of view, the device cannot accurately monitor the
area for flame.
Make sure that there is no ice, dirt, or debris on the optical window. Blockage of the optical window
can result in a Fault condition.
During a Fault condition, the device does not monitor the area for flame.
Failure to obey these warnings can result in serious injury or death.
4.1Start-Up
Before you supply power to the device, do the following:
•Replace the red dust cap with an applicable cable gland.
•Disconnect external devices such as automatic extinguishing fire suppression systems to prevent
activation.
•Make sure that the settings for the DIP switch are in the correct configuration. Refer to Section
4.2.1 "Using the DIP Switch" for instructions.
•Make sure that the device is mounted and wired correctly.
•Make sure that there is no blockage of the field of view for each device.
•Make sure that the optical window and reflectors are clean. Refer to Section 5.2 "Cleaning the
Optical Window" for cleaning instructions.
•Make sure that the power supply is connected correctly.
Apply power to the device. Each device starts a self-test start-up sequence. For the first 10 seconds,
the device sends 0 mA output, the Fault relay stays de-energized, and the green, yellow, and red
LEDs flash. After this 10-second period, the device sends 4 mA output, the Fault relay is energized,
the red LED goes off, and the green LED comes on and flashes every 5 seconds.
After the start-up sequence is complete, do a sensitivity check. Refer to Section 4.3 "Sensitivity
Check" for instructions.
Operation
US
4.2Changing Device Settings
All device settings can be changed through Modbus, HART, or the DIP switch. Settings made through
Modbus and HART override settings made through the DIP switch.
4.2.1 Using the DIP Switch
To change device settings through the DIP switch, do the following:
(1) Use a flat-blade screwdriver to remove the screws that attach the detector head to the base
assembly.
(2) Find the DIP switch.
(3) Make the applicable switch assignments.
(4) Cycle power to the device.
FL500 UV/IR Flame Detector
27
Operation
Fig. 17 DIP Switch Location
On the DIP switch, the nomenclature "ON/CLOSED" is used when the switch is pushed in on the side
labeled "ON" or "CLOSED" (opposite the side labeled "OPEN"). The nomenclature "OFF/OPEN" is
used when the switch is pushed in on the side with the number related to the switch position or the
side labeled "OPEN".
The time delay is the amount of time an Alarm Low condition continues before an Alarm High condition
occurs.
Option
Position12345678910
High SensitivityOFFOFF-------Medium SensitivityONOFF-------Low SensitivityOFFON-------2-second Alarm Time Delay--OFFON-----4-second Alarm Time Delay--OFFOFF-----8-second Alarm Time Delay--ONOFF-----10-second Alarm Time Delay--ONON-----Alarm High Non-Latching ----OFF----Alarm High Latching----ON----Alarm Low Non-Latching-----OFF---Alarm Low Latching-----ON---Alarm High Normal Energized------ON--Alarm High Normal
De-Energized
Alarm Low Normal Energized-------ON-Alarm Low Normal
To use the HART protocol, it is necessary to select the applicable current (1.25 mA or 3.5 mA). The
factory default setting is 3.5 - 20 mA. This setting can only be changed through HART or Modbus.
Settings for Modbus and HART can be changed through the DIP switch.
For information about changing device settings through Modbus, refer to the FL500 Modbus Commu-
nication Operating Manual (PN 10193214).
For information about changing device settings through HART, refer to the FL500 HART Communica-
tion Operating Manual (PN 10193215).
4.3Sensitivity Check
Use the TL105 Test Lamp or the Alarm Test feature to make sure that each device operates correctly.
If the device does not operate correctly, refer to Section 7 "Troubleshooting" for instructions.
4.3.1 TL105 Test Lamp
The TL105 test lamp is a battery operated, rechargeable test source used to make sure that operation
of the device is correct. The test lamp has a high-energy broadband radiation source that emits sufficient energy in both the UV and IR spectra to activate the UV and IR detectors. To simulate a fire, the
TL105 test lamp automatically flashes at the correct rate for different models. When fully charged, the
internal batteries operate continuously for 30 minutes. When the battery charge goes below the level
necessary to supply the correct intensity, an internal low-voltage circuit stops operation of the test
lamp until the batteries are recharged. For recharging instructions, refer to the TL105 Instruction
Manual (PN MANTL105).
Operation
Fig. 18 TL105 Test Lamp
(1) Make sure that the batteries are fully charged.
(2) Stand 15 - 20 ft (5 - 6 m) away from the device.
(3) Point the TL105 test lamp directly at the front of the device.
(4) Shake the test lamp from side to side or up and down. Motion increases the simulation of flames
flickering and increases the response of the device to the test lamp.
If device operation is correct, after a few flashes of the test lamp, an Alarm Low condition occurs.
If the test lamp stays pointed at the device for the period of the time-delay setting, an Alarm High
condition occurs.
To conserve the battery charge, operate the test lamp only as long as necessary to do
a test of each device.
FL500 UV/IR Flame Detector
US
29
4.3.2 Alarm Test Feature
To use the Alarm Test feature, do the following:
(1) Connect one contact of a normally open, momentary switch to TB1 Terminal 4.
(2) Connect the other contact to TB1 Terminals 9 and 10 (COM).
(3) Activate the switch for the period set for the time delay (2 - 10 seconds).
•If the device senses the source, it immediately sends Alarm Low output, then the time-delayed
Alarm High ouput. After 1 to 8 seconds, the device resets the non-latching Alarm Low and Alarm
High conditions. Latching Alarm Low and Alarm High conditions stay latched until they are reset
manually. Refer to Section 3.5.4 "Alarm Reset Switch" for instructions.
•If the device does not sense the source, it sends Fault output and does the test again every
10 seconds.
The Alarm Test feature can be used through Modbus and HART.
Multiple devices cannot be put in a daisy-chain configuration to do testing for Alarm High
output.
Operation
FL500 UV/IR Flame Detector
US
30
5Maintenance
WARNING!
Repair or alteration of the device beyond the scope of the maintenance instructions in this manual
or by anyone other than General Monitors or General Monitors-approved service personnel can
cause incorrect operation of the device and put persons who use this device for their safety at risk
of serious injury or death.
The device has components that can be damaged by electrostatic discharge (ESD). When you do
work with the device wiring, be careful to touch only the connection points. The warranty does not
supply coverage for components that are damaged by ESD.
Failure to obey these warnings can result in serious injury or death.
General Monitors recommends that maintenance intervals be set through a documented procedure
that includes a maintenance log kept by plant personnel or third-party testing services.
5.1Regular Maintenance
WARNING!
Maintenance
Use ONLY a damp cloth to clean the device. Otherwise, electrical shock or ignition from ESD can
occur.
Failure to obey this warning can result in serious injury or death.
Clean the optical window every 30 days at a minimum. Refer to Section 5.2 "Cleaning the Optical
Window" for instructions. Do sensitivity checks regularly. Refer to Section 4.3 "Sensitivity Check" for
instructions.
Examine, clean the optical window, and do sensitivity checks more frequently for
devices that are installed in dirty areas.
5.2Cleaning the Optical Window
WARNING!
Use ONLY Industrial Strength Windex® with Ammonia D (General Monitors PN 10272-1) to clean the
optical window. The optical window material is sapphire, not glass. Using any other commercial glass
cleaner will cause damage to the optical window. The warranty does not supply coverage for optical
windows that are damaged in this way.
Failure to obey this warning can result in serious injury or death.
Remove debris and film buildup on the optical window and reflectors regularly to make sure that the
device has the correct sensitivity and to prevent COPM Faults. General Monitors recommends that
you clean the optical window and reflectors every 30 days at a minimum. Clean the optical window
and reflectors more frequently for devices that are installed in dirty areas.
US
FL500 UV/IR Flame Detector
31
(1) Use a clean, soft, lint-free cloth, tissue, or cotton swab soaked with Industrial Strength Windex
with Ammonia D to clean the optical window.
(2) Use a clean, dry, cloth to rub the optical window until it is clean. Do NOT touch the lens with your
fingers.
(3) Let the optical window air-dry fully.
5.3Annual Maintenance
Make sure that all wiring and terminal connections are connected correctly.
Make sure that the mounting for all integral safety equipment, including but not limited to following
components, is stable:
•Power supplies
•Control modules
•Field detection devices
•Signaling devices
•Accessories connected to field and signaling devices
Maintenance
FL500 UV/IR Flame Detector
US
32
6Storage
WARNING!
Keep the device safe from vibration and mechanical shock, which can cause damage.
Failure to obey this warning can result in serious injury or death.
Keep the device in a clean area with an ambient temperature of -40°F to 185°F (-40°C to 85°C) and
a humidity range of 0% to 95% RH noncondensing.
For extended storage, do the following:
(1) If possible, keep the device in the mold as shipped by the manufacturer.
(2) Install the red dust caps in the cable entry holes.
(3) Seal the device and a desiccant in a plastic bag.
(4) Seal the plastic bag inside another plastic bag.
Storage
FL500 UV/IR Flame Detector
US
33
Troubleshooting
7Troubleshooting
WARNING!
Repair or alteration of the device beyond the scope of the maintenance instructions in this manual or
by anyone other than General Monitors or General Monitors-approved service personnel can cause
incorrect operation of the device and put persons who use this device for their safety at risk of serious
injury or death.
During a Fault condition, the device does not monitor the area for flame.
7.1Troubleshooting Table
The troubleshooting table gives information about common faults that occur during commissioning
and operation. These common faults can be repaired by a competent operator.
Before you do the following corrective actions, inhibit or disconnect the external alarm wiring to
prevent an accidental Alarm High condition.
ProblemPossible CauseCorrective Action
No output signal and all LEDs
are off
2 mA signal, green LED is off,
yellow LED is blinking
0 mA, 1.25 mA, or 3.5 mA
signal, and yellow LED is on
Constant 8 mA signal with no
known radiation to device
Constant 12 mA signal with no
known radiation to device
Constant 16 mA or 20 mA
signal (Alarm Low or Alarm
High) with no known radiation
at device
No dc power to the device
Device is in COPM Fault
Low supply voltage or other
fault
Background IR radiation at
device
Background UV radiation at
device
Background UV radiation at
device
Make sure that 24 Vdc is
applied with the correct polarity.
Clean the optical window and
reflectors. Refer to Section 5.2
"Cleaning the Optical Window"
for instructions.
Make sure that the supply
voltage is ≥20 Vdc at the
device. If it is, cycle the power
to see if the fault is removed.
Put a cover over the optical
window for 10 seconds. If the
device senses background IR,
and the analog output still
shows 8 mA, contact technical
support for more troubleshooting.
Put a cover over the UV part of
the optical window for 10
seconds. If the device senses
background UV, and the analog
output still shows 12 mA,
contact technical support for
more troubleshooting.
Put a cover over the optical
window for 10 seconds. If the
analog output still shows
16 mA or 20 mA, contact technical support for more troubleshooting.
US
FL500 UV/IR Flame Detector
34
Troubleshooting
If the corrective actions recommended in the troubleshooting table do not correct operation of the
device, return the device to General Monitors for repair.
7.2Returning the Device for Repairs
Use the following contact information to return a device to General Monitors for repair. Include a
detailed written description of the problem.
UNITED STATES
26776 Simpatica Circle
Lake Forest, CA 92630
IRELAND
Ballybrit Business Park
Galway
Republic of Ireland
MIDDLE EAST
P.O. Box 54910
Dubai Airport Freezone
United Arab Emirates
Additional locations are available at www.MSAsafety.com.
7.3Removing the Device from Service Permanently
EU member states must discard devices in accordance with the Waste Electrical and Electronic
Equipment (WEEE) Directive. All other countries or states must discard devices in accordance with
existing federal, state, and local environmental control regulations.
Zeta = -0.001
The margin of error in the range measurement is esti-
mated at ±5 ft (±1.5 m) due to wind conditions and flame
turbulence.
90
60
Response Time
(s)
6
<3
US
* Applicable to FM approvals only.
Notes:
Response times and field of view data were derived by testing the device with a 1 ft
cup of heptane on top of a 1-in. layer of water was ignited for each test. These are typical values. The
variation of each fire can cause different results.
BS EN 54-10 identifies the limit of the field of view to ±25 degrees because of the requirements of the
Directional Dependence test. This result is from indoor benchtop testing with a Bunsen burner as the
fire source, rather than the outdoor flame testing used to identify the field of view in Section 3.2.1
"Field of View".
FL500 UV/IR Flame Detector
2
heptane fire. One
36
8.2Mechanical Specifications
Enclosure material316 Stainless Steel
ColorRed
Finish TGIC polyester powder coat
Height6.4 in. (16.2 cm)
Width5.0 in. (12.7 cm)
Depth4.3 in. (11.0 cm)
Weight9.4 lb (4.3 kg)
Cable Entry
Earth Terminals
8.3Electrical Specifications
2 x ¾ in. NPT (M25 adapters included for some configurations)
8-32 x 3/8 Philips pan-head screw, stainless steel,
zinc-plated, green dye; external stainless steel tooth
lock washer included. Applicable for connection of
2
4mm
or smaller.
Specifications
Nominal supply voltage24 Vdc
Supply voltage range20 to 36 Vdc (measured at device)
Maximum supply current 200 mA during COPM only
Typical current80 to 150 mA
Maximum output signal load 600 ohms
Output signal range0 to 20 mA *
Fault signal0 to 0.2 mA *
COPM fault signal2.0 ±0.2 mA *
Ready signal4.0 ±0.2 mA
IR only signal8.0 ±0.2 mA
UV only signal12.0 ±0.2 mA
Alarm Low signal16.0 ±0.2 mA
Alarm High signal20.0 ±0.2 mA
North American Approved Applications:
SPDT, 5A @ 250 Vac, or 5A @ 30 Vdc resistive max.
Relay contact ratings
European Union (EU) Approved Applications:
SPDT, 5A 30V RMS/42.4V Peak, or 5A @ 30 Vdc
resistive max.
Modbus RTU
RS-485 output
128 devices in series max.
(247 devices with repeaters)
Baud rate: 2400, 4800, 9600, or 19200 bps
Fully HART 7 FieldComm compliant. Refer to the
HART
FL500 HART Communication Operating Manual
(PN 10193215).
HART impedanceRX = 50 K CX = 5 nF
US
FL500 UV/IR Flame Detector
37
RFI/EMI protectionComplies with BS EN 50130-4 and BS EN 61000-6-4
Status indicatorThree LEDs identify status, fault, and alarm conditions
8.4Environmental Specifications
Specifications
Operating temperature
range
Storage temperature range -40°F to 185°F (-40°C to 85°C)
Humidity range 0% to 95% RH noncondensing
False Alarm SourceDistance from FL500 (ft)Trouble / False Alarm
Direct sunlight3N
Reflected sunlight3N