Msa FL3101H, FL3100H User Manual

Page 1
Models FL3100H/FL3101H
UV/IR and UV only
Flame Detectors
The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General Monitors.
Instruction Manual DATE 01-16
General Monitors reserves the right to change published specifications and designs without prior notice.
MANFL3100H/3101H
Part No. MANFL3100/3101H Revision H/01-16
Page 2
Models FL3100H/3101H
ii
Page 3
Models FL3100H/3101H
Table of Contents
MODELS FL3100H/FL3101H ........................................................................................................ I
UV/IR AND UV ONLY FLAME DETECTORS ............................................................................... I
TABLE OF FIGURES ................................................................................................................. VII
TABLE OF TABLES .................................................................................................................. VIII
QUICK START GUIDE ................................................................................................................. 1
Mount and Wire the Detector .................................................................................................................. 1
Apply Power to the Detector ................................................................................................................... 4
Testing the Detector Using the TL105 .................................................................................................... 4
1.0INTRODUCTION .................................................................................................................... 5
1.1 Protection for Life ....................................................................................................................... 5
1.2 Special Warnings ....................................................................................................................... 5
1.3 System Integrity Verification ...................................................................................................... 5
2.0PRODUCT DESCRIPTION ..................................................................................................... 7
2.1 General Description ................................................................................................................... 7
3.0INSTALLATION ...................................................................................................................... 8
3.1 Tools Required ........................................................................................................................... 8
3.2 Choosing Product Locations ...................................................................................................... 8
3.2.1Detector Field of View ................................................................................................... 8
3.2.2Optical Sensitivity Range .............................................................................................. 8
3.2.3Environmental Factors .................................................................................................. 8
3.3 Mounting and Wiring ................................................................................................................ 12
3.3.1Terminal Connections ................................................................................................. 18
3.3.2Terminal Block TB2 – Alarm Relay Connections ........................................................ 18
3.3.3Terminal Block TB-2 Warning Relay Connections ...................................................... 19
3.3.4Fault Relay .................................................................................................................. 19
3.3.5Alarm Reset Terminal ................................................................................................. 20
3.3.6Analog Output ............................................................................................................. 20
3.3.7Cable Requirements ................................................................................................... 21
3.3.8Power .......................................................................................................................... 21
3.3.9Modbus Interface ........................................................................................................ 22
3.3.10Chassis Ground .......................................................................................................... 22
3.3.11Connection to Fire Cards/Panels ................................................................................ 22
3.3.12Cable Termination in the Non-Hazardous Area .......................................................... 23
4.0OPERATION ......................................................................................................................... 24
4.1 Checklist ................................................................................................................................... 24
4.2 Start Up .................................................................................................................................... 24
4.3 System Test ............................................................................................................................. 24
4.4 User Selectable Options/Factory Defaults ............................................................................... 24
5.0MODBUS INTERFACE ........................................................................................................ 26
iii
Page 4
Models FL3100H/3101H
Baud Rate ................................................................................................................................ 26
5.1
5.2 Data Format ............................................................................................................................. 26
5.3 Modbus Read Status Protocol (Query/Response) ................................................................... 26
5.3.1Modbus Read Query Message ................................................................................... 26
5.3.2Modbus Read Response Message ............................................................................. 27
5.4 Modbus Write Command Protocol (Query/Response) ............................................................ 27
5.4.1Modbus Write Query Message ................................................................................... 27
5.4.2Modbus Write Response Message ............................................................................. 28
5.4.3Function Codes Supported ......................................................................................... 28
5.5 Exception Responses and Exception Codes ........................................................................... 28
5.5.1Exception Responses ................................................................................................. 29
5.6 Command Register Locations .................................................................................................. 30
5.6.1Operational Mode Commands .................................................................................... 30
5.7 FL3100H / FL3101H Operational Mode Command Register Details ...................................... 34
5.7.1Analog (00H) ............................................................................................................... 34
5.7.2Mode (01H) ................................................................................................................. 34
5.7.3Status/Error (02H) ....................................................................................................... 34
5.7.4Faults .......................................................................................................................... 35
5.7.5UV/IR Only (03H) ........................................................................................................ 35
5.7.6Model Type (04H) ....................................................................................................... 35
5.7.7Software Revision (05H) ............................................................................................. 36
5.7.8COPM Fault (06H) ...................................................................................................... 36
5.7.9EEPROM Override (07H) ............................................................................................ 36
5.7.10Options (08H) .............................................................................................................. 36
5.7.11Comm 1 Address (09H) .............................................................................................. 37
5.7.12Comm 1 Baud Rate (0BH) .......................................................................................... 37
5.7.13Comm 1 Data Format (0CH) ....................................................................................... 38
5.7.14UV Signal Count (0DH) ............................................................................................... 38
5.7.15IR Signal Count (0EH) ................................................................................................ 38
5.7.16UV Fault Total (0FH) ................................................................................................... 38
5.7.17IR Fault Total (10H) ..................................................................................................... 38
5.7.18Remote Reset (11H) ................................................................................................... 38
5.7.19Remote Alarm Test (12H) ........................................................................................... 39
5.7.20Clear COPM Faults (13H) ........................................................................................... 39
5.7.21Serial Number (15/16H) .............................................................................................. 39
5.7.22HART Enable (1D) ...................................................................................................... 39
5.7.23HART Test (1E) ........................................................................................................... 39
5.7.24Not Used (1F) .............................................................................................................. 40
5.7.25Comm 1 Total Illegal number of registers Errors (20H) .............................................. 40
5.7.26Comm 1 Bus Activity Rate % (21H) ............................................................................ 40
5.7.27Comm 1 Function Code Errors (22H) ......................................................................... 40
5.7.28Comm 1 Starting Address Errors (23H) ...................................................................... 40
5.7.29Comm 1 Total Receive Errors (24H) ........................................................................... 40
5.7.30RXD CRC Errors Hi (25h) ........................................................................................... 40
5.7.31RXD CRC Errors Lo (Same as Hi) (26h) .................................................................... 40
5.7.32Comm 1 Overrun Errors (27H) .................................................................................... 40
5.7.33Comm 1 Parity Errors (28H) ....................................................................................... 40
5.7.34Comm 1 Framing Errors (29H) ................................................................................... 41
5.7.35Comm 1 Total UART Receive Errors (2AH) ............................................................... 41
5.7.36Comm 1 Total Receive Errors (2BH) .......................................................................... 41
5.7.37Clear Comm 1 UART Errors (2CH) ............................................................................. 41
5.7.38Clear Comm 1 Modbus Errors (2DH) .......................................................................... 41
5.7.39HART Current (2E) ...................................................................................................... 41
iv
Page 5
Models FL3100H/3101H
Comm 2 Address (2FH) .............................................................................................. 41
5.7.40
5.7.41Comm 2 Baud Rate (30H) .......................................................................................... 42
5.7.42Comm 2 Data Format (31H) ....................................................................................... 42
5.7.43Not Used (32H) ........................................................................................................... 42
5.7.44Input Voltage (33H) ..................................................................................................... 42
5.7.45Alarm Test Voltage (34H) ........................................................................................... 43
5.7.46Reset Relays Voltage (35H) ....................................................................................... 43
5.7.47Dip Switch Settings (36H) ........................................................................................... 43
5.7.48Not Used (37 – 3FH) ................................................................................................... 43
5.7.49See Event Logging - Section 6.0 (40H – 67H) ............................................................ 43
5.7.50User Information (68h to 77h) ..................................................................................... 43
5.7.51Comm 2 Total Illegal Number of Registers Errors (78H) ............................................ 43
5.7.52Comm 2 Bus Activity Rate % (79H) ............................................................................ 43
5.7.53Comm 2 Function Code Errors (7AH) ......................................................................... 43
5.7.54Comm 2 Starting Address Errors (7BH)...................................................................... 43
5.7.55Comm 2 Total Receive Errors (7CH) .......................................................................... 43
5.7.56RXD CRC Errors Hi (7DH) .......................................................................................... 44
5.7.57RXD CRC Errors Lo (Same as Hi) (7EH) ................................................................... 44
5.7.58Comm 2 Overrun Errors (7FH) ................................................................................... 44
5.7.59Comm 2 Parity Errors (80H) ....................................................................................... 44
5.7.60Comm 2 Framing Errors (81H) ................................................................................... 44
5.7.61Comm 2 Total UART Receive Errors (82H) ................................................................ 44
5.7.62Not Used (83H) .......................................................................................................... 44
5.7.63Clear Comm 2 UART Errors (84H) ............................................................................. 44
5.7.64Clear Comm 2 Modbus Errors (85H) .......................................................................... 44
6.0EVENT LOGGING ................................................................................................................ 45
6.1.1Faults .......................................................................................................................... 45
6.1.2Warning ....................................................................................................................... 45
6.1.3Alarm ........................................................................................................................... 45
6.1.4Maintenance ................................................................................................................ 45
6.1.5Setting Clock ............................................................................................................... 45
7.0MAINTENANCE ................................................................................................................... 48
7.1 General Maintenance ............................................................................................................... 48
7.2 Cleaning the Lenses/Light Rods .............................................................................................. 48
7.3 Sensitivity Check ...................................................................................................................... 49
7.3.1Alarm Test ................................................................................................................... 49
7.3.2TL105 Test Lamp ........................................................................................................ 50
7.3.3TL105 Operating Instructions ...................................................................................... 50
7.3.4TL105 Recharging Instructions ................................................................................... 50
7.4 Storage ..................................................................................................................................... 51
8.0TROUBLESHOOTING ......................................................................................................... 52
8.1 Troubleshooting ....................................................................................................................... 52
8.1.1Introduction ................................................................................................................. 52
9.0CUSTOMER SUPPORT ....................................................................................................... 53
9.1 Other Sources of Help .............................................................................................................. 53
10.0 APPENDIX ................................................................................................................ 54
v
Page 6
Models FL3100H/3101H
Warranty ................................................................................................................................... 54
10.1
10.2 Principle of Operation ............................................................................................................... 54
10.2.1UV Detector - FL3100H and FL3101H........................................................................ 54
10.2.2UV/IR Flame Detector - FL3100H ............................................................................... 55
10.2.3COPM Circuitry ........................................................................................................... 55
10.2.4Alarm Test ................................................................................................................... 56
10.2.5Two-color Visual Indicators ......................................................................................... 56
10.2.6Three-color Visual Indicators ...................................................................................... 56
10.3 Specifications ........................................................................................................................... 57
10.3.1System Specifications ................................................................................................. 57
10.3.2Mechanical Specifications ........................................................................................... 58
10.3.3Electrical Specifications .............................................................................................. 58
10.3.4Environmental Specifications ...................................................................................... 59
10.4 Approvals ................................................................................................................................. 59
10.5 Accessories .............................................................................................................................. 59
10.5.1Mounting Swivel/Union ............................................................................................... 59
10.5.2Mounting Bracket ........................................................................................................ 59
10.6 Storage ..................................................................................................................................... 59
10.7 Final Assembly ......................................................................................................................... 60
vi
Page 7
Models FL3100H/3101H
Table of Figures
Figure 1: P/N 961-004 Union Swivel Mounting Hardware ................................................................................. 1
Figure 2: P/N 71172 Side View Bracket Assembly ............................................................................................ 2
Figure 3: P/N 71172 Top View Bracket Assembly ............................................................................................ 2
Figure 4: P/N 71172 Rear View Bracket Assembly ............................................................................................ 3
Figure 5: Field Terminations ............................................................................................................................... 3
Figure 6: Model FL3100H ..................................................................................................................................... 7
Figure 7: Model FL3101H ..................................................................................................................................... 7
Figure 8: FL3100H (UV/IR) Field of View ............................................................................................................ 9
Figure 9: FL3100H (UV/IR) Hydrogen Flame Detector Field of View ............................................................. 10
Figure 10: FL3101H (UV) Field of View ............................................................................................................. 11
Figure 11: P/N 961-004 Swivel Elbow Drawing ................................................................................................ 12
Figure 12: P/N 71072 Side View Mounting Bracket Drawing .......................................................................... 13
Figure 13: P/N 71072 Top View Mounting Bracket Drawing ........................................................................... 13
Figure 14: P/N 71072 Rear View Mounting Bracket Drawing ......................................................................... 14
Figure 15: FL3100H and FL3101H Outline Drawing ........................................................................................ 15
Figure 16: FL3100H and FL3101H Outline Drawing ........................................................................................ 15
Figure 17: FL3100H and FL3101H Field Terminations .................................................................................... 16
Figure 18: Detector Housing and Base ............................................................................................................ 17
Figure 19: Terminal Block Operation ................................................................................................................ 17
Figure 20: Protection Circuits for Relay Contacts .......................................................................................... 18
Figure 21: DIP switch Location ......................................................................................................................... 25
Figure 22: UV and IR Windows .......................................................................................................................... 49
Figure 23: Spectral Response of UV and IR Detectors ................................................................................... 55
Figure 24: P/N 71450 FL3100H (UV/IR), Final Assembly ................................................................................ 60
Figure 25: P/N 71451 FL3101H (UV), Final Assembly .................................................................................... 61
vii
Page 8
Models FL3100H/3101H
Table of Tables
Table 1: TB2 Alarm Relay Connections ........................................................................................................... 18
Table 2: TB2 Warning Relay Connections ....................................................................................................... 19
Table 3: Fault Relay Connections ..................................................................................................................... 19
Table 4: Alarm Reset Terminal Connections ................................................................................................... 20
Table 5: Maximum Cable Requirements .......................................................................................................... 21
Table 6: Power Connections ............................................................................................................................. 21
Table 7: Maximum Cable Lengths for +24 VDC Supply .................................................................................. 21
Table 8: Connections for the Modbus Interface .............................................................................................. 22
Table 9: Connections for the Second Modbus Interface ................................................................................ 22
Table 10: Chassis Ground Connection ............................................................................................................ 22
Table 11: DIP Switch Options ............................................................................................................................ 25
Table 12: Data Format ........................................................................................................................................ 26
Table 13: Modbus Query Messages .................................................................................................................. 26
Table 14: Modbus Read Response Messages ................................................................................................. 27
Table 15: Modbus Write Query Message.......................................................................................................... 27
Table 16: Modbus Write Response Message ................................................................................................... 28
Table 17: Exception responses ......................................................................................................................... 29
Table 18: Exception Code Field ........................................................................................................................ 29
Table 19: Operational Mode Commands .......................................................................................................... 33
Table 20: Fire Status Mode ................................................................................................................................ 34
Table 21: Status/Error ........................................................................................................................................ 34
Table 22: Model Type ......................................................................................................................................... 35
Table 23: EEPROM Override .............................................................................................................................. 36
Table 24: Setting Options .................................................................................................................................. 37
Table 25: Comm 1 Baud Rate ............................................................................................................................ 37
Table 26: Comm 1 Data Format ......................................................................................................................... 38
Table 27: Remote Reset ..................................................................................................................................... 38
Table 28: Remote Alarm Test ............................................................................................................................ 39
Table 29: Clear COPM Faults Function ............................................................................................................ 39
Table 30: Comm 2 Baud Rate ............................................................................................................................ 42
Table 31: Comm 2 Data Format ......................................................................................................................... 42
Table 32: Event Logging Registry Table ......................................................................................................... 47
Table 33: Troubleshooting Table ...................................................................................................................... 52
Table 34: Locations ............................................................................................................................................ 53
viii
Page 9
Models FL3100H/3101H
Quick Start Guide
Mount and Wire the Detector
Pay special attention to the conduit seal entry (Canadian Electrical Code Handbook Part 1, Section 18-154). Also, lithium based grease is applied to the O-ring seal between the back­plate and housing, as additional protection to avoid water ingression into the housing. Mount detector using swivel mount or mounting bracket hardware.
Figure 1: P/N 961-004 Union Swivel Mounting Hardware
1
Page 10
Models FL3100H/3101H
Figure 2: P/N 71172 Side View Bracket Assembly
Figure 3: P/N 71172 Top View Bracket Assembly
2
Page 11
Models FL3100H/3101H
Figure 4: P/N 71172 Rear View Bracket Assembly
Term #
Terminal Block 2 Terminal Block 1
Term #
10
1 2 3 4 5 6 7 8 9
10
9 8 7 6 5 4 3 2 1
Figure 5: Field Terminations
3
Page 12
Models FL3100H/3101H
Apply Power to the Detector
Two light emitting diodes (LEDs) are visible through the UV window (the larger window on UV/IR units). Immediately upon powering up the detector, the LEDs will start blinking alternately
- green and red in the two-color configuration and green, yellow, and red in the three-color configuration. The flashing pattern lasts 10 seconds. Upon the detector entering the “Ready” mode, the green LED will flash off 1 second, every 10 seconds. Section 10.2.6 (Three-color Visual Indicators) describes the flashing scheme of the product configuration with three LEDs.
Testing the Detector Using the TL105
Test the integrity of your system by using the TL105 test lamp. The original configuration (i.e. sensitivity and relay options) can be changed by using the “Switch Selectable Options” (Table
11) and then changing the dipswitch settings located on the bottom of the power board (SW1). The instrument is now ready to operate. Please consult the manual for more information on the
instrument’s many features.
NOTE: If you have any problems in the set-up or testing of the detector, please refer to the
“Troubleshooting Section”, or call the factory direct.
Worldwide service is available by calling:
Lake Forest, California (24 hr. service)
Houston, Texas
Ireland
Singapore
United Arab Emirates
United Kingdom
Toll Free: +1-800-446-4872 Phone: +1-949-581-4464 Fax: +1-949-581-1151
Phone: +1-281-855-6000 Fax: +1-281-855-3290
Phone: +353-91-751175 Fax: +353-91-751317
Phone: +65-6748-3488 Fax: +65-6748-1911
Phone: +971-4-294-3640 Phone: +44-1625-619583
Fax: +44-1625-619098
4
Page 13
Models FL3100H/3101H
1.0 Introduction
1.1 Protection for Life
General Monitors’ mission is to benefit society by providing solutions through industry leading safety products, services, and systems that save lives and protect capital resources from the dangers of hazardous flames, gases, and vapors.
This manual provides instruction for installing and operating General Monitors’ Models FL3100H and FL3101H for UV/IR and UV Only Flame Detection. While the FL3100H/3101H is easy to install and operate, this manual should be read in full and the information contained herein understood before attempting to place the system in service.
The safety products you have purchased should be handled carefully and installed, and maintained in accordance with the respective product instruction manual. Remember these products are for your safety.
1.2 Special Warnings
Through engineering design, testing, manufacturing techniques, and rigid quality control, General Monitors supplies the finest flame detection systems available. The user must recognize his responsibility for maintaining the flame detection system in operational condition. Installation and maintenance must be carried out by suitably skilled and competent personnel only.
The FL3100H UV/IR and FL3101H UV only flame detectors contain components, which can be damaged by static electricity. Special care must be taken when wiring the system, to ensure that only the connection points are touched.
Special Conditions For Safe Use
This equipment uses an external non-metallic coating and may therefore generate an
ignition-capable level of electrostatic charge under certain extreme conditions. The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions (such as high-pressure steam) which might cause a build-up of electrostatic charge on non-conducting surfaces. Additionally, cleaning of the equipment should be done only with a damp cloth.
In accordance with EN 60079-1:2014/ IEC 60079-1:Ed 7 Clause 11.3, the 4 x M6
housing retaining bolts are Class A2-70 304 Stainless Steel.
In accordance with EN 60079-1:2014/ IEC 60079-1:Ed 7 Clause 5.1, the flameproof
joints are not intended to be repaired.
1.3 System Integrity Verification
Commissioning Safety Systems
Before power up, verify wiring, terminal connections and stability of mounting for all integral safety equipment including, but not limited to:
Power supplies Control modules Field detection devices
5
Page 14
Models FL3100H/3101H
Signaling / output devices  Accessories connected to field and signaling devices
After the initial application of power (and any factory specified warm-up period) to the safety system, verify that all signal outputs, to and from devices and modules, are within the manufacturers’ specifications. Initial testing should be performed per the manufacturers’ recommendations and instructions.
Proper system operation should be verified by performing a full, functional test of all component devices of the safety system, ensuring that the proper levels of alarming occur. Fault/Malfunction circuit operation should be verified.
Periodic Testing of Field Devices
Periodic testing should be performed per the manufacturers’ recommendations and instructions. Testing procedures should include, but not be limited to:
Verify integrity of all optical surfaces and devices  For flame detectors, use the appropriate test lamp
When testing produces results outside of the manufacturers’ specifications, replacement of the suspect device(s) should be performed as necessary.
Periodic System Verification
The following system verifications should be performed at least annually: Verify wiring, terminal connections and stability of mounting for all integral safety equipment
including, but not limited to:
 Power supplies  Control modules  Field detection devices  Signaling / output devices  Accessories connected to field and signaling devices
Proper system operation should be verified by performing a full, functional test of all component devices of the detection system, ensuring that the proper levels of alarming occur. Fault/Malfunction circuit operation should be verified.
Maintenance intervals should be independently established through a documented procedure, including a maintenance log maintained by plant personnel or third party testing services.
6
Page 15
Models FL3100H/3101H
2.0 Product Description
2.1 General Description
Fire is usually manifested in heat (IR), smoke, light (visible), and flame (UV). Flame is the gaseous region of a fire where vigorous combustion chain reactions take place. These reactions emit radiation covering the Infrared, Ultraviolet and the Visible Spectral Regions.
The General Monitors’ Model FL3100H is an ultraviolet/infrared (UV/IR) flame detector (Figure
6). It detects the ultraviolet and infrared spectral regions of flame to produce a system which is highly immune to false alarms caused by lightning, arc-welding, hot objects, and other sources of radiation. The Model FL3101H is an ultraviolet (UV) flame detector (Figure 7). It only responds to UV and has been optimized for speed of response.
Both units may be used with the General Monitors TA402A trip amplifier, FL802 controller, or with other equipment, which accepts the 4 to 20 mA output. They may also be interfaced directly with alarm/suppression devices or with switched input modules using integral relays. If HART is used with the above controllers, you must use the special 1.25 mA to 20 mA mode.
NOTE: The Model FL802 is not CE Marked and, therefore, cannot be supplied to the EU. The Models FL3100H and FL3101H features include:
Compact unitized design  Continuous optical path monitoring (COPM)  4-20 mA, alarm relays, and Modbus RTU RS-485 standard (Dual Modbus optional)
(HART optional)
Wide field of view  High false alarm immunity and visual indicators
Figure 6: Model FL3100H
7
Figure 7: Model FL3101H
Page 16
Models FL3100H/3101H
3.0 Installation
WARNING: Suitably skilled and competent personnel must carry out installation and
maintenance.
3.1 Tools Required
“T” Allen head wrench to remove detector head from detector base (included with flame
detector).
Flat head screwdriver maximum 3/16 in (5 mm) width for terminal block connections.  Adjustable wrench for conduit, or cable gland connections.
3.2 Choosing Product Locations
Several variables are involved in selecting the locations to install detectors to ensure proper flame detection. There are no hard and fast rules defining the optimum location. Following are some general suggestions that should be considered in regard to particular conditions at the site where the unit(s) are being installed:
3.2.1 Detector Field of View
The FL3100H and FL3101H flame detectors have a maximum cone of vision of 120 and 140 maximum respectively. This cone has its vertex at the center of the detector (Figure 8 and Figure 10).
3.2.2 Optical Sensitivity Range
The distance at which the detector will respond to a flame is a function of the intensity of that flame. The maximum distance is 50ft (15.2m) for a heptane fire with a surface area of 1 sq. ft. (0.093m2).
3.2.3 Environmental Factors
Mounting should be as free from shock and vibration as possible and convenient for visual inspection and cleaning.
Detectors mounted in dirty atmospheric conditions will require frequent inspection, cleaning, and sensitivity checking. Make sure the field-of-view of the detector is not obstructed by the cover or nearby objects.
Observe the ambient temperature range for the specific model (Section 10.3.4). For outdoor installations or other areas exposed to intense, direct solar radiation, the detector may reach temperatures well above specifications. For these installations, a shade or cover may be required to keep the detector temperature within specifications.
Avoid conditions that would allow ice build-up on the optical detector windows. Complete icing over of the detector window(s) can result in fault conditions. Mount away from sources of electrical noise where possible. A constant UV source detected by the unit will cause the detector to go into FAULT after 9 – 10 minutes of exposure. The source must be removed or the detector must be repositioned. (UV detectors can pick-up arc welding up to 2–3 miles away). Users should be aware that any UV detector may be triggered by other sources of EMI, for instance X-rays, sunlight, reflected sunlight, Gamma rays, lightning, arc welding, industrial lighting, fluorescent lighting, etc., and due regard should be paid to the possible presence of such radiation.
8
Page 17
Models FL3100H/3101H
Figure 8: FL3100H (UV/IR) Field of View
9
Page 18
Models FL3100H/3101H
Figure 9: FL3100H (UV/IR) Hydrogen Flame Detector Field of View
NOTE: Response Times and Field of View data have been derived by testing the Model
FL3100H flame detector with a flame from a round 6 inch diameter burner. The hydrogen gas was supplied from a high pressure tank via a reducing regulator, set to 12 psi. This produces a flame 6 inches in height. The FL3100H-Hydrogen detector can be tested by the TL105 as far as 40 feet. These are typical values and different results may occur depending on the variation of each fire.
NOTE: The FL3100H-Hydrogen detector is not FM approved.
10
Page 19
Models FL3100H/3101H
75°
70°
60°
45°
30°
15°
50'
45'
40'
35'
30'
25'
20'
15'
10'
15°
30°
45°
60°
70°
75°
+15°
-15°
+30°
' 0 5
(±5°)
HORIZONTAL
SENSITIVIT Y
100% 75%, 50%
+75°
+70°
+60°
+45°
'
'
'
'
'
'
5
0
0
5
3
3
4
4
' 5 2
'
0
5
0
2
1
1
VERTICAL
- 15°
- 30°
- 45°
- 60°
- 70°
- 75°
100%
50' 50' 50' 50' 50' 25'
<20'
TABLE CHART
50%
75%
40'
45'
40'
45'
40'
45' 45'
40'
45'
<15'
<20'
<15'
<20'
TABLE CHART
100%
50' 50' 50' 50' 50' 25' 20'
100%
50' 50' 50'
50' 30'
<20' <15'
HORIZONTAL
± 15° ± 30° ± 45° ± 60° ± 70° ± 75°
VERTICAL
0° + 15° + 30° + 45° + 60° + 70° + 75°
75%
45' 45' 45' 45' 45'
<15'
75% 50%
45' 45' 45' 45'50'40'
<15'20'
<20' <20'
50%
45' 45' 45' 45'
45' <15' <15'<15'
45' 45' 45' 45' 20'
-30°
-45°
-60°
-70°
(±5°)
VERTICAL
-75°
SENSITIVITY
100% 75%
50%
Figure 10: FL3101H (UV) Field of View
11
Page 20
Models FL3100H/3101H
3.3 Mounting and Wiring
WARNING: The conduit entries should be sealed per the Canadian Electrical Code
Handbook (Part 1, Section 18-154) or NEC 500-3d. An additional benefit of conduit seals is the prevention of water entering the housing through the conduit entry.
WARNING: Unused cable entry holes must be sealed with an approved stopping plug.
Red caps supplied by GM are for dust protection only and must not be left on the unit when installed.
The FL3100H/FL3101H flame detectors should be mounted pointing downward so that dust/moisture will not accumulate on the optical window(s). The detector(s) should be mounted in locations which will inhibit people or objects from obscuring the detector’s cone of vision.
Detectors should be mounted such that the conduit or cable gland entries are pointed downward. See above warning for conduit entries. For cable glands and stopping plugs, the threads should be sealed with Castrol EP and boots fitted over the cable gland to prevent water ingress at the cable-to-gland junction. Mounting hardware should be used as shown in Figure 12, and Figure 13.The overall dimensions of the detector and mounting hardware are shown in Figure 15 and Figure 16.
NOTE: General Monitors does not recommend the use of cable shoes or crimps on any
junction box or housing wiring terminals. Poor crimping can cause a bad connection when the unit experiences temperature variations.
Figure 11: P/N 961-004 Swivel Elbow Drawing
12
Page 21
Models FL3100H/3101H
Figure 12: P/N 71072 Side View Mounting Bracket Drawing
Figure 13: P/N 71072 Top View Mounting Bracket Drawing
13
Page 22
Models FL3100H/3101H
Figure 14: P/N 71072 Rear View Mounting Bracket Drawing
14
Page 23
Models FL3100H/3101H
Figure 15: FL3100H and FL3101H Outline Drawing
[139.7]
5.0[127.0]
6.2[157.5]
.75[19.1]
2X 3/4 NPT ENTRY
5.5
1.50[38.1]
4X M6 X 1
2.94[74.7]
6.2[157.5]
1.63[41.4]
.75[19.1]
1.67[42.4]
Figure 16: FL3100H and FL3101H Outline Drawing
15
Page 24
Models FL3100H/3101H
Figure 17: FL3100H and FL3101H Field Terminations
16
Page 25
Models FL3100H/3101H
Figure 18: Detector Housing and Base
Term #
10
Terminal Block 2 Terminal Block 1
1 2 3 4 5 6 7 8 9
Term #
10
9 8 7 6 5 4 3 2 1
Figure 19: Terminal Block Operation
The optional HART signal will be on pin TB1- 5
17
Page 26
3.3.1 Terminal Connections
Models FL3100H/3101H
All wire connections are made through the base entries to the terminal block (Figure 19). The terminal block accepts 14 AWG to 22 AWG (2.1 to 0.3 mm
2
) stranded or solid core wire. Each wire should be stripped to .25 in (.64 cm). To connect the wire to the terminal block, insert the conductor into the connection space as shown in Figure 19 and tighten the corresponding screw terminal. There are twenty terminal connections. The following pages contain descriptions and specifications for each connection.
WARNING: Relay contacts must be protected against transient and over-voltage conditions
(Figure 20).
H
H
Figure 20: Protection Circuits for Relay Contacts
3.3.2 Terminal Block TB2 – Alarm Relay Connections
TB2
Position
2 C Common Common 3 1 Normally Closed Normally Open 4 2 Normally Open Normally Closed
These connections are for the SPDT ALARM relay. The ALARM output is time delayed for 2, 4, 8 or 10 seconds. This time delay can be set by Modbus, HART, or by Dipswitch. The ALARM output can be normally energized or normally de-energized, latching or non-latching, and these options are also set via can be set by Modbus, HART, or by Dipswitch (Section 4.4). For all relay connections see Figure 20.
North American Approved Applications: The ALARM relay contact ratings are 8A @ 250 VAC and 8A @ 30 VDC resistive max.
European Union (EU) Approved Applications: The ALARM relay contact ratings are 8A, 30 V RMS/42.4 V peak or 8A @ 30 VDC resistive max.
Alarm
Relays
Relay Contact
(De-Energized)
Table 1: TB2 Alarm Relay Connections
H
H
Relay Contact
(Energized)
18
Page 27
Models FL3100H/3101H
3.3.3 Terminal Block TB-2 Warning Relay Connections
TB2
Position
5 C Common Common 6 1 Normally Closed Normally Open
7 2 Normally Open Normally Closed
These connections are for the SPDT WARN relay. The WARN output is immediate on the FL3100H/FL3101H. The WARN output can be normally energized or normally de-energized, latching or non-latching, and these options are also set via Modbus, HART, or by Dipswitch (Section 4.4).
The WARN relay contact ratings are 8A @ 250VAC and 8A @ 24VDC.
CAUTION: Inductive loads (bells, buzzers, relays, etc.) on dry relay contacts must be clamped
Warn Relays
Table 2: TB2 Warning Relay Connections
down as shown in Figure 20. Unclamped inductive loads can generate voltage spikes in excess of 1000 Volts. Spikes of this magnitude may cause false alarms and contact damage.
Relay Contacts
(De-Energized)
Relay Contacts
(Energized)
North American Approved Applications: The WARN relay contact ratings are 8A @ 250 VAC and 8A @ 30 VDC resistive max.
European Union (EU) Approved Applications: The WARN relay contact ratings are 8A, 30 V RMS/42.4 V peak or 8A @ 30 VDC resistive max.
3.3.4 Fault Relay
These connections are for the SPDT FAULT relay. The FAULT output configuration is normally energized and non-latching. This is the standard configuration and it cannot be changed. The FAULT circuit will be activated during the time-out function, a low power or loss of power condition, and during a failed COPM check. During these conditions the FAULT relays will de­energize and the analog output signal will drop to 0 mA (2 mA for COPM faults) for the duration of the FAULT.
TB2
Position
8 C C C 9 1 Normally Closed Normally Open
10 2 Normally Open Normally Closed
North American Approved Applications: The FAULT relay contact ratings are 8A @ 250 VAC and 8A @ 30 VDC.
European Union (EU) Approved Applications: The FAULT relay contact ratings are 8A, 30 V RMS/42.4 V peak or 8A @ 30 VDC resistive max.
Fault
Relays
Relay Contacts
(De-Energized)
Table 3: Fault Relay Connections
Relay Contacts
(Energized)
19
Page 28
Models FL3100H/3101H
3.3.5 Alarm Reset Terminal
The RESET, when activated, returns a latched ALARM and/or WARN output that is no longer valid, to its original state. For this RESET function, place one contact of a normally open momentary switch to TB1 Terminal 3 and the other contact to DC COM (the detector’s common). To activate, just press and release the switch.
TB1
Position
3 RESET 4 TEST 5 0-20 mA
Table 4: Alarm Reset Terminal Connections
By connecting one contact of a normally open, momentary switch, to TB1 Terminal 4 and the other contact to TB1 Terminals 9 and 10 (DC COM), the user can test the alarm outputs of the flame detector by activating this switch for two to ten seconds depending on the alarm time delay setting. The Alarm Test will activate the WARN and ALARM relay outputs as well as the appropriate analog output. The flame detector will remain in this state until the switch is released. Note: This function is also available via Modbus and HART.
NOTE: The latching WARN and/or ALARM will have to be RESET manually. The Alarm Test
feature cannot be daisy chained between two or more FL3100H/FL3101H flame detectors.
Relays
3.3.6 Analog Output
The 0 to 20 mA output is a current signal that corresponds to the following signals:
Condition Current Modbus HART (Normal) HART (Special)
START UP:
0 to 0.2 mA 3.5 ± 0.1 mA 1.25 ± 0.1 mA
FAULT:
COPM Fault:
Ready:
IR (FL3100H only):
UV (FL3100H only):
WARN:
ALARM:
When HART is selected, the output current changes to comply with the HART Foundation requirements. The HART Foundation does not specify current below 3.5 mA. In normal HART mode, the actual current does not go below 3.5 mA. Modbus reports the analog output as if HART was not there, meaning it reports 2.0 mA for COPM. This allows users to use a constant Modbus program. The digital HART reports the actual current. When the alarm or warning
20
0 to 0.2 mA 3.5 ± 0.1 mA 1.25 ± 0.1 mA
2.0 ± 0.1 mA 3.5 ± 0.1 mA 2.0 ± 0.1 mA
4.05 ± 0.05 mA 4.05 ± 0.05 mA 4.05 ± 0.05 mA
8.0 ± 0.1 mA 8.0 ± 0.1 mA 8.0 ± 0.1 mA
12.0 ± 0.1 mA 12.0 ± 0.1 mA 12.0 ± 0.1 mA
16.0 ± 0.1 mA 16.0 ± 0.1 mA 16.0 ± 0.1 mA
20.0 ± 0.1 mA 20.0 ± 0.1 mA 20.0 ± 0.1 mA
Page 29
Models FL3100H/3101H
relays are latched, the highest output current is also latched. The output current will return to
4.0 mA after the relay reset is activated via Modbus, HART, or remote switch. The HART special mode allows the current to go down to 1.25 mA. The HART will still function.
This mode must be used with GMI’s products that rely on 2 mA output for COPM and 1.5 for offline and zero for fault (TA402A).
NOTE: The maximum analog output load is 600 ohms, including wiring.
3.3.7 Cable Requirements
For interfacing with 250 ohm input impedance devices, the following maximum cable lengths apply (maximum 50-ohm loop):
Cable
AWG
Run Feet
Cable
2
mm
Run
Meters
14 9000 2.50 2750 16
5800
1.50 1770 18 3800 1.00 1160 20 2400 0.75 730 22 1700 0.50 520
Table 5: Maximum Cable Requirements
3.3.8 Power
The supply voltage range is 20 to 36 VDC at the detector (low voltage is detected at approximately 18.5 VDC).
TB1
Position
7 +24 VDC 8 +24 VDC 9 COM
10 COM
Table 6: Power Connections
The following maximum cable lengths apply for a +24 VDC supply (maximum 20 ohm loop):
Cable
AWG
Run
Meters
14 1370 2.5 4500 16 715 1.5 2340 18 470 1.00 1540 20 300 0.75 970 22 205 0.50 670
Connection
Cable
2
mm
Run
Feet
Table 7: Maximum Cable Lengths for +24 VDC Supply
21
Page 30
Models FL3100H/3101H
3.3.9 Modbus Interface
The Modbus interface is used to either query the unit’s status or to configure the unit. See Section 5.0 for detailed information on Modbus RTU Protocol.
TB1
Position
1 DATA + 2 DATA -
Table 8: Connections for the Modbus Interface
NOTE: If Dual Modbus output is ordered, then the 0-20 mA and HART output is not available
and the wiring terminals for the second Modbus channels are as follows:
TB1
Position
5 DATA2 + 6 DATA2 -
Table 9: Connections for the Second Modbus Interface
Connection
Connection
3.3.10 Chassis Ground
This connection is available for use in wiring that requires a connection to chassis ground. It is recommended the chassis be grounded at all times.
TB2
Position
1 CHAS GND
Connection
Table 10: Chassis Ground Connection
3.3.11 Connection to Fire Cards/Panels
For detectors wired together for monitoring via standard fire cards, GM will factory-fit EOL and alarm resistors. If this special option is required, please specify at time of order and provide the following information:
Specify one or two resistors (i.e. alarm only, or alarm resistor and EOL).  Specify value of resistors.
Where detectors are used in conjunction with a GM Model IN042 card, values would be 470­ohm alarm resistor and 5.6K EOL. The EOL resistors are onboard the IN042, selectable by DIP-switches.
NOTE: Contact General Monitors or an authorized representative for further details. European Union (EU) Approved Applications: Interconnecting cables must have an overall
screen or screen and armor. Cables BS5308 Part 2, Type 2, or equivalents are suitable. Note that the terms ‘screen’ and ‘shield’ are equivalent for the purpose of this manual. The cable armor must be terminated in a suitable cable gland at the detector to ensure a positive electrical connection.
22
Page 31
Models FL3100H/3101H
3.3.12 Cable Termination in the Non-Hazardous Area
The cable armor must be connected to safety earth in the safe area. The cable screen (drain wire) must be connected to an instrument earth in the safe
area.
The power supply OV return must be connected to an instrument earth in the safe
area.
The interconnecting cables should be segregated from power and other noisy cables.
Avoid proximity to cables associated with radio transmitters, welders, switch mode power supplies, inverters, battery chargers, ignition systems, generators, switch gear, arc lights and other high frequency or high power switching process equipment. In general, maintain separation of at least 1m between instrument and other cables. Greater separations are required where long parallel cable runs are unavoidable. Avoid running instrument cable trenches close to lightning conductor earthing pits.
Complete all cable insulation testing before connecting the cable at either end.
WARNING: Under no circumstances should equipment be connected or disconnected when
under power. This is contrary to hazardous area regulations and may lead to serious damage to the equipment. Equipment damaged in this manner is not covered under warranty.
23
Page 32
Models FL3100H/3101H
4.0 Operation
4.1 Checklist
Prior to starting the system verify the following:
Inhibit any external devices, such as automatic extinguishing fire suppression systems
or others, which you do not want activated.
Verify that the DIP-switch settings are set for the desired configuration.  Verify that the unit is properly mounted. Ensure the conduit/cable gland entries are
pointed downward.
Verify the field of view for each detector covers the area intended for flame detection.  Verify that the wiring is correct.  Verify that the power supply is connected properly. The detector is powered by +24
VDC (20 to 36 VDC voltage range). The detector will output a low voltage fault at 18.5 VDC or below.
4.2 Start Up
To start up the system, apply power to the flame detectors. Each detector will begin its self-test start up sequence. For the first 10 seconds, the unit will output 0 mA, the fault relay stays de­energized, and the green and red LED will flash alternately. Each is on for about 300 ms. After this 10-second period, the unit will output 4 mA, the fault relay will energize, the red LED will turn off, and the green LED will turn on constant and briefly flash off every 5 seconds. The dual Modbus version does not have a current output.
NOTE: If you ordered unit with three-color LED option, please refer to section 10.2.6 “Three-
color Visual Indicators” for the LED status.
4.3 System Test
To test the system, use the General Monitors Test Lamp Model TL105 (Section 7.3.2).
4.4 User Selectable Options/Factory Defaults
All settings on the Models FL3100H and FL3101H are done via a DIP switch on the Power/Relay Board or via Modbus or HART which will override the dipswitch settings. To set these options, remove the detector head from the base assembly and locate the DIP switch (Figure 21). On the DIP switch, ON/CLOSED means the switch is pushed in on the side labeled ON or CLOSED (opposite the OPEN side). OFF/OPEN means the switch is pushed in on the side with the number corresponding to the switch position or the side labeled OPEN. Refer to Table 11 for the switch assignments. The settings for the WARN and ALARM outputs have been covered in Section 3.3. The time delay specifies the amount of time a WARN condition persists before an ALARM condition will occur. If the HART option is ordered the current you desire must be selected (1.25 mA or 3.5 mA). Factory default is 3.5 mA to 20 mA. HART current is only HART or Modbus selectable, not DIP switch selectable.
24
Page 33
Models FL3100H/3101H
Option Off On
1. 100% Sens – 1 ft2@ 50 ft 1, 2
2. 75% Sens – 1 ft2 @ 35 ft 2 1
3. 50% Sens – 1 ft2 @ 25 ft 1 2
4. 2 Second ALARM Time Delay 3 4
5. 4 Second ALARM Time Delay 3, 4
6. 8 Second ALARM Time Delay 4 3
7. 10 Second ALARM Time Delay 3, 4
8. ALARM non-latching 5
9. ALARM latching 5
10. WARN non-latching 6
11. WARN latching 6
12. ALARM normally energized 7
13. ALARM normally de-energized 7
14. WARN normally energized 8
15. WARN normally de-energized 8
Table 11: DIP Switch Options
Figure 21: DIP switch Location
25
Page 34
Models FL3100H/3101H
5.0 Modbus Interface
Standard FL3100H or FL3101H flame detectors include a single Modbus that is referenced as Comm 1. A dual Modbus feature is optional, which includes two independent communications channels referenced as Comm 1 and Comm 2.
NOTE: If the dual Comm option is ordered, the analog output and HART will not be available.
5.1 Baud Rate
The Baud Rate is a selectable setting via the Modbus communications interface. The selectable baud rates are 19.2K, 9600, 4800, or 2400 bits per second.
5.2 Data Format
The Data Format is a selectable setting via the Modbus communications interface. The selectable data formats are as follows:
Data Bits Parity Stop Bit Format
8 None 1 8-N-1 8 Even 1 8-E-1 8 Odd 1 8-O-1 8 None 2 8-N-2
Table 12: Data Format
5.3 Modbus Read Status Protocol (Query/Response)
5.3.1 Modbus Read Query Message
Byte Modbus Range Referenced to FL3100H / FL3101H
1st Slave
Address
2nd Function
Code
3rd Starting
Address Hi**
4th Starting
Address Lo**
5th No. of
Registers Hi
6th No. of
Registers Lo 7th CRC Lo 00-FF (Hex) CRC Lo Byte 8th CRC Hi 00-FF (Hex) CRC Hi Byte
*: Address 0 is reserved for broadcast mode and will not be supported at this time.
NOTE
1-247 * FL3100H / FL3101H ID (Address)
(X = 0 or 1 Model Type)
03 Read Holding Registers 00 Not Used by FL3100H / FL3101H
00-FF (Hex) FL3100H / FL3101H Commands
00 Not Used by FL3100H / FL3101H 01 No. of 16 Bit Registers
Table 13: Modbus Query Messages
NOTE**: Start Address can be a maximum of 247 Address Locations (0000-0x00F7)
26
Page 35
Models FL3100H/3101H
5.3.2 Modbus Read Response Message
Byte Modbus Range
1st Slave
Address
2nd Function
Code 3rd Byte Count 02 – FF (Hex) No. of Data Bytes 4th Data Hi 00-FF (Hex) FL3100H / FL3101H Hi Byte
5th Data Lo 00-FF (Hex) FL3100H / FL3101H Lo Byte 6th CRC Lo 00-FF (Hex) CRC Lo Byte
7th CRC Hi 00-FF (Hex) CRC Hi Byte
Table 14: Modbus Read Response Messages
NOTE: Address 0 is reserved for broadcast mode and will not be supported at this time.
* (Decimal)
1-247
03 or 04 Read Holding Registers
Referenced to FL3100H,
FL3100H1
FL3100H / FL3101H ID (Address)
Status Data Status Data
5.4 Modbus Write Command Protocol (Query/Response)
5.4.1 Modbus Write Query Message
Byte Modbus Range
1st Slave Address
2nd Function Code 06 Preset Single Register 3rd Register Address
**
Hi
4th Register Address
Lo**
5th Preset Data Hi 00-FF (Hex) FL3100H / FL3101H Hi Byte 6th Preset Data Lo 00-FF (Hex) FL3100H / FL3101H Lo Byte
th
7 8th CRC Hi 00-FF (Hex) CRC Hi Byte
*: Address 0 is reserved for broadcast mode and will not be supported at this time.
NOTE
NOTE**: Start Address can be a maximum of 247 Address Locations (0000-0x00F7).
CRC Lo 00-FF (Hex) CRC Lo Byte
Table 15: Modbus Write Query Message
*
1-247 (Decimal)
00 Not used by FL3100H /
00-FF (Hex) FL3100H / FL3101H Commands
Referenced to FL3100H /
FL3101H
FL3100H / FL3101H ID (Address)
FL3101H
Command Data Command Data
27
Page 36
Models FL3100H/3101H
5.4.2 Modbus Write Response Message
Byte Modbus Range
1st Slave Address 1-247*
(Decimal) 2nd Function Code 06 Preset Single Register 3rd Register Address
Hi**
4th Register Address
Lo**
5th Preset Data Hi 00-FF (Hex) FL3100H / FL3101H Hi Byte 6th Preset Data Lo 00-FF (Hex) FL3100H / FL3101H Lo Byte 7th CRC Lo 00-FF (Hex) CRC Lo Byte
8th CRC Hi 00-FF (Hex) CRC Hi Byte
Table 16: Modbus Write Response Message
NOTE*: Address 0 is reserved for broadcast mode and is not supported at this time. NOTE**: Start Address can be a maximum of 247 Address Locations (0000-0x00F7).
00 Not used by FL3100H / FL3101H
00-FF (Hex) FL3100H / FL3101H Commands
Referenced to FL3100H /
FL3101H
FL3100H / FL3101H ID (Address)
Command Data Command Data
5.4.3 Function Codes Supported
Function Code 03 or 04 (Read Holding Registers) is used to read status from the slave unit. Function Code 06 (Preset Single Register) is used to write a command to the slav e unit.
5.5 Exception Responses and Exception Codes
In a normal exchange, the master device sends a query to the FL3100H / FL3101H. The FL3100H / FL3101H receives the query and returns a normal response to the master. If a normal communications error occurs, there are 4 possible responses from the FL3100H / FL3101H:
1. If the FL3100H / FL3101H does not recognize the query due to a communications error, then no response is returned from the FL3100H / FL3101H and the master device will eventually process a timeout condition for the query.
2. If the FL3100H / FL3101H receives the query, but detects a communication error (CRC, etc.), then no response is returned from the FL3100H / FL3101H and the master device will eventually process a timeout condition for the query.
3. An exception code is returned when the FL3100H / FL3101H receives the query without a communications error, but cannot process it due to reading or writing to a non-existent or illegal Function Code, Illegal Command Starting Address or Register Address, or Illegal Data Value. The exception response message has two fields that differentiate it from a normal response. See the next section for more information.
28
Page 37
Models FL3100H/3101H
5.5.1 Exception Responses
Byte Modbus Range
1st Slave Address 1-247* (Decimal) FL3100H / FL3101H ID (Address) 2nd Function Code 83 or 86 (Hex) MSB is set with Function Code 3rd Exception Code 01 - 06 (Hex) Appropriate Exception Code (See
4th CRC Lo 00-FF (Hex) CRC Lo Byte 5th CRC Hi 00-FF (Hex) CRC Hi Byte
Table 17: Exception responses
5.5.1.1 Exception Code Field
In a normal response, the FL3100H / FL3101H returns data and status in the data field, requested in the query from the master. In an exception response, the FL3100H / FL3101H returns an exception code in the data field, which describes the condition that caused the exception. Below is a list of exception codes that are supported by the FL3100H / FL3101H:
Code Name Description
01 Illegal Function The function code received in the query is not an
allowable action for the FL3100H / FL3101H.
02 Illegal Data Address The data address received in the query is not an
allowable address for the FL3100H / FL3101H.
03 Illegal Data Value A value contained in the query data field is not an
allowable value for the FL3100H / FL3101H.
04 Slave Device Failure An unrecoverable error occurred while the
FL3100H / FL3101H was attempting to perform the requested action.
05 Acknowledge The FL3100H / FL3101H has accepted the request
and is processing it, but a long duration of time will be required. This response is returned to prevent a timeout error from occurring in the master.
06 Device Busy The FL3100H / FL3101H is engaged in processing
a long-duration program command. The master should retransmit the message later when the slave is free.
Referenced to FL3100H /
FL3101H
below)
Table 18: Exception Code Field
29
Page 38
Models FL3100H/3101H
5.6 Command Register Locations
5.6.1 Operational Mode Commands
See section number listed below and reference Section 5.7 for details of each register. NOTE: The FL3100H has Modbus error reporting. The optional dual Modbus has error
reporting for each channel. It can also provide simultaneous block mode.
R - indicates Read Only Access R/W - indicates Read/Write Access
Parameter Function Type Scale Access
Analog 0-20 mA Current Output Value 16-Bit R 0000 40001 Mode Indicates Fire Status Mode Value (0-11) R 0001 40002 Status/Error Indicates Error Bit 16-Bit R 0002 40003 UV/IR Only Indicates Detection of UV
Only or IR Only (FL3100H only)
Model Type Identifies the Model
FL3100H / FL3101H
Software Rev COPM Fault UV/IR COPM Fault Bit 2-Bit R 0006 40007 Override Override Dipswitch Settings Bit 1-Bit R/W 0007 40008 Options Indicates Unit Options Bit 8-Bit R/W 0008 40009 Comm 1 Address
Not Used 000A 40011 Comm 1 Baud Rate Comm 1 Data Format UV Sig Count IR Sig Count UV Fault Total IR Fault Total Remote Reset
Indicates the Software Revision
Unit Address Decimal
Baud Rate (2400, 4800, 9600,19.2K) Data Format (8N-1, 8E-1, 8O-1, 8N-2) Indicates No. of UV Signal Pulses within 500 ms Indicates No. of IR Signal Pulses within 500 ms Indicates Total No. of UV COPM Faults Indicates Total No. of IR COPM Faults Remotely Resets the Alarm and Warn Relays
Bit 2-Bit R 0003 40004
Decimal 310X R 0004 40005
ASCII 2-Char R 0005 40006
(1-247)
Hex
Value (0-3) R/W 000B 40012 Value (0 - 3) R/W 000C 4001 3 Value 16-Bit R 000D 40014 Value 16-Bit R 000E 40015 Value 16-Bit R 000F 40016 Value 16-Bit R 0010 40017 Bit 1-Bit R/W 0011 40018
(01­F7)
R/W 0009 40010
REG
Addr
Master
I/O
Addr
Refer to
Section
30
Page 39
Models FL3100H/3101H
Parameter Function Type Scale Access
Remote Alarm Test Clear COPM Faults NOT Used 0014 40021 Serial Number Serial Number NOT Used 0017-
Optional HART All “1” or “0” HART Test 0 off 1, 2 Bit 2 Bit R/W 001E 40031 Not Used 001F 40032 Comm 1 Register errors Comm 1 Bus Activity Rate % Comm 1 Function Code Errors Comm 1 Starting Address Errors Comm 1 Total Receive Errors Comm 1 RXD CRC Errors Comm 1 RXD CRC Errors Comm 1 Overrun Errors
Remotely Activates Alarm Test Clears UV/IR COPM Fault Counters
Serial Number Upper Value 16 bit R 0015 40022 Serial Number Lower Value 16 bit R 0016 40023
HART Enable Bit 1 bit R/W 001D 40030
Total # of Register Errors
Bus Activity Rate in % Of this Addressed Node vs. Other Addressed Nodes Total # of Function Code Errors
Total # of Starting Addresses Errors
Total # of Comm 1 Receive Errors
Total # of RXD CRC Errors
Total # of RXD CRC Errors
Total # of Overrun Errors
Bit 1-Bit R/W 0012 40019 Bit 1-Bit R/W 0013 40020
Value 16-Bit R 0020 40033
Decimal Hex
Value 16-Bit R 0022 40035
Value 16-Bit R 0023 40036
Value 16-Bit R 0024 40037
Value 16-Bit R 0025 40038
Value 16-Bit R 0026 40039
Value 16-Bit R 0027 40040
(0­100%) (0-64)
R 0021 40034
REG Addr
1C
Master
I/O
Addr
40024- 40029
Refer to
Section
31
Page 40
Models FL3100H/3101H
Parameter Function Type Scale Access
Comm 1 Parity Errors
Comm 1 Framing Errors
Comm 1 UART errors Comm 1 Total Receive Errors Comm 1 Clear UART Comm1 Clear Stats HART Current Range Comm 2 Address
Total # of Parity Errors Value 16-Bit R 0028 40041
Total # of Framing Errors
Total # of UART errors Value 16 Bit 002A 40043 Total # of Comm 1
Receive Errors
Clear UART errors Bit 1-Bit R/W 002C 40045 Clear Comm Stats Bit 1-Bit R/W 002D 40046
3.5 ma to 20 ma
1.25 ma to 20 ma Unit Address Decimal
Value 16-Bit R 0029 40042
Value 16-Bit R 002B 40044
Bit 1-Bit R/W 002E 40047
Hex
(1-247) (01-F7)
R/W 002F 40048
REG Addr
Master
I/O
Addr
Refer to
Section
Comm 2 Baud Rate
Comm 2 Data Format Not Used 0032 40051 Input Voltage Voltage at the alarm input Voltage at the Reset input The position of the dip switch Not used 0037
Indicates present Baud Rate (2400, 4800, 9600, 19.2K)
Indicates present Data Format (8N-1, 8E-1, 8O-1, 8N-2)
Indicates the 24 volts Value 16-Bit R 0033 40052 Indicates alarm test input
voltage Indicates reset input voltage Value 16-Bit R 0035 40054
Dip Switch Data Bits 16-Bit R 0036 40055
Value (0-3) R/W 0030 40049
Value (0-3) R/W 0031 40050
Value 16-Bit R 0034 40053
40056
003F
40064
32
Page 41
Models FL3100H/3101H
Parameter Function Type Scale Access
EVENT LOGGING USER INFO Comm 2 Register errors Comm 2 Bus Activity Rate % Comm 2 Function Code Errors Comm 2 Starting Address Errors Comm 2 Total Receive Errors Comm 2 RXD CRC Errors Comm 2 RXD CRC Errors Comm 2 Overrun Errors Comm 2 Parity Errors Comm 2 Framing Errors Comm 2 UART errors Not Used 0083 40132 Comm 2 Clear UART Comm2 Clear Stats
Event logging See Section 6.0 User Information Value 16-Bit R/W 0068
Total # of Register Errors
Bus Activity Rate in % Of this Addressed Node vs. Other Addressed Nodes Total # of Function Code Errors
Total # of Starting Addresses Errors
Total # of Comm 2 Receive Errors
Total # of RXD CRC Errors
Total # of RXD CRC Errors
Total # of Overrun Errors
Total # of Parity Errors Value 16-Bit R 0080 40129
Total # of Framing Errors
Total # of UART errors Value 16-Bit R 0082 40131
Clear UART errors Bit 1-Bit R/W 0084 40133 Clear Comm Stats Bit 1-Bit R/W 0085 40134
Value 0040
Value 16-Bit R 0078 40121
Decimal Hex
Value 16-Bit R 007A 40123
Value 16-Bit R 007B 40124
Value 16-Bit R 007C 40125
Value 16-Bit R 007D 40126
Value 16-Bit R 007E 40127
Value 16-Bit R 007F 40128
Value 16-Bit R 0081 40130
16-Bit R 0079 40122
REG Addr
0067 0077
Master
I/O
Addr
40065 40104 40105 40120
Refer to
Section
Table 19: Operational Mode Commands
33
Page 42
Models FL3100H/3101H
5.7 FL3100H / FL3101H Operational Mode Command Register Details
5.7.1 Analog (00H)
A read returns a value which is proportional to the 0-20 mA output current. The current is based on a 16-bit value. The master scaling is 0-65535 decimal, which corresponds to the FL3100H / FL3101H scaling which is 0-20 mA.
5.7.2 Mode (01H)
A read returns the fire status mode of the FL3100H / FL3101H.
Mode Decimal Value
Power-up Delay 1 Warn Non-latching Only 2 Warn and Alarm Non-Latching 3 Warn Latching Only 4 Alarm Latching Only 5 Warn and Alarm Latching 6 Ready State (No Fire) 7 UV Only Fire (FL3100H Model Only) 8 IR Only Fire (FL3100H Model Only) 9 Alarm Test 10 COPM Fault Detected 11
Table 20: Fire Status Mode
5.7.3 Status/Error (02H)
A read returns the errors that are occurring, which are indicated by bit position.
Byte Function Bit Position Hex
Reset Line Shorted 8 0x8000 UV 10 Minute 7 0x4000 Not Used 6 0x2000
High
Low
Not Used 5 0x1000 Output Current Fault 4 0x0800 Not Used 3 0x0400 Not Used 2 0x0200 Not Used 1 0x0100
Flash Checksum 8 0x0080 EEPROM Checksum 7 0x0040 RAM Test 6 0x0020 Low Line Voltage Check 5 0x0010 UV COPM 4 0x0008 IR COPM 3 0x0004 Not Used 2 0x0002 Internal Voltage 1 0x0001
Table 21: Status/Error
34
Page 43
Models FL3100H/3101H
5.7.4 Faults
Reset Line Shorted: The FL3100H sees a continuous short. Check TB1-3.
UV 10 Minute: The UV detector sees a constant source of UV. Check for welding, arcing, very
bright lights or other sources of UV.
Output Current Fault: There is an error in the current output circuit. Return for service.
Flash Checksum: The main program memory is not functioning properly. Return for service.
EEPROM Checksum: There are two sources of EEPROM error. One is recoverable, the
other must be sent back to the factory. The recoverable error can be reset by turning the power on and off. The user then must check all the FL3100H options; Latch/Non-latch, Energized/De-energized, Baud rate etc.
RAM Test: The memory is not functioning. Return for service.
Low Line Voltage Check: The input voltage is low. Check the input voltage with a meter or
via HART or Modbus.
UV COPM: The UV window needs to be cleaned.
IR COPM: The IR window needs to be cleaned.
Internal Voltage: The FL3100H monitors various internal voltages. Return for service.
5.7.5 UV/IR Only (03H)
A read indicates the detection of UV Only or IR only when using the UV/IR Model FL3100H. UV Only Detected = 01 (Lo Data Byte) IR Only Detected = 02 (Lo Data Byte) The High Data Byte is Not Used.
5.7.6 Model Type (04H)
A read returns the Decimal Value 3100 or 3101, which identifies each particular type of unit by model number.
Model Configuration HART ID Modbus ID
FL3100 Standard UV/IR NA 3100 0x0C1C FL3100H Standard UV/IR 0x90 3103 0x0C1F FL3100H Long Range 0x90 3106 0x0C22 FL3100H Hydrogen 0x90 3105 0x0C21 FL3101 Standard UV NA 3101 0x0C1D FL3101H UV only 0x90 3104 0x0C20
Table 22: Model Type
35
Page 44
Models FL3100H/3101H
5.7.7 Software Revision (05H)
A read returns the software revision of the FL3100H / FL3101H in 2 ASCII characters. (REV “A” appears as a blank and the letter A).
5.7.8 COPM Fault (06H)
A read returns the type of Continuous Optical Path Monitoring (COPM) Fault which is an UV COPM Fault or an IR COPM Fault, or both. The UV COPM and/or the IR COPM Faults indicate that the UV and/or IR windows are dirty and need to be cleaned, or that there is a hardware problem with the UV and/or IR detection circuitry.
UV COPM Fault = 01 (Lo Data Byte) IR COPM Fault = 02 (Lo Data Byte) The High Data Byte is Not Used.
5.7.9 EEPROM Override (07H)
A read indicates the status of the EEPROM Override bit. A write command changes the state of the EEPROM Override bit. When the EEPROM Override bit is enabled, the options for the Detector Sensitivity, Relay Delay, Relay Latching/Non-Latching and Relay Energized/Non­Energized features are now controlled by the data stored in the EEPROM and are no longer controlled by the 8-position DIP switch located on the bottom of the Power/Relay Board. When the EEPROM Override bit is disabled the options are under the control of the 8-position DIP switch. The EEPROM Override bit is located in the LSB of the Low Data Byte and the High Data Byte is not used.
Function Bit (LSB) Access
Enable 1 Read/Write
Disable 0 Read/Write
Table 23: EEPROM Override
NOTE: By grounding the ALARM TEST input during power-up cycle (approximately 10
seconds), the FL3100H / FL3101H will disable the EEPROM Override and set the Bit = 0, thus enabling the 8-position DIP switch.
5.7.10 Options (08H)
A read returns the status of the settings for the Detector Sensitivity, Relay Delay, Relay Latching/Non-Latching and Relay Energized/Non-Energized features either from the Options Dipswitch or the EEPROM depending on the setting of the EEPROM Override bit listed above. A write command changes the settings for the EEPROM only when the EEPROM Override bit is set.
EXCEPTION - If an attempt to change the EEPROM Options is made while the EEPROM Override bit is not set, then the unit shall return an Exception Code 01 (Illegal Function).
36
Page 45
Models FL3100H/3101H
These functions are indicated on the Low Data Byte and the High Data Byte is not used.
Function Bit
Position
Warn Energized 8 (MSB) Alarm Energized 7 Warn Latched 6 Alarm Latched 5
10 8 4 2 Time Delay in Seconds
Alarm Time Delay 2 4 1 0 0 1 Read/Write Alarm Time Delay 1 3 1 1 0 0 Read/Write
100 75 50 % Sensitivity
Sensitivity 2 2 0 0 1 Read/Write Sensitivity 1 1 (LSB) 0 1 0 Read/Write
1 = Energized 0= Non-Energized 1 = Energized 0= Non-Energized 1 = Latched 0 = Non-Latched 1 = Latched 0 = Non-Latched
Table 24: Setting Options
Conditions Access
Read/Write Read/Write Read/Write Read/Write
5.7.11 Comm 1 Address (09H)
A read returns the Comm 1 address of the FL3100H / FL3101H. A write changes the address to the requested address. The range of the address is 1 to 247 (01 to F7 Hex). After the address has been changed to the slave unit, the Modbus communications will cease because the address has changed; therefore the master will have to change its query address to the slave’s new address in order to restart the communications.
EXCEPTION - If an illegal data value is entered (must be between 1, 0x00F7), then the Exception Code 03 (Illegal Data Value) is returned.
NOTE: By grounding the RESET input during power-up cycle (approximately 10 seconds), the
FL3100H / FL3101H Address will default to 1.
5.7.12 Comm 1 Baud Rate (0BH)
A read returns the Comm 1 baud rate of the FL3100H / FL3101H. A write changes the baud rate to the requested baud rate. After the baud rate has been changed to the addressed unit, the Modbus communications will cease because the baud rate has changed; therefore the master will have to change its baud rate to the slave’s new baud rate in order to restart the communications.
Baud Rate Low Data Byte Access
19.2K 03 Read/Write 9600 02 Read/Write 4800 01 Read/Write 2400 00 Read/Write
Table 25: Comm 1 Baud Rate
This function is indicated on the Low Data Byte (the High Data Byte is not used). EXCEPTION - If an illegal data value is entered which is not listed above, then the Exception
Code 03 (Illegal Data Value) is returned. NOTE: By grounding the RESET input during power-up cycle (approximately 10 seconds), the
FL3100H, and FL3101H Baud Rate will default to 19.2K.
37
Page 46
Models FL3100H/3101H
5.7.13 Comm 1 Data Format (0CH)
A read returns the Comm 1 data format of the FL3100H / FL3101H. A write changes the data format to the requested data format. After the data format has been changed to the addressed unit, the Modbus communications may cease or start producing Comm errors because the data format has changed; therefore the master will have to change its data format to the slave’s new data format in order to restart or provide proper communications.
Data Parity Stop Format
8 None 1 8-N-1 00 Read/Write 8 Even 1 8-E-1 01 Read/Write
8 Odd 1 8-O-1 02 Read/Write 8 None 2 8-N-2 03 Read/Write
Table 26: Comm 1 Data Format
This function is indicated on the Low Data Byte and the High Data Byte is not used. EXCEPTION - If an illegal data value is entered which is not listed above, then the Exception
Code 03 (Illegal Data Value) is returned. NOTE: By grounding the RESET input during power-up cycle (approximately 10 seconds), the
FL3100H, and FL3101H Data Format will default to 8-N-1.
Low Data
Byte
Access
5.7.14 UV Signal Count (0DH)
A read indicates the number of UV Signal Counts that have occurred within 500 ms, which is the time duration that is required to detect a fire in the UV spectrum.
5.7.15 IR Signal Count (0EH)
A read indicates the number of IR Signal Counts that have occurred within 500 ms which is the time duration that is required to detect a fire in the IR spectrum.
5.7.16 UV Fault Total (0FH)
A read indicates the total number of UV COPM Faults for an indefinite period of time until the Clear COPM Fault command is activated. The maximum count is 65535 and then the counter will rollover to zero and begin counting again.
5.7.17 IR Fault Total (10H)
A read indicates total number of IR COPM Faults for an indefinite period of time until the Clear COPM Fault command is activated. The maximum count is 65535 and then the counter rolls back to zero and begins counting again.
5.7.18 Remote Reset (11H)
Writing a 1 to the bit activates the Remote Reset function that resets the Alarm and Warn Relays. The function is active momentarily and resets automatically after being used.
Function Bit (LSB) Access
Enable 1 Read/Write
Disable 0 Read/Write
Table 27: Remote Reset
EXCEPTION - If an illegal data value is entered which is not listed above, then the Exception
Code 03 (Illegal Data Value) is returned.
38
Page 47
Models FL3100H/3101H
5.7.19 Remote Alarm Test (12H)
Writing a 1 to the bit activates the Remote Alarm Test function, which activates the Warn and Alarm relay and causes the Analog current to show warn then alarm. Once the Alarm Test is complete, the Remote Alarm Test function should be disabled by writing a zero to the Remote Alarm Test and then resetting the Alarm and Warn relays by writing a one to the Remote Reset (referenced above).
Function Bit (LSB) Access
Enable 1 Read/Write
Disable 0 Read/Write
Table 28: Remote Alarm Test
EXCEPTION - If an illegal data value is entered which is not listed above, then the Exception
Code 03 (Illegal Data Value) is returned.
5.7.20 Clear COPM Faults (13H)
Writing a 1 to the bit activates the Clear COPM Faults function that resets both the UV and IR COPM faults. The function is active momentarily and resets automatically after being used.
Function Bit (LSB) Access
Enable 1 Read/Write
Disable 0 Read/Write
Table 29: Clear COPM Faults Function
EXCEPTION - If an illegal data value is entered which is not listed above, then the Exception
Code 03 (Illegal Data Value) is returned.
5.7.21 Serial Number (15/16H)
The serial number is a 32-bit word but the value is only 23 bits long. The upper bits are always zero. This is done to keep the same serial number as the HART serial number. Address 0x16 contains the lower part of the number and address 0X15 contains the upper part.
5.7.22 HART Enable (1D)
This command enables or disables HART. A “0” is HART disabled. A “1” is HART Enabled. This is an option that must be ordered. If HART is not installed, an exception will be returned.
5.7.23 HART Test (1E)
This command is used to test the HART output. It produces constant zeros or constant ones on the HART output. This is only available if the HART option was purchased.
Code Results
0 Normal 1 Constant ones 2 Constant zeros
39
Page 48
Models FL3100H/3101H
5.7.24 Not Used (1F)
5.7.25 Comm 1 Total Illegal number of registers Errors (20H)
A read indicates the total illegal number of registers errors on the Modbus. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.26 Comm 1 Bus Activity Rate % (21H)
A read indicates the Comm 1 Bus Activity Rate in percent of this Slave's addressed node versus other addressed nodes. Range of this value is in hex (0-64), which translates to decimal (0-100%).
5.7.27 Comm 1 Function Code Errors (22H)
A read indicates the number of Comm Function Code Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.28 Comm 1 Starting Address Errors (23H)
A read indicates the number of Comm 1 Starting Address Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.29 Comm 1 Total Receive Errors (24H)
A read indicates the total Modbus Comm 1 Only Receive Errors that occurred in the slave device. These are address, function, etc. type of errors. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.30 RXD CRC Errors Hi (25h)
A read indicates the number of RXD CRC Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.31 RXD CRC Errors Lo (Same as Hi) (26h)
NOTE: Since the FL3100H has a 16 bit CRC, the Hi and Lo CRC errors are now reported in
the same 16 bit word. A read from either the old high Hi or Lo CRC address will return the same count.
5.7.32 Comm 1 Overrun Errors (27H)
A read indicates the number of Comm 1 Overrun Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
NOTE: An overrun error occurs when the next received byte of data tries to overwrite an
existing received data byte, which has not been processed. Therefore, the next received byte of data is lost. This can be controlled by implementing the proper DCS or PLC Error Handling Timing Setting (ex. Reply Timeout Setting, Delay Time, and Number of Retries) and proper Baud Rate Setting.
5.7.33 Comm 1 Parity Errors (28H)
A read indicates the number of Comm 1 Only Parity Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
40
Page 49
Models FL3100H/3101H
5.7.34 Comm 1 Framing Errors (29H)
A read indicates the number of Comm 1 Framing Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.35 Comm 1 Total UART Receive Errors (2AH)
A read indicates the total Modbus Comm 1 Receive Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again. The total errors are an accumulation of the individual Comm errors such as Overrun, CRC, Parity and Framing errors.
5.7.36 Comm 1 Total Receive Errors (2BH)
A read indicates the total Modbus Comm 1 Only Receive Errors that occurred in the slave device. These are address, function, etc type of errors. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.37 Clear Comm 1 UART Errors (2CH)
Writing a 0 to the bit activates the Clear Comm 1 Errors function, which resets all of the Modbus UART Comm Error counters to zero. The function is active momentarily and will reset automatically after being used.
5.7.38 Clear Comm 1 Modbus Errors (2DH)
Writing a 0 to the bit activates the Clear Comm 1 Errors function, which resets all of the Modbus Comm Error counters to zero. The function is active momentarily and resets automatically after being used.
5.7.39 HART Current (2E)
Normally in HART mode the low current does not go below 3.5 mA. In order for the current to distinguish between COPM Fault and Fault there is a HART setting that allows the current to go as low as 1.25 mA. A read returns “1” or “0”.
Condition Normal HART Current HART Expanded Scale Units
Run
COPM Fault
Fault
4 ,8, 12,16, 20 4 ,8, 12,16, 20 mA
3.5 2.0 mA
3.5 1.25 mA
5.7.40 Comm 2 Address (2FH)
A read returns the Comm 2 address of the FL3100H / FL3101H. A write changes the address to the requested address. The range of the address is 1 to 247 (01 to F7 Hex). After the address has been changed to the slave unit, the Modbus communications will cease because the address has changed. Therefore, the master will have to change its query address to the slave’s new address in order to restart communications.
EXCEPTION - If an illegal data value is entered which is not listed above, then the Exception Code 03 (Illegal Data Value) is returned.
NOTE: By grounding the RESET input during power-up cycle (approximately 10 seconds), the
FL3100H / FL3101H Address defaults to 2.
41
Page 50
Models FL3100H/3101H
5.7.41 Comm 2 Baud Rate (30H)
A read returns the Comm 2 baud rate of the FL3100H / FL3101H. A write changes the baud rate to the requested baud rate. After the baud rate has been changed to the addressed unit, the Modbus communications ceases because the baud rate has changed. Therefore, the master will have to change its baud rate to the slave’s new baud rate in order to restart communications.
Baud
Rate
19.2K 03 Read/Write 9600 02 Read/Write 4800 01 Read/Write 2400 00 Read/Write
Table 30: Comm 2 Baud Rate
This function is indicated on the Low Data Byte (the High Data Byte is not used). EXCEPTION - If an illegal data value is entered which is not listed above, then the Exception
Code 03 (Illegal Data Value) is returned. NOTE: By grounding the RESET input during power-up cycle (approximately 10 seconds), the
FL3100H / FL3101H Baud Rate will default to 19.2K.
Low Data
Byte
Access
5.7.42 Comm 2 Data Format (31H)
A read returns the Comm 2 data format of the FL3100H / FL3101H. A write changes the data format to the requested data format. After the data format has been changed to the addressed unit, the Modbus communications may cease or start producing Comm errors because the data format has changed. Therefore, the master will have to change its data format to the slave’s new data format in order to restart or provide proper communications.
Data Parity Stop Format
8 None 1 8-N-1 00 Read/Write 8 Even 1 8-E-1 01 Read/Write 8 Odd 1 8-O-1 02 Read/Write 8 None 2 8-N-2 03 Read/Write
Low Data
Byte
Access
Table 31: Comm 2 Data Format
This function is indicated on the Low Data Byte (the High Data Byte is not used). EXCEPTION - If an illegal data value is entered which is not listed above, then the Exception
Code 03 (Illegal Data Value) is returned. NOTE: By grounding the RESET input during power-up cycle (approximately 10 seconds), the
FL3100H / FL3101H Data Format will default to 8-N-1.
5.7.43 Not Used (32H)
5.7.44 Input Voltage (33H)
A read returns the input voltage. This allows the user to remotely read the actual input voltage via Modbus. If the measured voltage is below the required 20 volts measures should be taken or low line faults may occur.
42
Page 51
Models FL3100H/3101H
5.7.45 Alarm Test Voltage (34H)
This is useful if the Alarm test button is located a long distance from the FL3100H or the ground is not a good ground. A read returns the Alarm input voltage. If the voltage is below 3.5 volts, the Alarm test is activated.
5.7.46 Reset Relays Voltage (35H)
This is useful if the Reset test button is located a long distance from the FL3100H or the ground is not a good ground. A read returns the Reset input voltage. If the voltage is below 3.5 volts, the Reset is activated.
5.7.47 Dip Switch Settings (36H)
A read returns a digital copy of the dip switch. This is useful to check the FL3100H configuration.
5.7.48 Not Used (37 – 3FH)
5.7.49 See Event Logging - Section 6.0 (40H – 67H)
5.7.50 User Information (68h to 77h)
There is a section in memory that allows the user to store information. This is useful if the physical location or other user identification is required. The only restriction on the information is it must be Modbus compatible. Only one word can be written per command. There are a total of 16 words for the user.
NOTE: The following information only applies if the dual Modbus configuration was purchased.
5.7.51 Comm 2 Total Illegal Number of Registers Errors (78H)
A read indicates the total illegal number of registers errors on the Modbus. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.52 Comm 2 Bus Activity Rate % (79H)
A read indicates the Comm 2 Bus Activity Rate in percent of this slave's addressed node versus other addressed nodes. Range of this value is in hex (0-64), which translates to decimal (0-100%).
5.7.53 Comm 2 Function Code Errors (7AH)
A read indicates the number of Comm 2 Function Code Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.54 Comm 2 Starting Address Errors (7BH)
A read indicates the number of Comm 2 Starting Address Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.55 Comm 2 Total Receive Errors (7CH)
A read indicates the total Modbus Comm 2 Only Receive Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
43
Page 52
Models FL3100H/3101H
5.7.56 RXD CRC Errors Hi (7DH)
A read indicates the number of RXD CRC Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.57 RXD CRC Errors Lo (Same as Hi) (7EH)
NOTE: Hi and Lo CRC errors are reported in the same word. A read from either Hi or Lo will
return the same count.
5.7.58 Comm 2 Overrun Errors (7FH)
A read indicates the number of Comm 2 Only Overrun Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
NOTE: An overrun error occurs when the next received byte of data tries to overwrite an
existing received data byte, which has not been processed. Therefore, the next received byte of data is lost. This can be controlled by implementing the proper DCS or PLC Error Handling Timing Setting (ex. Reply Timeout Setting, Delay Time, and Number of Retries) and proper Baud Rate Setting.
5.7.59 Comm 2 Parity Errors (80H)
A read indicates the number of Comm 2 Parity Flag Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.60 Comm 2 Framing Errors (81H)
A read indicates the number of Comm 2 Framing Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.61 Comm 2 Total UART Receive Errors (82H)
A read indicates the total Modbus Comm 2 UART Receive Errors that occurred in the slave device. The maximum count is 65535 and then the counter rolls over to zero and begins counting again.
5.7.62 Not Used (83H)
5.7.63 Clear Comm 2 UART Errors (84H)
Writing a 0 to the bit activates the Clear Comm 2 UART Errors function, which resets all of the Modbus UART Error counters to zero. The function is active momentarily and will reset automatically after being used.
5.7.64 Clear Comm 2 Modbus Errors (85H)
Writing a 0 to the bit activates the Clear Comm 2 Modbus Errors function, which resets all of the Modbus Error counters to zero. The function is active momentarily and will reset automatically after being used.
44
Page 53
Models FL3100H/3101H
6.0 Event Logging
6.1.1 Faults
Whenever the fault word changes, the time will be recorded. The time of the fault will be saved. The quantity of faults will be saved in a counter. When the fault is removed, it is not saved and the counter is not incremented. A fault event is logged for every 30 seconds recorded. There are a total of 10 event time stamps stored.
6.1.2 Warning
At the time the fire level reaches the Warning level, the time is recorded. Each time this happens a counter is incremented and saved. The end of the event is after the fire has gone away and the latching state has been reset. There are a total of 10 event time stamps stored.
6.1.3 Alarm
At the time the fire level reaches the Alarm level, the time is recorded. Each time this happens a counter is incremented and saved. The end of the event is after the fire has gone away and the latching state has been reset. There are a total of 10 event time stamps stored.
6.1.4 Maintenance
At the time an alarm test occurs, the time is saved in the maintenance event log. Each successful test increments and saves the maintenance counters. There are a total of 10 event time stamps stored.
6.1.5 Setting Clock
Please see the table below.
Address
(hex)
40 Seconds Time Hi Seconds Time Hi Numeric value 0 – 65535 41 Seconds Time
42 Real Time Clock
43 Real Time Clock
44 Real Time Clock
Minute, Second
46 Event Index Event index of
Parameter Function Data Type Data range Access
Seconds Time Numeric value 0 – 65535
Low
Year, Month
Day, Hour
Read/Set year and
month of RTC
Read/Set day and
hour of RTC
Read/Set minutes
and seconds of
RTC
Logged Event
2 Numeric
Values
2 Numeric
Values
2 Numeric
Values
Numeric value 0 - 9
0-99 year,
1 – 12 month
1 – 31 day, 0 – 23 hour
0 – 59 minute, 0 – 59 second
Timer Sec Timer Sec
Timer Struct
Timer Struct
Index
47 Warn
Seconds Time Hi
45
Seconds Time Hi
for warning event
log entries
Numeric value 0 – 65535
Warn
Page 54
Models FL3100H/3101H
Address
(hex)
48 Seconds Time
49 Structure time Hi Hi byte – year, low
4A Structure time
4B Structure time
4C Reserved Reserved Numeric value 0 4D Reserved Reserved Numeric value 0 4E Warn Event
Parameter Function Data Type Data range Access
Low
Mid
Low
Count
Seconds Time Low
for warning event
log entries
byte – month for
warning event log
entries
Hi byte – day, low
byte – hour warning
event log entries
Hi byte – min, low
byte – sec for
warning event log
entries
Warning Event
Count
Numeric value 0 – 65535
Numeric value 0 – 65535
Numeric value 0 – 65535
Numeric value 0 – 65535
Numeric value 0 – 65535
Warn
Warn
Warn
Warn
Warn
4F Alarm Seconds
Time Hi
50 Seconds Time
Low
51
52 Structure time
54 Reserved Reserved Numeric value 0 55 Reserved Reserved Numeric value 0 56 Alarm Event
57 Fault
Structure time Hi Hi byte – year, low
Seconds time Hi
Mid
Count
Seconds Time Hi
for alarm event log
entries
Seconds Time Low
for alarm event log
entries
byte – month for
alarm event log
entries
Hi byte – day, low
byte – hour alarm
event log entries
Alarm Event Count Numeric value 0 – 65535
Seconds Time Hi for fault event log
entries
Numeric value 0 – 65535
Numeric value 0 – 65535
Numeric value
Numeric value 0 – 65535
Numeric value 0 – 65535
0 – 65535
Alarm
Alarm
Alarm
Alarm
Alarm
Fault
58 Seconds time
Low
46
Seconds Time Low
for fault event log
entries
Numeric value 0 – 65535
Fault
Page 55
Models FL3100H/3101H
Address
(hex)
59 Structure time Hi Hi byte – year, low
5A Structure time
5B Structure time
5C Fault code Fault code. Same
5D Reserved Reserved Numeric value 0 5E Fault Event Count Fault Event Count Numeric value 0 – 65535
5F
Parameter Function Data Type Data range Access
Numeric value 0 – 65535
byte – month for
fault event log
entries
Mid
Low
Maintenance
Seconds time Hi
Hi byte – day, low
byte – hour alarm
event log entries
Hi byte – min, low
byte – sec for fault
event log entries
code as register 2
Seconds Time Hi
for event log entries
Numeric value 0 – 65535
Numeric value 0 – 65535
Numeric value 0 – 65535
Numeric value 0 – 65535
Fault
Fault
Fault
Fault
Fault
Maintenance
60 Seconds time
Low
61 Structure time Hi Hi byte – year, low
62 Structure time
64 Maintenance
65 Reserved Reserved Numeric value 0 66 Maintenance
67 Reset Event
Mid
code
Count
Counters
Seconds Time Low
for event log entries
byte – month for event log entries
Hi byte – day, low
byte – hour event
log entries
Cal check Numeric value 0
Maintenance Count Numeric value 0 – 65535
Reset Event
Counters
Table 32: Event Logging Registry Table
Numeric value 0 – 65535
Numeric value 0 – 65535
Numeric value 0 – 65535
Numeric value 1
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Reset
47
Page 56
Models FL3100H/3101H
7.0 Maintenance
7.1 General Maintenance
Once correctly installed, the unit requires very little maintenance other than regular sensitivity checks and cleaning of the lenses. General Monitors recommends that a schedule be established and followed.
WARNING: Disconnect or inhibit external devices, such as automatic extinguishing or fire
suppression systems before performing any maintenance.
NOTE: The removal of particulate matter and any film buildup on the windows and light rods is
necessary to ensure proper sensitivity of the system. It is recommended that the window and light rods be cleaned at least every 30 days or more often if the detector is located in a particularly dirty environment.
During routine maintenance of the equipment, if the base plate is removed, the flame path should be replenished with grease compound.
European Union (EU) Approved Applications: The following grease compound is recommended for use: High Vacuum Grease (or equivalent), as a jointing compound on flameproof electrical enclosures. This is available from General Monitors Ireland.
The viton o-ring gasket should also be lubricated with Castrol EP (P/N 916-062) or High Vacuum (916-078) grease available from General Monitors should it become dry.
The removal of dust and film build-up on the windows is necessary to ensure proper sensitivity of the system. Windows may be cleaned periodically, to avoid a COPM fault being triggered by build-up, dirt or debris.
7.2 Cleaning the Lenses/Light Rods
NOTE: DO NOT USE A COMMERCIAL GLASS CLEANER OTHER THAN "INDUSTRIAL
A clean, soft, lint-free cloth, tissue or cotton swab should be used to apply the cleaning solution. Do not touch the lenses or light rods with fingers.
NOTE: The removal of particulate matter and any film buildup on the lenses and light rods is
STRENGTH WINDEX® with Ammonia D”. The lenses are not glass. The UV lens material is quartz and the IR lens material is sapphire. The cleaning solution should be General Monitors’ P/N 10272-1 ("Industrial Strength Windex
1. Wet the window with the cleaning solution.
2. Rub with a dry, unsoiled cloth until the window is clean.
3. Let the window dry completely.
4. Repeat steps 1, 2 and 3 for the light rods (Figure 22). Take care only to clean the non­coated (non - aluminum) areas of the light rods.
necessary to ensure proper sensitivity of the system. It is recommended that the window and light rods be cleaned at least every 30 days or more often if the detector is located in a particularly dirty environment.
®
with Ammonia D").
48
Page 57
Models FL3100H/3101H
IR SAPPHIRE WINDOW
LIGHT RODS
UV QUARTZ WINDOW
Figure 22: UV and IR Windows
7.3 Sensitivity Check
To verify that each detector is functioning correctly, the General Monitors TL105 Test Lamp and/or the ALARM TEST function should be used.
7.3.1 Alarm Test
The Models FL3100H and FL3101H flame detectors have a built-in Alarm Test feature. By connecting one contact of a SPST momentary switch to TB1 position 4 and the other contact to DC COM TB1, position 9 or 10 (Section 3.3.1), the user can test the alarm outputs of the flame detector by activating this switch for two to ten seconds depending on the Alarm Time Delay Setting.
If the flame detector detects these sources, it will immediately go into WARN and then into the time delayed ALARM. After two to ten seconds the flame detector will reset the non-latching WARN and/or ALARM. A latching WARN and/or ALARM will remain latched until manually reset. If the flame detector does not respond to the sources, it will output a FAULT condition and will retest every ten seconds, as in the COPM FAULT case.
49
Page 58
Models FL3100H/3101H
7.3.2 TL105 Test Lamp
The General Monitors TL105 Test Lamp is a battery operated, rechargeable test source specifically designed to test General Monitors’ UV and UV/IR flame detectors.
It consists of a high-energy broadband radiation source, which emits sufficient energy in both the Ultraviolet and Infrared spectra to activate UV and/or IR detectors. To simulate a fire, the test lamp automatically flashes at the proper rate for different models. See TL105 instruction manual.
The Model TL105, rated explosion-proof, is CSA certified for use in Class I, Groups C and D areas.
The test lamp operates on internal batteries which, when fully charged, will operate continuously for 30 minutes. An internal circuit will prevent operation when the batteries are low.
7.3.3 TL105 Operating Instructions
It is always important to start a series of TL105 checks with a fully charged unit. Stand within 20 feet (FL3100H), 40 feet (FL3100H-Hydrogen), or within 35 feet (FL3101H) of the unit to be tested and aim the TL105 squarely into the detector face. Shaking the lamp from side to side or up and down will increase the simulation of flame flicker, and improve the response of the flame detector to the lamp.
If the system is operating normally, the detector will go into a WARN condition after a few flashes of the test lamp. If the lamp remains ON for the time-delayed period of the DIP switch setting, the detector will go into ALARM.
To conserve charge, do not operate the test lamp longer than is necessary to test each detector. When the battery level drops below the level required to maintain the proper intensity of the lamp, an internal low voltage circuit will shut the lamp off until the batteries have been recharged.
7.3.4 TL105 Recharging Instructions
Insert the charging plug into the receptacle. Complete recharging takes less than 2 hours. A schedule of testing should be established and followed.
WARNING: Replace the knurled plug after charging is complete. Charging must be carried
out in a non-hazardous area. The charging receptacle is located inside the housing adjacent to the ON button. To gain access, it is necessary to unscrew the gnarled plug from the body of the unit. The plug is secured to the ON button by a safety strap to keep it from being lost. It is recommended that the TL105 be kept on charge when not in use to prevent excessive battery discharge. The batteries may be charged an average of 500 times and the battery pack is replaceable.
50
Page 59
Models FL3100H/3101H
Additional information can be found in the TL105 operating manual.
7.4 Storage
General Monitors Flame Detectors should be stored in a clean, dry area and within the temperature and humidity ranges quoted in the Appendix, under Environmental Specifications.
When prolonged storage is anticipated, detectors should be sealed together with a desiccant into plastic bags and double wrapped for protection. They should not be subjected to shock or vibration as this may cause damage. Ideally, the detectors should remain packed in the molds as shipped by General Monitors. Insert red dust caps into vacant cable entry holes.
51
Page 60
Models FL3100H/3101H
8.0 Troubleshooting
8.1 Troubleshooting
CAUTION: Component level repair must be undertaken either by General Monitors’
personnel or by competent authorized service engineers. SMT PCB repair shall only be performed at a GM facility.
8.1.1 Introduction
Included in this section is a troubleshooting table. The information included is designed to cope with the more common faults, which occur during commissioning and operation and which are repairable by a competent operator. Should the various actions suggested in the table fail to restore normal operation, the unit should be returned to General Monitors for repair. A complete written description of the problem should be included.
Be sure to inhibit or disconnect external alarm wiring before making any check that might send the unit into alarm.
NOTE: On no account should repair of the electronic circuit be undertaken by anyone other
than General Monitors’ personnel or authorized representative. Failure to comply with this requirement will invalidate the warranty.
PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION
No output signal and green LED in UV window is off.
No output signal and green LED in UV window is rapidly blinking; in three-color LED configuration: in addition to blinking green LED, yellow LED is on.
2mA signal and green LED in UV window is slowly blinking; in three-color LED configuration: in addition to blinking green LED, yellow LED is on.
Constant 12 mA signal with no known radiation to detector (FL3100H only).
Constant 16 mA or 20 mA signal (WARN or ALARM) with no known radiation at detector (FL3101H only).
No DC Power to the Unit
Low voltage FAULT (voltage at unit less than +18 VDC).
COPM FAULT, dirty or obscured optical path (UV or IR window)
Background UV radiation at detector.
Background UV radiation at detector.
Table 33: Troubleshooting Table
Be sure the +24 VDC is applied with the correct polarity.
Be sure that the unit is powered with at least +20 VDC under load.
Clean UV and IR window and associated source light rods.
Cover UV portion of FL3100H for ten seconds to determine if there is background UV. If there is, remove UV radiation source or change FL3100H location. If there is no background UV, replace UV detector tube in FL3100H. Cover UV portion of FL3101H for ten seconds to determine if there is background UV. If there is, remove UV radiation source or change FL3101H location. If there is no background UV, replace UV detector tube in FL3101H.
52
Page 61
9.0 Customer Support
Area Phone/Email
UNITED STATES
26776 Simpatica Circle Lake Forest, CA 92630
9776 Whithorn Drive Houston, TX 77095
UNITED KINGDOM
Heather Close Lyme Green Business Park Macclesfield, Cheshire, United Kingdom, SK11 0LR
IRELAND
Ballybrit Business Park Galway Republic of Ireland, H91, H6P2
SINGAPORE
No. 2 Kallang Pudding Rd. #09-16 Mactech Building Singapore 349307
MIDDLE EAST
PO Box 54910 Dubai Airport Free Zone United Arab Emirates
Phone: +1-949-581-4464. 800-446-4872 Email: info.gm@MSAsafety.com
Phone: +1-281-855-6000
Phone: +44-1625-619-583
Phone: +353-91-751175
Phone: +65-6-748-3488
Phone: +971-4294 3640
Models FL3100H/3101H
Table 34: Locations
Additional locations can be found on our web site, www.MSAsafety.com
9.1 Other Sources of Help
Extensive documentation, white papers, and product literature for our complete line of safety products can be found at http://www.MSAsafety.com/detection
53
Page 62
Models FL3100H/3101H
10.0 Appendix
10.1 Warranty
General Monitors warrants the Models FL3100H and FL3101H to be free from defects in workmanship or material under normal use and service within two years from the date of shipment.
General Monitors will repair or replace without charge any such equipment found to be defective during the warranty period. Full determination of the nature of, and responsibility for, defective or damaged equipment will be made by General Monitors’ personnel.
Defective or damaged equipment must be shipped to General Monitors’ plant or representative from which the original shipment was made. In all cases this warranty is limited to the cost of the equipment supplied by General Monitors. The customer will assume all liability for the misuse of this equipment by its employees or other personnel.
All warranties are contingent upon proper use in the application for which the product was intended and does not cover products which have been modified or repaired without General Monitors’ approval, or which have been subjected to neglect, accident, improper installation or application, or on which the original identification marks have been removed or altered.
Except for the express warranty stated above, General Monitors disclaims all warranties with regard to the products sold, including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of General Monitors for damages including, but not limited to, consequential damages arising out of, or in connection with, the performance of the product.
10.2 Principle of Operation
10.2.1 UV Detector - FL3100H and FL3101H
The Model FL3101H is a flame detector, which contains an ultraviolet phototube that responds to ultraviolet (UV) radiation in the 185 to 260 nanometer region (Figure 23). When radiation from a flame reaches the cathode plate within the UV detector tube, electrons are ejected from the cathode plate. These electrons are accelerated towards the positively charged anode of the tube. They collide with molecules of an ionizable gas, with which the tube is filled. This emits more electrons and produces an avalanche condition. More electrons are released which creates a momentary electron flow from the cathode to the anode. This momentary current (pulse) recurs at a rate proportional to the intensity of the UV radiation.
The Model FL3101H UV Flame Detector processes these UV pulses with a microcomputer and produces the following outputs:
4 to 20 mA signal  Immediate WARN relay contacts  Time delayed ALARM relay contacts  FAULT relay contacts  RS-485 Modbus RTU output  Optional: HART communication  Optional: Redundant RS-485 Modbus RTU output
54
Page 63
Models FL3100H/3101H
Figure 23: Spectral Response of UV and IR Detectors
(See Sections 3.0 and 5.2 for more information on detector outputs.)
10.2.2 UV/IR Flame Detector - FL3100H
The Model FL3100H is a discriminating UV/IR Detector, which makes use of an ultraviolet radiation sensitive phototube in addition to an infrared detector. This combination provides a flame detector which is highly immune to false alarms.
The UV portion of the detector, as described in the previous section, is combined with an infrared detector, which responds to changes in the intensity of infrared radiation. By sensing very specific wavelengths in both the UV and IR spectra (Figure 23) and then processing these signals with a microcomputer, a very high degree of discrimination is achieved.
Incorporated in the IR circuitry is a flicker discrimination circuit. This permits the detector to ignore steady IR sources such as hot objects. The inherent flickering of a flame provides the necessary modulation to activate the IR circuit.
Since a flame is a copious source of both ultraviolet and infrared radiation, discrimination is provided when both UV and IR emissions are detected. If only UV is detected, as in the case of arc welding, no alarm is given. If only IR is detected, such as a large modulating hot object, no alarm is given. However, if both conditions are met in the correct combination and intensity, as determined by an algorithm in the microcomputer, a fire is identified and the alarm outputs are activated.
10.2.3 COPM Circuitry
A self-testing feature called Continuous Optical Path Monitoring (COPM) checks the optical path, the detector(s), and the related electronic circuitry once every minute. If foreign material impairs the optical path of the UV detector tube (both Models FL3100H and FL3101H) or the infrared detector (Model FL3100H only) for two consecutive checks, the unit will indicate FAULT. The optical FAULT outputs are a 2.0 mA signal, de-energizing of the FAULT relay, and RS-485 output signal (Section 3.3.1). After a COPM FAULT, a COPM check is performed every 12 seconds until the fault condition is removed. Then the COPM check will resume a once per minute check.
55
Page 64
Models FL3100H/3101H
WARNING: Dirty or partially blocked windows can significantly reduce the detector’s field of
view and detection distance.
NOTE: Since the optical path is checked once per minute and it requires two check failures to
produce a FAULT, it may take up to two minutes for the unit to detect an obstruction.
10.2.4 Alarm Test
The Models FL3100H and FL3101H flame detectors have a built-in Alarm Test feature. By connecting one contact of a SPDT momentary switch to TB1 position 4 and the other contact to DC COM TB1, position 9 and 10 (Section 3.3.1), the user can test the alarm outputs of the flame detector by activating this switch for one to eight seconds depending on the Alarm Time Delay Setting.
If the flame detector detects these sources, it will immediately go into WARN and then into the time delayed ALARM. After one to eight seconds the flame detector will reset the non-latching WARN and/or ALARM. A latching WARN and/or ALARM will remain latched until manually reset. If the flame detector does not respond to the sources, it will output a FAULT condition and will retest every ten seconds, as in the COPM FAULT case.
10.2.5 Two-color Visual Indicators
Two light emitting diodes (LED’s) are visible through the UV window (the larger window). LED’s are provided for a visual indication that corresponds with the detectors outputs. The following blinking sequence indicates the standard operation condition:
Timeout (10 seconds when the unit is first powered) - Green and Red LED’s blinking
alternately
Ready - Green LED that flashes off 1 second, every 5 seconds  WARNING - Slow blinking Red LED with Green LED off  ALARM - Fast blinking Red LED with Green LED off  COPM FAULT - Slow blinking Green LED  Low Voltage FAULT/Shorted Reset Switch - Fast blinking Green LED
10.2.6 Three-color Visual Indicators
For a unit with three color LED’s, the following blinking sequence indicates the operating condition:
Timeout (10 seconds when the unit is first powered) – Green, Red and Yellow LED’s
blinking alternately
Ready - Green LED on steady with Red and Yellow LED off  WARNING - Fast blinking Red LED with Green LED on steady. Yellow LED is off.  ALARM - Red LED on steady with Green LED on steady. Yellow LED is off.  COPM FAULT - Slow blinking Green LED with Yellow LED on steady. Red LED is off.  Low Voltage FAULT/Shorted Reset Switch - Fast blinking Green LED with Yellow LED
on steady. Red LED is off.
56
Page 65
Models FL3100H/3101H
10.3 Specifications
10.3.1 System Specifications
Application:
Detector Location: (FL3100H/FL3101H/FL3100H­Hydrogen) Environmental Ratings: UV Detector Pass Band: IR Detector center wavelength:
Typical Alarm Activation Response Times
*
:
Minimum Detector Response Times: Zeta Value:
Field of View
*
:
*
NOTE
: Response Times and Field of View data have been derived by testing the Models
FL3100H/FL3101H flame detectors with a 1 square foot heptane fire. One cup of heptane on top of a one-inch layer of water was ignited for each test. These are typical values and different results may occur depending on the variation of each fire.
FL3100H UV/IR Flame Detection FL3101H UV Flame Detection FL3100H-H
UV/IR Hydrogen Flame Detection
2
Class I, Division 1, Groups B, C and D; Class II, Division 1, Groups E, F and G; Class III Ex db IIC T5 Gb; Ex tb IIIC T100°C Db Type 4x, IP66/IP67 185 to 260 nanometers
m, 2.7-3.2 m for Hydrogen
4.35 FL3100H < 3 s for 1 x 1 ft
2
heptane fire when detector is on axis to fire source and the distance of the detector to the fire is 15 -50 ft FL3101H < 1 s @ 50 ft (15.2 m) FL3100H-H
< 3 s @ 15 ft (4.6 m)
2
FL3100H < 500 ms FL3101H < 100 ms Zeta = -0.001 (The margin of error in the range measurement is estimated at ± 5 feet due to wind conditions and flame turbulence) FL3100H 120° maximum conical FL3101H 140° maximum conical FL3100H-H
120° maximum conical
2
57
Page 66
Models FL3100H/3101H
10.3.2 Mechanical Specifications
Enclosure Material:
Color: Finish:
Height: Width: Depth: Weight:
Cable Entry:
Cable Requirements:
Aluminum (AL) A-356 or Stainless Steel (SS): Natural 316 Aluminum Red Aluminum: Chemical Film per MIL-C-5541, Epoxy Powder Coated
6.0 in (15.2cm)
6.0 in (15.2cm)
5.5 in (14.0cm) 5 lbs (2.3 kg) AL 16 lbs (7.3 kg) SS 2 x 25 mm ISO or 2 x PG 13.5 or 2 x 20 mm ISO or 2 x ¾” NPT. Each unit has an Ex d approved stopping plug installed, plus a Red Dust cap. Dust caps must be replaced by Ex d IIC approved cable glands and must not be left on the unit when powered up. Screened or screened and armored to BS5308 Part 2, Type 2 or equivalent. Note that terms “Screen” and “Shield” are used interchangeably.
10.3.3 Electrical Specifications
European Union (EU) Approved Applications: PSU noise and ripple voltage 1.0Vpp max. The customer
supplied PSU must comply with IEC 61010-1, limiting current to 8A under Fault conditions, in order to comply with CE Marking requirements.
Nominal supply voltage: Supply voltage range: Maximum supply current: Typical current: Maximum output signal load: Output signal range: FAULT signal: COPM fault signal: Ready signal: IR only signal (FL3100H only): UV only signal (FL3100H only): WARN signal: ALARM signal: Relay Contact Ratings: North American Approved Applications:
RS-485 Output:
24 VDC 20 to 36 VDC 400 mA during COPM only 80 to 150 mA Depends on relays ETC 600 ohms 0 to 20 mA * 0 to 0.2 mA *
2.0
0.2 mA *
0.2 mA
4.0
0.2 mA
8.0
0.2 mA
12.0
0.2 mA
16.0
0.2 mA
20.0 SPDT, 8A, @ 250VAC, or 8A @ 30 VDC resistive max.
European Union (EU) Approved Applications:
SPDT, 8A 30V RMS/42.4V Peak, 8A @ 30 VDC, resistive max. Modbus RTU 128 units in series max. (247 units with repeaters) Baud Rate: 2400, 4800, 9600 or 19200 BPS Optional: Dual Modbus RTU Communications available (See Section 3.3 Terminal Connections, for Alarm Output Connections)
58
Page 67
Models FL3100H/3101H
HART:
HART Impedance: AMS Aware: RFI/EMI Protection: Status Indicator:
* Normal non-HART version. See analog output Section 3.3.6 for other currents. ** Standard configuration has two single-color LED’s, green and red, while three-color LED
configuration offers green, red, and yellow. Red and yellow are from a single bi-color LED.
Fully HART Foundation compliant. See separate HART manual for use of HART.
= _50 K CX= 5 nF
R
X
Certified by AMS Complies with EN 50130-4, EN 61000-6-4 Two LED’s indicate status, fault, and alarm conditions**
10.3.4 Environmental Specifications
Operating temperature range: Storage temperature range: Humidity range:
-40°F to 185°F (-40°C to 85°C)
-40°F to 185°F (-40°C to 85°C) 0% to 95% RH non-condensing
10.4 Approvals
CSA, FM, ATEX, IECEx, GOST, INMETRO, HART Registered, SIL 3 suitable and AMSAware. The FL3100H-Hydrogen flame detector is not FM approved.
10.5 Accessories
10.5.1 Mounting Swivel/Union
A mounting swivel and union are available to connect ¾” conduit into the base of the Model FL3100H/FL3101H. The swivel design allows for optical alignment adjustments for the flame detectors when using rigid conduit.
NOTE: Swivel is not approved for ATEX requirements.
10.5.2 Mounting Bracket
A mounting bracket is available to mount the FL3100H/FL3101H to a wall, pole, etc. The mounting bracket design allows for optical alignment adjustments for the flame detectors when installed to a fixed installation.
10.6 Storage
The flame detectors should be stored in a clean, dry area and within the temperature and humidity ranges mentioned in Section 10.3.4.
59
Page 68
10.7 Final Assembly
Models FL3100H/3101H
Figure 24: P/N 71450 FL3100H (UV/IR), Final Assembly
60
Page 69
Models FL3100H/3101H
Figure 25: P/N 71451 FL3101H (UV), Final Assembly
61
Page 70
Models FL3100H/3101H
This product may contain hazardous and/or toxic substa nces.
EU Member states shall dispose according to WEEE regulations. For further WEEE disposal
information please visit: www.MSAsafety.com
All other countries or states: please dispos e of in accordance with existing federal, state and local
environmental control regulations.
ADDENDUM
62
Loading...