4 OUTPUT ACTION
This detector is factory calibrated and ready for immediate use. Once power is applied, the
Red LEDs located at the top and bottom of the unit indicate status.
START-UP NORMAL
STATE
ALARM CALIBRATION
CHECK
FAULT
LED
STATE
Flash at
1 Hz
Flash every
60 seconds
Flash
fast at
3 Hz
Flash slow at 0.5Hz
(>=50 ppm fixed)
SOLID ON
Relay function:
Relay is normally energized, non-latching. It changes state upon alarm or fault condition.
During a sensor fault, the:
• current output is set to 2 mA or
• voltage output is set to 1 V
• digital output is defined in Register Map.
5 CONFIGURATION
All network communication uses serial framing (8 data bits, no parity, 1 stop bit) regardless of
protocol or Baud Rate. The serial framing cannot be changed.
Configuration Switches:
Switches Function
S300,S301,S302 Modbus address (Range = 1~255)
or
BACnet MAC address (Range = 0~127)
S303-1,S303-2,S303-3 Baud Rate
S303-4 Alarm level (ON (H) - default 50 ppm, OFF (L) - default 750 ppm)
S303-5 BACnet Instance Number setting
(OFF-(L) User’s setting, ON (H) factory setting)
S303-6 RS485 Termination match resistor (120 ohms).
ON position adds the resistor
Property Object Type
Device Analog Input Analog Values
Max APDU Length R
Segmentation
Support
R
APDU Timeout W(10~65535,65.535s)
Number APDU
Retries
W(0~10)
Max Master W(1~127)
Max Info Frames R
Device Address
Binding
R
Database Revision R
Active COV
Subscriptions
R
Present Value R R/W
Status Flags R R
Event State R R
Reliability R R
Out-Of-Service R R
Units R R
Priority Array R
Relinquish Default R
COV Increment W W
Modbus address
S300, S301and S302 are used to represent a value using the decimal number system for
Modbus address (Range = 1~255). S300 is hundreds number, S301 is tens digit number and
S302 is units digit number. The changes will only be valid after power reset. Invalid address
will cause an address fault.
BACnet MAC address
S300, S301 and S302 are used to represent a value using the decimal number system
for BACnet MAC address (Range = 0~127). S300 is hundreds number, S301 is tens digit
number, and S302 is units digit number. The changes will only be valid after power reset.
Invalid address will cause an address fault.
Baud Rate
S303-1, S303-2 and S303-3 are used to represent the Baud Rate configuration.
S303-1 S303-2 S303-3 Baud Rate
BACnet Modbus
OFF OFF OFF 9600
OFF OFF ON 19200
OFF ON OFF 38400
OFF ON ON 57600
ON OFF OFF 76800
ON OFF ON 115200
Alarm Level
There is one alarm whose value can be switched between two different levels. The factory
programmed alarm levels are: 50ppm when switch is in the ON (H) position, and 750ppm
when switch is in the OFF (L) position. The alarm values can be edited using a controller.
Any changes are valid immediately.
S303-4 Alarm Level
ON (H) Default 50 ppm
OFF (L) Default 750 ppm
BACnet Instance Number
Refer to the serial number label (Figure 1) for the default Instance Number (also Serial
Number). If switch S303-5 is ON (H) then the factory default is used and is unchangeable.
If S303-5 is OFF (L) then a user programmable Instance Number is used, although it is
initialized to the factory default.
5.2 Modbus RTU Connection
When connected to a Modbus network the following parameters must be set properly in
order to communicate with the Modbus controller:
• Modbus address
• Baud Rate
The following registers are available for exchange with the Modbus controller.
Modbus Objects:
REGISTER
NAME
PDU
ADDRESS
LOGICAL
ADDRESS
Property RANGE
Gas
Concentration
0x0000 1 Read 0 to 1000 (ppm)
Gas Number 0x0001 2 Read R-410A=34
Active Alarm
Level
0x0002 3 Read ( ppm )
Fault and Device
State
0x0003 4 Read Device Fault 80 (MSB)
Address Fault 8 (MSB)
Concentration
Alarm
10 (LSB)
Warm Up
Complete
0 (LSB)
High Alarm Level 0x0004 5 Read/Write 750 default
range = 25-1000
Low Alarm Level 0x0005 6 Read/Write 50 default
range = 25-1000
Room TEMP. (°C) 0x0008 9 Read
6 CALIBRATION CHECK
This detector with Photoacoustic infrared technology is designed to operate with a stable
baseline for years of operation. However, a unit must be checked periodically to verify
that it detects refrigerant gas. The calibration check can be done with the following MSA
equipment:
• (P/N 603806) Polyurethane Tubing
• (P/N 467895) 0.25 LPM regulator
• (P/N 10077766) Gas cylinder, 100ppm R410A in Nitrogen
5.1 BACnet Connection
When connected to a BACnet network, the following parameters must be set properly in
order to communicate with the BACnet controller:
• MAC address
• Instance Number
• Baud Rate
This monitor is configured for and connected to a BACnet network and has the following
BACnet Objects available for exchange with the BACnet controller.
BACnet Objects:
Object Name Instance Number Property RANGE
Gas Concentration 1 ( default ) Read 0 to 1000 (ppm)
Gas Number 2 ( default ) Read R-410A=34
Active Alarm Level 3 ( default ) Read ( ppm )
Fault and Device
State
4 ( default ) Read Device Fault 80 (MSB)
Address Fault 8 (MSB)
Concentration
Alarm
10 (LSB)
Warm Up
Complete
0 (LSB)
High Alarm Level 5 ( default ) Read/Write 750 default
range = 25-1000
Low Alarm Level 6 ( default ) Read/Write 50 default
range = 25-1000
Instance Number 7 ( default ) Read/Write Default value:
Serial Number Label (Figure 1)
Range: 0~4194302
Room TEMP. (°C) 8 ( default ) Read
BACnet Protocol Implementation Conformance Statement (PICS):
Device Profile BACnet Application Specific Controller (B-ASC)
Data Sharing Read Property-B (DS-RP-B)
Read Property Multiple-B (DS-RPM-B)
Write Property-B (DS-WP-B)
Write Property Multiple-B (DS-WPM-B)
COV-B(DS-COV-B)
A calibration check of the sensor requires a supply of:
• ZERO GAS (air or nitrogen). It may be possible to use ambient air if user is certain it does
not contain refrigerant gas or an interfering component
• SPAN GAS Cylinder comprised of refrigerant gas of appropriate concentration
6.1 Calibration Check Procedure
To verify proper sensor operation:
1. If the active alarm level is lower than the concentration of calibration gas, please be aware
that the relay may activate. You may modify the active alarm level via Modbus or BACnet
or you may switch to the alternate alarm level using switch S303-4 (refer to Alarm Level
section above).
2. If appropriate, deactivate any equipment connected to the outputs, or disconnect the wiring
of the outputs.
CAUTION
If any control instruments connected to this detector are wired to external devices (e.g., horns, exhaust
fans, and fire suppression systems), these devices may activate during the following procedures.
To prevent activating these devices while adjusting this monitor, disconnect the wiring to the control
device. Return all wiring to the control device when the calibration procedure is completed.
3. With the tubing connected to the regulator and cylinder, place tubing in the opening at the
bottom of this unit (see Figure 6).
4. Open the regulator and apply gas. This process may take up to five minutes.
5. If the unit is operating properly:
• The Red LED:
• illuminates when concentration level > Calibration Check level or Active Alarm level
• is visible through the upper and lower enclosure vents.
• the relay will activate if the Active Alarm level is exceeded.
6. Turn off regulator and remove tubing from opening.
7. Allow gas level to return to normal.
8. Reactivate any equipment connected to the outputs or reconnect the wiring to the outputs.
9. Remember to restore any alarm level settings that may have been changed for the Calibration
Check.
Device Management Dynamic Device Binding-B (DM-DDB-B)
Dynamic Object Binding-B (DM-DOB-B)
Device Communication Control-B (DM-DCC-B)
Reinitialize Device-B (DM-RD-B)
Data Link Layer Options MS/TP Master (Clause 9),
Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200
Static device binding Supported NO
Character Sets Supported ISO 10646 (UTF-8)
Segmentation Capability NO
BACnet Standard Object Types supported:
Property Object Type
Device Analog Input Analog Values
Object Identifier R R R
Object Name R R R
Object Type R R R
System Status R
Vendor Name R
Vendor Identifier R
Model Name R
Firmware Revision R
App Software
Revision
R
Protocol Version R
Protocol Revision R
Services Supported R
Object Type
Supported
R
Object List R
.25 LPM
REGULATOR
467895
SPAN OR ZERO
GAS CYLINDER
Figure 6: Applying Calibration Gas