Automatic Blowdown Operation & Testing
_________________________________
Blowdown Duration Adjustment Instruction
NOTE: The Time Clock controls boiler operation. The boiler is on when the
timer is on. The Blowdown Valve will open when the timer turns the boiler off.
WARNING
Hazard of Electric Shock. Disconnect all power supplies
!
before making any adjustments
CAUTION
!
To provide for safe and low temperature blowdown, and to
30
sec
comply with National and local plumbing and building Codes, it may be
necessary to blowdown into an ASME Code blowdown separator tank, or
to take other precautions to prevent damage to building drain plumbing.
Consult with a licensed plumber.
WARNING
Burn Hazard. Pressurized Steam and Hot Water is
!
discharged during blowdown.
Duration Adjustment
Using a small flathead screwdriver, rotate the adjustment screw to the
desired setting.
IMPORTANT: Do not set less than 10 seconds. Do not force screw past
min and max stops, screw does not rotate more than 300 degrees
Factory Recommended Settings:
• 100psi Trim: 50% turn (shown, 30 seconds)
• 15psi Trim: 100% turn (shown, 60 seconds)
60
sec
0
sec
10 sec
Automatic Blowdown Operation & Testing
1. Turn the override switch to permanent ON (I).
2. Turn the generator On/Off Switch to “ON”. On/Off Switch pilot
light and generator should be “ON”. Motorized drain valve should
be closed. Auto blowdown light should be “OFF”.
3. Turn the override switch to permanent OFF (0). On/Off Switch
pilot light and generator should be “OFF”. Auto blowdown light
should be “ON” Motorized drain valve remains open for the duration
set with the adjustment screw.
4. After the set time: Motorized drain valve closes. Auto blowdown
Back
light should be “OFF”. On/Off Switch pilot light and generator
remains “OFF”.
5. Turn the override switch to automatic ( ).
NOTE: ASME blowdown separator tank systems are available from Sussman Electric Boilers/Mr. Steam.
For more information please call 1-800-76 STEAM.
®
Sussman-Automatic Corporation
www.sussmanboilers.com
www.mrsteam.com
west coast: 9410 S. La Cienega Blvd. Inglewood CA 90301 • 800 72 STEAM • fax: 310 216 2944
®
•
seb@sussmancorp.com • 718-937-4500 • 800-238- 3535 • Fax: 718-937-4676
•
info@mrsteam.com
43-20 34th Street, Long Island City, NY 11101
•
800 76 STEAM
•
fax: 718 472 3256
mr.steam
100483 rev. 9.13