Mr. Steam CUALARM Installation Manual

Page 1
®
mr.steam
CU ALARM
___________________________________________________________________________________
The CU Alarm is an audible alarm that sounds in the event the steam room maximum set temperature is exceeded or if the CU-SteamStop button has been pressed.
The CU Alarm may be mounted outside the steam room in a location that will alert an attendant and/or user to an over-temperature condition.
Review local codes for mounting location as required
!
mounted inside the steam room.
.
WAR N IN G
The CU Alarm shall not be
d B A R AT I N G S
Tone High Standard
Horn 88 82 Bell 82 75
WAR N IN G
!
Instructions Carefully Before Using this Product. The 115VAC CU Alarm must be field
set to the desired dBa sound output level and alarm tone before installation. This is done by adjusting a four position switch in accor­dance with these instructions. Incorrect set­tings will result in improper performance.
IMPORTANT NOTE:
This information is important for the safe and efficient installation and operation of this generator. These are types of potential hazards that may occur during this installation and operation:
Please Read These
March Time Horn 85 79 *Code-3 Horn 85 75 *Code-3 Tone 79 75 Slow Whoop 88 82 Siren 85 82 Hi/Lo 82 79
*See note on Page 3
As you follow these instructions, you will notice warning and caution symbols.
dBA Reverberant
at 10 feet
CA U TI ON
!
WAR N IN G
!
mr.steam
Sussman-Automatic Corp.
info@mrsteam.com www.mrsteam.com
states a hazard may cause serious injury or death if precautions are not followed.
signals a situation where minor injury or product damage may occur if you do not follow instructions.
®
®
43-20 34th Street Long Island City, NY 11101
TEL: 718-937-4500 FAX: 718-472-3256
PUR 100452 Rev 4/10
9410 S. La Cienega Blvd. Inglewood CA 90301
TEL: 310-216-6565 FAX: 310-216-2944
Page 2
mr.steam
SW 1
+
AUD -
Slide Here for (0)
Slide Here for (1)
O N
1 2 3 4
SW1
O N
1 2 3 4
_____________________________________________________________________________________________________________________________
®
CU ALARM
WAR N IN G
!
MAKE SURE THAT ALL FUSES USED ON SIGNALING CIRCUITS ARE RATED TO HANDLE THE MAXIMUM INRUSH OR PEAK CURRENT FROM ALL APPLIANCES ON THOSE CIRCUITS. FAILURE TO DO THIS MAY RESULT IN LOSS OF POWER TO THE SIGNALING CIRCUIT AND THE FAILURE OF ALL APPLIANCES ON THAT CIRCUIT TO OPERATE.
The CU Alarm produce a brief inrush current that lasts for just 50 microseconds at a peak value of 5.0 Amps.
WAR N IN G
!
IF 115VAC CU ALARMS ARE OPERATED WITHIN 15 INCHES OF A PERSON, THEY CAN PRODUCE A SOUND PRESSURE LEVEL THAT EXCEEDS THE MAXIMUM 120 dBA PERMITTED BY ADA AND OSHA RULES. EXPOSURE TO SUCH SOUND LEVELS CAN RESULT IN HEARING DAMAGE.
SETTINGS:
The Switch (SW1) of the CU Alarm, shown in Figure 1, is used to set the desired dBA sound output level and alarm tone. The factory set­tings are shown below. Read these instructions carefully before chang­ing any of these factory settings.
Figure 1: PC Board Layout Showing Location of Switch
(Labeled SW1 on circuit board as shown)
THE FACTORY SETTINGS ARE:
HIGH dBA SW1 POS 1 set on 1
HORN TONE SW1 POS 2, 3, 4 set on 1, 1, 1
2
Page 3
mr.steam
P
O
S
1
P
O
S
2
P
O
S
3
P
O
S
4
USE A SMALL SCREWDR IVER TO CHANGE THE SWITCH P OSITION.
Slide Here for (0)
Slide Here for (1)
_____________________________________________________________________________________________________________________________
®
CU ALARM
STEP 1:
Set desired dBA sound output by setting POS 1 of the four position switch (SW1). (refer to Figure 2 and Table 2).
Figure 2: SW1 Switch
STEP 2:
Set desired alarm tone by setting the four-posi­tion switch (SW1). Use POS 2, 3, 4 to select the desired alarm tone (refer to Table 3 below).
TA B L E 2
dBA Sound Output Level Settings
Decibel Level (dBA) POS 1
High dBA 1 (Factory Setting)
Standard dBA 0
TA B L E 3 Alarm Tones
SWI Switch Settings
___________________________________
Tone Pattern Description POS 2 POS 3 POS 4
Horn Broadband Horn (Continuous) (Factory Setting) 111
Bell 1560 Hz Modulated (0.07 Sec. ON/Repeat) 101
March Time Horn Horn (0.25 Sec.ON/0.25 Sec. OFF/Repeat) 001
* Code-3 Horn Horn (ANSI S3.41 Temporal Pattern) 1 1 0
* Code-3 Tone 500 Hz (ANSI S3.41 Temporal Pattern) 0 1 1
Slow Whoop 500-1200 Hz Sweep (4.0 Sec. ON/0.5 Sec. OFF/Repeat) 0 10
Siren 600-1200 Hz Sweep (1.0 Sec. ON/Repeat) 1 0 0
HI/LO 1000/800 Hz (0.25 Sec. ON/Alternate) 0 0 0
* NOTE: The Code-3 Horn and Code-3 Tone (set on HIGH dBA) incorporate the temporal pat­tern specified by ANSI/NFPA for standard emergency evacuation signaling. They should be
used only for fire evacuation signaling and not for any other purpose.
3
Page 4
mr.steam
REMOVE JUMPER FOR
OPTIONAL TIMER
STEAM SOLENOID
VALVE
Factory Wiring
Field Wiring
CU ALARM
N
L
DI G ITAL 1 CO N TROL
_____________________________________________________________________________________________________________________________
®
CU ALARM
WIRING THE ALARM TO A MR.STEAM CU COMMERCIAL STEAM GENERATOR:
WAR N IN G
!
SHOCK CAN CAUSE DEATH OR SERIOUS INJURY.
IMPORTANT NOTE: All electrical wiring is to be installed by a qualified, licensed electrician in accordance with National and local electrical codes.
1. Strip leads 3/8 inches and connect to screw terminals. 115VAC CU Alarms have in-out wiring terminals
that accepts two #
Diagram: CU 360-4500 with 120 Volt Digital 1 Control:
SHUT OFF ALL POWER AT BREAKER BEFORE STARTING THE INSTALLATION. ELECTRIC
12 to #18 American Wire Gauge (AWG) wires at each screw terminal.
NOTES:
1. This Diagram shall only be used for wiring CU-Alarms. Consult the CU Installation Manual
PUR 100376) for complete boiler wiring information.
(
2. The Over Temperature Portion (Change Wires) of the D1 Temperature Controller must be connected for the CU-Alarm to operate correctly.
4
Page 5
mr.steam
CU ALARM
CU ALARM
REMOVE JUMPER FOR CU-HL
Control Terminal Block
Control Supply
120 Volt 1 PH 60 Hz
L
N
L
N
Factory Wiring
Field Wiring
_____________________________________________________________________________________________________________________________
®
CU ALARM
Diagram: CU 360-4500 with 120 Volt F1 Plus Control:
NOTES:
1. This Diagram shall only be used for wiring CU-Alarms. Consult the CU Installation Manual (PUR 100376) for complete boiler wiring information.
2. A CU-HL must be used in conjunction with each CU ALARM on boilers with F1 controls.
5
Page 6
mr.steam
(2) #10-32 SELF­TAPPING SCREWS
SIGNAL
(2) #8-32 SCREWS
4" SQ. X 2-1/8" Deep ELECTRICAL BOX
_____________________________________________________________________________________________________________________________
®
CU ALARM
SURFACE MOUNTING:
IMPORTANT NOTE:
All electrical wiring is to be installed by a qualified, licensed electrician in accordance with National and local electrical codes.
Review local codes for mounting location as required
WARNING
!
DO NOT mount the CU ALARM
.
inside the steam room.
CAUTION
!
conduit fittings are used, check that installed CU Alarm has suf­ficient clearance and wiring room prior to installing electrical boxes and conduit.
1.115 VAC CU ALARMs can be surface mounted to a
standard 4 inch square by 2- box (Figure A)
2. Select the largest electrical box possible (shown in Mounting
Options) to provide the maximum wiring clearance for easy installation.
3. Conduit entrance to electrical boxes should be selected to
insure sufficient wiring clearance for the CU Alarm. When extension rings are required, conduit should enter through electrical box, not extension ring.
4. Use care and proper techniques to position the field wires in
the electrical box so that they use minimum space and pro­duce minimum stress on the product. This is especially impor­tant for stiff, heavy gauge wires with thick insulation or sheathing.
5. Do not pass additional wires (used for other than signaling
appliances) through the electrical box. Such additional wires could result in insufficient wiring space for the signaling appliance. The CU Alarm is designed to produce an audible alarm in the event the steam room maximum set temperature is exceeded.
6. Place the CU-ALARM identification label on or adjacent
to the alarm.
IMPORTANT NOTE:
incorporate the temporal pattern specified by NSI/NFPA/
ISO for standard emergency evacuation signaling. They should be used only for fire evacuation signaling and not for any other purpose.
If sheathed multiconductor cable or 3/4"
1
/8inch deep electrical
STEAMROOM ALARM
mr.steam
43-20 34th Street, Long Island City, NY 11101 1 800 76 STEAM
The Code-3 Horn and Code-3 Tone
®
www.mrsteam.com
OPERATIONAL CHECK:
WHEN USED WITH THE DIGITAL 1 CONTROL:
1. Disconnect the probe wire connection at the back of the Digital 1 Control.
2. The boiler will shut off and the alarm will sound (the Digital 1 will read o o o).
3. If the alarm does not sound, disconnect power and swap the orange wires at terminal 7 & 8 on the back of the control.
4. Reconnect power and follow the operational check instructions.
WHEN USING THE CU-STEAMSTOP:
1. Press the CU-STEAMSTOP (the Digital 1 will read - - -)
2. The boiler will shut off and the alarm will sound.
3. If the alarm does not sound, disconnect power and swap
the orange wires at terminal 7 & 8 on the back of the control. If the Digital 1 control does not display - - -, refer to the CU-STEAMSTOP Installation operation & Maintenance Manual.
4. Reconnect power and follow the operational check instructions.
WHEN USED WITH THE F1 PLUS CONTROL AND CU-HL:
1. Turn the CU-HL temperature dial down until the boiler turns off.
2. The alarm will sound. Reset the CU-HL set point.
3. If the alarm does not sound disconnect power and
check wiring.
6
Loading...