Installer: Leave this manual with the appliance. Consumer: Retain this manual for future reference.
INSTALLATION INSTrucTIONS ANd OwNer’S MANuAL
Mr. HeATer
MODEL
MHVFB10LP
reAd INSTrucTIONS c AreFuLLY: Read and follow all instructions. Place
instructions in a safe place for future reference. Do not allow anyone who has not
read these instructions to assemble, light, adjust or operate the heater.
UNVENTED LP-GAS FIRED
BUDDY WALL-MOUNT HEATER
Operation Instructions Only
No Parts List
WARNING: If the information in this manual is not followed exactly, a re or explosion may result causing
property damage, personal injury, or loss of life.
- Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this or any other appliance.
- An LP cylinder not connected for use shall not be stored in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
• Shut off gas supply
• Do not try to light any appliance
• Do not touch an electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
- Installation and service must be performed by a qualied installer, service agency, or the gas supplier.
WARNING: This is an unvented gas-red heater. It uses air (oxygen) from the room in which it is installed.
Provisions for adequate combustion and ventilation air must be provided. Refer to Fresh Air for Combustion and
Ventilation section on page 3 of this manual.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property
damage. Refer to this manual for correct installation and operational procedures. For assistance or additional
information consult a qualied installer, service agency, or gas supplier.
This appliance may be installed in an aftermarket* permanently manufactured (mobile) home, where not prohibited
by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with any other gas.
*Aftermarket completion of sale, not for the purpose of resale, from the manufacturer.
WARNINGS
IMPORTANT: Read this owner’s manual carefully
and completely before trying to assemble, operate,
or service this heater. Improper use of this heater
can cause serious injury or death from burns, re,
explosion, electrical shock, and carbon monoxide
poisoning.
WARNING: This appliance is equipped for (natural
or propane) gas. Field conversion is not permitted.
WARNING: Do not use any accessory not approved for use with this heater.
WARNING: Any change to this heater or its controls can be dangerous.
•Do not place clothing or other ammable ma-
terial on or near the appliance. Never place
any objects on the heater.
•Due to high temperatures, heater should be
kept out of trafc and away from furniture and
draperies.
•Surface of heater becomes very hot when run-
ning. Keep children and adults away from hot
surfaces to avoid burns or clothing ignition.
Heater will remain hot for a time after shut-
down. Allow heater surfaces to cool before
handling.
•Young children should be carefully supervised
when they are in the same room with heater.
•Make sure grille guard is in place before
running heater. If screen or grille guard is
removed for servicing it must be replaced prior
to operating the heater.
•Keep the appliance area clear and free from
combustible materials, gasoline, and other
ammable vapors and liquids.
Every time hose or tank is connected to unit,
connection must be checked for leaks in one or
more ways: Apply soapy water to connection, look
for bubbles, listen for hiss of escaping gas, feel
for extreme cold, smell for rotten egg odor. Do not
use if leaking!
PRECAUTIONS:
WARNING:
1. This heater may be installed in a bedroom, but not a
bathroom, or any place where a strong wind would
shut down the appliance.
2. This heater needs outside ventilation air to run
properly. The Oxygen Depletion Sensor (ODS)
safety shutoff system shuts down the heater if not
enough fresh air is available. See Fresh Air for Combustion and Ventilation, page 3.
3. Keep all air openings in heater clear, free of debris
or any blockage. This will insure that enough air for
proper combustion enters the heater.
4. If heater shuts off, do not relight until you provide
fresh, outside air. If heater keeps shutting off, it
requires servicing.
5. Turn off and unplug heater and let cool before servicing. Only a qualied service person should service
and repair heater.
6. Do not run heater:
•Where ammable liquids or vapors are used or
stored
•During dusty conditions.
7. Before using furniture polish, wax, carpet cleaner or
similar products, turn heater off. If heated the vapors
from these products may create a white powder
residue within burner box or on adjacent walls or
furniture.
8. Do not use heater if any part has been underwater.
Immediately call a qualied service technician to inspect the room heater and to replace any part of the
control system and any gas control which has been
underwater.
9. Operating heater above elevations of 4,500 feet
could cause pilot/ODS to shutdown heater.
10. Always run heater with control knob in a locked
position. Never set control knob between locked positions. Poor combustion and higher levels of carbon
monoxide may result if control knob is left between
locked positions.
DANGER: Carbon monoxide poisoning may lead to
death.
Carbon Monoxide Poisoning:
Early signs of carbon monoxide poisoning resemble the
u, with headaches, dizziness, or nausea. If you have
these signs, the heater may not be working properly.
Get fresh air at once! Have heater serviced. Some
people are more affected by carbon monoxide than
others. These include pregnant women, persons with
heart or lung disease or anemia, those under the inuence of alcohol, and those at high altitudes.
Propane/LP Gas:
Propoane/LP gas is odorless. An odor making agent
is added to propane/LP gas. The odor helps you detect
a Propane/LP gas leak. However the odor added to
propane/LP gas may be present even though no odor
Unvented LP-Gas Fired Buddy Wall-Mount Heater
Installation Instructions and Owner’s Manual
2
Page 3
exists. Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to
safe and proper operation of this heater.
Product Features
Control Knob
Burner
Grill
Heater
Cabinet
Front Panel
Figure 1
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensor (ODS) safety shut off system. The ODS/pilot shuts
off the heater if there is not enough fresh air.
IGNITION SYSTEM
PIEZO: MHVFB10LP – The heater is equipped with a
piezo manual ignitor. This system requires no matches,
batteries, or other source to light heater.
LOCAL CODES
Install and use heater with care.
Installation must conform to local codes or in the absences of local codes, use the latest edition of National
Fuel Gas Code ANSI Z223.1/NFPA 54.
UNPACKING
1. Remove heater from carton.
2. Remove all protective packaging applied to
heater for shipment.
3. Check heater for any shipping damage. If
heater is damaged, promptly inform dealer
where you bought heater.
WARNING: Even though this heater may be
used in enclosures such as ice houses, lodges,
cabins or enclosed porches, fresh air for combustion and ventilations requirements apply the
same as below.
FRESH AIR FOR COMBUSTION AND
VENTILATION
WARNING: This heater shall not be installed in a
conned space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and other
fuel-burning appliances in your home.
Unvented LP-Gas Fired Buddy Wall-Mount Heater
ESTABLISHING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas
Code, NFPA 54/ ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation. All spaces in homes fall into
one of the three following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
This heater must not be installed in a conned space or
unusually tight construction unless provisions are provided for adequate combustion and ventilation air. The
information on pages 3 through 5 will help you classify
your space and provide adequate ventilation.
Unusually Tight Construction
If your home meets all of the three following criteria you
must provide additional fresh air. See Ventilation Air from Outdoors, page 5.
Unusually tight construction is dened as construction
where:
a. Walls and ceilings exposed to the outside atmo-
sphere have a continuous water vapor retarder with
a rating of one perm (6 x 10
-11
kg per pa-sec-m2) or
less with openings gasketed or sealed and
b. Weather stripping has been added on openable win-
dows and doors, and
c. Caulking or sealants are applied to areas such as
joints around windows and door frames, between
wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at
other openings.
If you home does not meet all of the three criteria
above, see Determine the Type of Heater Location
Space, page 4.
Conned Space and Unconned Space
The National Fuel Gas Code, NFPA 54/ ANSI Z223.1
denes a conned space as a space whose volume is
less than 50 cubic feet per 1,000 Btu per hour (4.8 m3
per kW) of the aggregate input rating of all appliances
installed in that space, and an unconned space as a
space whose volume is not less than 50 cubic feet per
1,000 Btu per hour (4.8 m3 per kW) of the aggregate
input rating of all appliances installed in that space.
Rooms communicating directly with the space in which
the appliances are installed*, through openings not furnished with doors, are considered a part of the unconned space.
*Adjoining rooms are communication only if there
are doorless passageways or ventilation grills between them.
DETERMINING THE TYPE OF HEATER
LOCATION SPACE:
Use this method to determine if you have a conned or
unconned space.
Note: the space includes the room in which you
Installation Instructions and Owner’s Manual
3
Page 4
install heater plus any adjoining rooms with doorless passageways or ventilation grills between the
rooms.
1. Find the volume of the space by multiplying room
length x width x height.
Example: Space size 18ft (length) x 18ft. (width) x 8ft.
(height) = 2592
If additional ventilation to adjoining room is supplied
with grills or openings, add the volume of these rooms
to the total volume of the space.
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/hr the space can support.
Example: 2592 cu.ft. (volume of space) / 50 cu.ft. =
51.8 or 51,800 (maximum Btu/hr the space can
support)
WARNING: If the area in which the heater may be
operated is smaller than dened as an unconned
space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by the methods described in the National
Fuel Gas Code, NFPA 54/ ANSI Z223.1, Section
5.3 or applicable local codes.
3. Add the Btu/hr of all the fuel-burning appliances
in the space such as, Vent–free heater, Gas water
heater, Gas furnace, Vented gas heater, Gas replace logs, and Other gas appliances*
*Do not include direct-vent gas appliances. Directvent draws combustion air from the outdoors and
vents to the outdoors.
Example:
Gas water heater 40,000 Btu/hr
Vent Free Heater + 20,000 Btu/hr
Total =60,000 Btu/hr
4. Compare the maximum Btu/hr the space can support
with the actual amount of Btu/hr used.
Example: 51,800 Btu/hr (maximum Btu/hr the
space can support)
60,000 Btu/hr (Actual amount of Btu/hr
used)
The space in the above example is a conned
space because the actual Btu/hr used is more than
the maximum Btu/hr the space can support.
You must provide additional fresh air. Your options
are as follows:
A. Rework worksheet, and the space of an adjoining
room. If the extra space provides an unconned
space, remove door to adjoining room or add ventilation grills between the rooms. See Ventilation Air
From Inside Building (Fig. 2)
B. Vent room directly to the outdoors. See Ventilation
Air From Outdoors (Fig. 3).
C. Install a lower Btu/hr heater if lower Btu/hr size
makes room unconned.
If actual Btu/hr used is less than the maximum Btu/
Unvented LP-Gas Fired Buddy Wall-Mount Heater
hr the space can support, the space is an unconned space. You will need no additional fresh air
ventilation.
VENTILATION AIR
Ventilation from Inside Building
This fresh air would come from an adjoining unconned
space. When ventilation to an adjoining unconned
space, you must provide two permanent openings: one
within 12” of the ceiling and one within 12” of the oor
on the wall connecting the two spaces (see options 1
& 2 of g. 2). You can also remove door into adjoining room (see option3, g 2). Follow the National Fuel
Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for
Combustion and Ventilation for required size of ventilation grills or ducts.
12”
Ventilation
Gills into
Adjoining
Room Option 1
Or remove
door into
Adjoining
Room Option 3
Ventilation Gills
into Adjoining
Room - Option 2
12”
Figure 2
WARNING: Rework worksheet, adding the space
of the adjoining unconned space. The combined
space must have enough fresh air to supply all appliance in both spaces.
VENTILATION AIR
OUTLET AIR
OUTLET
AIR
INLET
AIR
VENTILATION CRAWL SPACE
VENTILATED
ATTIC
TO CRAWL
SPACE
Figure 3.
Ventilation from Outdoors
If necessary provide extra fresh air by using ventilation
grills or ducts. Connect these items directly to the out-
Installation Instructions and Owner’s Manual
4
TO ATTIC
Page 5
doors or spaces open to the outdoors. These include
attics* and crawl spaces. Follow the National Fuel Gas
Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation
grills or ducts.
*IMPORTANT: Do not provide openings for inlet or
outlet into attic. If attic has a thermostat-controlled
power vent, heated air entering the attic will activate
the power vent.
IMPORTANT: Vent-free heaters add moisture to the
air. Although this is benecial, installing heater in
rooms without enough ventilation air may cause mildew to form from too much moisture. See Fresh Air
for Combustion and Ventilation, pages 3 through 5.
INSTALLATION
NOTICE: This heater is intended for the use as supple-
mental heat. Use this heater along with your primary
heating system. Do not install this heater as your
primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout
the house. In the event of a power outage, you can use
this heater as your primary heat source for the duration
of the outage.
WARNING: A qualied service person must install
heater. Follow all local codes.
CHECK GAS TYPE
Use only LP-gas. If your gas supply is not LP-gas, do
not install heater. Call dealer where you bought heater
for proper type heater.
•Where there is easy access for operation,
inspection, and service.
•In the coldest part of the room.
CAUTION: If you install the heater in a home garage:
• Heater pilot and burner must be at least 18
inches above oor .
• Locate heater where moving vehicle will not hit it.
CAUTION: This heater creates warm air currents. These
currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall covering or operating heater where impurities (such as tobacco smoke,
aromatic candles, cleaning uids, oil or kerosene lamps,
etc.) are present in the air may discolor walls.
WARNING: Never install the heater:
• In a bathroom.
• In a bedroom
• In a recreational vehicle .
•Where curtains, furniture, clothing, or other
ammable objects are less than 36 inches from
the front, top, or sides of the heater.
• As a replace insert
• In high-trafc areas
• In windy or drafty areas
WARNING: Heater must be mounted to maintain
the minimum clearances shown in Figure 4. If possible, provide greater clearances from the oor, ceiling, and joining walls.
FOR PERMANENT INSTALLATION:
Before installing heater, make sure you have the items
listed below:
•Piping (check local codes)
•Sealant (resistant to LP_Gas)
•Equipment shutoff valve*
•Ground joint union
•Test gauge connection*
•Sediment trap
•Tee joint
•Pipe wrench
*A CSA/AGA certied equipment shutoff valve with
1/8” NPT tap is an acceptable alternative to test gauge
connection. Purchase a CSA/AGA certied equipment
shutoff valve from your dealer. See Accessories, page
17.
This heater may also be installed with the hose and
regulator assembly included with heater.
LOCATING HEATER
This heater is designed to be mounted on the wall.
For convenience and efciency, install the heater:
36” min. from
6” Min from
adjoining
walls
Left
Side
Floor
2” min. to top surface of carpet, tile
or other combustible material
ceiling
Right
Side
Figure 4
FASTENING HEATER TO WALL
Mounting Bracket
The mounting bracket in located on the back panel of
heater (see gure 5). It has been taped there for ship-
Unvented LP-Gas Fired Buddy Wall-Mount Heater
Installation Instructions and Owner’s Manual
5
Page 6
ping. Remove mounting bracket from back panel.
Mounting
Bracket
Figure 5
Removing Front Panel of Heater
1. Remove three screws on bottom front of front
panel.
2. Pull bottom of front panel forward, then down
(see gure 6)
Figure 6
Attaching Mounting Bracket to Wall
Use holes on each end of mounting bracket to attach
bracket to wall. These holes are 16 inches apart. Attach mounting bracket to wall in one of two following
ways.
1. Attach to wall studs
2. Attach to wall anchor
Attaching to Wall Stud:
This way is the best providing the strongest mounting in
wood frame houses.
Attaching to Wall Anchor:
This way allows you to attach mounting bracket to hollow walls (wall areas between studs) or to solid walls
(concrete or masonry).
Decide which way best suits your needs. Either method
will provide a secure hold for the mounting bracket.
1. Tape mounting bracket to wall where heater
will be located. Make sure mounting bracket is
level. For wall stud mounting locate one end of
the mounting bracket over a wall stud.
WARNING: Maintain minimum clearances
shown in gure 7. If you can, provide greater
clearances from the oor and joining wall.
2. Mark screw locations on wall (see gure 7).
3. Remove tape and mount bracket from wall.
6-1/2” Min. 10,000 BTU
12-9/64” (Sm)
17-1/2” Min.
Adjoining Wall
Mark mounting hole locations
and drill holes where indicated.
Allow for minimum clearances
Figure 7
Attaching to Wall Stud:
For attaching mounting bracket to wall studs
1. Drill holes at marked locations using 9/64” drill bit.
2. Place mounting bracket onto wall. Line up
holes on each end of bracket with hole drilled in
wall.
3. Insert mounting screws through bracket and
into wall studs.
4. Tighten screws until mounting bracket is rmly
fastened to wall studs.
Attaching to Wall using Anchor:
For attaching mounting bracket to hollow walls (wall areas between studs) or solid walls (concrete or masonry)
Note: Wall anchors, mounting screws, and spacer
are in hardware package. The hardware package
is provided with heater.
1. Drill holes at marked locations using 5/16” drill
bit. For solid walls (concrete or masonry), drill
at least 1” deep.
2. Fold wall anchor as shown in gure 8 below.
Figure 8.
3. Insert wall anchor (wings rst) into hole. Tap
anchor ush to wall.
4. For thin walls (1/2” or less) insert red key into
wall anchor.
5. Place mounting bracket onto wall. Line up
holes on each end of bracket with wall anchors.
6. Insert mounting screws through bracket and
into wall anchors.
7. Tighten screws until mounting bracket is rmly
fastened to wall.
Unvented LP-Gas Fired Buddy Wall-Mount Heater
Installation Instructions and Owner’s Manual
6
Page 7
Placing Heater on Mounting Bracket
1. Locate two horizontal slots on back pane of
heater (see gure 19).
2. Place heater onto mounting bracket. Slide horizontal slots onto stand-out tabs on mounting
bracket.
Horizontal Slots
Mounting Bracket
mounted to wall
Mounting Screws
Figure 9
Installing Bottom Mounting Screws
1. Locate two bottom mounting screw holes.
These holes are near bottom on back panel of
heater (see gure 9).
2. Mark screws locations on wall.
3. Remove heater from mounting bracket.
4. If installing bottom mounting screw into hollow or solid wall, install wall anchors. Follow
steps 1 through 4 under Attaching to Wall using
Anchor. If installing bottom mounting screw into
wall stud, drill holes at marked locations using
9/64” drill bit.
5. Re-place heater onto mounting bracket.
6. Place spacers between bottom mounting holes
and wall anchor or drilled hole.
7. Hold spacer in place with one hand. With the
other hand, insert mounting screw through
bottom mounting hole and spacer. Place tip of
screw in opening of wall anchor or drilled hole.
8. Tighten both screws until heater is rmly secured to wall. Do not over tighten.
Note: Do not re-place front panel at this time. Replace front panel after making gas connections and
checking for leaks.
CONNECTING TO GAS SUPPLY FOR
PERMANENT INSTALLATION
WARNING: A qualied service person must con-
nect heater to gas supply. Follow all local codes.
WARNING: This appliance requires a 3/8” NPT
(National Pipe Thread) inlet connection to the pressure regulator.
CAUTION: Never connect heater directly to the Propane
supply. This heater requires an external regulator (not
supplied). Install the external regulator between the
heater and Propane/LP supply.
The installer must supply an external regulator. The external regulator will reduce the incoming gas pressure
to between 11 and 14 inches of water. If you do not
reduce incoming gas pressure heater regulator damage could occur. Install external regulator with the vent
pointing down as shown in Figure 12. Pointing the vent
down protects it from freezing rain or sleet.
CAUTION: Use only new black iron or steel pipe.
Internally-tinned copper tubing may be used in certain
areas. Check your local codes. Use pipe of larger
enough diameter to allow proper gas volume to heater.
If pipe is too small, undue loss of pressure will occur.
Installation must include an equipment shutoff valve,
union and plugged 1/8” NPT tap. Locate NPT tap within
reach of test gauge hookup. NPT tap must be upstream from heater (see gure 12).
Pressure
Regulator
3/8” NPT Pipe Nipple
Ground Joint Union
Equipment
Shutoff Valve
From Gas Meter
(4” W.C. to 10.5”
W.C. Pressure)
Tee Joint
Tee Joint
Pipe Nipple
Cap
3” Minimum
Heater
Cabinet
Test Gauge
Connection
Reducer Bushing
to 1/8” NPT
1/8” NPT Plug Tap
Sediment
Trap
Figure 12
*A CSA/AGA certied equipment shutoff valve with 1/8”
NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA/AGA certied equipment
shutoff valve from your dealer. See Accessories, page 17.
IMPORTANT: Install an equipment shutoff valve in an
accessible location. The equipment shutoff valve is for
turning on or shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male threads. This will
prevent excess sealant from going into pipe. Excess
sealant in pipe could result in clogged heater fuel train.
CAUTION: Use pipe joint sealant that is resistant to
LP-Gas.
Install sediment trap in supply line as shown in gure
12. Locate sediment trap where it is within reach for
Unvented LP-Gas Fired Buddy Wall-Mount Heater
Installation Instructions and Owner’s Manual
7
Page 8
cleaning. A sediment trap traps moisture and contaminants. This keeps them from going into heater. If
sediment trap is not installed or is installed improperly,
heater may not run correctly.
IMPORTANT: Hold pressure regulator with wrench
when connecting it to gas piping and/or ttings.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping and connections for
leaks after installing or servicing. Correct all leaks
at once.
WARNING: Never use an open ame to check for
a gas leak. Apply a mixture of liquid soap and water
to all joints. Bubbles forming show a leak. Correct
all leaks at once.
PRESSURE TESTING GAS SUPPLY PIPING
SYSTEM
Test pressure in Excess of ½ psig (3.5kPa)
1. Disconnect appliance with its appliance main
gas valve (control valve) and equipment shutoff
valve from gas supply piping system. Pressures in excess of ½ psig will damage heater
regulator.
2. Cap off open end of gas pipe where equipment
shutoff valve was connected.
3. Pressurize supply piping system by either using
compressed air or opening main gas valve on
or near gas meter.
4. Check all connections and joints in gas supply
piping system. Apply mixture of liquid soap and
water to gas joints. Bubbles forming show a
leak.
5. Correct all leaks at once.
6. Depressurize and relieve pressure in supply
piping system.
7. Reconnect heater and equipment shutoff valve
to gas supply.
8. Reconnected ttings must be checked for leaks
in next section.
Test Pressure Equal To or Less Than ½ psig
(3.5 kPa)
1. Close equipment shutoff valve (see gure 13).
2. Pressurize supply piping system by either using
compressed air or opening propane/LP supply
valve.
3. Check all joints from the propane/LP supply
valve to equipment shutoff valve (see gure
14). Apply mixture of liquid soap and water to
gas joints. Bubbles forming show a leak.
4. Correct all leaks at once.
5. Depressurize and relieve pressure from supply
piping system.
LIGHTING / OPerATING INSTrucTIONS FOr
uSe wITH HOSe cONNecTed TO A reMOTe
cYLINder, MAXIMuM SIZe 20 LBS:
• This Heater may be used in a Recreational Enclosure or
Temporary Construction Work Enclosure with a Remote
Refillable Propane Cylinder ONLY when the Cylinder
is Located Outdoors and the Heater is Used with Mr.
Heater Hose assembly supplied.
• dANGer: NEVER bring a refillable propane cylinder
indoors. A fire or explosion can occur causing property
damage, serious injury or death!
• Inspect the hose before each use of the heater. If there
is excessive abrasion or wear, or the hose is cut, replace
prior to using the heater with one of the Mr. Heater
Hose assembly supplied (see parts list).
• The propane cylinder must include a listed overfilling
protection device as well as a collar to protect the cylinder valve.
• Heater must be in an upright position during operation.
• Make sure five-position Control Knob is in “OFF” posi-
tion.
• Screw hose connector into regulator on heater and
screw connector on other end of hose into a regulated
LP-gas supply cylinder valve. Tighten all hose connections.
• Open valve at LP-gas supply cylinder.
• Check all hose connections for leaks with soapy water
at the threaded connection on heater where the hose
connector screws into the regulator and at LP-gas supply
cylinder.
Pressure Testing Heater Gas Connections:
1. Make sure that the heater supply piping system is connected and has been leak tested as
described above.
2. Make sure control knob of heater is in OFF
position.
3. Open equipment shutoff valve (see gure 13).
4. Open propane/LP supply valve.
5. Check all joints from equipment shutoff valve
to control valve (see gure 14). Apply mixture
of liquid soap and water to gas joints. Bubbles
forming show a leak.
6. Correct all leaks at once.
7. Light heater (see Operating Your Heater, pages
11 and 12 for thermostat models or pages 9
and 10 for non-thermostat models). Check the
rest of the internal joints for leaks.
8. Turn off heater (see To Turn OFF Gas to Appli-ance, page 12 for thermostat models and page
11 for non-thermostat models).
9. Replace lower front panel.
Unvented LP-Gas Fired Buddy Wall-Mount Heater
Installation Instructions and Owner’s Manual
8
Page 9
Open
Equipment
Shutoff Valve
Closed
Figure 13
Control Valve
Gas Meter
Equipment
Shutoff Valve
Figure 14
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions
exactly, a re or explosion may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot that must be lighted
by hand. When lighting the pilot, follow these
instructions exactly.
B. BEFORE LIGHTING smell all around the appli-
ance area for gas. Be sure to smell next to the
oor because some gas is heavier than air and
will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use
any phone in your building.
•Immediately call you gas supplier from a neigh-
bor’s phone. Follow the gas supplier’s instructions.
•If you can not reach your gas supplier, call the
re department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. It knob will not
push in or turn by hand, don’t try to repair it; call
a qualied service technician or gas supplier.
Force or attempted repair may result in a re or
explosion.
D. Do not use this appliance if any part has been
underwater. Immediately call a qualied service technician to inspect the appliance and to
replace any part of the control system which
has been underwater.
LIGHTING INSTRUCTIONS
1. STOP! Read the all safety information included
with and on the side of heater.
2. Check that gas supply to heater is on.
3. Push in gas control knob and slightly turn clock-
wise to the OFF position (see gure 16).
Note: Knob cannot be turned from PILOT to OFF
unless knob is pushed in slightly. Do not force.
4. Wait ve (5) minutes. Then smell for gas, in-
cluding near the oor. If you smell gas, STOP!
Follow “B” in the safety information above. If
you do not smell gas, go to the next step.
5. Push in gas control know slightly and turn
counterclockwise to PILOT/IGN and depress
for ve (5) seconds.
Note: The rst time that the heater is operated after
connecting the gas supply, the control knob should
be depressed for about 30 seconds. This will allow
air to bleed from the gas system.
6. Push in control knob and rotate control knob
back to OFF position then rotate counterclockwise to PILOT/IGN position. This will light pilot.
If needed gently keep rotating control knob
back and forth while depressed until pilot lights.
7. Keep control knob depressed in for ten (10)
seconds after lighting pilot. If pilot goes out,
repeat steps 4, 5, 6 and 7.
• If pilot does not stay lit, refer to Troubleshoot-
ing, pages 14 & 15. Also, contact a qualied
service person or gas supplier for repairs.
•If control knob does not pop up when released,
contact a qualied service person or gas supplier for repairs.
•When the pilot is lit, turn the control knob to “HI”
position to light heater.
•After ame is established (see Burner Flame
Pattern, Pages 12 and 13) on “HI”, adjust
heat output by turning control knob to desired
position (“LO” or “HI”). Do not operate heater
between locked positions.
Unvented LP-Gas Fired Buddy Wall-Mount Heater
Installation Instructions and Owner’s Manual
9
Page 10
Control Knob
Figure 16
PILOT FLAME PATTERN
Figure 21 show a correct pilot ame pattern. Figure 22
shows an incorrect pilot ame pattern. The incorrect
pilot ame pattern is not touching thermocouple. This
will cause the thermocouple to cool. When the thermocouple cools, the heater will shut down. If pilot ame
pattern is incorrect, as shown in Figure 22:
•Turn heater off (see To Turn OFF Gas to Appli-
ance, page 11 for non-thermostat models).
•See Troubleshooting, pages 14 and 15.
Figure 22
BURNER FLAME PATTERN
Figure 23 show a correct burner ame pattern. Figure
24 shows an incorrect burner ame pattern. If burner
ame pattern is incorrect, as shown in Figure 24:
Figure 17
CAUTION: Do not try to adjust heating level by using
equipment shutoff valve.
WARNING: When running heater, set control knob
at “LO” or “HI” locked positions. Poor combustion
and higher levels of carbon monoxide may result
if heater is operated with control knob positioned
between locked positions.
IMPORTANT: Release downward pressure while turning control knob. Control knob must be locked at the
desired position.
TO TURN OFF GAS TO APPLIANCE
SHUTTING OFF HEATER:
1. Turn control knob clockwise to the OFF position.
2. Turn off equipment shutoff valve.
SHUTTING OFF BURNER ONLY (PILOT STAYS LIT)
1. Turn control knob clockwise to the PILOT/IGN
position.
INSPECTING BURNER
Check pilot ame pattern and burner ame pattern
often.
•Turn heater off (see To Turn OFF Gas to Appli-
ance, page 11 for non-thermostat models).
•See Troubleshooting, pages 14 and 15.
1/2 Steel Panel
Height
Figure 23
1/2 Steel Panel
Height
Figure 24
CLEANING AND MAINTENANCE
WARNING: Turn off heater and let cool before
servicing.
CAUTION: You must keep control areas, burner and
circulation air passageways of heater clean. Inspect
these areas of heater before use. Have the heater
inspected yearly by a qualied service person. Heater
may need more frequent cleaning due to excess lent
from carpeting, bedding material, pet hair, etc.
Unvented LP-Gas Fired Buddy Wall-Mount Heater
Installation Instructions and Owner’s Manual
10
Page 11
Make sure grille guard is in place before running
heater. If screen or grille guard is removed for servicing it must be replaced prior to operating the heater.
WARNING: Failure to keep the primary air
opening(s) of the burner(s) clean may result in sooting and property damage.
CLEANING ODS/PILOT AND BURNER
•Use as vacuum cleaner, pressurized air or
small soft bristled brush to clean.
CLEANING BURNER PILOT AIR HOLE INLET
We recommend that you clean the unit ever 2,500
hours of operation or every three months. We also
recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these
parts we recommend using compressed air no greater
than 30 psig.
This can be done by using a vacuum cleaner in the
blow position, using compressed air in a can, please
follow the directions on the can. If you don’t follow
directions on the can you could damage the burner or
pilot assembly. In addition, the directions that follow
should also be followed.
1. Shut off the unit, including the pilot. Allow the
unit to cool for at least thirty minutes.
2. Inspect burner and pilot for dust and dirt.
3. Blow air through the port/slots and holes in the
burner.
A yellow tip on the pilot ame indicates dust and dirt
in the pilot assembly. To clean the pilot assembly nd
the small pilot air inlet hole about two inches from
where the pilot ame comes out of the pilot assembly
(see Pilot Air Inlet Hole in gure 25). With the unit off,
lightly blow air through the air inlet hole. You may blow
through a drinking straw if compressed air is not available.
CLEANING HEATER CABINET
Air passageways
•Use a vacuum cleaner or pressurized air to
clean exterior
•Use a soft cloth dampened with a mild soap
and water mixture. Wipe the cabinet to remove
dust.
SPECIFICATIONS
MHVFB10LP
BTU (Available) 10,000
Type of Gas LP-Gas Only
Ignition Piezo
Pressure Regulator Setting 10 Inches of
Water
Inlet Gas Pressure (Maximum) 14 Inches of
Water
Inlet Gas Pressure (Minimum) 11 Inches of
Water
Burners / Orice nozzles 1
Thermostatic Control No
Clearances: inches (mm)
Top 36” (915cm)
Sides 6” (152cm)
Floor (min. to top of carpet) 2” (51cm)
Figure 25
Unvented LP-Gas Fired Buddy Wall-Mount Heater
Fabric / ammable objects 36” (915cm)
Installation Instructions and Owner’s Manual
11
Page 12
TROUBLESHOOTING
NOTE: All troubleshooting items are listed in order of operation and likely occurrence.
WARNING: Only a qualied service person should service and repair heater.
CAUTION: Never use a wire needle, or similar object to clean ODS/pilot. This can damage ODS/pilot unit.
Make sure grille guard is in place before running heater. If screen or grille guard is removed for servicing it must be
replaced prior to operating the heater.
OBSERVED SYMPTOM POSSIBLE CAUSE REMEDY
When Piezo ignitor knob is
turned, there is no spark at pilot
1. Ignitor electrode positioned wrong.
2. Ignitor electrode is broken.
3. Ignitor electrode not connected to ignitor.
4. Ignitor cable pinched or wet.
5. Broken ignitor cable.
6. Bad Piezo ignitor.
1. Reposition electrode
2. Replace electrode
3. Reconnect ignitor cable
4. Free ignitor cable if pinched by any metal
or tubing. Keep ignitor cable dry.
5. Replace ignitor cable
6. Replace control valve (Piezo is part of
control valve on 10K units).
ODS/pilot lights but ame
goes out when control knob is
released
When Piezo ignitor knob is
turned, there is a spark at the
ODS/pilot but no ignition
Burner does not light after
ODS/pilot is lit
Delayed ignition of burner
1. Gas supply turned off or equipment shutoff valve closed.
2. Air in gas line when installed.
3. ODS/pilot is clogged.
4. Gas regulator setting is not correct
5. Control knob not in pilot position
1. Control knob not fully pressed in.
2. Control knob not pressed in long enough
3. Equipment shutoff valve not fully open
4. Thermocouple connection loose at con-
trol valve
5. Pilot ame not touching thermocouple,
which allows thermocouple to cool, causing pilot ame to go out. This problem
could be caused by one or both of the
following:
a. Low gas pressure
b. Dirty or partially clogged ODS/pilot
6. Thermocouple damaged
7. Control valve damaged
1. Burner orice is clogged
2. Burner orice diameter to small
3. Inlet gas pressure is too low
1. Manifold pressure is too low
2. Burner orice is clogged
1. Turn on gas supply or open equipment
shutoff valve.
2. Continue holding down control knob. Repeat ignition operation until air is removed.
3. Clean ODS/pilot (see Cleaning and Maintenance page 13).
4. Replace gas regulator
5. Turn Control knob to pilot position
1. Press in control knob fully
2. After ODS/pilot lights, keep control knob
pressed in for 30 seconds
3. Fully open equipment shutoff valve
4. Hand tighten thermocouple nut until snug,
and then tighten 1/4 turn more.
5. -
a. Contact local gas company
b. Clean ODS/pilot (see Cleaning and
Maintenance, page 13).
6. Replace thermocouple
7. Replace Control valve.
1. Clean burner orice (see Cleaning and
Maintenance on page 13), or replace
burner orice
2. Replace burner orice
3. Contact local gas company
1. Contact local gas company
2. Clean burner orice (see Cleaning and
Maintenance on page 13), or replace
burner orice
Unvented LP-Gas Fired Buddy Wall-Mount Heater
Installation Instructions and Owner’s Manual
12
Page 13
TROUBLESHOOTING CON’T
OBSERVED SYMPTOM POSSIBLE CAUSE REMEDY
Burner backring during opera-
tion
Slight smoke or odor during
initial operation
Heater produces a whistling
noise when burner is lit
White powder residue forming
within burner box or on adja-
cent walls or furniture
1. Burner orice is clogged or damaged
2. Burner damaged
3. Gas regulator defective
1. Residues from manufacturing process
1. Turning control knob to HI position when
burner is cold
2. Air in gas line
3. Air passageways on heater blocked
4. Dirty or partially clogged burner orice.
1. When heated, vapors from furniture polish,
wax, carpet cleaners, etc., turn into white
powder residue
1. Clean burner orice (see Cleaning and
Maintenance on page 13), or replace
burner orice
2. Replace burner
3. Replace gas regulator
1. Problem will stop after a few hours of
operation
1. Turn control knob to LO position and let
warm up for a minute.
2. Operate burner until air is removed from
line have gas line checked by local gas
company.
3. Observe minimum installation clearances
(see Figure 4 page6)
4. Clean burner orice (see Cleaning and
Maintenance on page 13), or replace
burner orice.
1. Turn heater off when using furniture
polish, wax, carpet cleaner or similar
products.
TROUBLESHOOTING
WARNING: If you smell gas:
•Shut off gas supply
•Do not try to light any appliance
•Do not touch any electrical switch; do not use any phone in your building
•Immediately call you gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
•If you cannot reach your gas supplier, call the re department.
IMPORTANT: Operating heater where impurities in air exist may create odors. Cleaning supplies, paint, paint remover,
cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air
and create odors and possible discoloration of walls and ceilings.
OBSERVED SYMPTOM POSSIBLE CAUSE REMEDY
Heater produces unwanted
odors.
Heater shuts off in use (ODS
operates)
Gas odor even when control
knob is in OFF position
Gas odor during combustion
Heater produces a clicking/ticking noise just after burner is lit
or shut off
Moisture/condensation noticed
on windows
Unvented LP-Gas Fired Buddy Wall-Mount Heater
1. Heater burning vapors from paint, hair
spray, glues, etc. See IMPORTANT statement above
2. Gas leak. See WARNING statement at top
of page.
1. Not enough fresh air is available
2. Low line pressure
3. ODS/pilot is partially clogged
1. Gas leak. See WARNING statement at top
of page
2. Control valve is defective
1. Foreign matter between control valve and
burner
2. Gas leak. See WARNING statement at top
of page
1. Metal expanding while heating or contracting while cooling
1. Not enough combustion/ventilation air
Installation Instructions and Owner’s Manual
13
1. Ventilate room. Stop using odor-causing
products while heater is running.
2. Locate and correct all leaks (see Checking
Gas Connections, page 8)
1. Open window and/or door for ventilation
2. Contact local gas company
3. Clean ODS/pilot (see Cleaning and Maintenance, page 11)
1. Locate and correct all leaks (see Checking
Gas Connections, page 8)
2. Replace control valve
1. Take apart gas tubing and remove foreign
matter
2. Locate and correct all leaks (see Checking
Gas Connections, page 8)
1. This is common with most heaters. If noise
is excessive, contact qualied service
person
1. Refer to Fresh Air for Combustion and
Ventilation page 3 through 5.
Page 14
REPLACEMENT PARTS
Note: use only original replacement parts. This will
protect you warranty coverage for parts replaced
under warranty.
TECHNICAL SERVICE
You may have further questions about installation,
operation, or troubleshooting, if so, contact Enerco
Group, Inc.’s 800# on the back of this manual.
PARTS UNDER WARRANTY
Contact authorized dealer from whom you purchased this product. If they are unable to supply
original replacement part(s), call the number on
back of manual. When contacting your dealer have
ready:
•Your name
•Your address
•Model and serial numbers of your heater
•How heater was malfunctioning
•Type of gas used (propane/LP)
•Purchase date
Usually, we will ask you to return the defective part
to the factory.
PARTS NOT UNDER WARRANTY
Contact authorized dealer of this product. If they
can’t supply original replacement part(s), call Enerco Group, Inc.’s 800# on the back of this manual.
ACCESSORIES
Purchase these heater accessories from your local
dealer. If they can not supply these accessories,
contact your nearest Parts Central or call Enerco
Group, Inc.’s 800# for information. You can also
write to the address listed on the front page of this
manual.
Equipment Shutoff Valve
For all models, Equipment shutoff valve with 1/8”
NPT tap.
PARTS LIST
Non-Thermostat model
MHVFB10LP
This list contains replacement parts used in your
heater. When ordering parts, follow the instructions
listed under Replacement Parts on page 17 of this
manual.
Unvented LP-Gas Fired Buddy Wall-Mount Heater
Installation Instructions and Owner’s Manual
14
Page 15
Unvented LP-Gas Fired Buddy Wall-Mount Heater
Installation Instructions and Owner’s Manual
15
Page 16
WARRANTY INFORMATION
Keep this warranty
Model ______________________
Serial No. ___________________
Date Purchased _______________
Always specify model and serial numbers when communication with the factory.
We reserve the right to amend these specications at any time without notice. The only warranty applicable is our standard written warranty. We make no other warranty, expressed or implied.
Enerco Group, Inc. warrants this product to be free from defects in materials and components for two (2)
years from the date of rst purchase, provided that the product has been properly installed, operated and
maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of
Sale or cancelled check must be presented.
The warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s)
required to restore the heater to proper operating condition and an allowance for labor when provided by
an Enerco Group, Inc. Authorized Service Center. Warranty part(s) MUST be obtained through authorized
dealers of this product and/or Enerco Group, Inc. who will provide original factory replacement parts. Failure to use original factory parts voids this warranty. The heater MUST be installed by a qualied installer in
accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear of
parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects
caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such costs
related to repairing a defective heater will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE
OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED
WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, TO TWO (2) YEARS OF ALL COMPONENTS FROM THE FIRST DATE OF PURCHASE; AND ENERCO GROUP, INC.’S LIABILITY IS HEREBY
LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND ENERCO GROUP, INC. SHALL NOT BE
LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation on
incidental or consequential damages, so the above limitation on implied warranties, or limitation on damages, may not apply to you.
This warranty gives you specic legal rights, and you may also have other rights that very from state to
state. Always specify model and serial number when communication with the factory.
ENERCO GROUP, INC., 4560 W. 160TH ST., CLEVELAND, OHIO 44135
216-881-5500 Toll Free Number 1-800-251-0001
www.mrheater.com