Mr. Heater TSIR10LP, TSBF30LPT, MHIR20LPT, TSIR20LPT, MHBF30LPT Installation Instructions And Owner's Manual

...
INSTALLATION INSTRUCTIONS AND OWNER’S MANUAL
READ INSTRUCTIONS CAREFULLY: Read and follow all instructions. Place instructions in a
safe place for future reference. Do not allow anyone who has not read these instructions to assemble, light, adjust or operate the heater.
UNVENTED LP-GAS FIRED ROOM HEATER
Blue Flame Heaters Plaque Heaters
Model # Burn Rate Model # Burn Rate MHBF10LP/TSBF10LP 10,000 Btu/hr MHIR10LP/TSIR10LP 10,000 Btu/hr MHBF20LPT/TSBF20LPT 20,000 Btu/hr MHIR20LPT/TSIR20LPT 20,000 Btu/hr MHBF30LPT/TSBF30LPT 30,000 Btu/hr MHIR30LPT/TSIR30LPT 30,000 Btu/hr
MHBF20LPT/
MHBF30LPT/ TSBF30LPT
MHIR30LPT/ TSIR30LPT
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing
property damage, personal injury , or loss of life.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
TSBF20LPT
MHIR20LPT/ TSIR20LPT
MHBF10LP/ TSBF10LP
MHIR10LP/ TSIR10LP
Do not try to light any appliance
Do not touch an electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire dep artment.
- Installation and service must be performed by a qualified installer, service agency, or the gas supplier. WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed.
Provisions for adequate combustion and ventilation air must be provided. Refer to Fresh Air for Combustion and V entilation section on page 3 of this manual.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer , service agency, or gas supplier.
ENERCO GROUP, INC., 4560 W. 160TH ST., CLEVELAND, OHIO 44135 · 216-916-3000
Installation instructions and Owners Manual
1
70575 Rev. C 08/05
This appliance may be installed in an aftermarket* permanently manufactured (mobile) home, where not prohibited by local codes.This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with any other gas.
*Aftermarket completion of sale, not for the purpose of resale, from the manufacturer .
WARNINGS
IMPORTANT: Read this owner’s manual carefully
and completely before trying to assembly , operate, or service this heater. Improper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
WARNING: Do not use any accessory not ap­proved for use with this heater.
WARNING: Any change to this heater or its controls can be dangerous.
Do not place clothing or other flammable
material on or near the appliance. Never place any objects on the heater.
Due to high temperatures, heater should be
kept out of traffic and away from furniture and draperies.
Surface of heater becomes very hot when
running. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Heater will remain hot for a time after shut­down. Allow heater surfaces to cool before handling.
Y oung children should be carefully supervised
when they are in the same room with heater.
Make sure grille guard is in place before
running heater. If screen or grille guard is removed for servicing it must be replaced prior to operating the heater.
Keep the appliance area clear and free from
combustible materials, gasoline, and other flammable vapors and liquids.
PRECAUTIONS:
1. MHBF-10 LP and MHIR-10LP may be installed in a bedroom, but not a bathroom, or any place where a strong wind would shut down the appliance.
2. MHBF-20 LPT, MHBF-30 LPT, MHIR-20 LPT and MHIR-30 LPT may not be installed in a bedroom or bathroom, or any place where a strong wind would shut down the appliance.
3. This heater needs outside ventilation air to run properly . The Oxygen Depletion Sensor (ODS) safety shutoff system shuts down the heater if not enough fresh air is available. See Fresh Air for Combustion and Ventilation, page 3.
4. Keep all air openings in heater clear, free of debris or any blockage. This will insure that enough air for proper combustion enters the heater.
5. If heater shuts off, do not relight until you provide fresh, outside air. If heater keeps shutting off, it requires servicing.
6. Turn of f and unplug heater and let cool before servicing. Only a qualified service person should service and repair heater .
7. Do not run heater:
Where flammable liquids or vapors are used or
stored
During dusty conditions.
8. Before using furniture polish, wax, carpet cleaner or similar products, turn heater off. If heated the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
9. Do not use heater if any part has been underwater . Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been underwater.
10.Operating heater above elevations of 4,500 feet could cause pilot/ODS to shutdown heater .
1 1.Always run heater with control knob in a locked
position. Never set control knob between locked positions. Poor combustion and higher levels of carbon monoxide may result if control knob is left between locked positions.
DANGER: Carbon monoxide poisoning may lead to death.
Carbon Monoxide Poisoning:
Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly . Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, persons with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Propane/LP Gas:
Propoane/LP gas is odorless. An odor making agent is added to propane/LP gas. The odor help s you detect a Propane/LP gas leak. However the odor added to propane/LP gas may be present even though no odor exists. Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
2 Installation instructions and Owner’s Manual
70575 Rev. C 8/05
Product Features
Ignitor Button
Burners
Control Knob
FRESH AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be inst alled in a
confined space or unusually tight construction unless provisions are provided for adequate com­bustion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
Grill
Heater Cabinet
Front Panel
Figure 1
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensor (ODS) safety shut off system. The ODS/pilot shuts of f the heater if there is not enough fresh air.
IGNITION SYSTEM
PIEZO: BF10LP/ IR10LP – The heater is equipped with
a piezo manual ignitor. This system requires no matches, batteries, or other source to light heater.
Electronic: BF20LPT/BF30LPT/IR20LPT/IR30LPT – The heater is equipped with an electronic manual ignitor. This system requires no matches, or other source to light heater, but does require one AA battery to operate ignitor.
To install or replace battery unscrew the ignitor cap (red button), insert battery and replace cap.
THERMOST ATIC CONTROL ON THERMOST AT MODELS
(BF20LPT, BF30LPT, IR20LPT and IR30LPT)
These heaters have a control valve with a thermostat sensing bulb. This results in the greatest heater comfort and may result in lower bills.
LOCAL CODES
Install and use heater with care. Installation must conform to local codes or in the
absences of local codes, use the latest edition of National Fuel Gas Code ANSI Z223.1/NFPA 54.
UNPACKING
1. Remove heater from carton.
2. Remove all protective packaging applied to heater for shipment.
3. Check heater for any shipping damage. If heater is damaged, promptly inform dealer where you bought heater.
ESTABLISHING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, NFP A 54/ ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation. All sp aces in homes fall
into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
This heater must not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air. The information on pages 3 through 5 will help you classify your space and provide adequate ventilation.
Unusually Tight Construction
If your home meets all of the three following criteria you must provide additional fresh air. See V entilation Air from Outdoors, page 5.
Unusually tight construction is defined as construction where:
a. Walls and ceilings exposed to the outside atmo-
sphere have a continuous water vapor retarder with a rating of one perm (6 x 10
-11
kg per pa-sec-m2) or less
with openings gasketed or sealed and
b. Whether stripping has been added on openable
windows and doors, and
c. Caulking or sealants are applied to areas such as
joints around windows and door frames, between wall-ceiling joints, between wall panels, at penetra­tions for plumbing, electrical, and gas lines, and at other openings.
If you home does not meet all of the three criteria above, see Determing the T ype of Heater Location Space, page 4.
Confined Space and Unconfined Space
The National Fuel Gas Code, NFP A 54/ ANSI Z223.1
defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m per kW) of the aggregate input rating of all appliances installed in that space, and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kW) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.
3
Installation instructions and Owner’s Manual
3
*Adjoining rooms are communication only if there are doorless passageways or ventilation grills between them.
DETERMINING THE TYPE OF HEA TER LOCATION SPACE:
Use this method to determine if you have a confined or unconfined space.
Note: the space includes the room in which you install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Find the volume of the space by multiplying room length x width x height.
Example: Space size 18f t (length) x 18ft. (width) x 8ft.
(height) = 2592
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Divide the space volume by 50 cubic feet to deter­mine the maximum Btu/hr the space can support.
Example: 2592 cu.ft. (volume of space) / 50 cu.ft. = 51.8
or 51,800 (maximum Btu/hr the space can support)
WARNING: If the area in which the heater may be operated in smaller that that defined as an uncon­fined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by on the methods described in the
National Fuel Gas Code, NFP A 54/ ANSI Z223.1,
Section 5.3 or applicable local codes.
3. Add the Btu/hr of all the fuel-burning appliances in the space such as, V ent–free heater, Gas water heater, Gas furnace, Vented gas heater, Gas fire­place logs, and Other gas appliances*
*Do not include direct-vent gas appliances. Direct­vent draws combustion air from the outdoors and vents to the outdoors.
Example: Gas water heater 40,000 Btu/hr Vent Free Heater + 20,000 Btu/hr T otal =60,000 Btu/hr
4. Compare the maximum Btu/hr the space can support with the actual amount of Btu/hr used.
Example: 51,800 Btu/hr (maximum Btu/hr the
space can support) 60,000 Btu/hr (Actual amount of Btu/hr
used)
The space in the above example is a confined space because the actual Btu/hr used is more than the maximum Btu/hr the space can support.
Y ou must provide additional fresh air. Your options are as follows:
A. Rework worksheet, and the space of an adjoining
room. If the extra space provides an unconfined space, remove door to adjoining room or add ventila­tion grills between the rooms. See Ventilation Air From Inside Building (Fig. 2)
B. V ent room directly to the outdoors. See Ventilation
Air From Outdoors (Fig. 3).
C.Inst all a lower Btu/hr heater if lower Btu/hr size
makes room unconfined.
If actual Btu/hr used is less than the maximum Btu/ hr the space can support, the space is an uncon­fined space. You will need no additional fresh air ventilation.
VENTILATION AIR Ventilation from Inside Building
This fresh air would come from an adjoining unconfined space. When ventilation to an adjoining unconfined space, you must provide two permanent openings: one within 12” of the ceiling and one within 12” of the floor on the wall connecting the two spaces (see options 1 & 2 of fig. 2). You can also remove door into adjoining room (see option3, fig 2). Follow the National Fuel Gas Code NFP A 54/ ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventila­tion grills or ducts.
12”
Ventilation Gills into Adjoining Room ­Option 1
Or remove door into Adjoining Room ­Option 3
Ventilation Gills into Adjoining Room ­Option 2
12”
Figure 2
WARNING: Rework worksheet, adding the space of the adjoining unconfined space. The combined space must have enough fresh air to supply all appliance in both spaces.
4 Installation instructions and Owner’s Manual
70575 Rev. C 8/05
OUTLET
5
6
6
12345
1
5
12345
12345
1
5
12345
AIR
INLET AIR
OUTLET AIR
234
VENTILA TION AIR
VENTILATED ATTIC
234
234
2345
VENTILA TION CRA WL SPACE
2345
TO ATTIC
TO CRAWL SPACE
Ground joint union
Test gauge connection*
Sediment trap
Tee joint
Pipe wrench
*A CSA/AGA certified equipment shutoff valve with 1/8” NPT tap is an acceptable alternative to test gauge connection. Purchase a CSA/AGA certified equipment shutoff valve from your dealer . See Accessories, page
17.
Figure 3.
Ventilation from Outdoors
If necessary provide extra fresh air by using ventilation grills or ducts. Connect these items directly to the outdoors or spaces open to the outdoors. These include attics* and crawl spaces. Follow the National Fuel Gas Code NFP A 54/ ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
*IMPORTANT: Do not provide openings for inlet or outlet into attic. If attic has a thermostat-controlled power vent, heated air entering the attic will activate the power vent.
IMPORTANT: Vent-free heaters add moisture to the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Fresh Air for Combustion and Ventilation, p ages 3 through
5.
INSTALLATION
NOTICE: This heater is intended for the use as supple-
mental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source for the duration of the outage.
WARNING: A qualified service person must install heater. Follow all local codes.
CHECK GAS TYPE
Use only LP-gas. If your gas supply is not LP-gas, do not install heater . Call dealer where you bought heater for proper type heater.
THIS INST ALLA TION REQUIRES:
Before installing heater , make sure you have the items listed below:
Piping (check local codes)
Sealant (resistant to LP_Gas)
Equipment shutoff valve*
LOCA TING HEATER
This heater is designed to be mounted on the wall. The heater can also be located on a non-combustible floor, away from a wall by using the floor mounting stands included with the heater. If installed on combustible flooring such as carpeting, tile or other combustible material other than wood flooring, the heater must be placed on a wood panel the full width and depth of the appliance.
For convenience and efficiency , install the heater:
Where there is easy access for operation,
inspection, and service.
In the coldest part of the room.
If planning to use fan, locate heater near an
electrical outlet.
CAUTION: If you install the heater in a home garage:
Heater pilot and burner must be at least 18
inches above floor.
Locate heater where moving vehicle will not hit it.
CAUTION: This heater creates warm air currents. These currents move heat to wall surfaces next to heater. In­stalling heater next to vinyl or cloth wall covering or oper­ating heater where impurities (such as tobacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) are present in the air may discolor walls.
WARNING: Never install the heater:
In a bathroom.
In a bedroom (IR20LPT, IR30LPT , BF20LPT or BF30LPT)
In a recreational vehicle.
Where curtains, furniture, clothing, or other
flammable objects are less than 36 inches from the front, top, or sides of the heater.
As a fireplace insert
In high-traf fic areas
In windy or draf ty areas
WARNING: Heater must be mounted to maintain the minimum clearances shown in Figure 4. If possible, provide greater clearances from the floor, ceiling, and joining walls.
Installation instructions and Owner’s Manual
5
36” min.
6” Min from adjoining walls
Left Side
Floor
2” min. to top surface of carpet, tile or other combustible material
from ceiling
Right Side
Figure 4
FASTENING HEATER TO WALL Mounting Bracket
The mounting bracket in located on the back panel of heater (see figure 5). It has been taped there for ship­ping. Remove mounting bracket from back panel.
1. Attach to wall studs
2. Attach to wall anchor
Attaching to Wall Stud:
This way is the best providing the strongest mounting in wood frame houses.
Attaching to Wall Anchor:
This way allows you to attach mounting bracket to hollow walls (wall areas between studs) or to solid walls (concrete or masonry).
Decide which way best suits your needs. Either method will provide a secure hold for the mounting bracket.
1. Tape mounting bracket to wall where heater will be located. Make sure mounting bracket is level. For wall stud mounting locate one end of the mounting bracket over a wall stud.
WARNING: Maintain minimum clearances shown in figure 7. If you can, provide greater clearances from the floor and joining wall.
2. Mark screw locations on wall (see figure 7).
3. Remove tape and mount bracket from wall.
6-1/2” Min. 10,000 BTU 10-1/4” min 20,000-30,000 BTU
Mounting Bracket
Figure 5
Removing Front Panel of Heater
1. Remove three screws on bottom front of front panel.
2. Pull bottom of front panel forward, then down (see figure 6)
Figure 6
Attaching Mounting Bracket to Wall
Use holes on each end of mounting bracket to attach bracket to wall. These holes are 16 inches apart. Attach mounting bracket to wall in one of two following ways.
16” (Lg) 12-9/64” (Sm)
Adjoining Wall
Mark mounting hole locations and drill holes where indicated. Allow for minimum clearances
Figure 7
Attaching to Wall Stud:
For attaching mounting bracket to wall studs
1. Drill holes at marked locations using 9/64” drill bit.
2. Place mounting bracket onto wall. Line up holes on each end of bracket with hole drilled in wall.
3. Insert mounting screws through bracket and into wall studs.
4. Tighten screws until mounting bracket is firmly fastened to wall studs.
Attaching to Wall using Anchor:
For attaching mounting bracket to hollow walls (wall areas between studs) or solid walls (concrete or ma­sonry)
Note: Wall anchors, mounting screws, and spacer are in hardware package. The hardware package is provided with heater.
6 Installation instructions and Owner’s Manual
70575 Rev. C 8/05
17-1/2” Min.
1. Drill holes at marked locations using 5/16” drill bit. For solid walls (concrete or masonry), drill at least 1” deep.
2. Fold wall anchor as shown in figure 8 below.
Figure 8.
3. Insert wall anchor (wings first) into hole. Tap anchor flush to wall.
4. For thin walls (1/2” or less) insert red key into wall anchor.
5. Place mounting bracket onto wall. Line up holes on each end of bracket with wall anchors.
6. Insert mounting screws through bracket and into wall anchors.
7. Tighten screws until mounting bracket is firmly fastened to wall.
Placing Heater on Mounting Bracket
1. Locate two horizontal slots on back pane of heater (see figure 19).
2. Place heater onto mounting bracket. Slide horizontal slots onto stand-out tabs on mounting bracket.
4. If installing bottom mounting screw into hollow or solid wall, install wall anchors. Follow steps 1 through 4 under Att aching to Wall using Anchor . If installing bottom mounting screw into wall stud, drill holes at marked locations using 9/64” drill bit.
5. Re-place heater onto mounting bracket.
6. Place spacers between bottom mounting holes and wall anchor or drilled hole.
7. Hold spacer in place with one hand. With the other hand, insert mounting screw through bottom mounting hole and spacer . Place tip of screw in opening of wall anchor or drilled hole.
8. Tighten both screws until heater is firmly secured to wall. Do not over tighten.
Note: Do not re-place front panel at this time. Re­place front panel after making gas connections and checking for leaks.
FLOOR MOUNTING AWAY FROM W ALL:
Horizontal Slots
Mounting Bracket mounted to wall
Figure 9
Installing Bottom Mounting Screws
1. Locate two bottom mounting holes. These holes are near bottom on back panel of heater (see figure 10).
Figure 10
2. Mark screws locations on wall.
3. Remove heater from mounting bracket.
Figure 11
Installing Support Feet (see figure 11)
1. Lay heater onto table on its back with bottom edge overhanging table edge.
2. Securely attach feet to bottom of heater using 2 – self-tapping screws each.
Note: Feet should have long end going out the front of heater, and the edge coinciding with side of heater. If feet overhang side of the heater, switch leg location.
3. Place heater on non-combustible surface (see Locating Heater above) before proceeding with gas connection. If this will be a permanent location, heater may be locked into position using anchoring holes in mounting feet.
Note: Use of floor mounting feet will require you to use a 3/8 NPT street elbow to make gas connec­tion.
CONNECTING TO GAS SUPPLY
WARNING: A qualified service person must connect
heater to gas supply . Follow all local codes.
Installation instructions and Owner’s Manual
7
WARNING: This appliance requires a 3/8” NPT
(National Pipe Thread) inlet connection to the pressure regulator. Use of floor mounting feet will require you to use a 3/8 NPT street elbow to make gas connection.
CAUTION: Never connect heater directly to the Propane supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and Propane/LP supply .
The installer must supply an external regulator . The external regulator will reduce the incoming gas pressure to between 1 1 and 14 inches of water. If you do not reduce incoming gas pressure heater regulator damage could occur. Inst all external regulator with the vent pointing down as shown in Figure 12. Pointing the vent down protects it from freezing rain or sleet.
CAUTION: Use only new black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of larger enough diameter to allow proper gas volume to heater. If pipe is too small, undue loss of pressure will occur.
Installation must include an equipment shutoff valve, union and plugged 1/8” NPT tap. Locate NPT tap within reach of test gauge hookup. NPT tap must be upstream from heater (see figure 12).
Pressure Regulator
3/8” NPT Pipe Nipple
Ground Joint Union
Equipment Shutoff Valve
From Gas Meter (4” W.C. to 10.5” W.C. Pressure)
Tee Joint
Tee Joint
Pipe Nipple
Cap
3” Minimum
Heater Cabinet
Test Gauge Connection
Reducer Bushing to 1/8” NPT
1/8” NPT Plug Tap
Sediment Trap
Figure 12
*A CSA/AGA certified equipment shutoff valve with 1/8” NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA/AGA certified equip­ment shutoff valve from your dealer . See Accessories, page 17.
IMPORTANT: Install an equipment shutof f valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater fuel train.
CAUTION: Use pipe joint sealant that is resistant to LP-Gas.
Install sediment trap in supply line as shown in figure
12. Locate sediment trap where it is within reach for cleaning. A sediment trap traps moisture and contami­nants. This keeps them from going into heater. If sediment trap is not installed or is installed improperly, heater may not run correctly .
IMPORTANT: Hold pressure regulator with wrench when connecting it to gas piping and/or fittings.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping and connections for
leaks after installing or servicing. Correct all leaks at once.
WARNING: Never use an open flame to check for a gas leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test pressure in Excess of ½ psig (3.5kPa)
1. Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pres­sures in excess of ½ psig will damage heater regulator .
2. Cap off open end of gas pipe where equipment shutoff valve was connected.
3. Pressurize supply piping system by either using compressed air or opening main gas valve on or near gas meter.
4. Check all connections and joints in gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Depressurize and relieve pressure in supply piping system.
7. Reconnect heater and equipment shutoff valve to gas supply .
8. Reconnected fittings must be checked for leaks in next section.
Test Pressure Equal To or Less Than ½ psig (3.5 kPa)
1. Close equipment shutoff valve (see figure 13).
2. Pressurize supply piping system by either using compressed air or opening propne/LP supply valve.
3. Check all joints from the propane/LP supply valve to equipment shutoff valve (see figure 14). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
4. Correct all leaks at once.
5. Depressurize and relieve pressure from supply piping system.
8 Installation instructions and Owner’s Manual
70575 Rev. C 8/05
Pressure Testing Heater Gas Connections:
1. Make sure that the heater supply piping system is connected and has been leak tested as described above.
2. Make sure control knob of heater is in OFF position.
3. Open equipment shutoff valve (see figure 13).
4. Open propane/LP supply valve.
5. Check all joints from equipment shutoff valve to control valve (see figure 14). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
6. Correct all leaks at once.
7. Light heater (see Operating Your Heater, pages 1 1 and 12 for thermost at models or pages 9 and 10 for non-thermostat models). Check the rest of the internal joints for leaks.
8. Turn off heater (see To Turn OFF Gas to Appliance, page 12 for thermostat models and page 11 for non-thermostat models).
9. Replace lower front panel.
Open
Equipment Shutoff Valve
Closed
ELECTRICAL WIRING DIAGRAM:
Figure 15
If any original wiring as supplied with the heater must be replaced, it must be replaced with type AWG 105oC wire or its equivalent except as indicated.
WARNING: Electrical Grounding Instructions: This heater is equipped with a three-prong (grounding) plug for your protection against shock hazard and should be plugged into a properly grounded three­prong receptacle.
Gas Meter
Figure 13
Equipment Shutoff Valve
Figure 14
Control Valve
OPERATING YOUR HEA TER NON-THERMOST A T MODELS
MHIR10LP / MHBF10LP / TSIR10LP / TSBF10LP FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions
exactly , a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot that must be lighted
by hand. When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Immediately call you gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
If you can not reach your gas supplier, call the
fire department.
Installation instructions and Owner’s Manual
9
C. Use only your hand to push in or turn the gas
control knob. Never use tools. It knob will not push in or turn by hand, don’t try to repair it; call a qualified service technician or gas supplier. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any p art has been
underwater. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system which has been underwater.
FOR BF10LP: Af ter flame is est ablished (see Burner Flame Pattern, Page 12) on “HI”, adjust heat output by turning control knob to desired position (“LO” or “HI”). Do not operate heater between locked positions.
Control Knob
LOW
HIGH
LIGHTING INSTRUCTIONS
1. STOP! Read the all safety information included with and on the side of heater.
2. Check that gas supply to heater is on.
3. Push in gas control knob and slightly turn clockwise to the OFF position (see figure 16).
Note: Knob cannot be turned from PILOT to OFF unless knob is pushed in slightly . Do not force.
4. Wait five (5) minutes. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information above. If you do not smell gas, go to the next step.
5. Push in gas control know slightly and turn counterclockwise to PILOT/IGN and depress for five (5) seconds.
Note: The first time that the heater is operated after connecting the gas supply , the control knob should be depressed for about 30 seconds. This will allow air to bleed from the gas system.
6. Push in control knob and rotate control knob back to OFF position then rotate counterclock­wise to PILOT/IGN position. This will light pilot. If needed gently keep rotating control knob back and forth while depressed until pilot lights.
7. Keep control knob depressed in for ten (10) seconds after lighting pilot. If pilot goes out, repeat steps 4, 5, 6 and 7.
If pilot does not st ay lit, refer to T roubleshooting, pages 14 & 15. Also, cont act a qualified service person or gas supplier for repairs.
If control knob does not pop up when released,
contact a qualified service person or gas supplier for repairs.
8. FOR IR10LP: When the pilot is lit, turn the control knob to “LO” position to light heater. Leave on “LO” position until first burner tile has turned bright red.
FOR BF10LP: When the pilot is lit, turn the control knob to “HI” position to light heater.
9. FOR IR10LP: After first burner tile has turned bright red, adjust heat output by turning control knob to desired position (“LO” or “HI”). Do not operate heater between locked positions.
OFF
Figure 16
Figure 17
CAUTION: Do not try to adjust heating level by using equipment shutoff valve.
WARNING: When running heater, set control knob at “LO” or “HI” locked positions. Poor combustion and higher levels of carbon monoxide may result if heater is operated with control knob positioned between locked positions.
Control Knob
LOW
HIGH
OFF
Figure 18.
IMPORTANT: Release downward pressure while turning control knob. Control knob must be locked at the desired position.
10 Installation instructions and Owner’s Manual
70575 Rev. C 8/05
TO TURN OFF GAS TO APPLIANCE
SHUTTING OFF HEATER:
1. Turn control knob clockwise to the OFF posi-
tion.
2. Turn off all electrical power to the appliance if
servicing is to be preformed.
3. Turn off equipment shutof f valve.
SHUTTING OFF BURNER ONL Y (PILOT STAYS LIT)
1. Turn control knob clockwise to the PILOT/IGN
position.
OPERATING YOUR HEATER THERMOST A T MODELS
TSIR20LPT, TSIR30LPT , TSBF20LPT, TSBF30LPT, MHIR20LPT, MHIR30LPT, MHBF20LPT, MHBF30LPT
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions
exactly , a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted
by hand. When lighting the pilot, follow these instructions exactly .
B. BEFORE LIGHTING smell all around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Immediately call you gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
If you can not reach your gas supplier, call the
fire department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If knob will not push in or turn by hand, don’t try to repair it call a qualified service technician or gas supplier. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any p art has been
underwater. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system which has been underwater.
LIGHTING INSTRUCTIONS
1. STOP! Read the all safety information included with and on the side of heater.
2. Make sure the equipment shutoff valve is fully open.
3. Push in gas control knob and slightly turn clockwise to the OFF position (see figure 19).
4. Wait five (5) minutes. Then smell for gas including near the floor. If you smell gas, STOP! Follow “B” in the safety information above. If you do not smell gas, go to the next step.
5. Push in and turn control knob counterclockwise to PILOT/IGN. Press in control knob for five (5) seconds.
Note: The first time that the heater is operated after connecting the gas supply , the control knob should be depressed for about 30 seconds. This will allow air to bleed from the gas system.
Ignitor Button
Control Knob
Figure 19.
6. With control knob pressed in, push down and release the ignition button. This will light pilot. If needed keep pressing igniter button until pilot lights.
7. Keep control knob pressed in for (30) seconds after lighting pilot. Af ter 30 seconds, release control knob.
Figure 20
If pilot does not stay lit, refer to Troubleshooting, pages 14 & 15. Also, cont act a qualified service person of gas supplier for repairs.
If control knob does not pop up when released,
contact a qualified service person or gas supplier for repairs.
Installation instructions and Owner’s Manual
11
8. When the pilot is lit, turn control know counter­clockwise to heating level. The main burner should light.
9. To select the desired heat level, turn the tem­perature setting knob counterclockwise to between 1 & 7.
THERMOST A T CONTROL OPERA TION
FOR IR20LPT / IR30LPT: The thermostatic control
used simply turns on and off the burner . FOR BF20LPT / BF30LPT: The thermostatic control
used modulates the flame size as the temperature gets closer to set point, then it turns off the burner upon reaching temperature.
The burner will cycle back on when room temperature drops below the set temperature. The control knob can be set to any heat level between 1 and 7. Selecting the HI setting will cause the burner to remain on.
Note: The thermostat sensing bulb measures the temperature of air near the heater cabinet. This may not always agree with room temperature (depending on housing construction, insulation location, room size, open air temperature, etc.). Frequent use of your heater will let you determine your own comfort levels.
TO TURN OFF GAS TO APPLIANCE
Shutting Off Heater
1. Turn control knob clockwise to the OFF posi­tion.
2. Turn off all electrical power to the appliance if servicing is to be preformed.
3. Turn off equipment shutof f valve.
SHUTTING OFF BURNER ONL Y (PILOT STAYS LIT)
1. Turn control knob clockwise to the PILOT/IGN position.
Figure 21
Figure 22
BURNER FLAME P ATTERN
Figure 23 show a correct burner flame pattern. Figure 24 shows an incorrect burner flame pattern. If burner flame pattern is incorrect, as shown in Figure 24:
Turn heater off (see To Turn OFF Gas to
Appliance, page 11 for non-thermostat models or page 12 for thermostat models).
See Troubleshooting, p ages 14 and 15.
Figure 23a
INSPECTING BURNER
Check pilot flame pattern and burner flame pattern often.
PILOT FLAME P A TTERN
Figure 21 show a correct pilot flame pattern. Figure 22 shows an incorrect pilot flame pattern. The incorrect pilot flame pattern is not touching thermocouple. This will cause the thermocouple to cool. When the thermo­couple cools, the heater will shut down. If pilot flame pattern is incorrect, as shown in Figure 22:
Turn heater off (see To Turn OFF Gas to
Appliance, page 1 1 for non-thermost at models
or page 12 for thermostat models).
See Troubleshooting, p ages 14 and 15.
Figure 23b
Figure 24a
12 Installation instructions and Owner’s Manual
70575 Rev. C 8/05
Figure 24b
Figure 25
CLEANING AND MAINTENANCE
WARNING: Turn off heater and let cool before
servicing.
CAUTION: You must keep control areas, burner and circulation air passageways of heater clean. Inspect these areas of heater before use. Have the heater inspected yearly by a qualified service person. Heater may need more frequent cleaning due to excess lent from carpeting, bedding material, pet hair, etc.
Make sure grille guard is in place before running heater. If screen or grille guard is removed for servicing it must be replaced prior to operating the heater.
WARNING: Failure to keep the primary air opening(s) of the burner(s) clean may result in sooting and property damage.
CLEANING ODS/PILOT AND BURNER
Use as vacuum cleaner, pressurized air or
small soft bristled brush to clean.
CLEANING BURNER PILOT AIR HOLE INLET
We recommend that you clean the unit ever 2,500 hours of operation or every three months. We also recom­mend that you keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these parts we recommend using compressed air no greater than 30 psig.
This can be done by using a vacuum cleaner in the blow position, using compressed air in a can, please follow the directions on the can. If you don’t follow directions on the can you could damage the burner or pilot assem­bly . In addition, the directions that follow should also be followed.
1. Shut off the unit, including the pilot. Allow the
unit to cool for at least thirty minutes.
2. Inspect burner and pilot for dust and dirt.
3. Blow air through the port/slots and holes in the
burner.
A yellow tip on the pilot flame indicates dust and dirt in the pilot assembly . To clean the pilot assembly find the small pilot air inlet hole about two inches from where the pilot flame comes out of the pilot assembly (see figure
25). With the unit off, lightly blow air through the air inlet
hole. You may blow through a drinking straw if com­pressed air is not available.
CLEANING HEA TER CABINET
Air passageways
Use a vacuum cleaner or pressurized air to
clean
Exterior
Use a soft cloth dampened with a mild soap and
water mixture. Wipe the cabinet to remove dust.
Installation instructions and Owner’s Manual
13
TROUBLESHOOTING
NOTE: All troubleshooting items are listed in order of operation and likely occurrence.
WARNING: Only a qualified service person should service and repair heater.
CAUTION: Never use a wire needle, or similar object to clean ODS/pilot. This can damage ODS/pilot unit.
Make sure grille guard is in place before running heater. If screen or grille guard is removed for servicing it must be replaced prior to operating the heater.
OBSERVED SYMPTOM POSSIBLE CAUSE REMEDY
When ignitor button is pressed in, there is no spark at pilot
ODS/pilot lights but flame goes out when control knob is released
When ignitor button is pressed in, there is a spark at the ODS/ pilot but no ignition
Burner does not light after ODS/pilot is lit
Delayed ignition of burner
1. Ignitor electrode positioned wrong.
2. ignitor electrode is broken.
3. Ignitor electrode not connected to ignitor.
4. Ignitor cable pinched or wet.
5. Broken ignitor cable.
6. Bad Piezo ignitor.
7. Low Battery.
1. Gas supply turned off or equipment shutoff valve closed.
2. Control knob not fully pressed in while pressing ignition button.
3. Air in gas line when installed.
4. ODS/pilot is clogged.
5. Gas regulator setting is not correct
6. Control knob not in pilot position
1. Control knob not fully pressed in.
2. Control knob not presed in long enough
3. Equipment shutoff valve not fully open
4. Thermocouple connection loose at control valve
5. Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This problem could be caused by one or both of the following:
a. Low gas presure b. Dirty or partially clogged ODS/pilot
6. Thermocouple damaged
7. Control vlave damaged
1. Burner orifice is clogged
2. Burner orifice diameter to small
3. Inlet gas pressure is too low
1. Manifold pressure is too low
2. Burner orifice is clogged
1. Reposition electrode
2. Replace electrode
3. Reconnect ignitor cable
4. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry.
5. Replace ignitor cable
6. Replace control valve (Piezo is part of control valve on 10K units).
7. Replace battery
1. Turn on gas supply turn off or open equipment shutoff valve closed
2. Fully press in control knob while pressing ignition button
3. Continue holding down control knob. Repeat ignition operation until air is removed.
4. Clean ODS/pilot (see Cleaning and Maintenance page 13).
5. Replace gas regulator
6. Turn Control knob to pilot position
1. Press in control knob fully
2. After ODS/pilot lights, keep control knob pressed in for 30 seconds
3. Fully open equipment shutoff valve
4. Hand tighten thermocouple nut until snug, and then tighten 1/4 turn more.
5. -
a. Contact local gas company b. Clean ODS/pilot (see Cleaning and
Maintenance, page 13).
6. Replace thermocouple
7. Replace Control valve.
1. Clean burner orifice (see Cleaning and Maintenance on page 13), or replace burner orifice
2. Replace burner orifice
3. Contact local gas company
1. Contact local gas company
2. Clean burner orifice (see Cleaning and Maintenance on page 13), or replace burner orifice
14 Installation instructions and Owner’s Manual
70575 Rev. C 8/05
TROUBLESHOOTING CON’T
OBSERVED SYMPTOM POSSIBLE CAUSE REMEDY
Buner backfiring during combustion
Burner plaque(s) does not glow [Infrared Only]
Slight smoke or odor during initial operation
Heater produces a whistling noise when burner is lit
White powder residue forming within burner box or on adjacent walls or furniture
1. Burner orifice is clogged or damaged
2. Burner damaged
3. Gas regulator defective
1. Plaque damaged
2. Control knob set between locked posi­tions.
3. Inlet gas pressure is too low
1. Residues from manufacturing process
1. Turning control knob to HI position when burner is cold
2. Air in gas line
3. Air passageways on heater blocked
4. Dirty or partially clogged burner orifice.
1. When heated, vapors from furniture polis, wax, carpe cleaners, etc., turn into white powder residue
1. Clean burner orifice (see Cleaning and Maintenance on page 13), or replace burner orifice
2. Replace burner
3. Replace gas regulator
1. Replace buner
2. Turn control knob until it locks at desired setting.
3. Replace gas regulator
1. Problem will stop after a few hours of
operation
1. Turn control knob to LO position and let warm up for a minute.
2. Operate buner until air is removed from line have gas line checked by local gas company.
3. Observe minimum installation clearances(see Figure 4 page6)
4. Clean burner orifice (see Cleaning and Maintenance on page 13), or replace burner orifice.
1. Turn heater off when using furniture poils,wax, carpet cleaner or similar products.
TROUBLESHOOTING
WARNING: If you smell gas:
Shut off gas supply
Do not try to light any appliance
Do not touch any electrical switch; do not use any phone in your building
Immediately call you gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire dep artment.
IMPORTANT: Operating heater where impurities in air exist may create odors. Cleaning supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air and create odors.
OBSERVED SYMPTOM POSSIBLE CAUSE REMEDY
Heater produces unwanted odors.
Heater shuts off in use (ODS operates)
Gas odor even when control knob is in OFF position
Gas odor during combustion
Heater produces a cliking/ ticking noise just after butner is lit or shut off
Moisture/condensation noticed on windows
1. Heater burning vapors from paint, hair
2. Gas leak. See WARNING statement at
1. Not enough fresh air is available
2. Low line pressure
3. ODS/pilot is partially clogged
1. Gas leak. See WARNING statement at
2. Control valve is defective
1. Foreign matter between control valve and
2. Gas leak. See WARNING statement at
1. Metal expanding while heating or contract-
1. Not enough combustion/venitlation air
spray, glues, etc. See IMPORTANT statement above
top of page.
top of page
burner
top of page
ing while cooling
Installation instructions and Owner’s Manual
15
1. Ventilate room. Stop using odor-causing products while heater is running.
2. Locate and correct all leaks (see Checking Gas Connections, page 8)
1. Open window and/or door for ventilation
2. Contact local gas company
3. Clean ODS/pilot (see Cleaning and Maintenance, page 13)
1. Locate and correct all leaks (see Checking Gas Connections, page 8)
2. Replace control valve
1. Take apart gas tubing and remove foreign matter
2. Locate and correct all leaks (see Check­ing Gas Connections, page 8)
1. This is common with most heaters. If noise is excessive, contact qualified service person
1. Refer to Fresh Air of Combustion and Ventilation page 3 through 5.