The Signature Series is NOT designed for amateur installation. Installation SHOULD be performed by an authorized technician.
Please read this manual carefully before installation and keep it for future reference.
Owner & Installation
Manual
Signature Series
MGM*95SE*XA Gas Furnace
The Signature Series is NOT designed for amateur installation. Installation SHOULD be performed by an authorized technician.
Please read this manual carefully before installation and keep it for future reference.
Page 2
Gas Furnace
INSTALLATION INSTRUCTIONS
MGM*95SE*XA
Warm Air Gas Furnace
This manual must be left with the homeowner for future reference.
Table of Contents
2
3
Gas Piping38
WARNING
MRCOOL, LLC
13
13
16
6
6
9
CAUTION
50
52
55
56
*F507276-C*
(P) 507276-05C
Save these instructions for future reference
507276-05CPage 1 of 57mrcool.com
Page 3
Unit Dimensions
1
NOTE - C*55
2
RAir B
Model
070-3
110-5
135-5
FRONT VIEWSIDE VIEW
ABCD
in.mmin.mmin.mmin.mm
16
21533
62223283
505238
507276-05CPage 2 of 57mrcool.com
Page 4
Parts Arrangement
Figure 1.
507276-05CPage 3 of 57mrcool.com
Page 5
Gas Furnace
MG*95SE*XA
MG*95SE*XA
NOTE: In Direct Vent installations, combustion air is taken
Shipping and Packing List
Non-Direct Vent installations, combustion air is taken from
Figure 2.
NOTE:
Safety Information
DANGER
DANGER OF EXPLOSION!
Figure 3.
MG*95SE*XA
Building Codes
507276-05Cmrcool.com
Page 6
Installation Locations
NOTE:
NOTE:
Figure 4. Heating Unit Installed Parallel to Air Handler
Unit
NOTE:
Installed in Combination with a Cooling Coil
Use of Furnace as a Construction Heater
DO NOT USE THE UNIT FOR CONSTRUCTION HEAT
UNLESS ALL OF THE FOLLOWING CRITERIA ARE
MET:
507276-05CPage 5 of 57mrcool.com
Page 7
COMPONENT FAILURE AS A RESULT OF FAILURE TO
•
•
NOTE:
•
•
•
CAUTION
General
•
Combustion, Dilution & Ventilation Air
NOTE: In Non-Direct Vent Installations, combustion air is
•
•
507276-05CPage 6 of 57mrcool.com
Page 8
WARNING
•
•
•
•
•
•
•
•
•
•
•
•
•
CAUTION
Air from Inside
507276-05CPage 7 of 57mrcool.com
Page 9
Figure 5.
Air from Outside
Inside
Figure 7.
ROOF TERMINATED
EXHAUST PIPE
Outside
(All Air through Ventilated Attic)
Figure 6.
Outside
(Inlet Air from Crawl Space and Outlet Air to
Ventilated Attic)
OUTLET AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−Each air duct opening shall have a free area of at least one
square inch per 2,000 Btu (645mm
input rating of all equipment in the enclosure. If the equipment room
is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area
of at least 1 square inch per 4,000 Btu (645mm
hour of the total input rating of all other equipment in the enclosure.
FURNACE
INLET AIR
2
per .59kW) per hour of the total
2
per 1.17kW) per
Figure 8.
Outside
507276-05CPage 8 of 57mrcool.com
Page 10
WARNING
Shipping Bolt Removal
Roof Terminated
Exhaust Pipe
Ventilation Louvers
*Intake Debris
Screen
(Provided)
Furnace
Inlet Air
(Minimum 12 in.
(305mm) above
Attic Floor)
* See Maximum Vent Lengths table
NOTE
Figure 9.
(Inlet Air from Ventilated Attic and Outlet Air to
Outside)
Roof Terminated
Exhaust Pipe
Figure 11.
Installation
Setting Equipment
WARNING
Inlet Air
Minimum
Ventilation
Louvers
(Crawl Space)
Coupling or
3 in. to 2 in.
Transition
(Field Provided)
Furnace
12 in. (305mm)
above Crawl
Space Floor
*Intake Debris Screen Provided
* See Maximum Vent Lengths table
NOTE
Figure 10.
(Inlet Air from Ventilated Crawl Space and Outlet Air
Maintain a minimum of24 in. (610mm)forfrontserviceaccess.
**An8"serviceclearancemustbemaintainedbelowtheunitto provide
for servicing of the condensate trap.
‡For installations onacombustible
oncarpeting,tileorothercombustiblematerialsother than wood
ooring.
oor, donot install the furnace directly
0
0
0†
0
0‡
Figure 17.
Figure 18. Installation Clearances
Horizontal Applications
Suspended Installation of Horizontal Unit
Figure 19. Typical Horizontal Application
507276-05CPage 12 of 57mrcool.com
Page 14
NOTE:
Filters
NOTE:
Platform Installation of Horizontal Unit
Furnace Cabinet
Width
Duct System
NOTE:
Supply Air Plenum
Filter Size
Side ReturnBottom Return
Table 1.
Figure 20.
Return Air - Horizontal Applications
507276-05CPage 13 of 57mrcool.com
Return Air Plenum
NOTE:
Page 15
F891
MGM95*E
CAUTION
IMPORTANT
(Pipe)
PRIMER & SOLVENT CEMENT
CANADA PIPE & FITTING & SOLVENT
CEMENT
F628
ASTM
SPECIFICATION
F656
MARKING
Canadian Applications Only
POLYPROPYLENE VENTING SYSTEM
TM
Table 2.
ULCS636
ULC-S636
ULC-S636
ULC-S636
507276-05Cmrcool.com
Page 16
STANDARDCONCENTRIC
Capacity
070
090
110
1353
VENT
PIPE DIA.
(in.)
2
3
2
3
2
3
2
3
Outdoor
Exhaust
Accelerator
(Dia. X Length)
Outdoor
Exhaust
Accelerator
(Dia. X Length)
Flush Mount
Kit
51W11**
Concentric KitKitKit
71M80
OR
+44W92++
69M29
OR
+44W92++
60L46
OR
44W93+
Joint Cementing Procedure
NOTE:
DANGER
DANGER OF EXPLOSION!
Table 3. Outdoor Termination Kits Usage
NOTE:
507276-05CPage 15 of 57mrcool.com
Page 17
NOTE:
Venting Practices
WARNING
CARBON MONOXIDE POISONING HAZARD
Figure 21.
Removal of the Furnace from Common Vent
507276-05CPage 16 of 57mrcool.com
Page 18
CHIMNEY
OR GAS
VENT
(Check sizing
for remaining
appliance)
REPLACING FURNACE THAT
Vent Piping Guidelines
WAS PART OF A COMMON
VENT SYSTEM
NOTE: In non-Direct Vent installations, combustion air is
In Direct Vent installations, combustion air is taken from
FURNACE
(Removed from
from common
vent system)
If this gas furnace replaces a furnace which
was commonly vented with another gas appliance,
the size of the existing vent pipe for that gas
appliance must be checked. Without the heat of the
original furnace flue products, the existing vent pipe
is probably oversized for the single water heater or
other appliance. The vent should be checked for
proper draw with the remaining appliance.
Exhaust Piping
WATER
HEATER
Figure 22.
OPENINGS
(ToAdjacent
Room)
MRCOOL, LLC
NOTE:
NOTE:
CAUTION
CAUTION
507276-05CPage 17 of 57mrcool.com
Figure 23.
Page 19
IMPORTANT
CapacityMin. Vent Length*
Furnace capacity?
1
045, 070,
090, 110,
135
135 **
Table 4.
Which termination?
2
Which needs most
3
elbows?
How many?
4
Desired pipe size?
5
Standard or
Concentric?
See Table 3
Intake or
Exhaust?
2”, 2-1/2”
or 3”
What is the altitude?
6
Use Table 5 to find
7
max pipe length.
Figure 24.
507276-05CPage 18 of 57mrcool.com
Page 20
MG*M95SE*XA Maximum Allowable Intake or Exhaust Vent Length in Feet
(Inlet Air from Ventilated Attic and Outlet Air to
Outside)
507276-05Cmrcool.com
Page 26
Roof Terminated
Exhaust Pipe
Ventilation
Louvers
(Crawl Space)
Furnace
NOTE:
Inlet Air
Minimum
12 in. (305mm)
above Crawl
Space Floor
NOTE:
Coupling or
3 in. to 2 in.
Transition
(Field Provided)
*Intake Debris Screen Provided
* See Maximum Vent Lengths table
NOTE:
Figure 32.
(Inlet Air from Ventilated Crawl Space and Outlet Air
to Outside)
General Guidelines for Vent Terminations
IMPORTANT
IMPORTANT
For Canadian Installations Only:
507276-05CPage 25 of 57mrcool.com
Page 27
Maximum Allowable Exhaust Vent Pipe Length (in ft.) without Insulation in Unconditioned Space For Winter Design
Winter Design Temperatures
1
2
1
ºF (ºC)
Vent Pipe
Diameter
Unit Input Size
045070090110135
PVC
2
PPPVC2PPPVC2PPPVC2PPPVC2PP
18163128503030
1356
99181835355252
98181632293030
513
88191926263030
53121022193027
71522
101016161818
Conditioned
Space
Table 6.
Conditioned
Space
Pipe Insulation
Unconditioned
Space
Exhaust
Pipe
Intake
Pipe
Figure 33. Insulating Exhaust Pipe in an Unconditioned Space
507276-05CPage 26 of 57mrcool.com
Page 28
VENT TERMINATION CLEARANCES
FOR NON-DIRECT VENT INSTALLATIONS IN THE US AND CANADA
INSIDE CORNER
DETAIL
G
D
A
E
B
L
C
Fixed
F
Closed
Operable
B
Operable
B
B
VENT TERMINAL
AIR SUPPLY INLET
US Installations
A =
Clearance above grade, veranda,
porch, deck or balcony
B =
Clearance to window or
door that may be opened
C =
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
D =
located above the termin
al within a
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
4 feet (1.2 m) below or to side of opening;
1 foot (30cm) above opening
* 12”
* Equal to or greater than soffit depth.
horizontal distance of 2 feet (610 mm)
from the center line of the terminal
E =
F =
G =
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
H =
tended above meter / regulator assembly
I =
Clearance to service regulator
vent outlet
J =
Clearance to non-mechanical air
* Equal to or greater than soffit depth.
* No minimum
3 feet (.9m) within a height 15 feet (4.5m)
*
above the meter / regulator assembly
* 3 feet (.9m)
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
pliance
K =
ply inlet
L =
Clearance above paved sidewalk or
paved driveway located on public property
M =
Clearance under veranda, porch, deck or balcony
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is
located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open
on a minimum of two sides beneath the floor. HVAC Distributing recommends
avoiding this location if possible.
3 feet (.9m) above if within 10 feet
(3m) horizontally
7 feet (2.1m)†
*12 inches (305mm)‡
H
B
Fixed
Closed
A
J
I
M
AREA WHERE TERMINAL
IS NOT PERMITTED
1
Canadian Installations
2
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12”
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
to outside corner* No minimum to outside corner
**
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)†
12 inches (305mm)‡
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, clearance will be in accordance with local installation
codes and the requirements of the
lation instructions.”
K
Figure 34.
507276-05CPage 27 of 57mrcool.com
Page 29
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
D
A
E
B
L
C
Fixed
F
Closed
Operable
B
Operable
B
A
B
VENT TERMINAL
AIR SUPPLY INLET
US Installations
A =
B =
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap-
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
C =
D =
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
located abo
ve the terminal within a
horizontal distance of 2 feet (610mm)
* 12”
* Equal to or greater than soffit depth* Equal to or greater than soffit dept
from the center line of the terminal
E =
F =
G =
H =
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex-
tended above meter / regulator assembly
I =
Clearance to service regulator
vent outlet
J =
Clearance to non-mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* No minimum to outside corner
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
*
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap-
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
K =
Clearance to mechanical air sup-
ply inlet
L =
Clearance above paved sidewalk or
paved driveway located on public property
M =
Clearance under veranda, porch, deck or balcony
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is located
between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of
two sides beneath the floor. HVAC Distributing recommends avoiding this location
if possible.
3 feet (.9m) above if within 10 feet
(3m) horizontally
* 7 feet (2.1m)
*12 inches (305mm)‡
H
Fixed
Closed
J
B
I
M
K
AREA WHERE TERMINAL
IS NOT PERMITTED
1
Canadian Installations
2
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12”
h
* No minimum to outside corner
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 i
nches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)†
12 inches (305mm)‡
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, clearance will be in accordance with local installation
codes and the requirements of the gas supplier and these
installation instructions.”
Figure 35. Vent Termination Clearances for Direct Installations
507276-05CPage 28 of 57mrcool.com
Page 30
Details of Intake and Exhaust Piping
Terminations for Direct Vent Installations
NOTE: In Direct Vent installations, combustion air is taken
NOTE:
Inches (MM)
8” (203MM) MIN
12” (305MM) ABOVE
AVERAGE SNOW
ACCUMULATION
3” (76MM) OR
2” (51MM) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
3” (76MM) MIN.
SIZE PER EXHAUST PIPE
TERMINATION SIZE
REDUCTION TABLE
UNCONDITIONED
ATTIC SPACE
1/2” (13MM) FOAM
INSULATION IN
UNCONDITIONED
SPACE
Figure 36. Direct Vent Roof Termination Kit
(15F75 or 44J41)
CapacityExhaust Pipe Size
Termination
Pipe Size
90
110
135
Table 7. Exhaust Pipe Termination Size Reduction
NOTE:
Figure 37.
Figure 38.
507276-05CPage 29 of 57mrcool.com
Page 31
NOTE − FIELD−PROVIDED
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
* WALL
SUPPORT
C1
REDUCER MAY BE
TO TERMINATION
C1
A
E
D
B
Intake
Elbow
STRAIGHT
APPPLICATION
D
B
A
EXTENDED
APPLICATION
FIELD FABRICATED WALL TERMINATION
A− Minimum clearance
above grade or average
snow accumulation
B− Maximum horizontal
separation between
intake and exhaust
C1 -Minimum from end of
exhaust to inlet of intake
C2 -Minimum from end of
exhaust to inlet of intake
D− Maximum exhaust
pipe length
E− Maximum wall support
distance from top of each
pipe (intake/exhaust)
D
B
* Use wall support every 24” (610 mm). Use two
wall supports if extension is greater than
24” (610 mm) but less than 48” (1219 mm).
NOTE − One wall support must be within 6” (152 mm)
from top of each pipe (intake and exhaust) to prevent
movement in any direction.
The exhaust termination tee should be connected to the 2” or 3” PVC flue pipe as shown in the illustration.
Do not use an accelerator in applications that include an exhaust termination tee.
The accelerator is not required.
2
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
termination is used and flue gases will impinge on the building materials, a corrosion-resistant shield
(24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield
is recommended. The shield should be constructed using wood, sheet metal or other suitable material.
All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust
away from adjacent property. The exhaust must never be directed toward the combustion air inlet.
3” (76MM)
Vent Pipe
6” (152 mm) Min.
24” (610 mm) Max.
9” (227 mm) Min.
12” (305 mm) Min.
20” (508 mm) Max.
6” (152 mm) Max.
Figure 39.
507276-05CPage 30 of 57mrcool.com
Page 32
Figure 40.
Figure 42.
Figure 43.
8” - 12”
(203MM - 305MM)
3”-8”
(76MM-203MM)
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE
Figure 41.
507276-05CPage 31 of 57mrcool.com
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
INTAKE PIPE
INSULATION (optional)
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
3” - 8”
(76MM-
203MM)
ALTERNATE
INTAKE PIPE
EXTERIOR
PORTION OF
CHIMNEY
* SIZE TERMINATION PIPE
PER EXHAUST PIPE TERMINATION
SIZE REDUCTION TABLE
Figure 44. Direct Vent Application Using Existing
Chimney
Page 33
Direct Vent Applications
12” (305MM)
ABOVE AVE.
SNOW
ACCUMULATION
3” (76MM) OR
2” (51MM) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
SIZE PER EXHAUST PIPE
TERMINATION SIZE
REDUCTION TABLE
UNCONDITIONED
ATTIC SPACE
SIZE TERMINATION
PER EXHAUST PIPE
TERMINATION SIZE
REDUCTION TABLE
* Use wall support every 24” (610 mm). Use two supports of extension is greater than 24”
(610 mm) but less than 48” (1219 mm).
Figure 47.
Termination Extended
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE
Figure 45.
SIZE TERMINATION
PER EXHAUST PIPE
TERMINATION SIZE
REDUCTION TABLE
Instruct the homeowners to pay attention to their
furnace.
Red LED Flash Code
1
1
NOTE
Table 15.
507276-05CPage 55 of 57mrcool.com
Page 57
Red LED Flash Code
1
1
2
NOTE
2
Repair Parts List
Cabinet Parts
•
•
•Top Cap
Control Panel Parts
•Transformer
•
•
Blower Parts
•
•
•
•
•
Table 16.
Heating Parts
•
•
•
•
•
•
•
•
•
•
•
507276-05CPage 56 of 57mrcool.com
Page 58
Requirements for Commonwealth of Massachusetts
requirements:
INSTALLATION OF CARBON MONOXIDE
DETECTORS
INSPECTION
EXEMPTIONS: The following equipment is exempt
from 24 CMR 5.08(2)(a) 1 through 4:
VENTING SYSTEM PROVIDED.
APPROVED CARBON MONOXIDE DETECTORS.
SIGNAGE
GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
VENTING SYSTEM NOT PROVIDED.
A copy of all installation instructions for all Product
equipment, all venting instructions, all parts lists
instructions shall remain with the appliance or
equipment at the completion of the installation.
507276-05CPage 57 of 57mrcool.com
Page 59
Signature Series
MGM*95SE*XA Gas Furnace
ELECTRICIAN and /or HVAC TECHNICIAN:
LICENSE #:
INSTAL LATI ON DAT E:
INSTALLATION LOCATION:
SERIAL NUMBER:
The design and specifications of this product and/or manual are subject to change without prior notice.
Consult with the sales agency or manufacturer for details.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.