The Signature Series is NOT designed for amateur installation. Installation SHOULD be performed by an authorized technician.
Please read this manual carefully before installation and keep it for future reference.
Owner & Installation
Manual
Signature Series
MPC*1M414A & MPH*1M414A
Residential Packaged Units
The Signature Series is NOT designed for amateur installation. Installation SHOULD be performed by an authorized technician.
Please read this manual carefully before installation and keep it for future reference.
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
WARNING
Installation and servicing of air conditioning equipment
can be hazardous due to internal refrigerant pressure
and live electrical components. Only trained and
this equipment. Installation and service performed by
WARNING
other appliance. Such actions could result in property
WARNING
If this unit is to be installed in a mobile or manufactured
guidelines. All other installation guidelines must also
the unit.
Manufactured By
MRCOOL LLC
*F507296-C*
C
CAUTION
The installation of this appliance must conform to the requirements of the National Fire Protection Association; the
jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence
over the general instructions in this manual.
Save these instructions for future reference
507296-02CPage 1 of 12mrcool.com
Location
WARNING
or maintenance can cause injury or property damage.
Refer to this manual. For assistance or additional
agency.
Installation
These instructions explain the recommended method of
installation of the packaged heat pump and air conditioner
system.
clearance for free entrance to the air inlet and discharge
service access.
not settle or shift. Adequate structural support must be
provided. Install the unit in level position. Isolate the base
from the building structure to avoid possible transmission
of sound or vibration into the conditioned space.
The heat pump unit foundation should be raised to a
In areas that have
prevent ice accumulation. The unit should not be located
defrost condensate.
Avoid placing the unit near quiet areas, such as
sleeping quarters or study rooms. Normal operating
sound levels may be objectionable if the unit is placed near
certain rooms.
read prior to beginning installation. Note particularly any
CAUTIONS or WARNINGS in these instructions and all
labels on the units.
equipment should be determined prior to installation.
Inspection of Shipment
the unit inside the carton if the carton is damaged. File a
as claim may be denied.
are as ordered.
Limitations
For improved start-up performance, the indoor coil
should be washed with suitable detergent to remove
any residue from manufacturing processes.
Roof Curb Installation
Instructions and be sure that all required clearances are
observed.
Rigging and Handling
CAUTION
packaging until the unit is near the place of installation.
An optional lifting lug kit may be purchased separately for
used across the top of the unit.
and local safety codes.
of the forklift must be a minimum of 42”.
also be observed.
outdoor air stream. The outdoor fan is not designed to
operate against any additional static pressure.
Page 2 of 12507296-02Cmrcool.com
The lengths of the forks
REDUCE
TO
6.00
REDUCE
TO
W1
C
L
R
O
Y1
FAN
O-OUT
LO-PS
DF
HI-PS
COMMON
Y1 OUT
2
2
24 V
Y
W2
RED
YEL
BLU
WHT
GRN
ORN
W1 & W2 CAN BE USED TO STAGE
ELECTRIC HEAT ACCESSORY ON
15 & 20KW MODELS
5, 7.5 & 10KW HEATER ACCESSORIES
FUNCTION OFF W1 ONLY.
WHT
DEFROST
CONTROL
P-6
P-5
G
W1
CRO
THERMOSTAT
537663-01
NOTE:
IF ANY OF THE ORIGINAL
WIRE IS REPLACED THE
SAME SIZE AND TYPE WIRE
MUST BE USED.
USE COPPER CONDUCTOR
ONLY, MIN 75C WIRE
CONNECTION MUST BE JUMPERED
WHEN PRESSURE SWITCH IS NOT USED.
LINE VOLTAGE FIELD INSTALLED
WARNING-
ELECTRIC SHOCK HAZARD. UNIT
MUST BE GROUNDED IN ACCORDANCE
WITH NATIONAL AND LOCAL CODES.
REV. VALVE
Service Access
Access to all serviceable components is provided by four
WARNING
Figure 1. Rigging Unit
Figure 2. Typical Field Wiring
Clearances
All units require certain clearances for proper operation
and service. Refer to Table 1 for the minimum clearances
proper unit operation.
Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet.
Clearance to
Combustibles
Front of unit
Back of unit
Right side
Base of unit
Top of unit48 in.
Clearance for
Service Access
24 in.
24 in.
24 in.
CAUTION
Compressor
adjusted and ready for operation. Do not loosen
compressor mounting bolts.
Unpacking
Carefully remove outer packaging material and discard.
corner and seal the shipping openings in the base from
prevent air leakage during unit operation.
the installer. Refer to the unit rating plate for maximum
507296-02CPage 3 of 12mrcool.com
Table 1. Minimum Clearances
Electrical Wiring
or pigtail leads located on the main control box and are
CAUTION
during normal operation.
Units are factory wired for a 230-volt power supply.
If power supply is 208 volts, it will be necessary to
change a wire connection on the unit transformer from
240V terminal to 208V terminal as shown on the wiring
diagram.
Use only copper conductors.
*
“O” connection used only on heat pump models
*
Thermostat
The room thermostat should be located on an inside
installation.
Contactor
changed
Figure 3. 208/230 Line Voltage Wiring
or Circuit Breaker
Disconnect
Single Phase
off W1 only.
Figure 4. Typical Wiring Connections
Duct System
Duct system should be designed and sized according to the
methods in Manual Q of the Air Conditioning Contractors of
A closed return duct system shall be used. This shall not
preclude use of economizers or outdoor fresh air intake. It
is recommended that supply and return duct connections
The supply and return air duct systems should be designed
for the CFM and static requirements of the job. They
should not be sized to match the dimensions of the
duct connections on the unit.
panel. Duct to unit connections must be sealed and
Page 4 of 12507296-02Cmrcool.com
1.
the unit base insulation to access bottom metal covers
underneath the insulation.
2.
3.
bottom duct connections or roof curb seals.
4.
5.
NOTE: Install drain lines and trap so they do not block
service access to the unit.
See Figure 5 for proper drain arrangement. The drain line
must pitch to an open drain or pump to prevent clogging
material to prevent air leakage into the return air system.
CAUTION
Filters
NOTE:
is limited.
Unit ModelFilter 1Filter 2
Table 2. Unit Air Filter Sizes - inches
Minimum Pitch:
Open
Mounting
Frame
Trap must be deep enough to offset maximum static difference
Figure 5. Typical Condensate Drain Connection
Condensate Drain
Crankcase Heater (if used)
to prevent excessive migration of liquid refrigerant into the
for condensate line connection. Plumbing must conform
to the unit to keep this feature active.
threads.
Do not
the system disconnect switch.
Heater Kit Accessory (if used)
The condensate drain line must be properly trapped,
routed to a suitable drain and primed prior to unit
commissioning.
507296-02CPage 5 of 12mrcool.com
auxiliary heat. A heater kit accessory may also be used. To
1.
do not open
access.
2.
and discard.
3.Remove the heater blockoff by removing the four
4.Insert the heater into the control panel and fasten in
the same mounting holes.
5.
connections on the heater kit.
Sequence of Operation
Cooling
Heating - Heat Pump Stage
and outdoor fan. The reversing valve is not energized in
the heating mode. The thermostat again automatically
stops unit operation.
Heating - Auxiliary Electric Heat
continues to operate until all heating elements have turned
off.
Defrost System
compressor and outdoor fan. The thermostat automatically
thermostat and the defrost control.
Defrost Thermostat
The defrost thermostat is located on the outdoor coil.
thermostat contacts close and send a signal to the defrost
control board to start the defrost timing. It also terminates
Figure 6. Heater Kit Accessory Installation
507296-02Cmrcool.com
Defrost Control
The defrost control board includes the combined functions
heating operation to defrost mode and back. During the
relay is energized and the defrost begins.
1.
°F in heating
NOTE: 15°F is an approximate temperature,
depending upon model and installation location.
2.
The maximum defrost period is 14 minutes and cannot be
adjusted.
NOTE:
A test option is provided for troubleshooting. The test mode
may be started any time the unit is in the heating mode and
the defrost thermostat is closed or jumpered. If the jumper
the test pins. When the jumper is placed across the TEST
in defrost mode until the defrost thermostat opens or 14
minutes have passed. If the jumper is not removed until
and the defrost time interval must not have expired.
3.
conditions.
DEFROST TIMING
PINS (P1)
TEST
PINS
DIAGNOSTIC
COMPRESSOR
DELAY PINS
REVERSING
VALVE
S87
LOW PRESSURE
SWITCH
DEFROST
THERMOSTAT (S6)
S4
HIGH PRESSURE
SWITCH
LEDS
24V TERMINAL
STRIP
CONNECTIONS
SERVICE LIGHT
CONNECTIONS
Figure 7. Defrost Control Board
Defrost Control Timing Pins
Each timing pin selection provides a different accumulated
compressor run time period during one thermostat run
cycle. This time period must occur before a defrost cycle
again until the jumper is removed and reapplied.
Compressor Delay (Quiet Shift)
NOTE: The 30-second “off” cycle is not functional when
jumpering the TEST pins.
Time Delay
ensures the compressor is off for a minimum amount of
to protect the compressor from short cycling in case the
The delay is bypassed by placing the timer select jumper
Pressure Switch Circuit
defrost control board on heat pump models. Air conditioning
During a single demand cycle, the defrost control will
It is intended that this
product should be set at the 60-minute time interval at
initial installation. If the timing selector jumper is not in
507296-02Cmrcool.com
interrupted by any pressure switch wired to the control
board. In addition, the diagnostic LEDs will indicate a
of an open pressure switch (see Table 3).
The unit will remain locked out until power to the board
is interrupted, then re-established, or until the jumper
is applied to the TEST pins for 0.5 seconds.
NOTE: The defrost control board ignores input from the
low pressure switch terminals as follows:
If the measured performance value varies from table value
refrigerant to nameplate charge. It is critical that the exact
•During the TEST mode
•During the defrost cycle
•
•
If the TEST pins are jumpered and the 5-minute delay
is being bypassed, the LO PS terminal signal is not
ignored during the 90-second start-up period.
Diagnostic LEDs
Defrost Board Diagnostic LEDs
Green LED
(DS2)
OFFOFF
Red LED
(DS1)
Condition
system performance.
components.
Model
2 Ton13
2.5 Ton
3 Ton14
3.5 Ton14
4 Ton
5 Ton
Suction
Superheat +/- 3°
Subcooling +/- 2°
Table 4. Air Conditioner Unit Cooling System
Performance Values
Model
Suction
Superheat +/- 3°
Liquid Subcooling
Liquid
+/- 2°
ON
Fault & Lockout Codes
OFF
OFFON
OFF
ONOFF
Table 3. Defrost Control (CMC1) Diagnostic LEDs
System Performance
the suction superheat value to judge performance. When
checking performance of a unit that uses an expansion
system performance.
2 Ton18
2.5 Ton
3 Ton
3.5 Ton22
4 Ton22
5 Ton5
Table 5. Heat Pump Cooling System Performance
Values
ModelLiquid Subcooling +/- 2°
2 Ton
2.5 Ton
3 Ton
3.5 Ton
4 Ton
5 Ton
25
15
28
35
28
Table 6. Heat Pump Heating System Performance
Values
Page 8 of 12507296-02Cmrcool.com
Maintenance
WARNING
Motors
Indoor and outdoor fan and vent motors are permanently
lubricated and require no maintenance.
Before performing maintenance operations on the
shock could cause personal injury or death.
constant torque motor. These motors remain energized and
use Tap 3 for cooling speed and Tap 5 for heating speed.
Outdoor Coil
Periodic inspection and maintenance normally consists of
the outdoor coil surface or other parts in the air circuit.
Cleaning should be as often as necessary to keep the coil
cleaning.
Filters
Replace disposable or clean permanent type as necessary.
Table 7. Cooling Performance - AC Models
80 DB / 67 WB Deg.
Return Air
Cooling
Input
(1000 BTU)
24
42
48132143144145151152154
24
42248325385411
48338352455482
Pressure65°70°75°80°82°85°90°95°100°105°110°115°
135
135142143145152154155
Suction
135142143144151152154155
132135141143145148
131133134135141144152
282318388413438
Air Temperature Entering Outdoor Coil, Degree F
314323358432483
damaged.
141143148152154
351423
324415438
507296-02Cmrcool.com
Table 9. Cooling Performance - HP Models
80 DB / 67 WB Deg.
Return Air
Cooling
Input
(1000 BTU)
24
42
48132135138142143144
24255388414
42238324348421445
48248412438
Pressure65°70°75°80°82°85°90°95°100°105°110°115°
134138141143145148151152154155
133141143145151153
Suction
133134135138142
254314322383
245312415438
138142143144145151152154
131134138141144148148148
285322343443
Air Temperature Entering Outdoor Coil, Degree F
151152154155
Table 8. Heating Performance - HP Models
70 Deg. F Return AirAir Temperature Entering Outdoor Coil, Degree F
Cooling
Input
(1000 BTU)
24
4225334254
483284114122
24283312323
42
48
Pressure0°5°10°17°20°25°35°40°47°50°55°60°
Suction
3341
313845558188
35425882115
85111
445458
253281312323
251258321328335
311315322331333341
318323332358384
281334343355
113121
507296-02Cmrcool.com
S4
S79
S173
J1-11
Wiring Diagrams
LINE VOLTAGE FIELD INSTALLED
CONTACTOR
K1-2
L2
YEL W/ STRIPE
J1-2
PUR
FAN
MOTOR
J2-2
J1: PLUG THROUGH CONTROL PANEL (12 PIN)
J2: PLUG FOR ACCESSORY HEAT (6 PIN)
B4
YEL W/ STRIPE
208/230-1-60
POWER SUPPLY WITH MIN.
C COPPER WIRE
75
BLK
COMPRESSOR
B1
T2
RED
GRY
F
J1-1
ORG
OUTDOOR
BLK W/ STRIPE
R
C
C
S
BLACK
G
N
(IF USED)
HR1
H
HEATER
CRANK
CASE
BLK
CAPACITOR
YEL
J1-3
INDOOR
BLOWER
MOTOR
240V
DUAL
B3
C12
L
208V
BLK
T1
CONTACTOR
24V
L1
K1-1
BLK
TRANSFORMER
TI
BLK
BLK
J2-1
A/C (CONSTANT TORQUE BLOWER)
CONNECTION DIAGRAM
SINGLE PHASE
NOTE: TAP1 FOR FAN ONLY
TAP 2 FOR COOLING
TAP3 FOR HIGH STATIC COOLING
TAP4 AND TAP5 FOR ELECTRIC HEAT- REFER TO HEATING LABEL
The design and specifications of this product and/or manual are subject to change without prior notice.
Consult with the sales agency or manufacturer for details.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.