3. Circuit #1 includes blower motor amps except 20kW models
mrcool.com
Page 4
Page 5
ENHANCED AIR HANDLER
BLOWER
MAHM*ETA
Model
MAHM24ETA1/210 x 8
MAHM30ETA1/210 x 8
MAHM36ETA1/210 x 8
MAHM42ETA3/412 x 10
MAHM48ETA112 x 10
MAHM60ETA112 x 10
Motor
Size (hp)
Blower
Size
(in.)
Speed
Tap
Application
CFM @ ESP - in. W.C.
0.10.20.30.40.5
1Fan Only590575530480430
2Matched with 1.5 ton condensing unit750650610550480
3Nominal 2 ton match without electric heat 950825785740690
4Nominal 2 ton match with electric heat 10401020985940920
5High static application11601140112010801050
1Fan Only700665625565490
2Matched with 2 ton condensing unit860810770715665
3Nominal 2.5 ton match without electric heat 10401010980940890
4Nominal 2.5 ton match with electric heat 1140110010451015980
5High static application13901375134012851245
1Fan Only850800750665600
2Matched with 2.5 ton condensing unit1080950910850775
3Nominal 3 ton match without electric heat 12701230117011201060
4Nominal 3 ton match with electric heat 14401400133012801240
5High static application15401475143013801300
1Fan Only990915860810725
2Matched with 3 ton condensing unit11901150110010601020
3Nominal 3.5 ton match without electric heat 13901350131512801230
4Nominal 3.5 ton match with electric heat 16651625158515501510
5High static application17501710167516401600
1Fan Only12501210118511301110
2Matched with 3.5 ton condensing unit1500146514
3514001360
3Nominal 4 ton match without electric heat 17151670163516151575
4Nominal 4 ton match with electric heat 17701735170016701650
5High static application18951860183517951760
1Fan Only110010501000925830
2Matched with 4 ton condensing unit16251595156515201490
3Nominal 5 ton match without electric heat 18151785176017301685
4Nominal 5 ton match with electric heat 19051870183518101765
5High static application19801955192518951860
All data given while air handler is operating with a wet coil and without air filter installed.
Speed tap 1 to be used for continuous fan operation.
Speed tap 2 to be used for cooling speed of 1/2 ton smaller outdoor unit match. Speed tap 3 to be used for cooling speed of nominal tonnage match.
Speed tap 4 to be used for heating speed for units with electric heat. This is the minimum speed for heating. Speed tap 5 to be used for high static applications.
mrcool.com
Page 5
Page 6
ENHANCED AIR HANDLER
FRONT VIEWSIDE VIEW
(Top and Left Side
1 (25)
8
DIMENSIONS (IN.)
SUPPLY AIR
E
MAHM*ETA
OPENING
1 (25)
LINE VOLTAGE
INLETS
3-5/8
(92)
5 (102)
F
)
TOP VIEW
CIRCUIT
BREAKER
COVER
AIR FLOW
G
D
SUCTION
LINE
LIQUID
LINE
1 (25)
LOW VOLTAGE
INLETS
(Top and Right Side)
3/4 (19)
LINE VOLTAGE INLETS
A
CONDENSATE DRAIN
PIPING PLATE (4)
(2-1/4 x 3-3/4)
FILTER ACCESS
CB
(Top and Right Side)
LOW VOLTAGE INLETS
(Either Side)
1/2
(13)
JH
Dimension
1-1/8
(29)
1-1/8
OPENINGOPENING
(29)
18243036-424860
in.mmin.mmin.mmin.mmin.mmin.mm
A43.5110545.5115647119453.63136255139759.751518
B18.547018.547018.547021.554621.554621.5546
C16.541916.541916.541919.549519.549519.5495
D16.2541316.2541316.2541319.2548919.2548919.25489
All specifications and illustrations subject to change without notice and without incurring obligations.