MR VACUTAP VR I HD-Ex, VACUTAP VR I-Ex, VACUTAP VR II-Ex, VACUTAP VR III-Ex Installation And Commissioning Instructions

On-Load Tap-Changer VACUTAP® VR I HD-Ex
Installation and Commissioning Instructions
5293014/00 EN
© All rights reserved by Maschinenfabrik Reinhausen
Dissemination and reproduction of this document and use and disclosure of its content are strictly prohibited unless expressly permitted.
Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents, utility models or designs.
The product may have been altered since this document was published.
We reserve the right to change the technical data, design and scope of supply.
Generally the information provided and agreements made when processing the individual quotations and orders are binding.
The original operating instructions were written in German.

Table of contents

Table of contents
1 Introduction......................................................................................................................... 8
1.1 Manufacturer....................................................................................................................................... 8
1.2 Subject to change without notice......................................................................................................... 8
1.3 Completeness...................................................................................................................................... 8
1.4 Safekeeping......................................................................................................................................... 9
1.5 Notation conventions........................................................................................................................... 9
1.5.1 Symbols................................................................................................................................................................. 9
1.5.2 Hazard communication system........................................................................................................................... 10
1.5.3 Information system.............................................................................................................................................. 11
2 Safety................................................................................................................................. 13
2.1 Appropriate use................................................................................................................................. 13
2.2 Fundamental safety instructions........................................................................................................ 14
2.3 Standards and regulations................................................................................................................. 15
2.3.1 Application range of the on-load tap-changer..................................................................................................... 15
2.3.2 Standards and regulations.................................................................................................................................. 18
2.4 Measures for ensuring compliance with explosion protection requirements..................................... 18
2.4.1 Measures taken by the manufacturer.................................................................................................................. 18
2.4.2 Measures to be taken by the transformer manufacturer/operator....................................................................... 18
2.5 Personnel qualification...................................................................................................................... 22
2.6 Personal protective equipment.......................................................................................................... 23
3 Product description.......................................................................................................... 25
3.1 Scope of delivery............................................................................................................................... 25
3.2 On-load tap-changer.......................................................................................................................... 25
3.2.1 Function description............................................................................................................................................ 25
3.2.2 Setup/models...................................................................................................................................................... 26
3.2.3 Name plate.......................................................................................................................................................... 31
3.3 Drive shaft......................................................................................................................................... 31
3.3.1 Function description............................................................................................................................................ 31
3.3.2 Design/Model...................................................................................................................................................... 33
3.3.3 Identification plate............................................................................................................................................... 35
3.4 Protective relay.................................................................................................................................. 35
3.4.1 Function description............................................................................................................................................ 35
3.4.2 Setup/versions..................................................................................................................................................... 36
Maschinenfabrik Reinhausen GmbH 2017 35293014/00 EN VACUTAP® VR I HD-Ex
Table of contents
3.4.3 Name plate.......................................................................................................................................................... 37
4 Packaging, transport and storage................................................................................... 38
4.1 Packaging.......................................................................................................................................... 38
4.1.1 Suitability............................................................................................................................................................. 38
4.1.2 Markings.............................................................................................................................................................. 38
4.2 Transportation, receipt and handling of shipments............................................................................ 39
4.3 Storage of shipments......................................................................................................................... 40
4.4 Unpacking shipments and checking for transportation damages...................................................... 41
5 Mounting............................................................................................................................ 42
5.1 Preparatory work............................................................................................................................... 42
5.1.1 Fitting mounting flange on transformer cover...................................................................................................... 43
5.1.2 Fitting stud bolts on mounting flange................................................................................................................... 43
5.2 Installing the standard version on-load tap-changer in the transformer............................................ 44
5.2.1 Fastening on-load tap-changer to transformer cover.......................................................................................... 44
5.2.2 Connecting the tap winding and on-load tap-changer take-off lead.................................................................... 56
5.2.3 Carrying out transformer ratio test before drying................................................................................................. 64
5.2.4 Measuring DC resistance on transformer............................................................................................................ 65
5.2.5 Drying on-load tap-changer in autoclave............................................................................................................. 66
5.2.6 Drying on-load tap-changer in transformer tank.................................................................................................. 68
5.2.7 Carrying out transformer ratio test after drying.................................................................................................... 89
5.3 Installing on-load tap-changer in transformer (bell-type tank version)............................................... 90
5.3.1 Inserting on-load tap-changer into supporting structure...................................................................................... 90
5.3.2 Connecting the tap winding and on-load tap-changer take-off lead.................................................................. 100
5.3.3 Carrying out transformer ratio test before drying............................................................................................... 108
5.3.4 Measuring DC resistance on transformer.......................................................................................................... 109
5.3.5 Drying on-load tap-changer in autoclave........................................................................................................... 110
5.3.6 Lifting top part of on-load tap-changer head off supporting flange (bottom part).............................................. 112
5.3.7 Fit the bell-type tank and connect the on-load tap-changer to the top part of the on-load tap-changer head... 121
5.3.8 Drying on-load tap-changer in transformer tank................................................................................................ 134
5.3.9 Carrying out transformer ratio test after drying.................................................................................................. 156
5.4 Filling the oil compartment of the on-load tap-changer with oil....................................................... 157
5.5 Fitting protective devices and drive components............................................................................. 158
5.5.1 Connecting the tap-change supervisory device................................................................................................ 158
5.5.2 Installing protective relay in piping and connecting........................................................................................... 159
5.5.3 Fitting motor-drive unit....................................................................................................................................... 168
Maschinenfabrik Reinhausen GmbH 20174 5293014/00 ENVACUTAP® VR I HD-Ex
Table of contents
5.5.4 Fitting drive shaft............................................................................................................................................... 168
5.5.5 Centering on-load tap-changer and motor-drive unit......................................................................................... 192
5.5.6 Installing electrics for motor-drive unit............................................................................................................... 192
6 Commissioning the on-load tap-changer at the transformer manufacturer's site... 193
6.1 Bleeding on-load tap-changer head and suction pipe..................................................................... 193
6.1.1 Bleeding on-load tap-changer head.................................................................................................................. 193
6.1.2 Bleeding suction pipe on pipe connection S...................................................................................................... 194
6.2 Grounding the on-load tap-changer................................................................................................. 194
6.3 Performing tests on motor-drive unit............................................................................................... 196
6.4 Performing trial tap-change operations........................................................................................... 196
6.5 High-voltage tests on the transformer............................................................................................. 197
7 Transporting transformer to the operating site........................................................... 199
7.1 Transport with removed drive.......................................................................................................... 199
7.2 Transport with oil fill and without oil conservator............................................................................. 199
7.3 Transport without oil fill.................................................................................................................... 200
7.3.1 Emptying oil compartment via pipe connection S.............................................................................................. 200
8 Commissioning the transformer at the operating site................................................ 202
8.1 Checking motor-drive unit................................................................................................................ 202
8.2 Checking protective relay................................................................................................................ 203
8.2.1 Checking protective relay (RS 2001, 2001/V, 2001/H, 2001/E, 2001/5, 2001/R, 2003).................................... 203
8.2.2 Checking protective relay (RS 2004)................................................................................................................. 204
8.3 Filling the oil compartment of the on-load tap-changer with oil....................................................... 204
8.4 Bleeding on-load tap-changer head and suction pipe..................................................................... 206
8.4.1 Bleeding on-load tap-changer head.................................................................................................................. 206
8.4.2 Bleeding suction pipe on pipe connection S...................................................................................................... 207
8.5 Performing trial tap-change operations........................................................................................... 207
8.6 Commissioning the transformer....................................................................................................... 208
9 Fault elimination.............................................................................................................. 209
9.1 Tripping of the protective relay and re-commissioning the transformer........................................... 211
9.1.1 Flap valve in IN SERVICE position................................................................................................................... 212
9.1.2 Flap valve in OFF position................................................................................................................................. 212
9.1.3 Re-commissioning the transformer................................................................................................................... 212
10 Technical data................................................................................................................. 213
Maschinenfabrik Reinhausen GmbH 2017 55293014/00 EN VACUTAP® VR I HD-Ex
Table of contents
10.1 Limit values for dielectric strength and water content of on-load tap-changer oil............................ 214
10.2 Technical data for protective relay................................................................................................... 215
10.2.1 Protective relay with several dry-reed magnetic switches................................................................................. 216
11 Drawings.......................................................................................................................... 217
11.1 VACUTAP® VRC/VRE-Ex, installation drawing (899992)............................................................... 217
11.2 VACUTAP® VRC/VRE-Ex, installation drawing (743600)............................................................... 218
11.3 VACUTAP® VRD/VRF-Ex, installation drawing (899898)............................................................... 219
11.4 VACUTAP® VRD/VRF-Ex, installation drawing (743601)............................................................... 220
11.5 VACUTAP® VRG-Ex, installation drawing (899945)....................................................................... 221
11.6 VACUTAP® VRG-Ex, installation drawing (743602)....................................................................... 222
11.7 VACUTAP® VRC/VRE-Ex, installation position of tap selector connection contacts (727042)...... 223
11.8 VACUTAP® VRC/VRE-Ex, installation position of tap selector connection contacts (743603)...... 224
11.9 VACUTAP® VRD/VRF/VRG-Ex, fine tap selector connection contact and change-over selector
connection contact (899941)........................................................................................................... 225
11.10 VACUTAP® VR-Ex, special design for bell-type tank installation (720781).................................... 226
11.11 VACUTAP® VR-Ex, lifting device for bell-type tank installation (720845)....................................... 227
11.12 VACUTAP® VR-Ex, on-load tap-changer head (720847)............................................................... 228
11.13 Pipe connection Q with tap-change supervisory control (766161).................................................. 229
11.14 VACUTAP® VR-Ex, adjustment positions (728557)....................................................................... 230
11.15 VACUTAP® VRC/VRE-Ex, adjustment plan without change-over selector (719853)..................... 231
11.16 VACUTAP® VRC/VRE-Ex, adjustment plan without change-over selector (742422)..................... 233
11.17 VACUTAP® VRD/VRF-Ex, adjustment plan without change-over selector (721089)..................... 235
11.18 VACUTAP® VRD/VRF-Ex, adjustment plan without change-over selector (742423)..................... 237
11.19 VACUTAP® VRC III/VRC II/VRE III-Ex, adjustment plan with reversing change-over selector
connection (719850)........................................................................................................................ 239
11.20 VACUTAP® VRC I/VRE I-Ex, adjustment plan with reversing change-over selector connection
(719851).......................................................................................................................................... 240
11.21 VACUTAP® VRD/VRF-Ex, adjustment plan with reversing change-over selector connection
(721092).......................................................................................................................................... 241
11.22 VACUTAP® VRD/VRF-Ex, adjustment plan with reversing change-over selector connection
(745024).......................................................................................................................................... 242
11.23 VACUTAP® VRG-Ex, adjustment plan with reversing change-over selector connection (727074).......
243
11.24 VACUTAP® VRG-Ex, adjustment plan with reversing change-over selector connection (742424).......
244
11.25 VACUTAP® VRC/VRE-Ex, adjustment plan with coarse tap selector connection (719852)........... 245
11.26 VACUTAP® VRC/VRE-Ex, adjustment plan with coarse tap selector connection (742425)........... 246
Maschinenfabrik Reinhausen GmbH 20176 5293014/00 ENVACUTAP® VR I HD-Ex
Table of contents
11.27 Adjustment plan VACUTAP® VRC-Ex with multiple coarse change-over selector for change-over
selector division 10, 2-5 coarse tap connections (731412)............................................................. 247
11.28 Adjustment plan VACUTAP® VRC-Ex with multiple coarse change-over selector for change-over
selector division 10, 2-5 coarse tap connections (745032)............................................................. 248
11.29 Adjustment plan VACUTAP® VRC-Ex with multiple coarse change-over selector for change-over
selector division 12, 2-5 coarse tap connections (731411)............................................................. 249
11.30 Adjustment plan VACUTAP® VRC-Ex with multiple coarse change-over selector for change-over
selector division 12, 2-5 coarse tap connections (745031)............................................................. 250
11.31 Adjustment plan VACUTAP® VRC-Ex with multiple coarse change-over selector for change-over
selector division 14, 2-5 coarse tap connections (731410)............................................................. 251
11.32 Adjustment plan VACUTAP® VRC-Ex with multiple coarse change-over selector for change-over
selector division 14, 2-5 coarse tap connections (745030)............................................................. 252
11.33 Adjustment plan VACUTAP® VRC-Ex with multiple coarse change-over selector for change-over
selector division 16, 2-5 coarse tap connections (731000)............................................................. 253
11.34 Adjustment plan VACUTAP® VRC-Ex with multiple coarse change-over selector for change-over
selector division 16, 2-5 coarse tap connections (745029)............................................................. 254
11.35 Adjustment plan VACUTAP® VRC-Ex with multiple coarse change-over selector for change-over
selector division 18, 2-5 coarse tap connections (730977)............................................................. 255
11.36 Adjustment plan VACUTAP® VRC-Ex with multiple coarse change-over selector for change-over
selector division 18, 2-5 coarse tap connections (745028)............................................................. 256
11.37 VACUTAP® VRD/VRF-Ex, adjustment plan with coarse tap selector connection (721091)........... 257
11.38 VACUTAP® VRD/VRF-Ex, adjustment plan with coarse tap selector connection (742426)........... 258
11.39 VACUTAP® VRG-Ex, adjustment plan with coarse tap selector connection (727075)................... 259
11.40 VACUTAP® VRG-Ex, adjustment plan with coarse tap selector connection (742427)................... 260
11.41 Tracing template for on-load tap-changer head (890183)............................................................... 261
11.42 Socket wrench for kerosene drain plug (723015)............................................................................ 262
11.43 Screw tools for installation and maintenance (723016)................................................................... 263
11.44 Bevel gear CD 6400, dimensional drawing (892916)...................................................................... 264
Maschinenfabrik Reinhausen GmbH 2017 75293014/00 EN VACUTAP® VR I HD-Ex

1 Introduction

Introduction
1
This technical file contains detailed descriptions of the safe and proper in­stallation, connection, and commissioning of the product.
It also includes safety instructions and general information about the prod­uct.
Information about operation can be found in the operating instructions.
This technical file is intended solely for specially trained and authorized per­sonnel.

Manufacturer

1.1
The product is manufactured by:
Maschinenfabrik Reinhausen GmbH
Falkensteinstraße 8 93059 Regensburg, Germany Tel.: (+49) 9 41/40 90-0 Fax: (+49) 9 41/40 90-7001 E-mail: sales@reinhausen.com
Further information on the product and copies of this technical file are avail­able from this address if required.

Subject to change without notice

1.2
The information contained in this technical file comprises the technical speci­fications approved at the time of printing. Significant modifications will be in­cluded in a new edition of the technical file.
The document number and version number of this technical file are shown in the footer.

Completeness

1.3
This technical file is incomplete without the supporting documents.
The following documents apply:
Unpacking instructions (included in the scope of delivery)
Supplement (included in the scope of delivery)
Routine test report (included in the scope of delivery)
Connection diagrams (included in the scope of delivery)
Dimensional drawings (included in the scope of delivery)
Technical data - General section (available on request)
Technical data - Product-specific section (available on request)
Maschinenfabrik Reinhausen GmbH 20178 5293014/00 ENVACUTAP® VR I HD-Ex
1 Introduction

Safekeeping

1.4
Keep this technical file and all supporting documents ready at hand and ac­cessible for future use at all times.

Notation conventions

1.5
This section contains an overview of the symbols and textual emphasis used.
1.5.1

Symbols

Symbol Meaning
Wrench size
Tightening torque
Number and type of fastening material used
Fill with oil
Cut open, cut through
Clean
Visual inspection
Use your hand
Adapter ring
Apply a coat of paint
Use a file
Grease
Maschinenfabrik Reinhausen GmbH 2017 95293014/00 EN VACUTAP® VR I HD-Ex
Symbol Meaning
Coupling bolt
Use a ruler
Use a saw
Hose clip
Wire eyelet, safety wire
Use a screwdriver
1 Introduction
WARNING
1.5.2
1.5.2.1
Apply adhesive
Lock tab
Table 1: Symbols

Hazard communication system

Warnings in this technical file are displayed as follows.
Warning relating to section
Warnings relating to sections refer to entire chapters or sections, sub-sec­tions or several paragraphs within this technical file. Warnings relating to sections use the following format:
Type and source of danger
Consequences
► Action
► Action
1.5.2.2
Embedded warning information
Embedded warnings refer to a particular part within a section. These warn­ings apply to smaller units of information than the warnings relating to sec­tions. Embedded warnings use the following format:
Maschinenfabrik Reinhausen GmbH 201710 5293014/00 ENVACUTAP® VR I HD-Ex
1 Introduction
DANGER! Instruction for avoiding a dangerous situation.
1.5.2.3
Signal words and pictograms
The following signal words are used:
Signal
Meaning
word
DANGER Indicates a hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING Indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION Indicates a hazardous situation which, if not avoided, could
result in injury.
NOTICE Indicates measures to be taken to prevent damage to
property.
Table 2: Signal words in warning notices
Pictograms warn of dangers:
Pictogram Meaning
Warning of a danger point
Warning of dangerous electrical voltage
1.5.3
Warning of combustible substances
Warning of danger of tipping
Table 3: Pictograms used in warning notices

Information system

Information is designed to simplify and improve understanding of particular procedures. In this technical file it is laid out as follows:
Maschinenfabrik Reinhausen GmbH 2017 115293014/00 EN VACUTAP® VR I HD-Ex
Important information.
1 Introduction
Maschinenfabrik Reinhausen GmbH 201712 5293014/00 ENVACUTAP® VR I HD-Ex

2 Safety

Safety
2
This technical file contains detailed descriptions on the safe and proper in­stallation, connection, commissioning and monitoring of the product.
Read this technical file through carefully to familiarize yourself with the
product.
This technical file is part of the product.
Read and observe the safety instructions provided in this chapter in par-
ticular.
Observe the warnings in this technical file in order to avoid function-re-
lated dangers.
The product is manufactured on the basis of state-of-the-art technology.
Nevertheless, risks to life and limb of the user or impairment of the prod­uct and other material assets may occur during use due to function-re­lated dangers.

Appropriate use

2.1
The product is an on-load tap-changer and keeps the output voltage of a transformer constant. The product is designed solely for use in electrical en­ergy systems and facilities. If used as intended and in compliance with the requirements and conditions specified in this technical file as well as the warning notices in this technical file and attached to the product, then the product does not present any danger to people, property or the environment. This applies across the entire service life of the product, from delivery to in­stallation and operation through to disassembly and disposal.
The following is considered appropriate use:
Use the product only with the transformer specified in the order.
The serial numbers of on-load tap-changers and on-load tap-changer
accessories (drive, drive shaft, bevel gear, protective relay, etc.) must match if the on-load tap-changers and on-load tap-changer accessories are supplied as a set for one order.
You will find the standard valid for the product and the year of issue on
the nameplate.
Operate the product in accordance with this technical file, the agreed-
upon delivery conditions and the technical data.
Ensure that all necessary work is performed by qualified personnel only.
Only use the equipment and special tools included in delivery for the in-
tended purpose and in accordance with the specifications of this techni­cal file.
The on-load tap-changer is not intended to be used with an oil filter unit.
The measures described in this technical file must be taken in order to
comply with explosion protection requirements.
Maschinenfabrik Reinhausen GmbH 2017 135293014/00 EN VACUTAP® VR I HD-Ex

Fundamental safety instructions

2.2
To prevent accidents, disruptions and damage as well as unacceptable ad­verse effects on the environment, those responsible for transport, installa­tion, operation, maintenance and disposal of the product or parts of the prod­uct must ensure the following:
Personal protective equipment
Loosely worn or unsuitable clothing increases the danger of becoming trap­ped or caught up in rotating parts and the danger of getting caught on pro­truding parts. This increases the danger to life and limb.
All necessary devices and personal protective equipment required for
the specific task, such as a hard hat, safety footwear, etc. must be worn. Observe the section "Personal protective equipment" [ 23].
Never wear damaged personal protective equipment.
Never wear rings, necklaces, or other jewelry.
If you have long hair, wear a hairnet.
2 Safety
Work area
Untidy and poorly lit work areas can lead to accidents.
Keep the work area clean and tidy.
Make sure that the work area is well lit.
Observe the applicable laws for accident prevention in the relevant
country.
Working during operation
You must only operate the product when it is in a sound operational condi­tion. Otherwise it poses a danger to life and limb.
Regularly check the operational reliability of safety equipment.
Comply with the maintenance work and maintenance intervals descri-
bed in this technical file.
Explosion protection
Highly flammable or explosive gases, vapors and dusts can cause serious explosions and fire.
Do not install the product in potentially explosive areas.
Safety markings
Warning signs and safety information plates are safety markings on the product. They are an important aspect of the safety concept.
Observe all safety markings on the product.
Make sure all safety markings on the product remain intact and legible.
Replace safety markings that are damaged or missing.
Maschinenfabrik Reinhausen GmbH 201714 5293014/00 ENVACUTAP® VR I HD-Ex
2 Safety
Ambient conditions
To ensure reliable and safe operation, the product must only be operated under the ambient conditions specified in the technical data.
Observe the specified operating conditions and requirements for the in-
stallation location.
Auxiliary materials and operating materials
Auxiliary materials and operating materials not approved by Maschinenfabrik Reinhausen GmbH could damage the product.
Only use lubricants and auxiliary materials approved by the manufactur-
er.
Contact Maschinenfabrik Reinhausen GmbH.
Modifications and conversions
Unauthorized or inappropriate changes to the product may lead to personal injury, material damage and operational faults.
Only modify product following consultation with Maschinenfabrik Rein-
hausen GmbH.
2.3
2.3.1
Spare parts
Spare parts not approved by Maschinenfabrik Reinhausen GmbH may cause physical injury and damage the product.
Only use spare parts approved by the manufacturer.
Contact Maschinenfabrik Reinhausen GmbH.

Standards and regulations

The standards and regulations which apply to the explosion-protected prod­uct are described in the following chapters.

Application range of the on-load tap-changer

The on-load tap-changer is certified for Ex II 3G Ex nAC IIC T3 Gc. Refer to the following overview for the resulting application range.
1 2 3 4 5 6 7 8
II 3G Ex nAC IIC T3 Gc
Table 4: Example of the application range
Number Meaning
1 Sign for explosion protection
2 Equipment group
3 Equipment category
Maschinenfabrik Reinhausen GmbH 2017 155293014/00 EN VACUTAP® VR I HD-Ex
Number Meaning
4 Ex: Symbol for explosion-protected equipment
5 Ignition protection type
6 Explosion group
7 Temperature class
8 EPL (Equipment Protection Level)
Equipment groups (number 2)
I Equipment in this category is intended for use in under-
ground parts of mines as well as those parts of surface in­stallations of such mines endangered by firedamp and/or combustible dust.
II Equipment in this category is intended for use in other
areas in which explosive atmospheres may be present.
Table 5: Equipment groups
2 Safety
Equipment category / zone classification (number 3)
Designa­tion for gases
1G
(0)
Designa­tion for dusts
1D
(20)
Definition
Equipment in this category is intended for use in areas in which explosive atmospheres caused by mixtures of air and gases, vapors or mists or by air/dust mixtures are present continuously, for long periods or frequently.
2G
(1)
2D
(21)
Equipment in this category is intended for use in areas in which explosive atmospheres caused by gases, vapors, mists or air/dust mixtures occur occasionally.
3G
(2)
3D
(22)
Equipment in this category is intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air/dust mixtures are unlikely to occur or, if they do occur, are likely to do so only infrequently and for a short period only.
Table 6: Equipment category / zone classification
Ignition protection types (number 5)
d Pressure-proof enclosure
e Increased safety
I Intrinsic safety (ia, ib)
m Encapsulation
o Oil immersion
p Pressurized apparatus
Maschinenfabrik Reinhausen GmbH 201716 5293014/00 ENVACUTAP® VR I HD-Ex
2 Safety
q Powder filling
n Ignition protection type "n" (only zone 2)
n A: non-sparking equipment
n C: sparking equipment with special protection for con­tacts
n R: vapor-protected housing
Table 7: Ignition protection types
Explosion group (number 6)
EN/IEC Gases, vapors (examples) Min. ignition energy
(mJ)
IIA Ammonia -
IIA Acetic acid, acetone, benzene,
0.18 diesel, ethane, ether, fuel oil, hex­ane, methane, petrol, petroleum, propane
IIB Ethylene, isoprene, town gas 0.06
IIC Acetylene, carbon disulfide, hy-
0.02 drogen
Table 8: Explosion groups
Temperature classes (number 7)
Tempera­ture class
Maximum equipment surface temperature
Ignition tempera­ture of the flamma­ble substances
T1 450 °C > 450 °C
T2 300 °C > 300 °C < 450 °C
T3 200 °C > 200 °C < 300 °C
T4 135 °C > 135 °C < 200 °C
T5 100 °C > 100 °C < 135 °C
T6 85 °C > 85 °C < 100 °C
Table 9: Temperature classes
Equipment protection level (EPL) (number 8)
The EPL indicates the level of protection defined for a device based on the level of probability of ignition and taking account of the differences between potentially explosive gas atmospheres, potentially explosive dust atmos­pheres, and potentially explosive atmospheres in mine workings affected by firedamp.
Maschinenfabrik Reinhausen GmbH 2017 175293014/00 EN VACUTAP® VR I HD-Ex
2 Safety
2.3.2
2.4
2.4.1
2.4.1.1

Standards and regulations

The following standards and regulations apply to explosion-proof on-load tap-changers:
EN 60079-0: Equipment – General requirements
EN 60079-15: Equipment protection by type of protection "n"
Additional requirements apply to vacuum interrupters, as these are her-
metically sealed devices that generate arcs, sparks or hot surfaces.
Additional requirements apply to the diverter switch oil compartment, as
this is a sealed or encapsulated device that generates arcs, sparks or hot surfaces.

Measures for ensuring compliance with explosion protection requirements

Measures taken by the manufacturer

Maschinenfabrik Reinhausen has taken the following measures for ensuring compliance with explosion protection requirements. You do not need to take any special measures in this regard.
Quality of the insulating oil in the on-load tap-changer
2.4.1.2
2.4.2
The quality of the insulating oil required by IEC 60296 and the quality of the synthetic esters required by IEC 61099 in the oil compartment of the on-load tap-changer is ensured by using vacuum cells in transition resistors.
Monitoring the oil temperature in the diverter switch oil compartment
A temperature sensor is provided in the on-load tap-changer head cover for monitoring the oil temperature in the diverter switch oil compartment. The corresponding temperature monitoring relay is in the TAPMOTION® ED-Ex.
Temperature monitoring prevents further switching of the on-load tap-chang­er when the maximum permitted temperature is reached. This maximum per­mitted temperature is factory-configured for each specific order for all on­load tap-changer types (maximum 130 °C) and secured against accidental incorrect adjustment.

Measures to be taken by the transformer manufacturer/operator

The following measures for ensuring compliance with explosion protection requirements must be taken by the transformer manufacturer/operator.
Maschinenfabrik Reinhausen GmbH 201718 5293014/00 ENVACUTAP® VR I HD-Ex
2 Safety
2.4.2.1
Prescribed protective and drive components
Operate the on-load tap-changer only in conjunction with the following com­ponents:
Ex protective relay
Ex motor-drive unit
Ex drive shaft
Maschinenfabrik Reinhausen GmbH 2017 195293014/00 EN VACUTAP® VR I HD-Ex
2 Safety
2.4.2.2
Setting up the on-load tap-changer oil system
Operate the on-load tap-changer only with a suitable oil system. This divert­er switch oil system consists of the diverter switch oil compartment, protec­tive relay, and oil conservator of the on-load tap-changer. It ensures that enough insulating oil is present in the diverter switch oil compartment at all times.
2.4.2.3
Figure 1: On-load tap-changer oil system
1 Diverter switch oil compart-
5 Signaling contacts
ment
2 Temperature sensor 6 Oil conservator
3 Protective relay 7 Dehydrating breather
4 Level indicator
Oil conservator to be used
The oil conservator of the on-load tap-changer ensures that sufficient insu­lating oil is present in the on-load tap-changer oil system at all times during operation.
Therefore, operate the on-load tap-changer only with a oil conservator that fulfills the following requirements:
Maschinenfabrik Reinhausen GmbH 201720 5293014/00 ENVACUTAP® VR I HD-Ex
2 Safety
2.4.2.3.1
2.4.2.3.2
2.4.2.3.3
2.4.2.3.4
Dehydrating breather
The oil conservator must be equipped with a dehydrating breather in accord­ance with VDE 0532-216-5. The dehydrating breather prevents water, impur­ities, insects etc. from entering the insulating oil.
Level indicator
The oil conservator must have a level indicator from which the minimum oil quantity required and the maximum quantity permitted, as well as the current oil level, can be read.
Level monitoring
The oil level in the oil conservator must be monitored at all times during op­eration. Therefore, loop the signaling contact for falling below the minimum oil level in the on-load tap-changer's oil conservator to the tripping circuit of the circuit breaker so that the circuit breaker will immediately de-energize the transformer when the oil level in the oil conservator falls below this minimum.
Insulating oil to be used
When filling the diverter switch oil compartment and its oil conservator, use only new mineral insulating oil for transformers in accordance with IEC 60296 (Specification for unused mineral insulating oils for transformers and switchgear) or synthetic ester in accordance with IEC 61099 (Specifications for unused synthetic organic esters for electrical purposes).
2.4.2.3.5
Checking the quality of the insulating oil in the Ex transformer
During the tap changes, polarity sparks (low energy) may occur at the tap selector of the on-load tap-changer in the transformer tank. In this regard, observe Section 5.1.6 and 5.1.7 in the on-load tap-changer standard IEC
60214.
Therefore, check the quality and dielectric strength of the insulating oil in the transformer tank on a regular basis and comply with the service intervals for the oil change.
Maschinenfabrik Reinhausen GmbH 2017 215293014/00 EN VACUTAP® VR I HD-Ex
2 Safety
2.4.2.4
Corrosion protection measures
Because further installation steps are required before operation of the on­load tap-changer, sufficient corrosion protection cannot be provided at cer­tain interfaces to the transformer when the device leaves the factory.
Figure 2: On-load tap-changer head
1 Sealing surface on piping con-
nection flange
2 Air-vent valve 4 Through-holes
3 Contact surface on on-load
tap-changer head
The sealing surfaces on the piping connection flange are zinc-plated ex fac­tory. The through-holes are zinc-plated and partially painted.
The contact surface of the on-load tap-changer head is primed ex factory. The through-holes are primed and partially painted.
The transformer manufacturer is responsible for the design of the mating surfaces on the transformer and piping and that of the screw connections needed for these attachments.
1. Provide suitable sealing to prevent electrolytes from entering sealing surfaces and holes.
2. Design screws, washers, nuts etc. in A4 in accordance with ISO 3506-1/ISO 3506-2 standard.
3. If the painted surfaces are damaged, note repair instructions. These can be requested from Maschinenfabrik Reinhausen GmbH's Technical Service department.

Personnel qualification

2.5
The person responsible for assembly, commissioning, operation, mainte­nance and inspection must ensure that the personnel are sufficiently quali­fied.
Maschinenfabrik Reinhausen GmbH 201722 5293014/00 ENVACUTAP® VR I HD-Ex
2 Safety
Electrically skilled person
The electrically skilled person has a technical qualification and therefore has the required knowledge and experience, and is also conversant with the ap­plicable standards and regulations. The electrically skilled person is also pro­ficient in the following:
Can identify potential dangers independently and is able to avoid them.
Is able to perform work on electrical systems.
Is specially trained for the working environment in which (s)he works.
Must satisfy the requirements of the applicable statutory regulations for
accident prevention.
Electrically trained persons
An electrically trained person receives instruction and guidance from an electrically skilled person in relation to the tasks undertaken and the poten­tial dangers in the event of inappropriate handling as well as the protective devices and safety measures. The electrically trained person works exclu­sively under the guidance and supervision of an electrically skilled person.
Operator
The operator uses and operates the product in line with this technical file. The operating company provides the operator with instruction and training on the specific tasks and the associated potential dangers arising from im­proper handling.
Technical Service
We strongly recommend having maintenance, repairs and retrofitting carried out by our Technical Service department. This ensures that all work will be performed correctly. If maintenance is not carried out by our Technical Serv­ice department, please ensure that the personnel who carry out the mainte­nance are trained and authorized by Maschinenfabrik Reinhausen GmbH to carry out the work.
Authorized personnel
Authorized personnel are trained by Maschinenfabrik Reinhausen GmbH to carry out special maintenance.

Personal protective equipment

2.6
Personal protective equipment must be worn during work to minimize risks to health.
Always wear the personal protective equipment required for the job at
hand.
Never wear damaged personal protective equipment.
Observe information about personal protective equipment provided in
the work area.
Maschinenfabrik Reinhausen GmbH 2017 235293014/00 EN VACUTAP® VR I HD-Ex
2 Safety
Personal protective equipment to be worn at all times
Protective clothing
Close-fitting work clothing with a low tear­ing strength, with tight sleeves and with no protruding parts. It mainly serves to pro­tect the wearer against being caught by moving machine parts.
Safety shoes
To protect against falling heavy objects and slipping on slippery surfaces.
Special personal protective equipment for particular environments
Safety glasses
To protect the eyes from flying parts and splashing liquids.
Visor
To protect the face from flying parts and splashing liquids or other dangerous sub­stances.
Hard hat
To protect from falling and flying parts and materials.
Hearing protection
To protect from hearing damage.
Protective gloves
To protect from mechanical, thermal, and electrical hazards.
Maschinenfabrik Reinhausen GmbH 201724 5293014/00 ENVACUTAP® VR I HD-Ex

3 Product description

Product description
3
This chapter contains an overview of the design and function of the product.

Scope of delivery

3.1
The product is packaged with protection against moisture and is usually de­livered as follows:
Oil compartment with on-load tap-changer head and built-in diverter
switch insert
Selector
Ex motor-drive unit
Ex drive shaft with coupling parts and bevel gear
Ex protective relay
Technical files
Please refer to the delivery slip for full details of scope of delivery.
Single-phase on-load tap-changers are also available as an on-load tap­changer set with a common motor-drive unit.
3.2.1
Note the following information:
Check the shipment for completeness on the basis of the shipping docu-
ments.
Store the parts in a dry place until installation
The product must remain in its airtight, protective wrapping and may on-
ly be removed immediately before installation
You will find more information in the "Packaging, transport, and storage" [ 38] chapter.

On-load tap-changer

3.2

Function description

On-load tap-changers are used to adjust the transmission ratio of transform­ers without interrupting the load flow. Fluctuations in voltage occurring in the power transmission grid, for example, can therefore be compensated for. For this purpose, on-load tap-changers are fitted in transformers and connected to the active part of the transformer.
Maschinenfabrik Reinhausen GmbH 2017 255293014/00 EN VACUTAP® VR I HD-Ex
3 Product description
A motor-drive unit, which receives a control impulse (e.g. from a voltage reg­ulator), changes the on-load tap-changer's operating position, which adapts the transmission ratio of the transformer to the respective operating require­ments.
3.2.2
Figure 3: System overview of on-load tap-changer Transformer
1 Transformer tank 6 Upper gear unit
2 Motor-drive unit 7 On-load tap-changer
3 Vertical drive shaft 8 RS protective relay
4 Bevel gear 9 Oil conservator
5 Horizontal drive shaft 10 Active part of the transformer

Setup/models

The on-load tap-changer consists of the on-load tap-changer head, oil com­partment with built-in diverter switch insert and the tap selector mounted be­low (also available with change-over selector on request).
The design and designation of the most important on-load tap-changer com­ponents are shown in the installation drawings in the appendix.
Maschinenfabrik Reinhausen GmbH 201726 5293014/00 ENVACUTAP® VR I HD-Ex
3 Product description
For the number of maximum operating positions of the on-load tap-changer, refer to the Technical data.
Figure 4: VACUTAP® VRC/VRE
1 On-load tap-changer head 3 Tap selector
2 Oil compartment 4 Change-over selector
Maschinenfabrik Reinhausen GmbH 2017 275293014/00 EN VACUTAP® VR I HD-Ex
3 Product description
Figure 5: VACUTAP® VRD/VRF
1 On-load tap-changer head 3 Tap selector
2 Oil compartment 4 Change-over selector
Maschinenfabrik Reinhausen GmbH 201728 5293014/00 ENVACUTAP® VR I HD-Ex
3 Product description
3.2.2.1
Figure 6: VACUTAP® VRG
1 On-load tap-changer head 3 Tap selector
2 Oil compartment 4 Change-over selector
Pipe connections
The on-load tap-changer head features 4 pipe connections for different pur­poses.
Maschinenfabrik Reinhausen GmbH 2017 295293014/00 EN VACUTAP® VR I HD-Ex
3 Product description
Depending on the order, some or all of these pipe connections are fitted with pipe bends ex factory. All pipe bends without terminal box for the tap-change supervisory control can be freely swiveled once the pressure ring is loos­ened.
Figure 7: Pipe connections with pipe bends
Pipe connection Q
Pipe connection Q is sealed off with a blank cover and, depending on the on-load tap-changer type, is intended for the bushing of the tap-change su­pervisory device supplied as an option.
The functions of the R and Q pipe connections can be interchanged.
Pipe connection S
The pipe bend on pipe connection S features a vent screw and can be con­nected to a pipe that ends with a drain valve on the side of the transformer tank at operating height. If the on-load tap-changer is fitted with an oil suc­tion pipe, the on-load tap-changer can be completely emptied via pipe con­nection S.
Pipe connection R
Pipe connection R is provided for attachment of the protective relay and con­nection of the on-load tap-changer oil conservator and can be interchanged with pipe connection Q.
Pipe connection E2
The pipe connection E2 is sealed off with a blank cover. It leads into the oil tank of the transformer, directly under the on-load tap-changer head and can be connected to a collective pipe for the Buchholz relay, if necessary. This pipe connection serves a further purpose, namely to equalize the pressure
Maschinenfabrik Reinhausen GmbH 201730 5293014/00 ENVACUTAP® VR I HD-Ex
Loading...
+ 236 hidden pages