3 Mounting
Maschinenfabrik Reinhausen 2013 72349487/01 EN TAPGUARD® 260
7. Wire sensor connecting lead in the temperature sensor as shown in the
connection diagram.
8. Close temperature sensor cover.
When you close the temperature sensor cover, make sure that the seal is
correctly positioned and that no connecting leads are wedged in.
9. Ground the temperature sensor housing on the on-load tap-changer using the grounding cable.
The temperature sensor is connected. Please continue with the next section
to connect the transformer oil sensor.
Connecting temperature sensor for transformer oil
You have to perform the wiring in accordance with the connection diagram
that came with the motor-drive unit.
Do not loop the temperature sensor connecting leads when laying because
this may cause voltage coupling and result in measurement errors.
1. Open the transformer thermometer case.
2. Fill the thermometer case with oil until the heat conduction sensor is
completely immersed in oil.
3. Place the shielding of the sensor connecting lead on the grounding rails
in the motor-drive unit.
4. Connect the sensor connecting lead to the terminals in the motor-drive
unit as shown in the connection diagram.
5. Remove the temperature sensor cover.
6. Remove the shielding for the sensor connecting lead on the transformer
oil sensor.
7.
NOTICE! Do not place shielding in temperature sensor. Insulate tem-
perature sensor connecting leads using shrink tubing such that the
shielding is no longer exposed. If this is not done, current may flow via
the shielding and the device may be damaged.
8.
NOTICE! Guide connecting leads into temperature sensor. Ensure that
the cable entry point is watertight. If not, the temperature sensor may be
damaged.
9. Wire sensor connecting lead in the temperature sensor as shown in the
connection diagram.
10. Mount the temperature sensor cover.
3.1.2