MR TAPGUARD 260 Quick Reference Manual

Monitoring System TAPGUARD® 260
Quick Reference Guide
2349487/01 EN
1 Introduction
Maschinenfabrik Reinhausen 20132 2349487/01 ENTAPGUARD® 260
This quick reference guide contains information for quick start-up of the de­vice. It does not provide comprehensive operating instructions.
Manufacturer
The product is manufactured by:
Maschinenfabrik Reinhausen GmbH
Falkensteinstraße 8 93059 Regensburg, Germany Tel.: (+49) 9 41/40 90-0 Fax: (+49) 9 41/40 90-7001 E-mail: sales@reinhausen.com
Further information on the product and copies of this technical file are availa­ble from this address if required.
Completeness
This technical file is incomplete without the supporting documentation.
Supporting documents
The following documents apply to this product:
Operating instructions
Quick reference guide
Connection diagrams
Also observe generally valid legislation, standards, guidelines and specifica­tions on accident prevention and environmental protection in the respective country of use.
1
1.1
1.2
1.3
2 Product description
Maschinenfabrik Reinhausen 2013 32349487/01 EN TAPGUARD® 260
Product description
This chapter contains an overview of the design and function of the product.
Operating concept
The monitoring system is operated by keys for parameterization and configu­ration on the front panel of the device. Alternatively, configuration is also possible via the TAPCON®-trol visualization software.
The monitoring system is equipped with a key lock to prevent unintentional
operation. To activate or deactivate, press the and keys simultaneously.
Manual mode
Manual mode is an additional safety feature of the monitoring system and protects the parameters from being unintentionally changed.
The following activities cannot be performed until you have activated manual mode:
Acknowledging events
Acknowledging maintenance
Changing parameters
You can change the parameters regardless of manual mode via the visuali­zation software TAPCON®-trol.
To activate manual mode, proceed as follows:
► Press .
ð The relevant LED lights up.
Manual mode is activated. If no key on the monitoring system has been pressed after more than 5 minutes, manual mode is automatically deactivat­ed.
Serial interface
The parameters for the device can be set using a PC. The COM 1 (RS232) serial interface on the front panel is provided for this purpose. You can use the connection cable supplied to establish a connection to your PC via the RS232 or USB port (using the optional USB adapter).
TAPCON®-trol software is needed for parameterization via the serial inter­face. The software and the related operating instructions are contained on the CD provided.
2
2.1
2.2
2 Product description
Maschinenfabrik Reinhausen 20134 2349487/01 ENTAPGUARD® 260
Figure 1: Device connection to a PC
3 Mounting
Maschinenfabrik Reinhausen 2013 52349487/01 EN TAPGUARD® 260
Mounting
This chapter describes how to correctly mount and connect the device. Note the connection diagrams provided.
WARNING
Electric shock
Danger of death due to electrical voltage.
► De-energize device and system periphery and lock to prevent switching
back on again.
Installing and wiring temperature sensors
The following sections describe how to install and wire the temperature sen­sors for the diverter switch oil and the transformer oil.
Connecting temperature sensor for on-load tap-changer oil
A temperature sensor is mounted in the on-load tap-changer head cover in each on-load tap-changer. You have to perform the wiring in accordance with the connection diagram that came with the motor-drive unit. Please ob­serve the following:
Do not loop the temperature sensor connecting leads when laying because this may cause voltage coupling and result in measurement errors.
To connect the temperature sensor for the on-load tap-changer oil, proceed as follows:
1. Place the shielding of the sensor connecting lead on the grounding rails in the motor-drive unit.
2. Connect the sensor connecting lead to the terminals in the motor-drive unit as shown in the connection diagram.
3
3.1
3.1.1
3 Mounting
Maschinenfabrik Reinhausen 20136 2349487/01 ENTAPGUARD® 260
3. Remove the temperature sensor cover on the on-load tap-changer head cover.
Figure 2: Removing temperature sensor cover
4. Remove the shielding of the sensor connecting lead on the temperature sensor.
5.
NOTICE! Do not place shielding in temperature sensor. Insulate tem-
perature sensor connecting leads using shrink tubing such that the shielding is no longer exposed. If this is not done, current may flow via the shielding and the device may be damaged.
Figure 3: Correct insulation of connecting lead shielding
1 Exposed shielding 2 Correctly insulated connecting
lead
6. NOTICE! Guide connecting leads into temperature sensor. Ensure that the cable entry point is watertight. If not, the temperature sensor may be damaged.
3 Mounting
Maschinenfabrik Reinhausen 2013 72349487/01 EN TAPGUARD® 260
7. Wire sensor connecting lead in the temperature sensor as shown in the connection diagram.
8. Close temperature sensor cover.
When you close the temperature sensor cover, make sure that the seal is correctly positioned and that no connecting leads are wedged in.
9. Ground the temperature sensor housing on the on-load tap-changer us­ing the grounding cable.
The temperature sensor is connected. Please continue with the next section to connect the transformer oil sensor.
Connecting temperature sensor for transformer oil
You have to perform the wiring in accordance with the connection diagram that came with the motor-drive unit.
Do not loop the temperature sensor connecting leads when laying because this may cause voltage coupling and result in measurement errors.
1. Open the transformer thermometer case.
2. Fill the thermometer case with oil until the heat conduction sensor is completely immersed in oil.
3. Place the shielding of the sensor connecting lead on the grounding rails in the motor-drive unit.
4. Connect the sensor connecting lead to the terminals in the motor-drive unit as shown in the connection diagram.
5. Remove the temperature sensor cover.
6. Remove the shielding for the sensor connecting lead on the transformer oil sensor.
7.
NOTICE! Do not place shielding in temperature sensor. Insulate tem-
perature sensor connecting leads using shrink tubing such that the shielding is no longer exposed. If this is not done, current may flow via the shielding and the device may be damaged.
8.
NOTICE! Guide connecting leads into temperature sensor. Ensure that
the cable entry point is watertight. If not, the temperature sensor may be damaged.
9. Wire sensor connecting lead in the temperature sensor as shown in the connection diagram.
10. Mount the temperature sensor cover.
3.1.2
Loading...
+ 15 hidden pages