unless expressly permitted.
Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents,
utility models or designs.
The product may have been altered since this document was published.
We reserve the right to change the technical data, design and scope of supply.
Generally the information provided and agreements made when processing the individual quotations and orders
are binding.
The original operating instructions were written in German.
1.6.1Hazard communication system ........................................................................................................................... 10
1.6.2Information system .............................................................................................................................................. 11
2.1General safety information ................................................................................................................ 12
2.2Appropriate use ................................................................................................................................. 12
3.1Scope of delivery ............................................................................................................................... 14
3.2Function description of the voltage regulation ................................................................................... 14
3.3Performance features ........................................................................................................................ 15
3.5.3Display elements ................................................................................................................................................. 18
4.3.4Connecting cables to the system periphery ........................................................................................................ 37
5.2.1Setting the language ........................................................................................................................................... 40
5.2.2Setting date and time .......................................................................................................................................... 40
5.2.3Setting further parameters................................................................................................................................... 41
5.3.1Checking control functions .................................................................................................................................. 43
6.3.1Setting device ID ................................................................................................................................................. 53
6.3.2Setting the baud rate ........................................................................................................................................... 53
6.3.3Setting the voltage display kV/V.......................................................................................................................... 54
6.3.4Setting current display unit .................................................................................................................................. 54
6.3.5Setting the switching pulse time .......................................................................................................................... 54
6.3.6Configuring control inputs IO1-X1:33/31 ............................................................................................................. 56
6.3.7Configuring output relays IO1-X1:25/26 and IO1-X1:23/24 ................................................................................ 57
6.3.9Setting motor runtime monitoring ........................................................................................................................ 59
6.3.10Swapping tapping direction ................................................................................................................................. 61
6.5.1Setting desired value 1...3................................................................................................................................... 65
6.5.3Setting delay time T1........................................................................................................................................... 66
6.5.4Setting control response T1 ................................................................................................................................ 67
6.5.5Setting delay time T2........................................................................................................................................... 68
6.6.5Activating/deactivating function monitoring ......................................................................................................... 75
6.8.1Setting desired value for regulator 2 ................................................................................................................... 80
6.8.2Setting undervoltage limit value V< for regulator 2.............................................................................................. 81
6.8.3Setting overvoltage limit value V> for regulator 2................................................................................................ 82
6.8.4Setting delay time for error message .................................................................................................................. 83
6.8.5Setting transformer for regulator 2 ...................................................................................................................... 83
6.9Transformer data ............................................................................................................................... 84
6.9.1Setting the primary transformer voltage .............................................................................................................. 85
6.9.2Setting the secondary transformer voltage.......................................................................................................... 85
6.9.4Setting the current transformer connection ......................................................................................................... 87
6.9.5Setting the phase difference for the current transformer/voltage transformer..................................................... 87
6.10Parallel operation of several banks of transformers .......................................................................... 91
6.10.1Assigning CAN bus address................................................................................................................................ 91
6.13Measuring transducer function ........................................................................................................ 100
6.13.1Linking measured value with output .................................................................................................................. 100
6.13.3Assigning maximum physical parameter........................................................................................................... 101
6.13.4Assigning minimum absolute value ................................................................................................................... 101
6.13.5Assigning maximum absolute value .................................................................................................................. 102
6.14.3Setting time difference of average value interval .............................................................................................. 105
6.15.1Assigning a network mask................................................................................................................................. 115
6.15.3Entering the time server address ...................................................................................................................... 116
6.15.5Entering IED name ............................................................................................................................................ 117
6.16.1Selecting the communication port ..................................................................................................................... 117
6.16.2Selecting communication baud rate .................................................................................................................. 118
6.16.4Assigning the TCP port ..................................................................................................................................... 119
6.16.5Setting the transmission delay time for the RS485 interface............................................................................. 119
6.17Displaying information about device ................................................................................................ 120
6.17.1Displaying the info screen ................................................................................................................................. 120
6.17.3Carrying out LED test ........................................................................................................................................ 121
6.17.4Displaying input/output status ........................................................................................................................... 121
6.17.5Displaying UC card status ................................................................................................................................. 122
6.17.9Displaying data on CAN bus ............................................................................................................................. 123
6.17.10 Displaying measured value memory ................................................................................................................. 125
Further information on the product and copies of this technical file are available from this address if required.
Subject to change without notice
1.2
The information contained in this technical file comprises the technical specifications approved at the time of printing. Significant modifications will be included in a new edition of the technical file.
The document number and version number of this technical file are shown in
the footer.
Completeness
1.3
This technical file is incomplete without the supporting documentation.
Supporting documents
1.4
The following documents apply to this product:
▪Operating instructions
▪Connection diagrams
Also observe generally valid legislation, standards, guidelines and specifications on accident prevention and environmental protection in the respective
country of use.
This technical file and all supporting documents must be kept ready at hand
and accessible for future use at all times.
Notation conventions
1.6
This section contains an overview of the symbols and textual emphasis
used.
WARNING
1.6.1
1.6.1.1
1.6.1.2
Hazard communication system
Warnings in this technical file are displayed as follows.
Warning relating to section
Warnings relating to sections refer to entire chapters or sections, sub-sections or several paragraphs within this technical file. Warnings relating to
sections use the following format:
Type and source of danger
Consequences
► Action
► Action
Embedded warning information
Embedded warnings refer to a particular part within a section. These warnings apply to smaller units of information than the warnings relating to sections. Embedded warnings use the following format:
DANGER! Instruction for avoiding a dangerous situation.
1.6.1.3
Signal words and pictograms
The following signal words are used:
Signal
word
DANGERIndicates a hazardous situation which, if not avoided, will
WARNINGIndicates a hazardous situation which, if not avoided, could
CAUTIONIndicates a hazardous situation which, if not avoided, could
NOTICEIndicates measures to be taken to prevent damage to
The technical file contains detailed descriptions on the safe and proper installation, connection, commissioning and monitoring of the product.
▪Read this technical file through carefully to familiarize yourself with the
product.
▪Particular attention should be paid to the information given in this chap-
ter.
Appropriate use
2.2
The product and associated equipment and special tools supplied with it
comply with the relevant legislation, regulations and standards, particularly
health and safety requirements, applicable at the time of delivery.
If used as intended and in compliance with the specified requirements and
conditions in this technical file as well as the warning notices in this technical
file and attached to the product, then the product does not present any hazards to people, property or the environment. This applies throughout the
product's entire life, from delivery through installation and operation to disassembly and disposal.
2 Safety
The operational quality assurance system ensures a consistently high quality
standard, particularly in regard to the observance of health and safety requirements.
The following is considered appropriate use
▪The product must be operated in accordance with this technical file and
the agreed delivery conditions and technical data
▪The equipment and special tools supplied must be used solely for the in-
tended purpose and in accordance with the specifications of this technical file
Inappropriate use
2.3
Use is considered to be inappropriate if the product is used other than as described in the Appropriate use section. Please also note the following:
▪Risk of explosion and fire from highly flammable or explosive gases, va-
pors, or dusts. Do not operate product in areas at risk of explosion.
▪Unauthorized or inappropriate changes to the product may lead to per-
sonal injury, material damage, and operational faults. Only modify product following discussion with Maschinenfabrik Reinhausen GmbH.
The product is designed solely for use in electrical energy systems and facilities operated by appropriately trained staff. This staff comprises people who
are familiar with the installation, assembly, commissioning and operation of
such products.
Operator's duty of care
2.5
To prevent accidents, disruptions and damage as well as unacceptable adverse effects on the environment, those responsible for transport, installation, operation, maintenance and disposal of the product or parts of the product must ensure the following:
▪All warning and hazard notices are complied with.
▪Personnel are instructed regularly in all relevant aspects of operational
safety, the operating instructions and particularly the safety instructions
contained therein.
▪Regulations and operating instructions for safe working as well as the
relevant instructions for staff procedures in the case of accidents and
fires are kept on hand at all times and are displayed in the workplace
where applicable.
▪The product is only used when in a sound operational condition and
safety equipment in particular is checked regularly for operational reliability.
▪Only replacement parts, lubricants and auxiliary materials which are au-
thorized by the manufacturer are used.
▪The specified operating conditions and requirements of the installation
location are complied with.
▪All necessary devices and personal protective equipment for the specific
activity are made available.
▪The prescribed maintenance intervals and the relevant regulations are
complied with.
▪Installation, electrical connection and commissioning of the product may
only be carried out by qualified and trained personnel in accordance
with this technical file.
▪The operator must ensure appropriate use of the product.
This chapter contains an overview of the design and function of the product.
Scope of delivery
3.1
The following items are included in the delivery:
▪TAPCON® 260
▪CD MR-Suite (contains the TAPCON®-trol program)
▪Technical files
▪Serial cable RS232
▪USB adapter with installation CD (optional)
Please note the following:
▪Check the shipment for completeness on the basis of the shipping docu-
ments.
▪Store the parts in a dry place until installation.
Function description of the voltage regulation
3.2
The TAPCON® 260 serves to keep constant the output voltage of a bank of
transformers with on-load tap-changers. The bank of transformers consists
of 3 single-phase transformers, each with an on-load tap-changer and motor-drive unit.
The TAPCON® 260 compares the measured voltage of the bank of transformers (U
tween U
) with a defined reference voltage (U
actual
actual
and U
is the control deviation (dU).
desired
). The difference be-
desired
The TAPCON® 260 parameters can be optimally adjusted to the line voltage
response to achieve a balanced control response with a small number of
tap-change operations by the on-load tap-changer.
The following diagram shows an overview of voltage regulation.
Figure 1: Overview of voltage regulation of a bank of transformers
The TAPCON® 260 is responsible for controlling tapped transformers in a
bank of transformers.
Apart from control tasks, the TAPCON® 260 provides additional functions
such as:
▪Integrated protective functions:
–Undervoltage blocking and overvoltage blocking
–Overvoltage detection with high-speed return
▪Compensation for voltage drops on the line (line drop compensation)
▪Compensation for voltage fluctuations in the meshed grid (Z compensa-
tion)
▪Digital inputs and outputs can be individually programmed on-site by the
user
▪Additional indicators using LEDs outside the display
▪Display of all measured values such as voltage, current, active power,
apparent power or reactive power, power factor (cos φ)
▪Selection of 3 different desired values
▪When ordering you can choose between tap position capture:
–using analog signal 4…20 mA
–using analog signal via resistor contact series
–using digital signal via BCD code
▪Parallel operation of up to 16 banks of transformers in 2 groups using
the following methods:
–Master/Follower
–Circulating reactive current minimization
Operating modes
3.4
The device can be operated in the following operating modes:
Auto mode (AUTO)
In auto mode, the voltage is automatically controlled in accordance with the
set parameters. You cannot change further device settings in auto mode.
There is no active management by a higher level control system in this operating mode.
Manual mode (MANUAL)
In manual mode, there is no automatic control. The motor-drive unit can be
controlled via the device's operating panel. You can change the device settings.
*) Optional when connecting TAPCON® to a control system (SCADA)
Hardware
3.5
The individual assemblies are fitted in a standardized 19-inch plug-in housing. The front panels of the assemblies are secured to the plug-in housing at
the top and bottom. An IEC 60603-2 plug connector provides the electrical
connection.
The assemblies are connected to one another via a data bus and direct current (DC) supply. This allows for an upgrade with additional plug-in modules
and extension cards at a later date.
Current messages and events are displayed in the status line . You can
find more information about messages and events in the Messages [► 144]
chapter.
Serial interface
The parameters for the device can be set using a PC. The COM 1 (RS232)
serial interface on the front panel is provided for this purpose. You can use
the connection cable supplied to establish a connection to your PC via the
RS232 or USB port (using the optional USB adapter).
TAPCON®-trol software is needed for parameterization via the serial interface. The software and the related operating instructions are contained on
the CD provided.
Depending on configuration, the device may have various assemblies which
perform the functions required. Depending on configuration, the device may
be equipped with the following assemblies:
Page 22
3 Product description
CardDefault/optionMax. number
ANOption1
ACOption1
ADOption1, optional with extension
The functions of the assemblies are described in the following sections. You
can find more information about the assemblies in the Technical data
[► 152] section.
3.5.5.1
Power supply
The wide range power supply (SU card) supplies the device with power. Depending on configuration, the device is equipped with one of the following
variants:
▪SUH-P: Rated input voltage 100...240 V AC or 88...353 V DC (input volt-
age range 88...264 V AC, 88...353 V DC)
▪SUM-P: Input voltage 36...72 V DC
▪SUL-P: Input voltage 18...36 V DC
Only use the R8/R12 and R42/R46 rotary potentiometers to calibrate the resistance measurement.
AD8 card
The analog input card has 8 inputs that can record the analog signals
(4...20mA).
Figure 16: AD8 card
AN card
Depending on configuration, the AN card provides 2 analog outputs or with
an extension module AN1 a total of 4 analog outputs. The following signal
types are supported:
An additional non-regulated control voltage of 60 V DC can be created with
the AC card if your system does not have external DC voltage as the signal
voltage for the device's digital inputs. Depending on device configuration,
one of the following two variants can be fitted:
▪AC230: 230 V AC input voltage
▪AC115: 115 V AC input voltage
CAUTION
Risk of injury from increased output voltage
Slight loading of the AC card may result in the output voltage increasing to
up to 85 V DC.
► Only wire card when not energized.
The output performance of the AC card is limited. The generated DC voltage can be used only for the control inputs of the device.
The CPU card is the device's central computing unit. All internal device functions and the application functions, such as processing measured values,
are controlled and monitored by the CPU card.
The CPU card contains a flash memory (optional measured value memory)
as a non-volatile data storage in which the operating data such as measured
values or events are stored. An EEPROM for storing parameters and a realtime clock (RTC) for recording time are included on the CPU card.
The CPU card contains the following interfaces:
▪RS232 system interface
▪CAN bus
3.5.5.7
Figure 20: CPU card
1CAN bus interface
System networking
The device is equipped with the following assemblies:
As an option, the device can be equipped with up to 2 CIC cards. The CIC
cards are used to communicate using a control system protocol or
TAPCON®-trol software (CIC2).
Figure 21: CIC card
1RS2326TxD LED for transmit signal
2RS4857RxD LED for receive signal
3RJ45 (Ethernet), optional8Clk LED for operating mode
(flashes for 2 seconds)
4Fiber-optic cable, optional9Clip for connecting cable
shield
5Reset key
SID card
The SID interface card is used to connect the device to the control station
system (SCADA). The IEC 61850 protocol transfers the data using Ethernet.
Figure 22: SID card
1Reset key3RS232 system interface
2LED for operating status4RJ45 (Ethernet)
This chapter describes how to correctly mount and connect the device. Note
the connection diagrams provided.
WARNING
NOTICE
Electric shock
Risk of fatal injury due to electrical voltage.
► De-energize the device and system peripherals and lock them to pre-
vent them from being switched back on.
► Do so by short-circuiting the current transformer; do not idle the current
transformer.
Electrostatic discharge
Damage to the device due to electrostatic discharge.
► Take precautionary measures to prevent the build-up of electrostatic
charges on work surfaces and personnel.
Preparation
4.1
The following tools are needed for mounting:
▪Screwdriver for the fixing bolts (M6)
▪Small screwdriver for connecting the signal lines and supply lines
Depending on installation site and mounting variant, you may need additional tools and corresponding attachment material (screws, nuts, washers)
which are not included in the scope of supply.
Mounting device
4.2
Depending on your order, you can mount the device in one of the following
variants:
▪19" frame (in accordance with DIN 41494 Part 5)
▪19" flush control panel frame
Below you will find a description of how to mount the device in a 19" frame.
For control panel installation or wall mounting, note the technical files supplied.
To mount the device in a 19" frame, proceed as follows:
1.Place cage nuts in the desired locations on the 19" frame, noting the
Figure 23: Example of device mounting in a 19" frame
WARNING
4.3
4.3.1
Connecting device
The following section describes how to establish the electrical connection to
the device.
Electric shock
Risk of fatal injury due to connection mistakes
► Ground the device with a protective conductor using the grounding
screw on the housing.
► Note the phase difference of the secondary terminals for the current
transformer and voltage transformer.
► Connect the output relays correctly to the motor-drive unit.
Supply the voltage via separators and ensure that current paths can be
short circuited. Fit the separator, clearly labeled, near the device's power
supply so that it is freely accessible. This will allow the device to be replaced with ease in the event of a defect.
Cable recommendation
Please note the following recommendation from Maschinenfabrik Reinhausen when wiring the device.
Excessive line capacitance can prevent the relay contacts from breaking the
contact current. In control circuits operated with alternating current, take into
account the effect of the line capacitance of long control lines on the function of the relay contacts.
To ensure the smooth transfer of data via the fiber-optic cable, you must ensure that mechanical loads are avoided when laying the fiber-optic cable and
later on during operation.
Please note the following:
▪Radii must not fall below the minimum permissible bend radii (do not
bend fiber-optic cable).
▪The fiber-optic cables must not be over-stretched or crushed. Observe
the permissible load values.
▪The fiber-optic cables must not be twisted.
▪Be aware of sharp edges which could damage the fiber-optic cable's
coating when laying or could place mechanical loading on the coating
later on.
▪Provide a sufficient cable reserve near distributor cabinets for example.
Lay the reserve such that the fiber-optic cable is neither bent nor twisted
when tightened.
Electromagnetic compatibility
The device has been developed in accordance with applicable EMC standards. The following points must be noted in order to maintain the EMC
standards.
4.3.3.1
4.3.3.2
Wiring requirement of installation site
Note the following when selecting the installation site:
▪The system's overvoltage protection must be effective.
▪The system's ground connection must comply with all technical regula-
tions.
▪Separate system parts must be joined by a potential equalization.
▪The device and its wiring must be at least 10 m away from circuit-break-
ers, load disconnectors and busbars.
Wiring requirement of operating site
Note the following when wiring the operating site:
▪The connection cables must be laid in metallic cable ducts with a ground
connection.
▪Do not route lines which cause interference (for example power lines)
and lines susceptible to interference (for example signal lines) in the
same cable duct.
▪Maintain a gap of at least 100 mm between lines causing interference
▪Short-circuit and ground reserve lines.
▪The device must never be connected using multi-pin collective cables.
▪Signal lines must be routed in a shielded cable.
▪The individual conductors (outgoing conductors/return conductors) in
the cable core must be twisted in pairs.
▪The shield must be fully (360º) connected to the device or a nearby
ground rail.
Using "pigtails" may limit the effectiveness of the shielding. Connect closefitting shield to cover all areas.
In order for the CAN bus to operate faultlessly, you have to connect the
shielding using one of the following variants. If you are not able to use any of
the variants detailed below, we recommend using fiber optic cables. Fiber
optic cables decouple the voltage regulators and are not sensitive to electromagnetic interferences (surge and burst).
Damage to the device
If you connect the CAN bus cable to devices with different potential, current
may flow over the shielding. This current may damage the device.
► Connect the devices to a potential compensation rail to compensate for
potential.
► If both devices have different potentials, only connect the CAN bus ca-
ble's shielding to one device.
Variant 1: The connected devices share the same potential
If the devices to be connected share the same potential, proceed as follows:
1.Connect all devices to a potential compensation rail to compensate for
the potential.
2.Connect CAN bus cable's shielding to all connected devices.
You need to set several parameters and perform function tests before commissioning the device. These are described in the following sections.
NOTICE
Damage to device and system periphery
An incorrectly connected device can lead to damages in the device and system periphery.
► Check the entire configuration before commissioning.
► Prior to commissioning, be sure to check the actual voltage and operat-
ing voltage.
We recommend using a device for industrial instrumentation to record the
actual transformer voltage value in order to evaluate how the device is functioning.
Setting the display contrast
5.1
You can adjust the contrast in the display with the help of an adjustment
screw on the front of the device. To adjust the contrast, proceed as follows:
► Use a screwdriver to turn the adjustment screw on the front until the
contrast is adjusted to the desired setting.
Figure 28: Setting the display contrast
Setting parameters
5.2
To commission the device, you must set the following parameters. For more
detailed information about the parameters, refer to the respective sections.
1. > Configuration > Continue > Memory > Press
until the desired display appears.
ðDate
2.Press to highlight a digit.
ðThe desired position is highlighted and the value can be changed.
3.Press to increase the value or to reduce it.
4.Press .
ðThe date is set.
5.2.3
Setting further parameters
Set further parameters to commission the device. More detailed information
about each of the parameters can be found in the Functions and settings
[► 52] chapter.
Setting transformer data
Set the transformer data and phase difference of the current transformer and
voltage transformer:
1.Set primary transformer voltage [► 85].
2.Set secondary transformer voltage [► 85].
3.Set primary transformer current [► 86].
4.Select current-transformer connection [► 87].
5.Select transformer circuit [► 87].
Setting NORMset
If you want to commission voltage regulation quickly, you can activate
NORMset mode. If you want to set the parameters yourself, continue with
the sections below.
► Activate NORMset and set the relevant parameters [► 61].
Setting control parameters
Set the following control parameters:
1.Set desired value 1 [► 65].
2.Set the bandwidth [► 66].
3.Set delay time T1 [► 66].
4.Switch all motor-drive units into the same tap position [► 52].
If you need line drop compensation, you must set all important parameters
for this:
1.Select the LDC compensation method [► 75].
2.Set the line data for the ohmic voltage drop Ur [► 77].
3.Set the line data for the inductive voltage drop Ux [► 77].
Setting parallel operation on several banks of transformers (optional)
If you need parallel operation, you must set all important parameters for this:
1.Set the parallel operation method to the circulating reactive current
method [► 92].
2.Assign the CAN bus address [► 91].
3.Set circulating reactive current sensitivity [► 93].
4.Set circulating reactive current blocking [► 93].
Setting control system protocol (optional)
If you need a control system protocol, you must set all important parameters
for this. More detailed information about this can be found in the control system protocol description.
Setting tap position capture via analog input (optional)
If you want to capture the tap position via the analog input, you must set the
parameters required for this:
► Capture tap positions via analog input (input 1 or input 2) [► 96].
All parameters relevant to commissioning are entered. Continue with the
function tests.
Function tests
5.3
Before switching from manual mode to auto mode, Maschinenfabrik Reinhausen recommends carrying out function tests. These function tests are described in the following sections. Note the following points for all function
tests:
▪You must ensure that the REMOTE mode is disabled before you can
control the on-load tap-changer manually in manual mode.
▪You can only activate the on-load tap-changer manually in manual
mode using the and keys.
▪During the function test, you must set the most important parameters.
Details on the parameters listed can be found in the Functions and settings [► 52] chapter.
19. Press to select auto mode.
ðAfter 20 seconds, the device lowers the on-load tap-changer one
step and after another 10 seconds another step.
20. Press to select manual mode.
21. Set delay time T1 [► 66] and delay time T2 [► 68] to the desired
value.
We recommend a temporary setting of 100 seconds for delay time T1 when
commissioning the transformer. Depending on the operating conditions, you
can also specify the delay time following a longer observation period. In this
regard, it is useful to register how the actual voltage progresses and the
number of tap-change operations per day.
5.3.2
Checking additional functions
This section describes how you can check the following additional functions:
▪Undervoltage blocking
▪Overvoltage blocking
▪Activation of desired values 2 and 3
▪Line drop compensation
▪Z compensation
Proceed as follows:
Checking undervoltage blocking U<
1.Press to select manual mode.
2.Set undervoltage U < [%] to 85 % [► 70].
3.Set the absolute limit values parameter to Off [► 69].
4.Set the U< blocking parameter to On [► 71].
5.Set desired value 1 such that the measured voltage is below the undervoltage U< [%] limit value [► 65].
Measured voltage = 100 V
Desired value 1 = Set to 120 V (greater than 100 V/0.85 = 117 V).
ðThe Undervoltage U< LED will light up.
ðAfter around 10 seconds the Undervoltage message appears in the
display and the relevant signaling relay is activated.
6.Press to select auto mode.
ðThe device blocks and does not issue any control commands.
If you want to use line drop compensation, you need to run this function test.
A load current of ≥ 10 % of the nominal transformer current is needed for the
following function tests. Before the function test, ensure that all parameters
for line drop compensation [► 75] and for Z compensation [► 78] are set
to 0.
1.Press to select manual mode.
2.Press until the main screen is displayed.
3.If necessary, press until the control deviation dU is shown.
ðThe measured voltage must be within the bandwidth.
4.Set line drop compensation Ur parameter to 20.0 V [► 77].
ðThe control deviation dU must be negative.
5.Set line drop compensation Ux parameter to -20.0 V [► 77].
6.Press until the main screen is displayed.
7.If necessary, press until the control deviation dU is shown.
ðThe control deviation dU must be positive.
If the control deviation appears in the opposite direction, change the polarity
of the current transformer.
8.Set the line drop compensation Ur and line drop compensation Ux
parameters to the desired operating values.
ðThe function test for line drop compensation is complete.
Checking Z compensation
If you want to use Z compensation, you need to run this function test. A load
current of ≥ 10 % of the nominal transformer current is needed for the following function test .
1.Press to select manual mode.
2.Set all parameters for line drop compensation and Z compensation to 0.
3.Press until the main screen is displayed.
4.If necessary, press until the control deviation dU is shown.
ðThe measured voltage must be within the bandwidth.
5.Set the Z compensation parameter to 15.0 V.
6.Press until the main screen is displayed.
7.If necessary, press until the control deviation dU is shown.
ðThe control deviation dU must be negative.
If the control deviation appears in the opposite direction, change the polarity
of the current transformer.
8.Set the Z compensation and Z compensation limit value parameters
to the desired operating values.
ðThe function test for Z compensation is complete.
Also refer to
2 Setting Z compensation [► 79]
2 Setting the Z compensation limit value [► 79]
5.3.3
Checking parallel operation of several banks of transformers
This section describes how you can run the function test for parallel operation of several banks of transformers .
Requirements
To obtain perfect functioning in parallel operation, the voltage regulator must
be commissioned in simplex mode. Make sure that the conditions below
have been fulfilled.
▪All motor-drive units of the banks of transformers (ED1...ED3) are in the
same tap position.
▪All devices are set to the same operating parameters for desired value,
circulating reactive current sensitivity and delay time T1.
▪The circulating reactive current sensitivity on all devices must be set to
0 %.
▪The circulating reactive current blocking parameter must be set to
20 %.
▪You must undertake all settings in manual mode.
▪Each device needs an individual address on the CAN bus.
5.3.3.1
Checking circulating reactive current sensitivity
This section describes how to run the function test for circulating reactive
current sensitivity.
1.Adjust both transformers in simplex mode to the same actual voltage by
means of the on-load tap-changer.
ðWhen both devices are in a state of equilibrium, then the value of
the control deviation dV [%] is smaller than the set bandwidth. You
can see this in the main screen if the mark for the measured voltage U
is within the bandwidth.
actual
2.Connect the transformers in parallel and enable the parallel control.
ðThe two devices must still be in a state of equilibrium.
ðThe Parallel operation LED on the front panel is illuminated.
3.On one of the two transformers, raise the tap position of the on-load tapchanger by one setting; on the second transformer, lower the tap position of the on-load tap-changer by one setting.
ðThe two devices must still be in a state of equilibrium.
4.Adjust the circulating reactive current sensitivity until the result displayed exceeds the set value for the bandwidth by approx. 0.2 % to
0.3 %.
ðThe value for the result changes in the help text in the last line of
the display.
5.Set the value given in the previous step for all devices in parallel operation.
6.Press to select auto mode for both devices.
ðThe devices return the on-load tap-changer units to the original tap
positions.
ðThe function test for circulating reactive current sensitivity is complete.
If the earlier tap positions are not reached, increase the value of the circulating reactive current sensitivity [► 93] parameter.
If one of the two on-load tap-changer units switches one or more tap positions higher and the other switches the same amount lower, you need to reduce the value of the circulating reactive current sensitivity [► 93] parameter.
After you have set the circulating reactive current sensitivity parameter,
continue with the circulating reactive current blocking function test described
in the next section.
5.3.3.2
Checking circulating reactive current blocking
This section describes how to run the function test for circulating reactive
current blocking.
1.Press on one device to select manual mode.
2.Using manual control, adjust the relevant motor-drive unit upwards by
the maximum permitted tap difference in operating positions between
the parallel operating transformers (for example by 1 - 2 steps).
When setting the circulating reactive current blocking in the following process step, wait approx. 2 - 3 seconds between the individual steps.
3.Set the parallel operation method parameter to circulating reactive
4.The circulating reactive current blocking parameter should be reduced [► 93] from the set value of 20 % in steps of 1 % until the Par-allel operation error: circulating reactive current limitexceeded is displayed.
ðThe Parallel operation LED lights up when the circulating reactive
current blocking limit is reached.
ðAny further regulation is blocked.
5.After the set delay time for the parallel operation error message (time
can be adjusted [► 95]), the signaling relay UC-X1:1/UC-X1:2 (default
setting) is activated.
6.Increase the circulating reactive current blocking parameter again
until the message Parallel operation error: circulating reactive currentlimit exceeded disappears.
7.Press to select auto mode.
ðThe motor-drive unit automatically returns to the original operating
position.
8.Set the value determined for the circulating reactive current blocking
on the devices in parallel operation as well.
If one or all devices indicate Parallel operation error: circulating reactive cur-rent limit exceeded although the control inputs are correctly connected for
all the devices, then all the devices block.
This could be due to various causes. Further information is given in the
chapter Troubleshooting [► 139].
5.3.3.3
NOTICE
ðThe function test for circulating reactive current blocking is complete.
Checking tap synchronization method
This section describes how to run the function test for tap synchronization
(master/follower). If instances arise where a follower switches in the opposite
direction to the master step change, then the setting for the tapping direction
[► 61] parameter on the follower must be changed from Default to Swap-
ped.
Damage resulting from formation of circulating reactive current
If the parameters are not set correctly, damage may result from the formation of circulating reactive current and the resulting overload of transmission
lines and transformers.
► Check transformer type plate.
► Set device parameters in accordance with transformer configuration.
9.Press several times on the follower to manually increase the tap
position by the number of permitted steps (maximum permitted tap difference) and then one more step.
ðAfter expiry of the set delay time for parallel operation errors, the
following error messages are displayed on the master: Parallel op-
eration error: tap difference to follower
ðAfter expiry of the set delay time for parallel operation errors, the
following error messages are displayed on the follower: Parallel op-eration error: permitted tap difference to master exceeded.
10. Press on the follower to select auto mode.
ðThere is no response. All devices remain blocked.
11. Press on the master and follower to select manual mode.
12. Press or on the master and follower to manually set the desired step.
Because in parallel operation the tap positions of the transformers which are
running in parallel are compared following the Automatic tap synchroniza-tion method, it is absolutely essential that these transformers have the
same position designation and that the Raise and Lower signals produce
the same voltage change in all transformers.
ðThe function tests for the tap synchronization method are complete.
Installation and commissioning of the device is complete.
This chapter describes all the functions and setting options for the device.
Key lock
6.1
The device is equipped with a key lock to prevent unintentional operation.
You can only set or change the parameters when the key lock is deactivated
in manual mode.
Activating key lock
To activate the key lock, proceed as follows:
► Press and at the same time.
ðA confirmation appears in the display for a brief period. The key lock is
activated. Parameters can no longer be entered.
Deactivating key lock
To deactivate the key lock, proceed as follows:
► Press and at the same time.
ðThe key lock is deactivated. Parameters can be entered.
Carrying out tap-change operation manually
6.2
In manual mode [► 15] you can manually carry out an on-load tap-changer
tap-change operation. To do this, you can choose whether you want to
switch 1 motor-drive unit individually (ED 1...ED 3) or all 3 motor-drive units
at the same time (ED all).
By switching the motor-drive units individually, you can compare the tap positions of the on-load tap-changers in the 3 transformers. If the tap positions
are different, the tap difference LED lights up.
To carry out a tap-change operation manually, proceed as follows:
1.If necessary, press to activate manual mode.
2.Press and hold down or .
ðThe "Syn. Control up/down" display appears.
3.Press ... as required to select the option you want.
ðThe tap-change operation is carried out.
General
6.3
You can undertake general settings on the device in the General menu item.
You can use the device ID parameter to assign a 4-digit ID to the device.
This ID is used to uniquely identify the device in the TAPCON®-trol software.
To set the device ID, proceed as follows:
1. > Configuration > General > Press until the desired
parameter is displayed.
ðRegulator ID.
2.Press to change the first digit.
ðIf you wish to enter a multi-digit sequence, proceed to step 3. If you
do not wish to enter additional digits, proceed to step 7.
3.Press (digit > 9) until another digit position appears.
4.If necessary, press in order to highlight the digit position.
ðThe required digit is highlighted and can be changed.
5.Press or to change the digit.
6.Repeat steps 3 to 5 until all required digits have been entered.
7.Press .
ðThe device ID is set.
6.3.2
Setting the baud rate
You can use this parameter to set the COM1 interface's baud rate. You can
select the following options:
If you set the switching pulse time to 0 s, the motor-drive unit is activated
with a continuous signal. The signal then remains active for as long as the
or keys are pressed.
Switching pulse in normal
mode
If you set the switching pulse time to 1.5 seconds for example, after the set
delay time T1 or delay time T2 there will be a switching pulse of 1.5 sec-
onds .
The waiting time between 2 consecutive switching pulses corresponds to the
set delay time T1 or delay time T2 .
Switching pulse for rapid
return control
Figure 36: Switching pulse time in normal mode
1Set delay time T1 or T22Set switching pulse time (for
example 1.5 seconds)
If the motor-drive unit does not start with the factory setting (1.5 seconds),
you need to extend the raise switching pulse time / lower switching pulse
time.
If you set the raise switching pulse time or lower switching pulse time to
1.5 seconds, for example, the next earliest switching pulse occurs in rapid
return control mode 1.5 seconds after the previous switching pulse
Figure 37: Switching pulse in rapid return control mode
6 Functions and settings
6.3.6
1Start of first raise switching
pulse/lower switching pulse
3Earliest time for the next raise
switching pulse/lower switching pulse (for example
1.5 seconds)
2Set switching pulse time (for
example 1.5 seconds)
To set the pulse duration, proceed as follows:
1. > Configuration > General > Press until the desired
parameter is displayed.
ðR/L pulse duration.
2.Press or to select the pulse duration you want.
3.Press .
ðThe R/L pulse duration is now set.
Configuring control inputs IO1-X1:33/31
Depending on your device configuration, the following parameters can be
used by MR for special functions. In this case, these parameters are pre-assigned. You may not be able to view or freely assign these parameters.
You can use this parameter to assign functions to the freely configurable
control inputs. You can assign the following functions:
OffNo function selected
Master/FollowerMaster mode is activated when a signal is present.
Follower mode is activated when no signal is present.
Local/RemoteLocal operating mode is activated if the signal is
present.
Remote operating mode is activated if the signal is
not present.
BlockingAutomatic regulation is blocked.
LV S tap changeDelay time T1 and delay time T2 are deactivated.
Raise switching pulse and lower switching pulse
occur when value exceeds/falls below the band-
width.
MPS triggeredThe Motor protective switch was triggered mes-
sage is assigned to the control input.
Remote/LocalRemote operating mode is activated if the signal is
present.
Local operating mode is activated if the signal is
not present.
Table 10: Possible functions for control inputs
If you set both control inputs to Local/Remote and there is a signal (1) at
one input, but no signal (0) at the other control input, you can prevent the
device from being operated. This means that the Manual/Auto and Raise/lower functions are not possible with either the keys on the front panel or
the inputs for remote messages or serial interface.
To assign functions to the control inputs, proceed as follows:
1.Press > Configuration > General > until the desired
parameter is displayed.
ðIO1-X1:33 or IO1-X1:31.
2.Press or until the desired function appears in the display.
3.Press .
ðThe function is assigned.
6.3.7
Configuring output relays IO1-X1:25/26 and IO1-X1:23/24
Depending on your device configuration, the following parameters can be
used by MR for special functions. In this case, these parameters are pre-assigned. You may not be able to view or freely assign these parameters.
1.Press > Configuration > General > until the desired
parameter is displayed.
ðDisplay off.
2.Press or to activate/deactivate automatic dimming.
3.Press .
ðAutomatic dimming is set.
6.3.9
Behavior
Parameterizing control
input
Wiring control input/output
relay
Setting motor runtime monitoring
You can use this motor runtime parameter to set the motor runtime. The motor-drive unit's runtime can also be monitored by the device. This function is
used to identify motor-drive unit malfunctions during the tap-change operation and to trigger any actions needed.
The motor-drive unit issues the Motor-drive unit running signal during the
tap-change operation. This signal is present until the tap-change operation is
complete. The device compares the duration of this signal with the set motor
runtime. If the set motor runtime is exceeded, the device triggers the following actions:
1.Motor runtime monitoring message is issued
2.Continuous signal via output relay Motor-drive unit runtime exceeded
(optional)
3.Pulse signal via Trigger motor protective switch output relay (optional)
To use runtime monitoring, you need to correctly wire the corresponding
control input and parameterize to Motor running. The motor runtime must also be set.
If you want to monitor the motor runtime, the device and motor-drive unit
must be connected and parameterized as shown below.
If you want to use the output relay, the feedback from the motor-drive unit
Motor protective switch triggered must also be wired to a control input and
parameterized. This message resets the Motor runtime exceeded output relay when the motor protective switch is switched back on and activates the
Motor protective switch triggered message.
If the runtime monitoring is set to 0.0 seconds this equates to it being
switched off.
To set the motor runtime, proceed as follows:
1. > Configuration > General > Press until the desired
parameter is displayed.
ðMotor runtime.
2.Press to highlight the position.
ðThe desired position is highlighted and the value can be changed.
Depending on your configuration, with this parameter, you can set how the
device behaves in the event of a raise or lower tap change. This parameter
is taken into account in the parallel operation method "tap synchronization"
as follower and when checking the permitted tap position.
You can select the following options:
OptionDescription
StandardSignal at Raise relay: Device switches up one step
to increase the voltage.
Signal at Lower relay: Device switches down one
step to decrease the voltage.
SwappedSignal at Raise relay: Device switches down one
step to increase the voltage.
Signal at Lower relay: Device switches up one
step to decrease the voltage.
Table 12: Device response
To select the tapping direction, proceed as follows:
1.Press > Configuration > General > until the desired
parameter is displayed.
ðTapping direction turned.
2.Press or to select the required option.
3.Press .
ðThe tapping direction is selected.
NORMset
6.4
NORMset mode is used for quickly starting voltage regulation. In NORMset
mode, the bandwidth and delay time parameters are automatically adapted
to the requirements of the grid.
To start NORMset mode, you must set the following parameters:
▪Normset activation
▪Desired value 1
▪Primary voltage
▪Secondary voltage
1. > NORMset > Press until the desired parameter is displayed.
ðSecondary voltage.
2.Press to increase the value or to reduce it.
3.Press .
ðThe secondary voltage is set.
Setting desired value 1
With this parameter, you can set the desired value for automatic voltage regulation. You can enter the desired value in V or in kV. If you enter the desired value in V, the value relates to the voltage transformer's secondary
voltage. If you set the desired value in kV, the value relates to the voltage
transformer's primary voltage.
Settings in kV are only possible if you have previously entered the parameters for primary and secondary voltage.
To set the desired value, proceed as follows:
1. > NORMset > Press until the desired parameter is displayed.
ðDesired value 1.
2.Press to increase the value or to reduce it.
3.Press .
ðThe desired value is set.
Control parameters
6.5
All of the required for the regulation function are described in this section.
For voltage regulation, you can set the following parameters:
▪Desired values 1…3
▪Bandwidth
▪Delay time T1
▪Control response T1
▪Delay time T2
For voltage regulation, you can set delay time T1 and also delay time T2.
The following sections describe how the regulation function responds in both
cases:
commands are issued to the motor-drive unit for the tap-change operation.
Control commands will also not be issued to the motor-drive unit if the meas-
ured voltage returns to the tolerance bandwidth
. However, if the measured voltage deviates from the set bandwidth for
T1
a long period
, a tap-change command occurs after expiration of the
within the set delay time
set delay time T1. The on-load tap-changer carries out a tap-change in a
raise or lower direction to return to the tolerance bandwidth.
Figure 42: Behavior of the regulation function with delay time T1
1+ B %: Upper limit4Set delay time T1
2U
: Desired value5U
desired
: Measured voltage
actual
3- B %: Lower limit6B%: Tolerance bandwidth
AU
is outside the band-
actual
width. Delay time T1 starts.
BU
is within the bandwidth
actual
before delay time T1 is complete.
CU
is outside the band-
actual
width. Delay time T1 starts.
DU
is still outside the band-
actual
width when delay time T1 is
complete. Tap-change operation is initiated.
Behavior with delay times T1 and T2
Delay time T2 can be used to correct major control deviations more quickly.
Ensure that you set a lower value in the "Delay time T2" parameter than in
the "Delay time T1" parameter.
period , a control impulse is output to the motor-drive unit after the set delay time T1. If the measured voltage U
delay time T2
starts once delay time T1 is complete. Once delay time T2
is still outside the bandwidth,
actual
is complete, a control impulse is again output to the motor-drive unit for the
tap change to return to the tolerance bandwidth.
6.5.1
Figure 43: Behavior of the regulation function with delay times T1 and T2
1+ B %: Upper limit4Set delay times T1 and T2.
2U
: Desired value5U
desired
: Measured voltage
actual
3- B %: Lower limit6B%: Tolerance bandwidth
AU
CDelay time T2 complete. Tap
is outside the band-
actual
width. Delay time T1 starts.
BDelay time T1 complete. Tap
change triggered.
change triggered.
The following sections describe how to set the relevant control parameters.
Setting desired value 1...3
You can use this parameter to set up to 3 desired voltage values U
desired voltage value is specified as a fixed value. The desired value 1 is the
default desired value. Desired values 2 and 3 are activated if there is a continuous signal at factory-preset control inputs IO-X1:31 or IO-X1:33 provided
you have programmed these previously. If there is a signal at several control
inputs at the same time, desired value 2 is activated.
The device provides the following ways of changing the desired voltage value during operation:
▪Using the control parameters menu item via the operating screen
▪Using binary inputs
▪Using control system protocols if a communication card is ready for op-
eration
Desired values set in kV refer to the primary voltage of the voltage transformer. Desired values set in V refer to the secondary voltage of the voltage
transformer. The transformer data must be entered correctly for this display.
To set the desired value, proceed as follows:
1. > Parameter > Control parameter > Press until the
desired parameter is displayed.
2.If you have already entered the transformer data, press to select
the unit you want: "V" or "kV".
3.Press to highlight the position.
ðThe desired position is highlighted and the value can be changed.
4.Press to increase the value or to reduce it.
5.Press .
ðThe desired value is set.
6.5.2
6.5.3
Bandwidth
You can use this parameter to set the maximum permissible deviation in
measured voltage U
. The deviation relates to the activated desired value.
Act
The following sections describe how you determine and set the bandwidth
required.
Setting delay time T1
Use this parameter to set delay time T1. This function delays the issuing of a
tap-change command for a defined period. This prevents unnecessary tapchange operations if the tolerance bandwidth is exited.
To set the delay time T1, proceed as follows:
1. > Parameter > Control parameter > Press until the
desired parameter is displayed.
2.Press to highlight the position.
ðThe desired position is highlighted and the value can be changed.
The control response T1 can be set to linear or integral.
With linear control response, the device responds with a constant delay time
regardless of the control deviation.
With integral control response, the device responds with a variable delay
time depending on the control deviation. The greater the control deviation
(ΔV) in relation to the set bandwidth (B), the shorter the delay time. The delay time can therefore be reduced down to 1 second. This means that the
device responds faster to large voltage changes in the grid. Regulation accuracy improves as a result but the frequency of tap-changes increases too.
Figure 44: Diagram showing integral control response
ΔV/BControl deviation "ΔV" as % of desired value as ratio to the set
bandwidth "B" as % of desired value
1"Delay time T1" parameter
To set the control response T1, proceed as follows:
1. > Parameter > Control parameter > Press until the
desired parameter is displayed.
With this parameter, you can set delay time T2. Delay time T2 is used to
compensate for large control deviations faster.
The delay time T2 only takes effect if more than one tap-change operation is
required to return the voltage to within the set bandwidth. The first output
pulse occurs after the set delay time T1. After the set tap-change delay time
T2 has elapsed, additional pulses occur in order to correct the existing control deviation.
The following requirements must be noted to set delay time T2:
▪The delay time T2 must be greater than the switching pulse time.
▪The delay time T2 must be greater than the maximum operating time of
the motor-drive unit.
▪The delay time T2 must be less than the value set for delay time T1.
To set the delay time T2, proceed as follows:
1. > Parameter > Control parameter > Press until the desired parameter is displayed.
ðDelay time T2.
2.Press to increase the time or to reduce it.
3.Press .
ðThe delay time T2 is set.
Activating/deactivating delay time T2
To activate/deactivate delay time T2 , proceed as follows:
1. > Parameter > Control parameter > Press until the
desired parameter is displayed.
ðT2 activation.
2.Press or to activate/deactivate T2.
3.Press .
ðThe delay time T2 is activated/deactivated.
Limit values
6.6
In the Limit values menu item, you can set all the parameters needed for limit value monitoring as relative or absolute values. You can set three limit values:
ðThe absolute limit value is activated/deactivated.
Setting undervoltage monitoring V<
You can use these parameters to set the limit values for an undervoltage.
Undervoltage monitoring prevents tap-change operations if there is a power
cut.
Behavior
If the measured voltage U
falls below the set limit value, the red
actual
LED U< lights up . The switching pulses to the motor-drive unit are blocked
at the same time provided you have activated the blocking undervoltage U<
parameter. Once the set signaling delay time [► 71]
has passed, the
signaling relay activates. The Undervoltage U< message appears in the
display. The message is reset as soon as the measured voltage U
exceeds the limit value for undervoltage
. If the measured voltage U
actual
again
actual
falls below 30 V (for example when the transformer is switched off), the
Undervoltage message is also displayed. You can however suppress
[► 72] this message.
Figure 45: Response to value falling below limit value
1+ B %: Upper limit7U
2U
: Desired valueAValue falls below limit value
desired
: Measured voltage
actual
3- B %: Lower limitBUndervoltage U< message is
displayed
4Set limit value for undervolt-
CVoltage falls below 30 V
age U<
5Limit value for suppressing
DVoltage exceeds 30 V again
alarms below 30 V
6Set signaling delay time for
EValue exceeds limit value
limit value for undervoltage
U<
Setting undervoltage V< as %
You can use this parameter to set the limit value as a relative value (%). This
limit value refers to the desired value you have set. If you want to use the set
relative value as the limit value, go to Absolute limit values and activate
the Off selection.
To set the limit value for undervoltage V<, proceed as follows:
1. > Parameter > Limit values > Press until the desired
parameter is displayed.
You can use this parameter to set the limit value as an absolute value in V or
kV units. If you use the key to change the display to kV, this value re-
lates to the primary transformer voltage. If you change the display to V, this
relates to the secondary voltage.
If you want to use the set absolute values as the limit value, go to Absolutelimit values and activate the On selection.
To set the absolute limit value for undervoltage V<, proceed as follows:
1. > Parameter > Limit values > Press until the desired
parameter is displayed.
2.If necessary press to select the unit you want, "V" or "kV".
3.Press to increase the value or to reduce it.
4.Press .
ðThe limit value is set.
Setting signaling delay time for undervoltage V<
You can use this parameter to set the delay time after which the Undervoltage relay is to activate and the event message appear on the display. This
can be used to prevent messages from being issued when the value briefly
falls below the limit value. The undervoltage LED always lights up immediately regardless.
To set the delay time for this message, proceed as follows:
1. > Parameter > Limit values > Press until the desired
parameter is displayed.
2.Press to highlight the position.
ðThe desired position is highlighted and the value can be changed.
3.Press to increase the time or to reduce it.
4.Press .
ðThe signaling delay time for undervoltage V< is set.
Activating/deactivating undervoltage blocking
You can use this parameter to set how the device behaves if the voltage falls
below the undervoltage limit. You can select the following options:
OnAutomatic regulation is blocked.
OffAutomatic regulation remains active.
Table 14: Behavior
To activate/deactivate the undervoltage blocking, proceed as follows:
1. > Parameter > Limit values > Press until the desired
parameter is displayed.
ðV< blocking.
2.Press for On setting or for Off setting.
3.Press .
ðUndervoltage blocking is activated/deactivated.
Activating/deactivating message for voltages below 30 V
You can use this parameter to set whether the Undervoltage message is to
be suppressed at a measured value of less than 30 V. This setting is used to
ensure that no event message appears when the transformer is switched off.
You can select the following options:
6.6.3
SettingFunction
OnThe Undervoltage message is also displayed
when the measured value is less than 30 V.
OffThe Undervoltage message is no longer dis-
played when the measured value is less than
30 V.
Table 15: Response
To activate/deactivate the message, proceed as follows:
1. > Parameter > Limit values > Press until the desired
parameter is displayed.
ðV< also under 30 V.
2.Press for On setting or for Off setting.
3.Press .
ðThe message is activated/deactivated.
Setting overvoltage monitoring V>
You can use these parameters to set the limit values for overvoltage monitoring. This overvoltage monitoring triggers tap-change operations to return
to the desired operating status. If the operating status can no longer be corrected, a message is triggered by the Function monitoring relay.
1. > Parameter > Limit values > Press until the desired
parameter is displayed.
2.Press to increase the value or to reduce it.
3.Press .
ðThe limit value is set.
Setting overvoltage V> in V/kV
You can use this parameter to set the limit value as an absolute value in V or
kV units. If you use the key to change the display to kV, this value re-
lates to the primary transformer voltage. If you change the display to V, this
relates to the secondary transformer voltage.
If you want to use the set absolute values as the limit value, go to Absolute
limit values and activate the On selection.
6.6.4
To set the absolute limit value for overvoltage limit V>, proceed as follows:
1. > Parameter > Limit values > Press until the desired
parameter is displayed.
2.If necessary press to select the unit you want, V or kV.
3.Press to increase the value or to reduce it.
4.Press .
ðThe limit value is set.
Setting overcurrent monitoring I>
You can use this parameter to set the limit value for overcurrent to prevent
tap-change operations in the event of excess load currents.
If the measured current exceeds the set limit value, the red LED I> and associated signaling relay activate. The Overcurrent blocking message appears in the display. The device's output pulses are blocked at the same
time.
You have to enter the limit value as a relative value (%) of the current transformer's set nominal current. You can use the key to change the input
from a percentage % to absolute values in amps A. The percentage value
relates to the nominal current. To change the input, the transformer data
[► 84] must be set.
To set the limit value I> overcurrent for overcurrent blocking, proceed as follows:
1. > Parameter > Limit values > Press until the desired
parameter is displayed.
2.If necessary press to select the unit you want: % or A.
3.Press to increase the value or to reduce it.
4.Press .
ðThe limit value is set.
6.6.5
6.7
Activating/deactivating function monitoring
If the measured value leaves the current bandwidth (desired value +/- bandwidth) for more than 15 minutes without a tap-change operation taking place,
the function monitoring relay is activated. This results in a message on the
display which is only reset when the measured value returns to within the
current bandwidth.
If the measured voltage is below 30 V, then the measured value is outside
the bandwidth and the relevant relay is also activated after 15 minutes. You
can deactivate this function if you want to avoid a function monitoring message when the transformer is switched off:
1. > Parameter > Limit values > Press until the desired
parameter is displayed.
2.Press or to select the option you want.
3.Press .
ðFunction monitoring is activated/deactivated.
Compensation
You can use the "Compensation" function to compensate for the load-dependent voltage drop between the transformer and consumer. The device
provides 2 methods of compensation for this purpose:
▪R&X compensation (line drop compensation)
▪Z compensation
R&X compensation (LDC) requires exact cable data. Line voltage drops can
be compensated very accurately using LDC.
To set R&X compensation correctly, you need to calculate the ohmic and inductive voltage drop in V with reference to the secondary side of the voltage
transformer. You also need to correctly set the transformer circuit used.
Page 76
Figure 47: Equivalent circuit
6 Functions and settings
Figure 48: Phasor diagram
You can calculate the ohmic and inductive voltage drop using the following
formulas. This voltage drop calculation relates to the relativized voltage on
the secondary side of the voltage transformer.
Formula for calculating the ohmic voltage drop:
Formula for calculating the inductive voltage drop:
U
r
U
x
I
N
Ohmic resistance load in Ω/km
Inductive resistance load in Ω/km
Nominal current (amps) of selected current-trans-
former connection on device:0.2 A; 1 A; 5 A
k
CT
k
VT
Current transformer ratio
Voltage transformer ratio
xInductive resistance load in Ω/km per phase
LLength of line in km
KNominal current factor
6.7.1.1
Setting the ohmic voltage drop Vr
You can use this parameter to set the ohmic voltage drop (ohmic resistance
load).
If you do not want to use line drop compensation, you have to set the value
0.0 V.
To set the ohmic voltage drop Vr, proceed as follows:
1. > Parameter > Compensation.
ðVr line drop compensation.
2.Press to highlight the position.
ðThe desired position is highlighted and the value can be changed.
3.Press to increase the value or to reduce it.
4.Press .
ðThe ohmic voltage drop Vr is set.
6.7.1.2
Setting the inductive voltage drop Vx
You can use this parameter to set the inductive voltage drop (inductive resistance load). The compensation effect can be rotated by 180° in the display using a plus or minus sign.
If you do not want to use line drop compensation, you have to set the value
0.0 V.
To set the inductive voltage drop Vx, proceed as follows:
1. > Parameter > Compensation > Press until the desired parameter is displayed.
ðVx line drop compensation.
2.Press to highlight the position.
ðThe desired position is highlighted and the value can be changed.
To keep the voltage constant for the consumer, you can use Z compensation
to activate a current-dependent increase in voltage. You can also define a
limit value to avoid excess voltage on the transformer.
Figure 49: Z compensation
To use Z compensation, you need to calculate the increase in voltage (ΔU)
taking the current into account. Use the following formula for this purpose:
∆UVoltage increaseILoad current in A
UTrTransformer voltage with
current I
INNominal current of current-
transformer connection in A
(0.2 A; 1 A; 5 A )
U
Voltage on line end with
Load
kCTCurrent transformer ratio
current I and on-load tapchanger in same operating
position
Sample calculation: UTr = 100.1 V, U
= 100.0 V, IN = 5 A kCT = 200 A/5 A,
Load
I = 100 A
Produces a voltage increase ∆U of 0.2%
The following sections describe how you can set the parameters you need
for Z compensation.
This parameter sets the voltage increase ∆V previously calculated.
If you do not want to use Z compensation, you have to set the value 0.0 %.
To set the Z compensation, proceed as follows:
1. > Parameter > Compensation > Press until the desired parameter is displayed.
ðZ compensation.
2.Press to increase the value or to reduce it.
3.Press .
ðThe Z compensation is set.
Setting the Z compensation limit value
You can use this parameter to define the maximum permissible voltage increase to avoid excess voltage on the transformer.
If you do not want to use a limit value, you have to set the value 0.0 %.
To set the limit value, proceed as follows:
1. > Parameter > Compensation > Press until the desired parameter is displayed.
ðZ comp. limit value.
2.Press to increase the value or to reduce it.
3.Press .
ðThe limit value is set.
Cross-monitoring
6.8
You can use cross-monitoring to set reciprocal monitoring of 2 devices for
compliance with the set voltage limit values. At least 2 devices with different
CAN bus addresses are needed for cross-monitoring.
For the check, the measured voltage of the device is transmitted to the
device via a second separate measurement input and vice versa. The
calculated measured voltage is compared with the original measured values
via the CAN bus. If the measured values deviate, the Measured value error
message is issued.
When checking the limit values, one device transmits a measured voltage to
the other via the second separate measurement input. You can set the following limit values for this measured value:
▪Separate desired value [► 80]
▪Undervoltage limit value [► 81]
▪Overvoltage limit value [► 82]
As soon as one of the set limit values is exceeded, once the set delay time
for the error message [► 83] has lapsed, the Measured value error message is output. If wired accordingly, relay contacts can block the raise/lower
pulse to the motor-drive unit. Regulation of individual devices is not affected
by limit value monitoring.
The following sections describe how you set the relevant parameters for the
monitoring device.
Also refer to
2 Setting delay time for error message [► 83]
2 Setting desired value for regulator 2 [► 80]
2 Setting undervoltage limit value V< for regulator 2 [► 81]
2 Setting overvoltage limit value V> for regulator 2 [► 82]
6.8.1
Setting desired value for regulator 2
You can use this parameter to set the desired value for the device to be
monitored.
You can use the key to change the display to the following units:
This value relates to the secondary
voltage of the system's voltage
transformer.
Table 16: Units available
This value relates to the primary
voltage of the system's voltage
transformer.
If you want to change the display from V to kV, you have to set the transformer data of the device to be monitored.
To enter the desired value of the device to be monitored, proceed as follows:
1. > Parameter > Cross-monitoring.
ðV
regulator 2.
des.
2.Press to increase the value or to reduce it.
3.Press .
ðThe desired value of the device to be monitored is set.
6.8.2
Setting undervoltage limit value V< for regulator 2
You can use this parameter to set the undervoltage limit value V< of the device to be monitored. You can set the undervoltage limit value V< as an absolute value (V or kV).
Setting absolute value
You can use the key to change the display to the following units:
Volts (V)Kilovolts (kV)
This value relates to the secondary
voltage of the system's voltage
transformer.
Table 17: Units available
This value relates to the primary
voltage of the system's voltage
transformer.
If you want to change the display from V to kV, you have to set the transformer data of the device to be monitored.
To set the undervoltage limit value of the voltage regulator to be monitored,
proceed as follows:
1. > Parameter > Cross-monitoring > Press until the desired parameter is displayed.
ðV< regulator 2.
2.Press to increase the value or to reduce it.
3.Press .
ðThe undervoltage limit value is set as an absolute value.
Setting relative value
To set the undervoltage limit value of the voltage regulator to be monitored,
proceed as follows:
1. > Parameter > Cross-monitoring > Press until the desired parameter is displayed.
ðV< regulator 2.
2.Press to increase the value or to reduce it.
6.8.3
3.Press .
ðThe undervoltage limit value is set as a relative value.
Setting overvoltage limit value V> for regulator 2
You can use this parameter to set the overvoltage limit value V> of the device to be monitored. You can set the undervoltage limit value V< as an absolute value (V or kV).
Setting absolute value
You can use the key to change the display to the following units:
Volts (V)Kilovolts (kV)
This value relates to the secondary
voltage of the system's voltage
transformer.
Table 18: Units available
If you want to change the display from V to kV, you have to set the transformer data of the device to be monitored.
This value relates to the primary
voltage of the system's voltage
transformer.
To set the overvoltage limit value of the voltage regulator to be monitored,
proceed as follows:
1. > Parameter > Cross-monitoring > Press until the desired parameter is displayed.
ðV> regulator 2
2.Press to increase the value or to reduce it.
3.Press .
ðThe overvoltage limit value is set as an absolute value.
Setting relative value
To set the overvoltage limit value of the voltage regulator to be monitored,
proceed as follows:
1. > Parameter > Cross-monitoring > Press until the desired parameter is displayed.
ðV< regulator 2.
2.Press to increase the value or to reduce it.
6.8.4
6.8.5
3.Press .
ðThe overvoltage limit value is set as a relative value.
Setting delay time for error message
You can use this parameter to set the delay time for the cross-monitoring error message. If an error is recorded by a monitoring device, the error message is only displayed after the delay time .
To set the error message delay time, proceed as follows:
1. > Parameter > Cross-monitoring > Press until the desired parameter is displayed.
ðError message.
2.Press to increase the value or to reduce it.
3.Press .
ðThe delay time is set.
Setting transformer for regulator 2
You use these parameters to set the transformer data of the device to be
monitored.
Setting the primary transformer voltage
The primary transformer voltage is set in kV.
To set the primary transformer voltage of voltage regulator 2, proceed as follows:
1. > Parameter > Cross-monitoring > Press until the desired parameter is displayed.
ðP.T. prim. voltage reg. 2.
2.Press to highlight the decimal place.
ðThe decimal place is defined and the value can be changed.
3.Press to increase the value or to reduce it.
4.Press .
ðThe primary transformer voltage is set.
Setting the secondary transformer voltage
The secondary transformer voltage is set in V.
To set the secondary transformer voltage of voltage regulator 2, proceed as
follows:
1. > Parameter > Cross-monitoring > Press until the desired parameter is displayed.
ðP.T. sec. voltage reg. 2.
2.Press to increase the value or to reduce it.
3.Press .
ðThe secondary transformer voltage is set.
Transformer data
6.9
The transformation ratios and measuring set-up for the voltage and current
transformers used can be set with the following parameters. The device
uses this information to calculate the corresponding measured values on the
primary side of the current transformer (and therefore the transformer) from
the recorded measured values. These are then displayed.
The following parameters are available for this purpose:
▪Primary voltage
▪Secondary voltage
▪Primary current
▪Secondary current (current transformer connection)
▪Transformer circuit
The measured values displayed for the device are influenced by the settings
for the above parameters. Note the table below.
Table 19: Influence of transformer data on measured value display
Secon-
dary
voltage
Primary
current
Trans-
former
connec-
tion
Voltage (main
screen)
age [V]
[kV]
[kV]
[kV]
[kV]
Current
(main screen)
-Secondary cur-
-Secondary cur-
Primary cur-
rent [A]
-Secondary cur-
Primary cur-
rent [A]
Current (info
screen)
rent [% of con-
nection]
rent [% of con-
nection]
Secondary cur-
rent [% of con-
nection]
rent [A]
Secondary cur-
rent [A]
6.9.1
Setting the primary transformer voltage
This parameter can be used to set the primary transformer voltage in kV.
When you are setting the primary transformer voltage, the device shows the
primary voltage rather than the secondary voltage in the main screen and
you can also set the control parameters in kV.
If a setting of 0 kV is chosen, no primary transformer voltage is displayed.
To set the primary transformer voltage, proceed as follows:
4.Press .
ðThe primary transformer current is set.
6.9.4
6.9.5
Setting the current transformer connection
This parameter can be used to set the current transformer connection. This
setting is needed for the device to display the correct secondary current in
the info screen.
If you select the "Unknown" option, the percentage of current (with reference
to the current transformer connection used) is displayed in the info screen.
▪0.2 A
▪1 A
▪5 A
To set the current transformer connection, proceed as follows:
1. > Configuration > Transformer data > Press until the
desired parameter is displayed.
ðCurrent transformer connection.
2.Press or to select the required connection terminal.
3.Press .
ðThe current transformer connection is set.
Setting the phase difference for the current transformer/voltage
transformer
You can use this parameter to set the phase difference of the current transformer and voltage transformer. You can set the common transformer circuits as follows:
▪The voltage transformer VT is connected to the outer conductor and
neutral conductor.
▪The current transformer CT is looped into the outer conductor.
▪The voltage UL1 and current IL1 are in phase.
▪The voltage drop on an outer conductor is determined by the current IL1.
Circuit B: 1-phase measurement in 3-phase grid
Figure 52: Phase difference 0 3PHN
▪The voltage transformer VT is connected to the outer conductors L1 and
neutral.
▪The current transformer CT is looped into the outer conductor L1.
▪The voltage U and current I are in phase.
▪The voltage drop on an outer conductor is determined by the current IL1.
▪The voltage transformer VT is connected to the outer conductors L1 and
L2.
▪The current transformer CT1 is looped into the outer conductor L1 and
CT2 into the outer conductor L2.
▪The current transformers CT1 and CT2 are connected crosswise in par-
allel (total current = IL1 + IL2).
▪The total current IL1 + IL2 and voltage UL1-UL2 are in phase.
▪The voltage drop on an outer conductor is determined by the current:
(IL1 + IL2) / √3.
Circuit D
Figure 54: Phase difference 90 3PH
▪The voltage transformer VT is connected to the outer conductors L1 and
L2.
▪The current transformer CT is looped into the outer conductor L3.
▪The current IL3 is ahead of voltage UL1-VL2 by 90°.
▪The voltage drop on an outer conductor is determined by the current IL3.
▪The voltage transformer VT is connected to the outer conductors L1 and
L2.
▪The current transformer CT is looped into the outer conductor L2.
▪The current IL2 is ahead of voltage UL2-UL1 by 30°.
▪The voltage drop on an outer conductor is determined by the current IL2.
Circuit F
Figure 56: Phase difference -30 3PH
▪The voltage transformer VT is connected to the outer conductors L1 and
L2.
▪The current transformer CT is looped into the outer conductor L1.
▪The current IL1 lags behind UL1-UL2 by 30°. This corresponds to a phase
shift of -30°.
▪The voltage drop on an outer conductor is determined by the current IL1.
To set the phase difference for the transformer circuit, proceed as follows:
1. > Configuration > Transformer data > Press until the
desired parameter is displayed.
ðTransformer circuit.
2.Press or to select the required phase difference.
3.Press .
ðThe phase difference is set.
6.10
Conditions for parallel
operation
Parallel operation of several banks of transformers
In the Parallel operation menu item, you can set the parameters needed for
parallel operation of banks of transformers. Parallel operation of banks of
transformers is used to increase the throughput capacity or short-circuit capacity in one place.
Compliance with the following general conditions is required for operating
banks of transformers in parallel:
▪Identical rated voltage
▪Transformer power ratio (< 3 : 1)
▪Maximum deviation of short-circuit voltages (UK) for transformers con-
nected in parallel < 10 %
▪Same number of switching groups
You can control up to 16 banks of transformers connected in parallel in one
or 2 groups without detecting the system topology. Information is swapped
between the voltage regulators operating in parallel using the CAN bus. Parallel operation is activated using one of 2 status inputs or the control system.
Parallel control can take one of two forms:
▪Parallel operation following the "Circulating reactive current minimiza-
tion" principle
▪Parallel operation following the "Tap synchronization" (master/follower)
principle
The following sections describe how you can set the parameters.
You can use this parameter to assign a CAN bus address to the device. So
that all devices can communicate using the CAN bus, each device requires a
unique identifier. Addresses can be set from 1 to 16. If the value is set to 0,
then no communication takes place.
To enter the CAN bus address, proceed as follows:
Page 92
6 Functions and settings
1. > Configuration > Parallel operation > Press until the
desired parameter is displayed.
ðCAN address.
2.Press to increase the value or to reduce it.
3.Press .
ðThe CAN bus address is saved.
6.10.2
6.10.2.1
Selecting parallel operation method
You can use this parameter to select a parallel operation method. Two different methods can be assigned to the device.
▪Circulating reactive current minimization
▪Tap synchronization (master/follower)
You must select the same parallel operation method for all voltage regulators operating in parallel.
The following sections describe how you can set the parameters for a parallel operation method.
Setting circulating reactive current method
When the circulating reactive current parallel operation method is selected, then parallel operation is carried out using the circulating reactive current
minimization method. The circulating reactive current is calculated from the
transformer currents and their phase angles. A voltage proportional to the
circulating reactive current is added to the independently operating voltage
regulators as a correction for the measurement voltage. This voltage correction can be reduced or increased using the circulating reactive current sensitivity setting.
The circulating reactive current method is suited to transformers connected
in parallel with a similar nominal output and short-circuit voltage VK and to
vector groups with the same and different step voltages. This does not require any information about the tap position.
To set the circulating reactive current parallel operation method, proceed
as follows:
2.Press or until circulating reactive current appears in the display.
3.Press .
ðThe parallel operation method is set.
When using the circulating reactive current parallel operation method, you
have to set the parameters for the circulating reactive current sensitivity
and circulating reactive current blocking.
Setting circulating reactive current sensitivity
The circulating reactive current sensitivity is a measure of its effect on the
behavior of the voltage regulator. At a setting of 0 % no effect is present.
With circulating reactive current relating to the rated current of the current
transformer, if you set the value to 10 % for example, this would cause the
voltage in the voltage regulator to be corrected by 10 %. This correction to
the voltage can be increased or decreased with this setting to attain the optimum value.
As soon as you change the circulating reactive current sensitivity value, the
value for the result changes in the help text in the display.
To set the circulating reactive current sensitivity, proceed as follows:
1. > Configuration > Parallel operation > Press until the
desired parameter is displayed.
ðStability.
2.Press to increase the value or to reduce it.
3.If necessary, press to highlight the decimal place.
ðThe decimal place is now highlighted and the value can be
changed.
4.Press .
ðThe circulating reactive current sensitivity is set.
Setting circulating reactive current blocking
You can use this parameter to set the limit value for the maximum permissible circulating reactive current. If, during parallel operation, the circulating reactive current exceeds the set limit value, then the following event is activated:
▪Problem with parallel operation
All devices operating in parallel are blocked. Depending on the set delay
time for the parallel operation error message, the signaling relay Problem
with parallel operation is activated.
To set the blocking limit for the maximum permitted circulating reactive current, proceed as follows:
1. > Configuration > Parallel operation > Press until the
desired parameter is displayed.
ðBlocking.
2.Press to increase the value or to reduce it.
3.Press .
ðThe blocking limit for the maximum permitted circulating reactive current
is set.
6.10.2.2
Setting tap synchronization
With the tap synchronization method, you need to designate one voltage
regulator as the master and all others as followers. The master handles voltage regulation and transmits its latest tap positions to all followers via the
CAN bus. The followers compare the tap position received with their own tap
position. If the set permissible tap difference between the tap position received and their own position is exceeded, the followers switch to the tap position received from the master. This ensures that the transformers operating
in parallel are always in the same tap position.
For the tap synchronization method, you can select the following options:
OptionDescription
MasterThe voltage regulator is designated as the master.
FollowerThe voltage regulator is designated as the follower.
Sync.autoAutomatic assignment of master or follower.
If no master is detected, the voltage regulator with the
lowest CAN bus address is automatically designated
as the master. All other voltage regulators are designated as followers.
Table 22: Tap synchronization method
In parallel operation, an individual CAN bus address must be assigned to
each voltage regulator. Up to 16 CAN participants are supported.
Proceed as follows to set the tap synchronization method:
As an option, the device can be fitted with a plug-in card for parallel operation with an existing parallel operation control unit when extending existing
systems. You can connect the following parallel operation control units:
▪SKB 30E
▪VC 100E-PM/PC
The settings required for parallel control must be undertaken in accordance
with the relevant valid operating instructions of the parallel operation control
unit.
If you do not have a parallel control unit, in the SKB parallel operation display you must select the Off selection. The possible selections are described
in more detail in the table below.
SelectionFunction
OnParallel operation control with existing parallel control
unit
OffParallel operation control via CAN bus
Table 23: Settings for SKB parallel operation
To select the type of parallel operation control, proceed as follows:
1. > Configuration > Parallel operation > Press until the
desired parameter is displayed.
ðSKB parallel operation.
6.10.4
2.Press or to set the option you want.
3.Press .
ðThe type of parallel control is set.
Setting delay time for parallel operation error messages
You can use this parameter to set the delay time for a parallel operation error message so that brief fault messages are not received if the motor-drive
units involved in the parallel operation have different runtimes. Once the set
delay time has elapsed, the event is issued at the output relay. Automatic
regulation is blocked and the on-load tap-changers can only be adjusted in
manual mode.
To set the delay time for the parallel operation error message, proceed as
follows:
2.Press or to deactivate parallel operation with the Off selection.
3.Press .
ðParallel operation is deactivated.
Analog tap position capture (optional)
For the analog tap position capture, you must assign the lowest tap position
to the analog input for the minimum measured value and the highest tap position for the maximum measured value.
The device is configured at the factory according to the order. However,
should modifications be necessary, note the following sections.
The analog input card is used to record the tap position of an analog signal
transmitter. Depending on device configuration, you can capture the following signals:
6.11.1
AD cardAD8 card
Resistor contact series50...2,000 ohmsnot possible
Injected current0/4...20 mA0/4...20 mA
Table 24: Analog tap position capture
Setting lower limit value
You can use these parameters to set the lower limit value for the tap position . To do this, you must set the lower value of the signal range and the
linked lowest tap position.
You can undertake the settings for each input on the analog input card.
2.Press to highlight the position.
ðThe desired position is highlighted and the value can be changed.
3.Press to increase the value or to reduce it.
4.Press .
ðThe lower limit value for the tap position is assigned.
6.11.2
Setting lower value of input signal
To configure the analog input, an absolute value must be assigned to the
lower value of the applied signal.
To set the lower value for the input, proceed as follows:
1. > Configuration > Continue > Analog inputs > Press
until the desired parameter is displayed.
ðInput 1 lower value.
2.Press to increase the value or to reduce it.
3.Press .
ðThe lower value for the tap position is assigned.
Setting upper limit value
You can use parameters to set the upper value for the tap position. To do
this, you must set the upper value of the signal range and linked highest tap
position.
Depending on your device configuration, the following parameters can be
used by MR for special functions. In this case, these parameters are pre-assigned. You may not be able to view or freely assign these parameters.
Functions available for
LEDs
An overview of all possible functions which you can assign to the LEDs is
provided in the table below.
Functions
Function description
available
OffLED deactivated
IOxx/UCxxThere is a signal at control input IOxx/UCxx (e.g. IO:25)
SI:bef1SI:bef1 (command) is received
SI:bef2SI:bef2 (command) is received
UndervoltageUndervoltage present
OvervoltageOvervoltage present
OvercurrentOvercurrent present
Par. errorParallel operation error present
Motor protec-
Motor protective switch triggered
tion
BlockingRegulation is blocked
Circulating re-
active current
Parallel operation selected using circulating reactive
current method
MasterDevice in parallel operation activated as master
FollowerDevice in parallel operation activated as follower
AutomaticAuto mode activated
Bandwidth <Value is below bandwidth
Bandwidth >Value is above bandwidth
Power-
Power-dependent desired value adjustment activated
dep.des.
Table 27: Functions available for LEDs
Assigning function
To assign a function to an LED, proceed as follows:
1. > Configuration > Continue > LED selection > Press
until the desired parameter is displayed.
Depending on the configuration and version of the measuring transducer
module 2 or 4, the transducer module can be used to obtain measured values as analog values in the following ranges:
▪± 20 mA
▪± 10 mA
▪± 10 V (only AN2 card)
▪± 1 mA
The following values are available:
▪V1
▪V2 (optional via a second measurement input)
▪I1
▪Active current
▪Reactive current
▪Active power
▪Reactive power
▪Apparent power
▪Tap position
▪Desired value
6.13.1
6.13.2
If the analog outputs have not been set as you want them in the factory, the
section below describes how you can adjust the measuring transducer.
Linking measured value with output
In this display you can assign a measured value to be transferred to the
measuring transducer output.
In order to assign a measured value to the measuring transducer output,
proceed as follows (example using measuring transducer 1/2; "output 1
measured value"):