MR TAPCON 230 VC Operating Instructions Manual

www.reinhausen.com
Voltage Regulator TAPCON® 230 VC (Substitution for VC 100)
Operating Instructions BA 251/02
251/02 en
1
Contents
Contents
1 General .............................................................................................................................................................................................................. 4
1.3 Design and performance features of the TAPCON® 230 VC................................................................................................ 5
2 Technical Data................................................................................................................................................................................................ 6
3 Operation ......................................................................................................................................................................................................... 9
3.1 Input and output of data; functions .......................................................................................................................................... 9
3.2 Description of the front panel ...................................................................................................................................................... 9
3.2.1 Display..................................................................................................................................................................................... 10
3.2.2 Local/remote switch ........................................................................................................................................................... 11
4 Parametering .................................................................................................................................................................................................. 11
4.1 Normset setting ................................................................................................................................................................................. 11
4.2 Setting the desired voltage level 1 .............................................................................................................................................. 12
4.3 Setting the bandwidth .................................................................................................................................................................... 12
4.4 Setting the delay time T1 or T2 (DELAY 1/DELAY 2) and pulse duration (option) ........................................................ 12
4.5 Setting the overvoltage detection (U>) with automatic return control ......................................................................... 13
4.6 Setting the undervoltage blocking (U<) .................................................................................................................................... 13
4.7 Setting the overcurrent blocking (I>) ......................................................................................................................................... 13
4.8 Measuring transformers (VT, CT configuration) ....................................................................................................................... 15
4.9 Setting the desired voltage levels DVL2 and DVL3 ................................................................................................................. 15
4.10 Line compensation ............................................................................................................................................................................ 15
4.10.1 Line drop compensation (LDC) ........................................................................................................................................ 15
4.10.2 Z-Compensation .................................................................................................................................................................. 16
4.11 Analog remote position indication (option) ............................................................................................................................. 16
4.12 Voltage regulator identification ................................................................................................................................................... 17
4.13 Setting the unit to V or kV ............................................................................................................................................................. 17
4.14 Selection of the display in the 4th line of the display ........................................................................................................... 17
2
251/02 en
Contents
5 Commissioning ............................................................................................................................................................................................... 18
5.1 Installation .......................................................................................................................................................................................... 18
5.2 Connection .......................................................................................................................................................................................... 18
5.3 Easy setting of operating modes with Normset ...................................................................................................................... 19
5.4 Function tests; operational settings............................................................................................................................................ 19
5.5 Tap position indication .................................................................................................................................................................... 20
6 Parallel operation.......................................................................................................................................................................................... 21
6.1 Parallel operation with "Minimum Circulating Reactive Current Method“ .................................................................... 22
6.1.1 System configuration, settings ....................................................................................................................................... 22
6.1.2 Setting the interference variable (CIRCUL. REAC. CURR. STABILITY) .................................................................. 22
6.1.3 Setting the bandwidth for circulating reactive current (blocking threshold) ................................................. 22
6.1.4 Function tests, commissioning ........................................................................................................................................ 23
6.1.4.1 Preliminary settings .......................................................................................................................................... 23
6.1.4.2 Setting the interference variable (CIRCUL. REAC. CURR. STABILITY) ................................................ 23
6.1.4.3 Setting the circulating reactive current monitoring
(CIRCUL. REAC. CURR. MON. BANDWIDTH) ............................................................................................... 23
6.2 Parallel operation according to synchronized tap-change operation Master/ Follower ............................................ 23
6.2.1 System configuration, settings, transfer of the on-load tap-changer setting................................................ 24
6.2.1.1 Setting the tapping position range ............................................................................................................. 24
6.2.1.2 Selecting the Master/Follower operation .................................................................................................. 25
6.2.2 Function tests, commissioning and preliminary settings ........................................................................................ 25
6.3 Parallel operation with existing parallel control unit SKB 30 based on
"minimum circulating reactive current" .................................................................................................................................... 25
6.4 Disturbances during parallel operation...................................................................................................................................... 25
7 Appendix ........................................................................................................................................................................................................... 27
NOTE
A "PARAM?" message appearing in the first line of the display indicates a negative result of the parameter verification that may be caused by interference above the permissible electromagnetic compatibility limit (see information on standardisation and verification in section 2). In this case, voltage regulation is blocked for safety reasons. Check the settings in order to clear the blocking. Press and hold the "SELECT" key and press the "" or "" key for displaying the current settings (see section 3.2.1). Voltage regulation is reinstated once invalid settings have been corrected while cycling through the menu. The status LEDs and status relays are activated, and the display shows the current measurement readings.
NOTE
Data contained herein may differ in details from the equipment delivered. We reserve the right to make alterations without notice.
251/02 en
3
1 General
1 General
1.1 Safety instructions
All personnel involved in installation, commissioning, maintenance or repair of this equipment must:
- be suitably qualified and
- strictly observe these operating instructions.
Improper operation or misuse can lead to
- serious or fatal injury,
- damage to the equipment and property of the user and
- a reduction in the efficiency of the equipment.
Safety instructions in this manual are presented in three different forms to emphasize important information.
WARNING
This information indicates particular danger to life and health. Disregarding such a warning can lead to serious or fatal injury.
CAUTION
This information indicates particular danger to the equip­ment or other property of the user. Serious or fatal injury cannot be excluded.
NOTE
1.2 Specified application
The electronic voltage regulator TAPCON® 230 VC serves for automatic control of transformers with a motor-driven on­load tap-changer. The motor-drive mechanism receives the corresponding control commands from the voltage regulator. With these commands, the on-load tap-changer moves to the next position and the transformer’s voltage value is adapted to the preset desired voltage level.
To allow individual adaptation of the control system to the various field service conditions encountered, influencing variables such as time delay, bandwidth, and even line­dependent and load-dependent parameters can be pro­grammed for compensation of voltage-dependent and/or current-dependent limits. As a special feature, the voltage regulator is also capable of controlling parallel transformer operation.
CAUTION
Installation, electrical connection and commissioning of the electronic voltage regulator may only be carried out by qualified, skilled personnel and only in accordance with these operating instructions. It is the responsibility of the user to make sure that the electronic voltage regulator is used for the specific application only. For safety reasons, any unauthorized and improperly executed works, i.e. installation, modification, alteration of the equipment, electrical connection, or commissioning of the equipment, are forbidden without first consulting MR!
The trouble-free operation of the drive, the on-load tap­changer, and the transformer may be put at risk.
These notes give important information on a certain subject.
4
WARNING
All relevant fire protection regulations must be strictly observed
251/02 en
1 General
1.3 Design and performance features of the TAPCON® 230 VC
The electronic voltage regulator TAPCON® 230 VC is mounted in a protective housing with hinged cover and inspection win-dow. The protective housing is suitable for both flush and projected panel mounting.
The front panel contains several function keys for setting the individual operating parameters.
Display of the operating status is achieved by a 4-line, 16-digit alphanumeric LC display and light emitting diodes.
The electronic voltage regulator is controlled by a micro­controller (see appendix, block/connection diagram). Besides a voltage transformer and a current transformer it contains optocoupler inputs with potential separation as well as potential-free output relay contacts.
Apart from the usual well-known, versatile and individual set­ting options for the MR control system, the TAPCON® 230 VC voltage regulator also offers the option of fast and easy parametering by introducing the innovative "Normset" function.
The term „Normset“ function stands for an automatism which considerably simplifies the configuration of a voltage regulator. If the desired voltage level is entered while the „Normset“ function is active, the voltage regulator will examine the given line/network conditions and proceed to perform an automatic adaptation of all further inputs (comprised in part of the pre-parametering and standard reference values) which used to be required for customary regulators (also refer to the standard configuration accord­ing to Sub-menu 2).
Parallel operation follows alternatively the principles of either minimum circulating reactive current or the Master/ Follower principle for two transformers.
Using a supplementary device, up to six transformers can be controlled in parallel operation using the principle of minimum reactive current.
NOTE
When voltage regulation is effected by tap transformers and voltage regulators, it is assumed that a change of the tap position results in a significant voltage change. When generators feed the voltage level to be regulated, however, quite different conditions may result so that a correct regulation of the voltage cannot be guaranteed. In such cases MR should be consulted as early as the planning stage.
The parameters of the regulator can be set by means of a PC via the incorporated serial interface (RS232) integrated in the regulator; the appropriate PC software will be furnished by MR.
A load-dependent line-voltage drop, e.g. of a spur line lead­ing from the transformer to the load, can be compensated either by line simulation (Line Drop Compensation) or by load-current dependent increase of the voltage level (Z compensation).
Trouble-free operation is ensured by the regulator’s inherent undervoltage blocking, overcurrent blocking and overvoltage monitoring.
The functions of the TAPCON® 230 VC voltage regulator are just about compatible with those of the earlier voltage regulators VC 100-BU.
251/02 en
5
2 Technical Data
2 Technical Data
Setting ranges
Standard Standard setting range step width
Desired voltage level 1 85 – 140 V 0.1 V steps
Desired voltage level 2 85 – 140 V 0.1 V steps
Desired voltage level 3 85 – 140 V 0.1 V steps
Bandwidth ± 0.5 ... ± 9 % 0.1 %
Delay time T1 0 ... 180 s 1 s
Delay time T2 1 … 10 s 1 s
Switching pulse duration 0.5 ... 10 s 0.5 s
LDC Ur = 0 ... ± 25 V 0.1 V
Ux = 0 ... ± 25 V 0.1 V With optional Z compensation selection Voltage rise 0.1 %
0...15 %
Limitation 0...15 % 0.1 %
Undervoltage blocking 70 ... 99 % 1 % Overvoltage detection 101 ... 130 % 1 % with high speed return control pulse signal 1.5 / 1.5 s
Overcurrent blocking 50 ... 210 % 5 % Voltage transformer 0.1 ... 999,9 kV/100 V Current transformer 100 ... 5000 A/5/1/0.2 A
Measuring circuit Phase angle adjustable
between current and
voltage circuit:
-30° 3-phase 0° 3-phae
+30° 3-phase +90° 3-phase
1-phase
6
251/02 en
2 Technical Data
Display 4-line, 16-digit LC display
1 LED lamp (green) for signalling status 1 LED lamp (red) each for signalling U<, U>, I> 1 LED lamp (green) for signalling“parallel operation active“ status 1 LED lamp (green) for signalling "Normset active“ status
Inputs and outputs Input relays Output relays
1x parallel Rating of relay contacts: 1x high-speed circuit breaker of voltage AC: 250 V 5 A
limit monitoring indicator DC: 30 V 5 A; 110 V 0.4 A; 1 x analogue input of tapping position 4- 20 mA 220 V 0.3 A 1 x desired voltage level 2 1 x raise 1 x desired voltage level 3 1 x lower
1 x automatic control mode 1 x status 1x group interrupt U<, U>, I> 1x monitoring (function monitoring)
Voltage transformer 85 ... 140 V, measuring range 60 ... 185 V,
r.m.s. value 40 ... 60 Hz, intrinsic consumption < 1 VA
Current transformer 0.2 / 1 / 5 A, 40 ... 60 Hz, r.m.s. value
intrinsic consumption < 1 VA, overload capacity 2x In continuously, 100x In/1 s
Measuring errors Voltage measuring: < 0.3 % ± 40 ppm/°C
Current measuring: < 0.5 % ± 40 ppm/°C
Serial interfaces 1 x RS232 (COM1) for
parametering via PC 1 x RS 232 for parallel operation of two transformers with a second regulator or for parallel operation with digital MR parallel control unit SKB
IEC EN 60688
Power supply 115 V (+25 % - 35 %) 40 - 60 Hz, can be changed over either from
the measuring voltage or by separate change-over in the factory to a supply voltage of 230 V
Power consumption approx. 5.5 VA (at 115V, idle state)
251/02 en
7
2 Technical Data
Protective housing Steel-plate housing with inspection window for flush or projected panel mounting
W x H x D: 216 x 326 x 137mm Degree of protection provided by enclosure: IP 44 according to IEC 60529 Weight: approx. 5.4 kgs
Temperature limits Admissible ambient temperature for operation: -10 °C ... + 70 °C
Admissible ambient temperature for storage and transport: -25 °C ... +80 °C
Tests
IEC 255-5 Dielectric tests performed at 2.5 kV/1 min operating frequency and 5 kV, 1.2|50 μs impulse voltage
IEC 61000-4-2 Interference immunity tests (EMC): electrostatic discharge 4 kV / 8 kV
IEC 61000-4-3 Interference immunity tests (EMC): electromagnetic fields 10 V/m
80-1000 MHz
IEC 61000-4-4 Interference immunity tests (EMC): burst 1MHz, 4 kV
IEC 61000-4-5 Interference immunity, surge 2 kV
IEC 61000-4-6 HF interference immunity of leads: 10V, 150 kHz – 80 MHz
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-4 Emission standards for industrial environments
VDE 0435 Short-time current and continuous rating of the current transformer inputs,
100 x In/1s and 2 x In/continuously
VDE 0100 Provisions governing the erection of electrical power installations featuring rated system voltages
up to 1,000 V Grounding conductors, protective conductors, equipotential bonding conductors,
arrangement of operating elements
IEC 61010 / VDE 0411 Safety requirements for electrical equipment for measurement, control, regulation and
laboratory use
VDE 0110 Provisions governing the rating of clearance in air and creepage distances in electrical equipment
IEC 60529 Determination of the degree of protection provided by enclosures: „Shock-hazard protection,
protection against ingress of solid foreign bodies and protection against the ingress of water for electrical equipment“ Level IP00
IEC 60068 Basic environmental test procedures
IEC 60068-2-1 Cold test for heat-dissipating specimens, with slow temperature change rate -10°C / 20 hours
IEC 60068-2-2 Dry-heat test for heat-dissipating specimens, with slow temperature change rate
+70 °C / 16 hous
IEC 60068-2-3 Humid heat, constant
+40 °C / 93 % / 56 days
IEC 60068-2-30 Humid heat, cyclical (12 + 12 hours)
+ 55 °C / 93 % and + 25 °C / 95 % / 6 cycles
IEC 60068-2-31 Drops and topple, unpacked, 100 mm height
IEC 60068-2-32 Free fall, unpacked, 250 mm height
IEC 61000-4-8 Power frequency magnetic field immunity test
IEC 61000-4-11 Voltage dips, short interruptions and voltage variations immunity tests
8
251/02 en
3 Operation
3 Operation
3.1 Input and output of data; functions
The following instructions tell you how to call up the basic functions of the TAPCON® 230 VC voltage regulator and how to reset parameters.
3.2 Description of the front panel (fig. 1)
Generally, the keys located at the front panel fall into two different basic groups.
• Operating keys
• Function keys for menu guidance The LED’s located in the front panel’s upper area serve for
signalling the following system statuses:
• Operating status display
• Overcurrent blocking
• Undervoltage blocking
• Overvoltage monitoring
• Parallel operation
• NORMSET
Change-over between manual mode/automatic mode
Reset setting values via the Higher/Lower keys
LCD-Display
Parametering interface
Light-
emitting diodes
Reset setting
values via „SET“
Change the
windows via the Higher/ Lower keys
1
251/02 en
9
3 Operation
3.2.1 Display
<
<
The TAPCON® 230 VC contains a 4-line, 16-digit LC display. A distinction is made between the two following types of
displays: Basic display and parametering display.
a) Basic display In addition to the actual voltage level, the desired voltage
level and the deviations the basic display indicates an additional measuring value in the 4th line during normal operation. Selection of this measuring value in the display window „SELECT 4th LINE“.
The following values are available:
- Current I - Power factor cos PHI
- Apparent power S - Frequency f
- Reactive power Q - Status line
- Active power P - Position, optional
- Phase angle PHI
ACTUAL VOLT.LEVEL 64.90 kV DESIRED VOLT.LEVEL 66.00 kV dU% 1.67 % CURRENT I 253 A
b) Parametering display windows The TAPCON® 230 VC contains parametering display windows which serve to display set parameters and allow the user to modify any previously set parameters to suit his specifica-tions. Generally, these windows are set up as follows:
- 1st line: Title/designation of the parameter
- 2nd line: Set value
- 3rd line: Possible setting values and/or setting limits
- 4th line: Serial number of the display
DESIRED VOLT.LEVEL SW1 110V (85V- 140V)
02/30
The displays are situated behind one another in a ring­shaped arrangement, as shown in the illustration to the right, and can be selected by operating the function keys SELECT
and . The display will remain visible for as long as the SELECT key is being pressed, plus an additional 10 seconds after the SELECT key was released. It is possible to move in both directions within the menu. As a result, display no. 30 of the basic display can be reached just as quickly as display no. 1.
The preset value can be altered within the setting values and/ or setting limits by operating the SET and func­tion keys. Once the SET key is released, the new value will be set to ‚active’. For parametering purposes, please use the displays listed below, the functions of which are explained in detail in the following.
10
NORMSET ON ON/ OFF
DES.VOLTAGE LEVEL DVL1 100V (85V- 140V
BANDWIDTH
9.0% (0.5% - 9%)
DELAY T1 10s (0s- 180s)
T1 LINEAR INTEGRAL LINEAR (LINEAR/INTEGRAL)
DELAY T2 10s (PERM,1-10s,OFF)
OVERVOLTAGE U> 105% (101%-130%)
UNDERVOLTAGE U< 70% (70%- 99%)
OVERCURRENT I> 110% (50% - 210%)
NOM.TRANSF.VOLTAGE
10.0V (0.1kV- 999.9kV)
CURRENT 100A (100A- 5000A)
TRANSFORMER PHASE 90 3 PH (30,0,30,90,1PH)
DES.VOLT.LEVEL DVL2 100V (85V- 140.0V)
DES.VOLT.LEVEL DV3
100.0V (85.0V- 140.0V)
LDC UR
0.0V (-25.0V - 25.0V)
01/30
)
02/30
03/30
04/30
05/30
06/30
07/30
08/30
09/30
10/30
11/30
12/30
13/30
14/30
15/30
LANGUAGE GERMAN GER/GB/F/E
SELECTION 4th LINE CURRENT I (I,S,Q,P,PHI,..)
DISPLAY V/kV kV (V/ kV)
H/T PULSE DURATION 0,5 s (0.0 s - 10.0 s)
VOLT.REG.IDENTIFIER 1111 (0- 9999)
PARAL. OPERATION TWIN PARALLEL SKB/TWIN PARALL
CIRCUL.REAC.CURR. BANDWIDTH 20% (0.5% - 20.0%)24/30
CIRCUL.REAC.CURR. STABILITY
0.0 (0.0- 100.0) 23/30
TAPPING DIRECTION NEGATIVE POSITIVE / NEGATIVE
POS MAX 35 (-35 – 35)
POS MIN 1 (-35 – 35)
SELECT PARALLEL CIRCUL.REAC.CURR. CRC/MAST/FOLLOW
Z-COMP LIMIT
0.0% (0%- 15.0%)
Z-COMP VOLTRISE
0.0% (0.0% - 15.0%)
LDC UX
0.0V (-25.0V - 25.0V)
<
<
30/30
29/30
28/30
27/30
26/30
25/30
22/30
21/30
20/30
19/30
18/30
17/30
16/30
251/02 en
Loading...
+ 22 hidden pages