MR TAPCON 230 VC Operating Instructions Manual

www.reinhausen.com
Voltage Regulator TAPCON® 230 VC (Substitution for VC 100)
Operating Instructions BA 251/02
251/02 en
1
Contents
Contents
1 General .............................................................................................................................................................................................................. 4
1.3 Design and performance features of the TAPCON® 230 VC................................................................................................ 5
2 Technical Data................................................................................................................................................................................................ 6
3 Operation ......................................................................................................................................................................................................... 9
3.1 Input and output of data; functions .......................................................................................................................................... 9
3.2 Description of the front panel ...................................................................................................................................................... 9
3.2.1 Display..................................................................................................................................................................................... 10
3.2.2 Local/remote switch ........................................................................................................................................................... 11
4 Parametering .................................................................................................................................................................................................. 11
4.1 Normset setting ................................................................................................................................................................................. 11
4.2 Setting the desired voltage level 1 .............................................................................................................................................. 12
4.3 Setting the bandwidth .................................................................................................................................................................... 12
4.4 Setting the delay time T1 or T2 (DELAY 1/DELAY 2) and pulse duration (option) ........................................................ 12
4.5 Setting the overvoltage detection (U>) with automatic return control ......................................................................... 13
4.6 Setting the undervoltage blocking (U<) .................................................................................................................................... 13
4.7 Setting the overcurrent blocking (I>) ......................................................................................................................................... 13
4.8 Measuring transformers (VT, CT configuration) ....................................................................................................................... 15
4.9 Setting the desired voltage levels DVL2 and DVL3 ................................................................................................................. 15
4.10 Line compensation ............................................................................................................................................................................ 15
4.10.1 Line drop compensation (LDC) ........................................................................................................................................ 15
4.10.2 Z-Compensation .................................................................................................................................................................. 16
4.11 Analog remote position indication (option) ............................................................................................................................. 16
4.12 Voltage regulator identification ................................................................................................................................................... 17
4.13 Setting the unit to V or kV ............................................................................................................................................................. 17
4.14 Selection of the display in the 4th line of the display ........................................................................................................... 17
2
251/02 en
Contents
5 Commissioning ............................................................................................................................................................................................... 18
5.1 Installation .......................................................................................................................................................................................... 18
5.2 Connection .......................................................................................................................................................................................... 18
5.3 Easy setting of operating modes with Normset ...................................................................................................................... 19
5.4 Function tests; operational settings............................................................................................................................................ 19
5.5 Tap position indication .................................................................................................................................................................... 20
6 Parallel operation.......................................................................................................................................................................................... 21
6.1 Parallel operation with "Minimum Circulating Reactive Current Method“ .................................................................... 22
6.1.1 System configuration, settings ....................................................................................................................................... 22
6.1.2 Setting the interference variable (CIRCUL. REAC. CURR. STABILITY) .................................................................. 22
6.1.3 Setting the bandwidth for circulating reactive current (blocking threshold) ................................................. 22
6.1.4 Function tests, commissioning ........................................................................................................................................ 23
6.1.4.1 Preliminary settings .......................................................................................................................................... 23
6.1.4.2 Setting the interference variable (CIRCUL. REAC. CURR. STABILITY) ................................................ 23
6.1.4.3 Setting the circulating reactive current monitoring
(CIRCUL. REAC. CURR. MON. BANDWIDTH) ............................................................................................... 23
6.2 Parallel operation according to synchronized tap-change operation Master/ Follower ............................................ 23
6.2.1 System configuration, settings, transfer of the on-load tap-changer setting................................................ 24
6.2.1.1 Setting the tapping position range ............................................................................................................. 24
6.2.1.2 Selecting the Master/Follower operation .................................................................................................. 25
6.2.2 Function tests, commissioning and preliminary settings ........................................................................................ 25
6.3 Parallel operation with existing parallel control unit SKB 30 based on
"minimum circulating reactive current" .................................................................................................................................... 25
6.4 Disturbances during parallel operation...................................................................................................................................... 25
7 Appendix ........................................................................................................................................................................................................... 27
NOTE
A "PARAM?" message appearing in the first line of the display indicates a negative result of the parameter verification that may be caused by interference above the permissible electromagnetic compatibility limit (see information on standardisation and verification in section 2). In this case, voltage regulation is blocked for safety reasons. Check the settings in order to clear the blocking. Press and hold the "SELECT" key and press the "" or "" key for displaying the current settings (see section 3.2.1). Voltage regulation is reinstated once invalid settings have been corrected while cycling through the menu. The status LEDs and status relays are activated, and the display shows the current measurement readings.
NOTE
Data contained herein may differ in details from the equipment delivered. We reserve the right to make alterations without notice.
251/02 en
3
1 General
1 General
1.1 Safety instructions
All personnel involved in installation, commissioning, maintenance or repair of this equipment must:
- be suitably qualified and
- strictly observe these operating instructions.
Improper operation or misuse can lead to
- serious or fatal injury,
- damage to the equipment and property of the user and
- a reduction in the efficiency of the equipment.
Safety instructions in this manual are presented in three different forms to emphasize important information.
WARNING
This information indicates particular danger to life and health. Disregarding such a warning can lead to serious or fatal injury.
CAUTION
This information indicates particular danger to the equip­ment or other property of the user. Serious or fatal injury cannot be excluded.
NOTE
1.2 Specified application
The electronic voltage regulator TAPCON® 230 VC serves for automatic control of transformers with a motor-driven on­load tap-changer. The motor-drive mechanism receives the corresponding control commands from the voltage regulator. With these commands, the on-load tap-changer moves to the next position and the transformer’s voltage value is adapted to the preset desired voltage level.
To allow individual adaptation of the control system to the various field service conditions encountered, influencing variables such as time delay, bandwidth, and even line­dependent and load-dependent parameters can be pro­grammed for compensation of voltage-dependent and/or current-dependent limits. As a special feature, the voltage regulator is also capable of controlling parallel transformer operation.
CAUTION
Installation, electrical connection and commissioning of the electronic voltage regulator may only be carried out by qualified, skilled personnel and only in accordance with these operating instructions. It is the responsibility of the user to make sure that the electronic voltage regulator is used for the specific application only. For safety reasons, any unauthorized and improperly executed works, i.e. installation, modification, alteration of the equipment, electrical connection, or commissioning of the equipment, are forbidden without first consulting MR!
The trouble-free operation of the drive, the on-load tap­changer, and the transformer may be put at risk.
These notes give important information on a certain subject.
4
WARNING
All relevant fire protection regulations must be strictly observed
251/02 en
1 General
1.3 Design and performance features of the TAPCON® 230 VC
The electronic voltage regulator TAPCON® 230 VC is mounted in a protective housing with hinged cover and inspection win-dow. The protective housing is suitable for both flush and projected panel mounting.
The front panel contains several function keys for setting the individual operating parameters.
Display of the operating status is achieved by a 4-line, 16-digit alphanumeric LC display and light emitting diodes.
The electronic voltage regulator is controlled by a micro­controller (see appendix, block/connection diagram). Besides a voltage transformer and a current transformer it contains optocoupler inputs with potential separation as well as potential-free output relay contacts.
Apart from the usual well-known, versatile and individual set­ting options for the MR control system, the TAPCON® 230 VC voltage regulator also offers the option of fast and easy parametering by introducing the innovative "Normset" function.
The term „Normset“ function stands for an automatism which considerably simplifies the configuration of a voltage regulator. If the desired voltage level is entered while the „Normset“ function is active, the voltage regulator will examine the given line/network conditions and proceed to perform an automatic adaptation of all further inputs (comprised in part of the pre-parametering and standard reference values) which used to be required for customary regulators (also refer to the standard configuration accord­ing to Sub-menu 2).
Parallel operation follows alternatively the principles of either minimum circulating reactive current or the Master/ Follower principle for two transformers.
Using a supplementary device, up to six transformers can be controlled in parallel operation using the principle of minimum reactive current.
NOTE
When voltage regulation is effected by tap transformers and voltage regulators, it is assumed that a change of the tap position results in a significant voltage change. When generators feed the voltage level to be regulated, however, quite different conditions may result so that a correct regulation of the voltage cannot be guaranteed. In such cases MR should be consulted as early as the planning stage.
The parameters of the regulator can be set by means of a PC via the incorporated serial interface (RS232) integrated in the regulator; the appropriate PC software will be furnished by MR.
A load-dependent line-voltage drop, e.g. of a spur line lead­ing from the transformer to the load, can be compensated either by line simulation (Line Drop Compensation) or by load-current dependent increase of the voltage level (Z compensation).
Trouble-free operation is ensured by the regulator’s inherent undervoltage blocking, overcurrent blocking and overvoltage monitoring.
The functions of the TAPCON® 230 VC voltage regulator are just about compatible with those of the earlier voltage regulators VC 100-BU.
251/02 en
5
2 Technical Data
2 Technical Data
Setting ranges
Standard Standard setting range step width
Desired voltage level 1 85 – 140 V 0.1 V steps
Desired voltage level 2 85 – 140 V 0.1 V steps
Desired voltage level 3 85 – 140 V 0.1 V steps
Bandwidth ± 0.5 ... ± 9 % 0.1 %
Delay time T1 0 ... 180 s 1 s
Delay time T2 1 … 10 s 1 s
Switching pulse duration 0.5 ... 10 s 0.5 s
LDC Ur = 0 ... ± 25 V 0.1 V
Ux = 0 ... ± 25 V 0.1 V With optional Z compensation selection Voltage rise 0.1 %
0...15 %
Limitation 0...15 % 0.1 %
Undervoltage blocking 70 ... 99 % 1 % Overvoltage detection 101 ... 130 % 1 % with high speed return control pulse signal 1.5 / 1.5 s
Overcurrent blocking 50 ... 210 % 5 % Voltage transformer 0.1 ... 999,9 kV/100 V Current transformer 100 ... 5000 A/5/1/0.2 A
Measuring circuit Phase angle adjustable
between current and
voltage circuit:
-30° 3-phase 0° 3-phae
+30° 3-phase +90° 3-phase
1-phase
6
251/02 en
2 Technical Data
Display 4-line, 16-digit LC display
1 LED lamp (green) for signalling status 1 LED lamp (red) each for signalling U<, U>, I> 1 LED lamp (green) for signalling“parallel operation active“ status 1 LED lamp (green) for signalling "Normset active“ status
Inputs and outputs Input relays Output relays
1x parallel Rating of relay contacts: 1x high-speed circuit breaker of voltage AC: 250 V 5 A
limit monitoring indicator DC: 30 V 5 A; 110 V 0.4 A; 1 x analogue input of tapping position 4- 20 mA 220 V 0.3 A 1 x desired voltage level 2 1 x raise 1 x desired voltage level 3 1 x lower
1 x automatic control mode 1 x status 1x group interrupt U<, U>, I> 1x monitoring (function monitoring)
Voltage transformer 85 ... 140 V, measuring range 60 ... 185 V,
r.m.s. value 40 ... 60 Hz, intrinsic consumption < 1 VA
Current transformer 0.2 / 1 / 5 A, 40 ... 60 Hz, r.m.s. value
intrinsic consumption < 1 VA, overload capacity 2x In continuously, 100x In/1 s
Measuring errors Voltage measuring: < 0.3 % ± 40 ppm/°C
Current measuring: < 0.5 % ± 40 ppm/°C
Serial interfaces 1 x RS232 (COM1) for
parametering via PC 1 x RS 232 for parallel operation of two transformers with a second regulator or for parallel operation with digital MR parallel control unit SKB
IEC EN 60688
Power supply 115 V (+25 % - 35 %) 40 - 60 Hz, can be changed over either from
the measuring voltage or by separate change-over in the factory to a supply voltage of 230 V
Power consumption approx. 5.5 VA (at 115V, idle state)
251/02 en
7
2 Technical Data
Protective housing Steel-plate housing with inspection window for flush or projected panel mounting
W x H x D: 216 x 326 x 137mm Degree of protection provided by enclosure: IP 44 according to IEC 60529 Weight: approx. 5.4 kgs
Temperature limits Admissible ambient temperature for operation: -10 °C ... + 70 °C
Admissible ambient temperature for storage and transport: -25 °C ... +80 °C
Tests
IEC 255-5 Dielectric tests performed at 2.5 kV/1 min operating frequency and 5 kV, 1.2|50 μs impulse voltage
IEC 61000-4-2 Interference immunity tests (EMC): electrostatic discharge 4 kV / 8 kV
IEC 61000-4-3 Interference immunity tests (EMC): electromagnetic fields 10 V/m
80-1000 MHz
IEC 61000-4-4 Interference immunity tests (EMC): burst 1MHz, 4 kV
IEC 61000-4-5 Interference immunity, surge 2 kV
IEC 61000-4-6 HF interference immunity of leads: 10V, 150 kHz – 80 MHz
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-4 Emission standards for industrial environments
VDE 0435 Short-time current and continuous rating of the current transformer inputs,
100 x In/1s and 2 x In/continuously
VDE 0100 Provisions governing the erection of electrical power installations featuring rated system voltages
up to 1,000 V Grounding conductors, protective conductors, equipotential bonding conductors,
arrangement of operating elements
IEC 61010 / VDE 0411 Safety requirements for electrical equipment for measurement, control, regulation and
laboratory use
VDE 0110 Provisions governing the rating of clearance in air and creepage distances in electrical equipment
IEC 60529 Determination of the degree of protection provided by enclosures: „Shock-hazard protection,
protection against ingress of solid foreign bodies and protection against the ingress of water for electrical equipment“ Level IP00
IEC 60068 Basic environmental test procedures
IEC 60068-2-1 Cold test for heat-dissipating specimens, with slow temperature change rate -10°C / 20 hours
IEC 60068-2-2 Dry-heat test for heat-dissipating specimens, with slow temperature change rate
+70 °C / 16 hous
IEC 60068-2-3 Humid heat, constant
+40 °C / 93 % / 56 days
IEC 60068-2-30 Humid heat, cyclical (12 + 12 hours)
+ 55 °C / 93 % and + 25 °C / 95 % / 6 cycles
IEC 60068-2-31 Drops and topple, unpacked, 100 mm height
IEC 60068-2-32 Free fall, unpacked, 250 mm height
IEC 61000-4-8 Power frequency magnetic field immunity test
IEC 61000-4-11 Voltage dips, short interruptions and voltage variations immunity tests
8
251/02 en
3 Operation
3 Operation
3.1 Input and output of data; functions
The following instructions tell you how to call up the basic functions of the TAPCON® 230 VC voltage regulator and how to reset parameters.
3.2 Description of the front panel (fig. 1)
Generally, the keys located at the front panel fall into two different basic groups.
• Operating keys
• Function keys for menu guidance The LED’s located in the front panel’s upper area serve for
signalling the following system statuses:
• Operating status display
• Overcurrent blocking
• Undervoltage blocking
• Overvoltage monitoring
• Parallel operation
• NORMSET
Change-over between manual mode/automatic mode
Reset setting values via the Higher/Lower keys
LCD-Display
Parametering interface
Light-
emitting diodes
Reset setting
values via „SET“
Change the
windows via the Higher/ Lower keys
1
251/02 en
9
3 Operation
3.2.1 Display
<
<
The TAPCON® 230 VC contains a 4-line, 16-digit LC display. A distinction is made between the two following types of
displays: Basic display and parametering display.
a) Basic display In addition to the actual voltage level, the desired voltage
level and the deviations the basic display indicates an additional measuring value in the 4th line during normal operation. Selection of this measuring value in the display window „SELECT 4th LINE“.
The following values are available:
- Current I - Power factor cos PHI
- Apparent power S - Frequency f
- Reactive power Q - Status line
- Active power P - Position, optional
- Phase angle PHI
ACTUAL VOLT.LEVEL 64.90 kV DESIRED VOLT.LEVEL 66.00 kV dU% 1.67 % CURRENT I 253 A
b) Parametering display windows The TAPCON® 230 VC contains parametering display windows which serve to display set parameters and allow the user to modify any previously set parameters to suit his specifica-tions. Generally, these windows are set up as follows:
- 1st line: Title/designation of the parameter
- 2nd line: Set value
- 3rd line: Possible setting values and/or setting limits
- 4th line: Serial number of the display
DESIRED VOLT.LEVEL SW1 110V (85V- 140V)
02/30
The displays are situated behind one another in a ring­shaped arrangement, as shown in the illustration to the right, and can be selected by operating the function keys SELECT
and . The display will remain visible for as long as the SELECT key is being pressed, plus an additional 10 seconds after the SELECT key was released. It is possible to move in both directions within the menu. As a result, display no. 30 of the basic display can be reached just as quickly as display no. 1.
The preset value can be altered within the setting values and/ or setting limits by operating the SET and func­tion keys. Once the SET key is released, the new value will be set to ‚active’. For parametering purposes, please use the displays listed below, the functions of which are explained in detail in the following.
10
NORMSET ON ON/ OFF
DES.VOLTAGE LEVEL DVL1 100V (85V- 140V
BANDWIDTH
9.0% (0.5% - 9%)
DELAY T1 10s (0s- 180s)
T1 LINEAR INTEGRAL LINEAR (LINEAR/INTEGRAL)
DELAY T2 10s (PERM,1-10s,OFF)
OVERVOLTAGE U> 105% (101%-130%)
UNDERVOLTAGE U< 70% (70%- 99%)
OVERCURRENT I> 110% (50% - 210%)
NOM.TRANSF.VOLTAGE
10.0V (0.1kV- 999.9kV)
CURRENT 100A (100A- 5000A)
TRANSFORMER PHASE 90 3 PH (30,0,30,90,1PH)
DES.VOLT.LEVEL DVL2 100V (85V- 140.0V)
DES.VOLT.LEVEL DV3
100.0V (85.0V- 140.0V)
LDC UR
0.0V (-25.0V - 25.0V)
01/30
)
02/30
03/30
04/30
05/30
06/30
07/30
08/30
09/30
10/30
11/30
12/30
13/30
14/30
15/30
LANGUAGE GERMAN GER/GB/F/E
SELECTION 4th LINE CURRENT I (I,S,Q,P,PHI,..)
DISPLAY V/kV kV (V/ kV)
H/T PULSE DURATION 0,5 s (0.0 s - 10.0 s)
VOLT.REG.IDENTIFIER 1111 (0- 9999)
PARAL. OPERATION TWIN PARALLEL SKB/TWIN PARALL
CIRCUL.REAC.CURR. BANDWIDTH 20% (0.5% - 20.0%)24/30
CIRCUL.REAC.CURR. STABILITY
0.0 (0.0- 100.0) 23/30
TAPPING DIRECTION NEGATIVE POSITIVE / NEGATIVE
POS MAX 35 (-35 – 35)
POS MIN 1 (-35 – 35)
SELECT PARALLEL CIRCUL.REAC.CURR. CRC/MAST/FOLLOW
Z-COMP LIMIT
0.0% (0%- 15.0%)
Z-COMP VOLTRISE
0.0% (0.0% - 15.0%)
LDC UX
0.0V (-25.0V - 25.0V)
<
<
30/30
29/30
28/30
27/30
26/30
25/30
22/30
21/30
20/30
19/30
18/30
17/30
16/30
251/02 en
3 Operation 4 Parametering
4 Parametering
3.2.2 Local/remote switch
The local/remote switch next to the terminal strip of the VC extension module has no function during normal operation of the TAPCON® 230 VC voltage regulator since its original functions have now been completely taken over by the soft­ware of the voltage regulator. However, this switch can be assigned a function for special tasks for special applications.
4.1 Normset setting
NORMSET ON ON/ OFF
The term „Normset“ function stands for an automatism which considerably simplifies the configuration of a voltage regulator. The only thing left to do for the operator when commissioning during the Normset mode is to enter the desired voltage level and subsequently take the device into operation.
All other parameters required for simple voltage regulation will be preassigned at the factory (e.g. bandwidth of ± 1 %). Should the actual value exit the set bandwidth, an appro­priate switching operation will be initiated at the on-load tap-changer. The voltage change ensuing from the switching operation corresponds to the transformer’s tap voltage and is checked for plausibility by the regulator, using the preset bandwidth. The bandwidth value is then optimised in accord­ance with the results gleaned from this check.
If the next system deviation occurs, the new bandwidth will be used as basis, which will be rechecked and readjusted, if necessary.
01/30
The time parameters are handled in the same way by the regulator, which ensures optimum self-adjustment of the regulator after only a few regulating sequences.
Should the marginal conditions change, the regulator will again optimise itself automatically.
It goes without saying that mains-specific and/or customer­specific settings such as LDC, parallel operation or position indication can still be done in the standard mode and will be taken into consideration during determination of the optimum parameters.
NONO
TETE
NO
TE
NONO
TETE
The parameters for undervoltage/overvoltage and over­current are not set by the Normset function. These para­meters have to be entered manually during commissioning/ initiation.
251/02 en
11
4 Parametering
4.2 Setting the desired voltage level 1
DES.VOLTAGE LEVEL DVL1 100V (85V- 140V
)
02/30
The setting of the desired voltage level refers either to the secondary or to the primary voltage side of the voltage transformer connected to the TAPCON® 230 VC.
‘V’ stands for the secondary voltage which is indicated in Volt. ‘kV’ stands for the primary voltage which is indicated in Kilovolt. Press the SET and function keys to set the desired voltage level.
4.3 Setting the bandwidth
BANDWIDTH
9.0% (0.5% - 9%)
03/30
Set the bandwidth from ± 0.5 % to ± 9% in steps of 0.1 % by pressing the SET and function keys. The trans­former’s step voltage must be known to ensure proper setting of this value.
B (%) =
Control range (%)
No. of steps No. of positions -1
Control range (%)
=
For increased regulating sensitivity it is also possible to set lower values, although it is highly unadvisable to go beneath 60 % of the computed value. Higher values will cause a decrease in regulating sensitivity.
If the measuring-circuit voltage is altered far enough during operation to exceed the set bandwidth, the presignal will respond. An output pulse will be generated according to the set delay time.
If no compensation occurs for more than 15 min, the „function monitoring“ relay will respond (see connection diagram). The relay will not be reset until a shortfall of the bandwidth threshold has occurred.
Standard setting range: ± 0.5 – ±9 %
Standard step width: 0.1 %
4.4 Setting the delay time T1 or T2 (DELAY 1/ DELAY 2) and pulse duration (option)
The delay time starts as soon as the deviation exceeds the set bandwidth limits above or below. At the same time the cor­responding presignal arrow appears. If the deviation is still present after the delay time has elapsed, an output pulse is emitted. If the deviation returns to within bandwidth limits, then the current delay time is cancelled immediately.
Delay time T1
DELAY T1 10s (0s- 180s)
04/30
The delay time can be set from 0....180 s by pressing the SET
and function keys.
T1 Linear/integral
T1 LINEAR INTEGRAL LINEAR (LINEAR/INTEGRAL)
05/30
The delay time T1 can be set with linear or integral response. If a delay time with integral response „Int“ is set, the delay time is automatically shortened according to the relation of actual system deviation to set bandwidth, down to a minimum of 1 s (fig. 2).
The desired time behavior can be set by pressing the SET and
function keys.
DU [%] B [± %]
T1
<
12
Delay of the delay time DU/B – voltage change DU in % of the desired value, in relation to the set bandwidth of B in ± % of the desired value.
2
251/02 en
4 Parametering
Delay time T2
DELAY T2 10s (PERM,1-10s,OFF)
06/30
The delay time T2 will become effective only if more than one tap change is required for reduction of the control deviation below the bandwidth limit. The set delay time T2 is then valid for all consecutive output pulses.
Set the delay time T2 for a range of 1.0 … 10 s by pressing the SET and function keys.
If the voltage regulator is set to PERM, it will emit a continuous signal. If it is set to OFF, the delay time T2 will be deactivated.
H/T Pulse duration (option)
H/T PULSE DURATION
0.5 s (0.0 s - 10.0 s)
27/30
The value designated as "H/L pulse duration“ is the time interval occurring between two pulses during high-speed return control. The adjusting range is between 0 and 10 s at an increment of 0.1 s each.
The value parameterised in "H/T pulse duration“ is used both for the 'on’ time and the 'off’ time of a switching operation, i. e. for an adjusting value of "2 s“, the relay will be switched on for 2 seconds, and then remains switched off for another 2 seconds. That way a new switching operation cannot be initiated until after 4 seconds.
Here, the make time is identified as "n –> 1" or "1 –> n", and the break time is identified as "MOTOR RUNNING“ in the third display line.
4.5 Setting the overvoltage detection (U>) with automatic return control
OVERVOLTAGE U> 105% (101%-130%)
07/30
The response threshold can be set from 101 % to 130 % of the desired voltage level in steps of 1 % by pressing the SET and function keys.
In the event of an overvoltage detection response, the on­load tap-changer is operated by periodic pulses to the motor-drive until the overvoltage falls below the response threshold. The motor-drive is controlled by periodic pulses of
1.5 s through the "Lower“ output relay while the set delay
time re-mains inactive during this operation. At the same time the alarm signalling LED lamp "U>" responds and a signalling relay is energized (contacts 24/25/55) as long as overvoltage is present. If the voltage regulator regulates towards a higher voltage than the set limit U> due to an unfavourable parametering (e.g. too high LDC settings), it is prevented from exceeding the limit. This condition is signalled by the signalling relay for ‘function monitoring’, after 15 minutes.
4.6 Setting the undervoltage blocking (U<)
UNDERVOLTAGE U< 70% (70%- 99%)
08/30
The response threshold for undervoltage blocking can be set from 70 % to 99 % of the desired voltage level in steps of 1 % by pressing the function keys Set and .
Undervoltage blocking prevents tap change operations in the event of a network breakdown. The voltage regulator output pulses are blocked and the alarm signalling LED lamp "U<" and a signalling relay (contacts 22/23/56) respond when the measuring voltage falls below the set blocking value. After a delay time of approx. 10 s, the associated signalling relay is energized and remains that way. The signalling relay does not respond in case of a failure of the measuring-circuit voltage or supply voltage (< 30 V).
251/02 en
13
4 Parametering
4.7 Setting the overcurrent blocking (I>)
OVERCURRENT I> 110% (50% - 210%)
09/30
The overcurrent blocking response threshold can be set from 50 % to 210 % (of the rated current of the current trans­former) in steps of 1 % by pressing the Set and function keys. Overcurrent blocking prevents tap change operations in the presence of overload.
The voltage regulator output pulses are blocked and the alarm signalling LED lamp responds when the measured current exceeds the set blocking value. At the same time the corresponding signalling relay is energized and remains energized (contacts 26/27/28).
4.8 Measuring transformers (VT, CT CONFIGURATION)
The transformation ratios and measuring set-ups of the voltage and current transformers used can be set in the corresponding display windows by pressing the SET and
function keys.
Setting values for customary measuring circuits: 0° (for single-phase systems) 0° (for three-phase systems) 90° (for three-phase systems) 30° (for three-phase systems)
-30° (for three-phase systems)
Configuration a Phase angle setting
Configuration a Phase angle setting
Rated transformer voltage
NOM.TRANSF.VOLTAGE
10.0V (0.1kV- 999.9kV)
10/30
Primary voltage of the voltage transformer in kV, in relation to 100 V secondary voltage.
Rated transformer current
CURRENT 100A (100A- 5000A)
11/30
Primary voltage of the voltage transformer in A
Transformer phase, measuring circuit
TRANSFORMER PHASE 90 3 PH (30,0,30,90,1PH)
12/30
Phase angle of the current/voltage transformer, see fig. 3 for explanations.
Configuration b Phase angle setting
Configuration c Phase angle setting
Configuration d Phase angle setting
Configuration e Phase angle setting
14
3
intc230m
251/02 en
4 Parametering
4.9 Setting the desired voltage levels DVL2 and DVL3 4.10.1 Line Drop Compensation (LDC)
DES.VOLT.LEVEL DVL2 100V (85V- 140.0V)
13/30
NOTE
DES.VOLT.LEVEL DV3
100.0V (85.0V- 140.0V)
14/30
The voltage regulator TAPCON® 230 VC permits the preselection of three different desired voltage levels, each of which will be activated specifically in relation to the actuation of inputs 33/34.
No signal present at terminals 33 and 34 => Desired voltage
level 1 is active
Presence of a signal at terminal 34 => Desired voltage
level 2 is active
Presence of a signal at terminal 33 => Desired voltage
level 3 is active
Setting the desired voltage levels 2 and 3 is identical to the setting procedure for the desired voltage level 1, i.e. by operating the function keys SET and .
4.10 Line compensation
The line compensation, i.e. the inclusion of the voltage drop of a line connected to the transformer in the regulating process, can be accomplished in two different ways.
Comparison between LDC and Z Compensation
Application of the vectorial compensation (LDC):
- requires knowledge of the exact line data
- permits a more accurate determination of the line voltage drops
Application of the Z compensation:
- can be used in the case of minor shifts of the phase angle j
- can be also used in meshed network applications.
For the correct setting of the LDC it is necessary to calcu­late the resistive and inductive line voltage drop in relation to the secondary side of the voltage transformer in V and the correct setting of the existing measuring transformer configuration according to paragraph 4.8
Setting the resistive voltage drop Ur
LDC UR
0.0V (-25.0V - 25.0V)
15/30
The calculated resistive voltage drop is set in the LDC UR display by pressing the function keys SET and . The effect of the compensation can be reversed by 180° (minus sign preceding the setting). If no compensation is desired, then the value „0“ is to be set (condition at the time of delivery).
Setting the inductive voltage drop Ux
LDC UX
0.0V (-25.0V - 25.0V)
16/30
The calculated inductive voltage drop is set in the LDC Ux display by pressing the function keys SET and . The effect of the compensation can be reversed by 180° (minus sign preceding the setting). If no compensation is desired, then the value „0“ is to be set (condition at the time of delivery).
251/02 en
4
intVC13a
15
4 Parametering
Calculation of the required setting values:
Ur = I
N
Ux = IN
.
R
RCT
.
R
VT
VT
.
r . L (V)
.
x . L (V)
R
CT
Where
Ur = LDC setting for resistive line voltage drop in V Ux = LDC setting for inductive line voltage drop in V I
= Rated current in A of the selected current trans-
N
former connection to the voltage regulator,
i.e. 0.2 A or 1 A or 5 A RCT= Current transformer ratio, e. g. 200 A/ 5 A RVT= Voltage transformer ratio, e. g.
30000 V /Ö 3
100 V
r = Ohmic resistance of line in Ω/ km per phase
x = Inductive reactance of line in Ω / km per phase
L = Length of line in km
Setting the voltage rise (VOLTRISE)
The calculated percentage of the voltage rise, referred to the desired voltage level, is set by pressing the function keys SET and . If no compensation is desired, the value „0“ is to be set (link with ®LIMIT).
Z-COMP VOLTRISE
0.0% (0.0% - 15.0%)
17/30
Setting the limitation for DUmax (LIMIT)
Z-COMP LIMIT
0.0% (0%- 15.0%)
18/30
The value is set by pressing the function keys SET and
. If compensation is set to a certain value while avoidance of excessive transformer voltage rises (e.g. in case of an unusually high load) is desired, the limit values can be set to the desired voltage level.
If no compensation is desired, the value „0“ is to be set.
If the active voltage drops Ur and reactive voltage drops Ux are set correctly, then the line end voltage will remain constant regardless of load.
4.10.2 Z-Compensation
For correct setting of the parameters the voltage rise (ΔU) has to be calculated in consideration of the current.
Calculation of the required setting values:
UTr - U
= =
ΔU (%)
= 100
= =
U
Load
Load
IN . R
I
CT
ΔU = Setting of Z-Compensation in %
UTr= Transformer voltage at current I
ULa= Line end voltage at current I and with the same
service position of the tap-changer
I = Load current in A
I
= Rated current in A of the selected current trans-
N
former connection to the voltage regulator, i.e. 0.2 A or 1 A or 5 A
RCT= Current transformer ratio, e. g. 200 A / 5 A
4.11 Analog remote position indication (option)
Optionally, the voltage regulator TAPCON® 230 VC is available with an analog control/activation of the remote position indication. This option requires an analog module. The following analog values can be processed:
4 – 20 mA
Potentiometer range with a minimum total resistance of
50 Ω , up to a maximum total resistance of 2 kΩ .
Press the SET and function keys to set the respective minimum and maximum positions.
For POS MIN, please enter the position corresponding to e.g. 4mA; for POS MAX, please enter the position corresponding to e.g. 20mA.
The analog position indication will be included automatically if the TAPCON® 230 VC is equipped with the parallel operation option.
POS MIN 1 (-35 – 35)
POS MAX 35 (-35 – 35)
20/30
21/30
16
251/02 en
4 Parametering
4.12 Voltage regulator identification
VOLT.REG.IDENTIFIER 1111 (0- 9999)
26/30
The voltage regulator contains a parametering interface to allow parametering via laptop. The required visualization software is included in the standard scope of delivery. The purpose of voltage regulator identifier is to assign a specific ‘address’ to the individual voltage regulator to permit specified operation via visualization software.
A number ranging between 0 and 9999 can be entered to serve as a „name“ by operating the SET and function keys.
4.13 Setting the unit to V or kV
DISPLAY V/kV kV (V/ kV)
28/30
The voltage regulator TAPCON® 230 VC allows the user to both display and enter the unit of the actual voltage level and the desired voltage level in the basic display as well as the parametering displays for the "desired voltage level 1, 2 and 3" in the primary voltage transformer unit kV. To that end it is indispensable that the rated voltage of the voltage transformer be entered as indicated under paragraph
4.8. Set the desired unit by operating the SET and function keys.
4.14 Selection of the display in the 4th line of
the display
SELECTION 4th LINE CURRENT I (I,S,Q,P,PHI,..)
29/30
The basic display of the voltage regulator TAPCON® 230 VC shows an additional measuring value in the 4th line. This measuring value can be set individually by operating the SET and
function keys.
The following measuring values are available:
- Current I
- Apparent power S
- Reactive power Q
- Active power P
- Phase angle PHI
- Power factor cos PHI
- Frequency f
- Status line
- Position, optional
4.15 Language selection
LANGUAGE GERMAN GER/GB/F/E
30/30
The screen texts are available in four languages. Select the desired language by operating the SET and function key.
251/02 en
17
5 Commissioning
5 Commissioning
5.1 Installation
The voltage regulator is suitable for both flush and projected panel mounting (see dimension diagram). Be sure to install the device in an easily accessible place in the control room or in a switching cabinet attached to the transformer.
5.2 Connection
The voltage regulator is to be connected in accordance with the wiring diagram (see Appendix).
When connecting the equipment, please pay attention to: – the correct phase angle of the secondary terminals of
current transformer and potential transformer
– correct connection of the output relays to the motor
drive unit
– correct connection to earth of the housing.
WARNING
NOTE
The TAPCON® 230 VC was developed in accordance with the relevant EMC standards. The following instructions must be observed to ensure preservation of the EMC properties:
– Ensure correct connection to ground by means of the
ground screw attached to the housing, wire section not less than 4mm².
– Be sure to lead the individual power circuits (motor-
drive control, inputs, outputs) in separate cables.
– Be sure to use only shielded cables for the parallel
operation data links for the remote tap position
indication of the motor-drive unit. The screenings at
both line ends must be connected to ground via the grounding angle cable clamps at the housing included in the delivery (see fig. 6)
Take care to properly connect the voltage regulator and the housing to ground. Danger to life.
The voltage regulator is normally fed by the voltage trans­former.
NOTES
When using an auxiliary voltage AC 115V, 50...60Hz, be sure to remove the links between terminals 1/3 and 2/4:
Connect the voltage transformer to terminals 1 and 2, and the auxiliary voltage to terminals 3 and 4 (see fig. 5).
The TAPCON® 230 VC is optionally available with a supply input of AC 230 V preset at the factory.
TAPCON® 230 VC
Required connection for use of the auxiliary voltage
5
intVC18
18
GROUND INTERFACE CABLE SHIELDINGS HERE
6
ERD-ANL
251/02 en
5 Commissioning
5.3 Easy setting of operating modes with Normset
Prior to commissioning, be sure to check the entire circuity and the measuring and operating voltage. To assess the working mode of the voltage regulator, the use of a regis­tering device to record the regulator voltage (actual voltage level) is highly recommended. The related transformer should be subject to normal load.
a) Select the MANUAL operating mode at TAPCON® 230 VC b) Select the NORMSET function as indicated under 4.1 c) Set the Desired Voltage Level 1 as indicated under 4.2.
If you do not require a voltage display of the primary voltage in kV you may now proceed to initiate the regulator by operating the AUTO function key. If you do require a voltage display in kV, however, please proceed as follows:
d) Set the rated transformer voltage and the rated
transformer current as indicated under 4.8.
If you wish to configure the TAPCON® 230 VC voltage regu­lator to suit your specific requirements, please proceed as indicated under 5.4.
f) Set the VOLTAGE LEVEL to this value.
g) Set the bandwidth "ΔU max“ to 1.0 %. In most cases the
voltage regulator is now in a balanced state (no presignal LED lamp lights up). Otherwise change the desired voltage level in steps of 0.5 V until a balanced state is reached.
h) Set the bandwidth „ΔU max“ dependently of the step
voltage (see paragraph 4.3).
i) Set the delay time T1 to 20 s lin. as per paragraph 4.4;
by manual control, move the on-load tap-changer towards "Raise" (arrow in the display right "–>") by one step, the presignal LED lamp for "Lower“ (arrow in the
display left "–>") must come on. Set the mode of opera-
tion to "AUTO"; 20 s after the presignal lamp lights up, the voltage regulator must control the on-load tap­changer back to its previous service position. The pre­signal LED lamp goes out. Set the mode of operation to "MANUAL". Repeat the control procedure towards "Lower".
Set the operating delay time T2 to 10 s. Set the mode of operation to "MANUAL". By manual control, move the on-load tap-changer towards "Raise" by two steps, the pre-signal LED lamp for "Lower" must come on.
5.4 Function tests; operational settings
Prior to commissioning, be sure to check the entire circuity and the measuring and operating voltage. To assess the working mode of the voltage regulator, the use of a registering device to record the regulator voltage (actual voltage level) is highly recommended. The related transfor­mer should be subject to normal load.
a) Select the MANUAL operating mode at TAPCON® 230 VC
b) Set the transformation ratios of the transformers as
specified under paragraph 4.8, as well as the measuring circuit.
c) Let the measured actual voltage (= voltage from the
voltage transformer) be indicated on the display of the voltage regulator.
d) Let the current, power, and phase angle values be
indicated on the display and compare these values with those from possibly existing service measuring instruments. If wrong signs are indicated, reverse the polarity of the current or voltage transformer.
e) Set the desired voltage level. By manual control of the
motor-drive, bring the on-load tap-changer to the service position so that the desired voltage level is obtained (see paragraph 5.5).
Set the mode of operation to "AUTO", then 20 s after the presignal lamp has come on, the voltage regulator must automatically control the on-load tap-changer back to its previous service position by one step and after further 10 s by another step.
Set the delay times T1 and T2 to the desired value. If T2 is not utilized, the "OFF" setting will be required.
When putting the transformer into service, it is recom­mended to set the delay time T1 provisionally to 100 s. Depending on the existing operating conditions, you may want to determine the definitive setting only after some time of observation. For this purpose it is recommended to register the variation of the actual voltage and the number of tap change operations on a day-to-day basis. If an inverse response of the voltage regulator is desired, set an integral time response for the delay time 1. In this case the delay time is automatically shortened inversely proportional to the deviation.j) a
251/02 en
19
5 Commissioning
k) Set the response threshold for undervoltage blocking
U < to 85 %. Set the mode of operation to "MANUAL“ and set the existing voltage level, e.g. 110 V, to 110 V /
0.85 130 V, so that the actual voltage now corresponds to the set percentage of the response threshold for the blocking value. The presignal LED lamp for "Raise“ must light up. Set the mode of operation switch to "AUTO“. After approx.10 s the signalling relay "U <" must be energized, the signalling contact (Contacts 22/23/56) will open; the output relay "Raise" must not issue a control command. LED U < will now respond. Upon completion of this func-tion test you may now set the desired response threshold for undervoltage blocking.
l) Set the response threshold for overvoltage detection U>
to 115 %. Set the mode of operation to "MANUAL", e. g. 110 V to 110 V / 1.15 95 V so that the actual voltage now corresponds to the set percentage of the response threshold for overvoltage detection. The presignal LED lamp for "Lower" must light up. Set the mode of opera­tion to "AUTO". The output relay "Lower" must issue periodic control com­mands at 1.5 s intervals. The signalling contact 24/25/55 will close/open. LED U > will now respond. Now set the desired response threshold for overvoltage detection to the initially desired voltage level.
m) Set the response threshold for overcurrent blocking I >.
A function check is not necessary.
o) Setting of Z Compensation (as per paragraph 4.10.2) as an
alternative to LDC.
Set the mode of operation to MANUAL.
Set the voltage rise to 0, the voltage regulator is in a
balanced state, no presignal LED lamp must light up.
Set the voltage rise to 15 %, the presignal LED lamp for
"Raise" must light up (during this functional check a load
current of 10 % of the rated current of the current
transformer must flow).
The desired values for Z Compensation can be set upon
completion of the above settings.
Set the mode of operation to AUTO. Check if the setting
is correct by observing the voltage at a specific point in
the line and with different loads. When the setting is
correct the voltage at the line end will remain constant.
p) Set the DESIRED VOLTAGE LEVEL 2 to the desired value
(see paragraph 4.9). Set the mode of operation to
MANUAL and connect terminals 31/34. According to
the set value for Desired Voltage Level 2, the presignal
"Lower" or "Raise" must respond.
Please proceed in the same manner for DESIRED VOLTAGE
LEVEL 3 by connecting terminals 31/33 signalling relay for
DESIRED VOLTAGE LEVEL 3. Set the mode of operation to
AUTO.
5.5 Tap position indication
n) Setting the load drop LDC (as per paragraph 4.10.1). Set
the mode of operation to "MANUAL". Settings for Ux = Ur = 0, no presignal LED lamp for Raise/ Lower must light up. Setting of Ur = 20 V, Ux = 0 V, the presignal LED lamp for "Raise" must light up. Setting of Ur = -20 V, Ux = 0 V, the presignal LED lamp for "Lower" must light up (during this function check a minimum load current of 5 % of the rated current of the current transformer must flow.) If the presignals appear in opposite direction, change the polarity of the current transformer. The actually desired LDC can be set upon completion of the above settings. Set the mode of operation to AUTO. Check if the setting is correct by observing the voltage at the line end during service and with different loads. When the setting is correct the voltage at the line end will remain constant.
20
The position signal can be fed as a 4 - 20 mA signal to the regulator on terminals 94/95 (see connection diagram). The position range must be set as described in section 6.2.1.1.
251/02 en
6 Parallel operation
6 Parallel operation
The voltage regulator can be run with the SKB 30 parallel control unit (parallel operation of 2 to 6 transformers). Another possibility is to use parallel operation of two trans­formers which are each equipped with a voltage regulator but without an additional parallel control unit (twin parallel operation).
The selection is made with the following menu item:
PARAL. OPERATION TWIN PARALLEL SKB/TWIN PARALL
The menu item is selected by pressing the SELECT key and the
keys and then using the SET and keys to
choose between parallel operation with supplementary device SKB 30 and the twin parallel operation.
Parallel operation (twin parallel operation)
This setting permits parallel control of two transformers on one busbar. Parallel operation management is handled via an RS 232 connection.
Activation of parallel operation is performed via the status inputs terminals 90, 91.
Parallel control can be performed in two ways. Parallel operation using the principle of "minimum circulat-
ing reactive current" or Parallel operation using the principle of "synchronism control of tap-changer master-follower" A menu item is used to select the principle of parallel operation.
SELECT PARALLEL CIRCUL.REAC.CURR. CRC/MAST/FOLLOW
Select the menu item by pressing the SELECT key and the
keys and then setting the desired method of paral-
lel operation with jumper A (terminal 90/92), (see fig. 8/9). Connect both parallel-operating voltage regulators via the
interface (see fig. 7). The voltage regulators in parallel operation report the status
on terminals 80/81/82 and with LED .
25/30
19/30
TAPCON® 230 VC
TAPCON ® 230 VC / VC 100-BU-02
shielded cable, max. 25 m
7
7
6.1 Parallel operation with "Minimum Circulating Reactive Current Method“
The circulating reactive current is computed from the trans­former currents and their respective phase angles. For correc­tion of the measuring circuit voltage, a voltage proportional to the circulating reactive current is applied to self-suffi­ciently operating regulators. This correction voltage can be either decreased or increased through adjustment of the "stability" (see paragraph 6.1.3).
If an inadmissibly high circulating reactive current is detec­ted, all on-load tap-changers involved will be reset after only 10 s, regardless of the delay time preset at the regulator.
This method is suitable for transformers of comparable out­put and uk, whether with uniform or with non-uniform step voltage. No information on tap position is required.
to the second
251/02 en
21
6 Parallel operation
6.1.1 System configuration, settings
Feed the additional connections/terminals to the regulators (see fig. 8).
to the second
shielded cable, max. 25 m
TAPCON ® 230 VC / VC 100-BU-02
6.1.2 Setting the interference variable
(CIRCUL. REAC. CURR. STABILITY)
CIRCUL.REAC.CURR. STABILITY
0.0 (0.0- 100.0) 23/30
Operate the SELECT key and the keys to select the menu point and press the SET and function keys to
set a stability value between 0 and 100. The stability value is a measure used for determining the effect of the circulating reactive current on the voltage regulator. If it is set to "0", no effects will occur. For a circulating reactive current equal to the rated current of the voltage transformer, a setting value of 10 would result in a voltage correction of 10 % in the voltage regulators.
6.1.3 Setting the bandwidth for circulating reactive current (blocking threshold)
CIRCUL.REAC.CURR. BANDWIDTH 20% (0.5% - 20.0%)24/30
TACPCON® 230 VC
Operate the SELECT key and the keys to select the menu point and press the SET and function keys to set the bandwidth from 0.5 to 20 % (in relation to the rated
current of the voltage transformer). If the circulating reac­tive current exceeds the preset threshold value during paral­lel operation, the message "circulating reactive current" will be displayed in the status line and after a period of 30 s the signalling relay contact (terminal 83/84/85) will respond. All voltage regulators engaged in parallel operation will be blocked.
Single/parallel
22
8
251/02 en
6 Parallel operation
6.1.4 Function tests, commissioning
6.1.4.1 Preliminary settings
NOTE
The prerequisite for the proper functioning of parallel operation is the commissioning of the voltage regulators for individual operation.
The current transformer inputs must be connected and the transformer configuration must be parameterised correctly. The voltage regulators must be set to identical operating parameters for the desired voltage, bandwidth, time delay 1, and line compensation, if applicable (LDC or Z Compensation, respectively). In all cases, set STABILITY to "0“ and Blocking to "20“. During parallel operation, time delay 2 must never be set below 8 s! All settings must be performed in the "Manual“ operating mode.
6.1.4.2 Setting the interference variable
(CIRCUL. REAC. CURR. STABILITY)
Individually set both transformers to identical voltage with the on-load tap-changers so that both voltage regulators are in a balanced state (no presignal LED are lighting up, the indication of "dU %" must be as low as possible, i. e. lower than the preset bandwidth "dU max").
Now switch the transformers to parallel operation and enable parallel control (connect terminal 90/91).
The voltage regulators must continue to remain in a balanced state, the LED lamp "parallel operation" on the front panel is lighting up.
Raise one of the two transformers by one voltage step and lower the other of the two transformers by one voltage step. Both regulators must continue to remain in a balanced state.
Raise the setting value "CIRC.REAC.CURR.STABILITY" of both regulators in small steps starting with "0" until the corres­ponding presignals appear (the regulator of the transformer with the higher voltage step must show the tendency "lower" while the other transformer must show the tendency "raise“). Now add the setting values thus established and set the added-up value for both regulators.
Select the "Auto" operating mode for both voltage regula­tors. Both voltage regulators must control the on-load tap­changers back into their previous service positions. The presignals will go out.
If the previous service position cannot be achieved that way, the "CIRC.REAC.CURR. STABILITY“ setting needs to be in­creased. If the on-load tap-changers are regulating out of sync ("pumping“), this setting needs to be reduced.
6.1.4.3 Setting the circulating reactive current
monitoring (CIRCUL. REAC. CURR. MON.
BANDWIDTH)
Switch over one of the two voltage regulators to the "Manual“ operating mode. Using the manual control, the associated motor drive must now be reset to "Raise“ by the maximum admissible difference of the service positions between the parallel operating transformers (e. g. by 1 … 2 steps).
Starting with the preset value of "20 %", reset the blocking towards a lower value in small steps until the message "Circulating reactive current" appears in the status line of the display (please wait 2 – 3 s between the individual steps).
The bandwidth threshold of the circulating reactive current monitoring is reached as soon as this message appears. The voltage regulators will block all further regulating actions and the signalling relay will respond (terminal 83/84/85).
Now reset the blocking again towards a higher value until the message „circulating reactive current“ disappears from the status line of the display.
Again switch the voltage regulator back to the "Auto" operating mode. The motor-drive will be automatically controlled back to the original service position.
Use the value established for the "Blocking" threshold to set it for all of the other regulators.
6.2 Parallel operation according to synchronized tap-change operation Master/ Follower
This method is suitable for transformers featuring an identi­cal rated current, identical step voltage, and an identical number of service positions. The motor-drive must signal the tap-change position by means of a current of 4 … 20 mA (with 4 mA corresponding to the lowest position and 20 mA corresponding to the highest position).
During parallel operation, actual voltage regulation is per­formed by one of the voltage regulators (Master function). The second voltage regulator (Follower) receives the tap­change position of the motor-drive from the first regulator, for comparison with the tap-change position of its own motor drive. If a difference is noted, the motor-drive in question will receive a suitable control pulse.
251/02 en
23
6 Parallel operation
6.2.1 System configuration, settings, transfer of the on-load tap-changer setting
Lead the additional connections/terminals (see fig. 9) to the regulators.
zto the second
ashielded cable, max. 25 m
TAPCON ® 230 VC / VC 100-BU-02
TACPCON® 230 VC
6.2.1.1 Setting the tapping position range
POS MIN 0 (-35 – 35)
POS MAX 35 (-35 – 35)
20/30
21/30
Operate the SELECT key and the keys to select the menu point and set the respective lowest/highest tap posi­tions between –35 and +35 by pressing the SET and
keys. To perform a function check, set the deactivated transformer for all positions of the entire tap position range while checking the position indicator.
TAPPING DIRECTION NEGATIVE POSITIVE / NEGATIVE
22/30
Since a comparison of the tap positions of the transformers jointly engaged in parallel operation is performed during parallel operation in accordance with the principle of tap-
change synchronicity (Master-Follower), it is imperative to
maintain identical position designations for all of these transformers, and to ensure that the „higher“ and „lower“ signals will effect identical voltage changes in all the transformers.
If this is not the case, e.g. if the "Higher" command (higher voltage) is not equal to a higher position, it is also possible to "turn the tap direction" within the voltage regulator.
This function can be switched on or off by inserting or removing jumper B.
Single/parallel
With jumper A: Synchronism "master-follower"
4 ... 20 mA Þ tap position n min ...nmax
Insert jumper B when negative switching direction desired
9
Fig. 9
Feed the position signal in the form of a 4 ... 20 mA signal to the regulator at terminals 44-45 (see connection diagram).
24
6.2.1.2 Selecting the Master/Follower operation
SELECT PARALLEL CIRCUL.REAC.CURR. CRC/MAST/FOLLOW
19/30
Operate the SELECT key and the keys to select the menu point and assign the respective regulator as a Master or a Follower by pressing the SET and keys.
If both regulators were assigned as „Follower“ or „Master“ during parallel operation, the regulators will be blocked (see section 6.3 – Disturbances during parallel operation).
251/02 en
6 Parallel operation
6.2.2 Function tests, commissioning and
preliminary settings
NOTE
The prerequisite for the proper functioning of parallel
operation is the commissioning of the voltage regulators for individual operation.
The voltage regulators must be set to identical operating parameters for the desired voltage, bandwidth, time delay 1, and line compensation, if applicable. The tap position indication at the regulators must function correctly. Select the "MANUAL“ operating mode at the voltage regulators. Individually set all on-load tap-changers involved in parallel operation to identical voltage so that the voltage regulators are in a balanced state (no presignal appearing on the dis-
play).
Now switch the transformers to parallel operation connect terminals 90/91. The voltage regulators must continue to remain in a balanced state and the LED lamps "Parallel“ at the regulators must respond. Switch the Follower voltage regulator to the "AUTO“ operating mode. Use the manual control to raise the MASTER regulating unit engaged in the "MANUAL“ operating mode by one step; the follower regulator now has to automatically drag along the associated transformer to do the same.
6.3 Parallel operation with existing parallel control unit SKB 30 based on "minimum circulating reactive current"
The following menu item is used for the selection:
PARALLEL OPERATION TWIN PARALLEL SKB/TWIN PARALLEL
25/30
The menu item can be selected by pressing the SELECT key and the keys and then using the SET and keys to select parallel operation with supplementary device SKB 30.
To expand existing plants, the TAPCON® 230 VC voltage regulator is equipped with a communication interface to an existing SKB 30 parallel control unit.
The connection of the regulator with the parallel control unit and the setting for parallel control are made as described in operating instructions BA 117 (parallel control unit SKB 30).
Terminals 90, 91, 92, 93, 94, and 95 on the TAPCON® 230 VC have no function. The parallel operation signal, LED and signal relay (terminals 80, 81, 82) remain functional, how­ever.
6.4 Disturbances during parallel operation
In parallel operation the following messages appear in the status line (only for twin parallel operation, not for chap.
6.3).
During the short period while a tap position difference is present, the message "TAP DIFFERENCE“ will appear in the status line of the display. If a follower regulator fails to drag along its associated transformer, regulating action will be blocked and a signalling relay will respond (terminals 83/84/
85).
251/02 en
Message Cause
CIRCULATING Circulat. reactive current REACTIVE CURRENT was exceeded
TAP DIFFERENCE Synchronism disturbance
(tap difference £ 2 steps)
>1 MASTER More than one Master
was selected
NO MASTER No Master was selected
NO POSITION Failure of position
indication
DIFF. METHOD Different methods of
parallel operation were selected
If any of the above disturbances occur, the regulators will be blocked.
25
7 Appendix
7 Appendix
7 Appendix
Front view.................................................................................................................................................................................................... TC230_1
Control panel set-up and mounting ................................................................................................................................................... 899564
Block/connection diagram,115 V.......................................................................................................................................................... BA251_1.PIC
Block/connection diagram, 230 V ........................................................................................................................................................ BA251_2.PIC
26
251/02 en
TC230_1
TAPCON® 230
TAPCON® 230
Front view
Front view
251/02 en
27
8995640E
TAPCON® 230
Control panel set-up and mounting
Remove crimp cable­entries for flush mounting
Clamp for flush mounting
Bracketing fishplate for panel mounting
Panel cutout for
flush mounting
28
251/02 en
BA 251_1.PIC
TAPCON® 230 VC
Block/connection diagram, 115 V
251/02 en
29
BA 251_2.PIC
TAPCON® 230 VC
Block/connection diagram, 230 V
30
251/01/01/0
www.reinhausen.com
©Maschinenfabrik Reinhausen GmbH Phone +49 941 40 90-0
Falkensteinstrasse 8 Fax +49 941 40 90-7001 93059 Regensburg, Germany E-mail sales@reinhausen.com
Please note: The data in our publications may differ from the data of devices delivered. We reserve the right to make changes without notice.
BA 251/02 en • 0909 • F0125701 • Printed in Germany
Loading...