1.3Design and performance features of the TAPCON® 230 VC................................................................................................5
3.1Input and output of data; functions ..........................................................................................................................................9
3.2Description of the front panel ......................................................................................................................................................9
4.2Setting the desired voltage level 1 .............................................................................................................................................. 12
4.3Setting the bandwidth .................................................................................................................................................................... 12
4.4Setting the delay time T1 or T2 (DELAY 1/DELAY 2) and pulse duration (option) ........................................................ 12
4.5Setting the overvoltage detection (U>) with automatic return control ......................................................................... 13
4.6Setting the undervoltage blocking (U<) .................................................................................................................................... 13
4.7Setting the overcurrent blocking (I>) ......................................................................................................................................... 13
4.9Setting the desired voltage levels DVL2 and DVL3 ................................................................................................................. 15
4.10.1 Line drop compensation (LDC) ........................................................................................................................................ 15
4.13Setting the unit to V or kV ............................................................................................................................................................. 17
4.14Selection of the display in the 4th line of the display ........................................................................................................... 17
5.3Easy setting of operating modes with Normset ...................................................................................................................... 19
5.5Tap position indication .................................................................................................................................................................... 20
6.2Parallel operation according to synchronized tap-change operation Master/ Follower ............................................ 23
6.2.1 System configuration, settings, transfer of the on-load tap-changer setting................................................ 24
6.2.1.1Setting the tapping position range ............................................................................................................. 24
6.2.1.2Selecting the Master/Follower operation .................................................................................................. 25
6.2.2 Function tests, commissioning and preliminary settings ........................................................................................ 25
6.3Parallel operation with existing parallel control unit SKB 30 based on
6.4Disturbances during parallel operation...................................................................................................................................... 25
A "PARAM?" message appearing in the first line of the display indicates a negative result of the parameter verification that may
be caused by interference above the permissible electromagnetic compatibility limit (see information on standardisation and
verification in section 2). In this case, voltage regulation is blocked for safety reasons.
Check the settings in order to clear the blocking. Press and hold the "SELECT" key and press the "" or "" key for displaying
the current settings (see section 3.2.1). Voltage regulation is reinstated once invalid settings have been corrected while cycling
through the menu. The status LEDs and status relays are activated, and the display shows the current measurement readings.
NOTE
Data contained herein may differ in details from the equipment delivered. We reserve the right to make alterations without
notice.
251/02 en
3
1 General
1General
1.1Safety instructions
All personnel involved in installation, commissioning,
maintenance or repair of this equipment must:
-be suitably qualified and
-strictly observe these operating instructions.
Improper operation or misuse can lead to
-serious or fatal injury,
-damage to the equipment and property of the user
and
-a reduction in the efficiency of the equipment.
Safety instructions in this manual are presented in three
different forms to emphasize important information.
WARNING
This information indicates particular danger to life and
health. Disregarding such a warning can lead to serious or
fatal injury.
CAUTION
This information indicates particular danger to the equipment or other property of the user. Serious or fatal injury
cannot be excluded.
NOTE
1.2Specified application
The electronic voltage regulator TAPCON® 230 VC serves for
automatic control of transformers with a motor-driven onload tap-changer. The motor-drive mechanism receives the
corresponding control commands from the voltage regulator.
With these commands, the on-load tap-changer moves to
the next position and the transformer’s voltage value is
adapted to the preset desired voltage level.
To allow individual adaptation of the control system to the
various field service conditions encountered, influencing
variables such as time delay, bandwidth, and even linedependent and load-dependent parameters can be programmed for compensation of voltage-dependent and/or
current-dependent limits. As a special feature, the voltage
regulator is also capable of controlling parallel transformer
operation.
CAUTION
Installation, electrical connection and commissioning of
the electronic voltage regulator may only be carried out
by qualified, skilled personnel and only in accordance with
these operating instructions.
It is the responsibility of the user to make sure that the
electronic voltage regulator is used for the specific
application only. For safety reasons, any unauthorized and
improperly executed works, i.e. installation, modification,
alteration of the equipment, electrical connection, or
commissioning of the equipment, are forbidden without
first consulting MR!
The trouble-free operation of the drive, the on-load tapchanger, and the transformer may be put at risk.
These notes give important information on a certain
subject.
4
WARNING
All relevant fire protection regulations must be strictly
observed
251/02 en
1 General
1.3Design and performance features of the
TAPCON® 230 VC
The electronic voltage regulator TAPCON® 230 VC is mounted
in a protective housing with hinged cover and inspection
win-dow. The protective housing is suitable for both flush
and projected panel mounting.
The front panel contains several function keys for setting the
individual operating parameters.
Display of the operating status is achieved by a 4-line,
16-digit alphanumeric LC display and light emitting diodes.
The electronic voltage regulator is controlled by a microcontroller (see appendix, block/connection diagram).
Besides a voltage transformer and a current transformer it
contains optocoupler inputs with potential separation as well
as potential-free output relay contacts.
Apart from the usual well-known, versatile and individual setting options for the MR control system, the TAPCON® 230 VC
voltage regulator also offers the option of fast and easy
parametering by introducing the innovative "Normset"
function.
The term „Normset“ function stands for an automatism
which considerably simplifies the configuration of a voltage
regulator. If the desired voltage level is entered while the
„Normset“ function is active, the voltage regulator will
examine the given line/network conditions and proceed to
perform an automatic adaptation of all further inputs
(comprised in part of the pre-parametering and standard
reference values) which used to be required for customary
regulators (also refer to the standard configuration according to Sub-menu 2).
Parallel operation follows alternatively the principles of
either minimum circulating reactive current or the Master/
Follower principle for two transformers.
Using a supplementary device, up to six transformers can be
controlled in parallel operation using the principle of
minimum reactive current.
NOTE
When voltage regulation is effected by tap transformers
and voltage regulators, it is assumed that a change of the
tap position results in a significant voltage change. When
generators feed the voltage level to be regulated, however,
quite different conditions may result so that a correct
regulation of the voltage cannot be guaranteed. In such
cases MR should be consulted as early as the planning
stage.
The parameters of the regulator can be set by means of a PC
via the incorporated serial interface (RS232) integrated in
the regulator; the appropriate PC software will be furnished
by MR.
A load-dependent line-voltage drop, e.g. of a spur line leading from the transformer to the load, can be compensated
either by line simulation (Line Drop Compensation) or by
load-current dependent increase of the voltage level
(Z compensation).
Trouble-free operation is ensured by the regulator’s inherent
undervoltage blocking, overcurrent blocking and overvoltage
monitoring.
The functions of the TAPCON® 230 VC voltage regulator are
just about compatible with those of the earlier voltage
regulators VC 100-BU.
251/02 en
5
2 Technical Data
2Technical Data
Setting ranges
StandardStandard
setting rangestep width
Desired voltage level 185 – 140 V0.1 V steps
Desired voltage level 285 – 140 V0.1 V steps
Desired voltage level 385 – 140 V0.1 V steps
Bandwidth± 0.5 ... ± 9 %0.1 %
Delay time T10 ... 180 s1 s
Delay time T21 … 10 s1 s
Switching pulse duration0.5 ... 10 s0.5 s
LDCUr = 0 ... ± 25 V0.1 V
Ux = 0 ... ± 25 V0.1 V
With optional
Z compensation selectionVoltage rise0.1 %
0...15 %
Limitation 0...15 %0.1 %
Undervoltage blocking70 ... 99 %1 %
Overvoltage detection101 ... 130 %1 %
with high speed return controlpulse signal 1.5 / 1.5 s
Overcurrent blocking50 ... 210 %5 %
Voltage transformer0.1 ... 999,9 kV/100 V
Current transformer100 ... 5000 A/5/1/0.2 A
Measuring circuitPhase angle adjustable
between current and
voltage circuit:
-30°3-phase
0°3-phae
+30°3-phase
+90°3-phase
0°1-phase
6
251/02 en
2 Technical Data
Display4-line, 16-digit LC display
1 LED lamp (green) for signalling status
1 LED lamp (red) each for signalling U<, U>, I>
1 LED lamp (green) for signalling“parallel operation active“ status
1 LED lamp (green) for signalling "Normset active“ status
Inputs and outputsInput relaysOutput relays
1x parallelRating of relay contacts:
1x high-speed circuit breaker of voltageAC: 250 V 5 A
limit monitoring indicatorDC: 30 V 5 A; 110 V 0.4 A;
1 x analogue input of tapping position 4- 20 mA220 V 0.3 A
1 x desired voltage level 21 x raise
1 x desired voltage level 31 x lower
1 x automatic control mode
1 x status
1x group interrupt U<, U>, I>
1x monitoring (function monitoring)
Voltage transformer85 ... 140 V, measuring range 60 ... 185 V,
r.m.s. value 40 ... 60 Hz, intrinsic consumption < 1 VA
Current transformer0.2 / 1 / 5 A, 40 ... 60 Hz, r.m.s. value
intrinsic consumption < 1 VA,
overload capacity 2x In continuously, 100x In/1 s
parametering via PC
1 x RS 232 for parallel operation of two transformers with a second regulator or for parallel
operation with digital MR parallel control unit SKB
IEC EN 60688
Power supply115 V (+25 % - 35 %) 40 - 60 Hz, can be changed over either from
the measuring voltage or by separate change-over in the factory to
a supply voltage of 230 V
Power consumption approx. 5.5 VA (at 115V, idle state)
251/02 en
7
2 Technical Data
Protective housingSteel-plate housing with inspection window for flush or projected panel mounting
W x H x D: 216 x 326 x 137mm
Degree of protection provided by enclosure: IP 44 according to IEC 60529
Weight: approx. 5.4 kgs
Temperature limitsAdmissible ambient temperature for operation: -10 °C ... + 70 °C
Admissible ambient temperature for storage and transport: -25 °C ... +80 °C
Tests
IEC 255-5Dielectric tests performed at 2.5 kV/1 min operating frequency and 5 kV, 1.2|50 μs impulse voltage
IEC 60068-2-31Drops and topple, unpacked, 100 mm height
IEC 60068-2-32Free fall, unpacked, 250 mm height
IEC 61000-4-8Power frequency magnetic field immunity test
IEC 61000-4-11Voltage dips, short interruptions and voltage variations immunity tests
8
251/02 en
3 Operation
3Operation
3.1 Input and output of data; functions
The following instructions tell you how to call up the basic
functions of the TAPCON® 230 VC voltage regulator and how
to reset parameters.
3.2Description of the front panel (fig. 1)
Generally, the keys located at the front panel fall into two
different basic groups.
• Operating keys
• Function keys for menu guidance
The LED’s located in the front panel’s upper area serve for
signalling the following system statuses:
• Operating status display
• Overcurrent blocking
• Undervoltage blocking
• Overvoltage monitoring
• Parallel operation
• NORMSET
Change-over
between manual
mode/automatic mode
Reset
setting values via
the Higher/Lower keys
LCD-Display
Parametering
interface
Light-
emitting
diodes
Reset setting
values
via „SET“
Change the
windows via
the Higher/
Lower keys
1
251/02 en
9
3 Operation
3.2.1Display
<
<
The TAPCON® 230 VC contains a 4-line, 16-digit LC display.
A distinction is made between the two following types of
displays: Basic display and parametering display.
a) Basic display
In addition to the actual voltage level, the desired voltage
level and the deviations the basic display indicates an
additional measuring value in the 4th line during normal
operation. Selection of this measuring value in the display
window „SELECT 4th LINE“.
The following values are available:
- Current I- Power factor cos PHI
- Apparent power S- Frequency f
- Reactive power Q- Status line
- Active power P- Position, optional
- Phase angle PHI
ACTUAL VOLT.LEVEL64.90 kV
DESIRED VOLT.LEVEL66.00 kV
dU%1.67 %
CURRENT I253 A
b) Parametering display windows
The TAPCON® 230 VC contains parametering display
windows which serve to display set parameters and allow the
user to modify any previously set parameters to suit his
specifica-tions.
Generally, these windows are set up as follows:
The displays are situated behind one another in a ringshaped arrangement, as shown in the illustration to the right,
and can be selected by operating the function keys SELECT
and . The display will remain visible for as long as
the SELECT key is being pressed, plus an additional 10
seconds after the SELECT key was released. It is possible to
move in both directions within the menu. As a result, display
no. 30 of the basic display can be reached just as quickly as
display no. 1.
The preset value can be altered within the setting values and/
or setting limits by operating the SET and function keys. Once the SET key is released, the new value will be
set to ‚active’.
For parametering purposes, please use the displays listed
below, the functions of which are explained in detail in the
following.