unless expressly permitted.
Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents,
utility models or designs.
The product may have been altered since this document was published.
We reserve the right to change the technical data, design and scope of supply.
Generally the information provided and agreements made when processing the individual quotations and orders
are binding.
The original operating instructions were written in German.
1.5.1Hazard communication system .............................................................................................................................8
1.5.3Instruction system .................................................................................................................................................9
2.2Appropriate use ................................................................................................................................ 11
4.1Scope of delivery .............................................................................................................................. 14
4.2Function description of the voltage regulation .................................................................................. 15
4.3Performance features ....................................................................................................................... 16
5.1.2Suitability, structure and production ...................................................................................................................24
6.2.2Wall mounting with mounting brackets................................................................................................................30
6.2.5Removing the door..............................................................................................................................................33
6.3.4Connecting cables to the system periphery ........................................................................................................39
6.3.5Supplying the voltage regulator using auxiliary voltage ......................................................................................40
7.2.1Setting the language ...........................................................................................................................................43
7.2.2Setting further parameters ..................................................................................................................................43
7.3.1Checking control functions ..................................................................................................................................44
8.2.1Setting device ID .................................................................................................................................................49
8.2.2Setting the baud rate...........................................................................................................................................50
8.2.3Setting the switching pulse time..........................................................................................................................50
8.2.6Activating/deactivating the automatic key lock....................................................................................................53
8.2.7"Function monitoring" message for monitoring messages <30 V........................................................................54
8.2.8Setting motor runtime monitoring ........................................................................................................................55
8.2.11Setting the COM1 password ...............................................................................................................................58
8.2.12Setting the password duration.............................................................................................................................59
8.4.1Setting desired value 1...3...................................................................................................................................63
8.4.2Selecting a desired value ....................................................................................................................................64
8.4.4Setting delay time T1 ..........................................................................................................................................66
8.4.5Setting control response T1 ................................................................................................................................67
8.4.6Setting delay time T2 ..........................................................................................................................................68
8.5.5Activate/deactivate active power monitoring .......................................................................................................76
8.6.1Line drop compensation......................................................................................................................................76
8.7Transformer data .............................................................................................................................. 81
8.7.1Setting the primary transformer voltage ..............................................................................................................82
8.7.2Setting the secondary transformer voltage .........................................................................................................82
8.7.3Setting primary transformer current ....................................................................................................................83
8.7.4Setting the current transformer connection .........................................................................................................84
8.7.5Setting the phase difference for the current transformer/voltage transformer.....................................................84
8.8Configurable inputs and outputs....................................................................................................... 88
8.8.1Linking inputs with functions ...............................................................................................................................88
8.8.2Linking outputs with functions .............................................................................................................................90
8.10Information about device .................................................................................................................. 93
8.10.1Displaying info screen .........................................................................................................................................93
8.10.4Carrying out LED test..........................................................................................................................................95
8.10.5Displaying status of the MIO card .......................................................................................................................95
13.1Display elements ............................................................................................................................ 108
13.2Electrical data ................................................................................................................................. 108
13.3Dimensions and weight................................................................................................................... 108
Further information on the product and copies of this technical file are available from this address if required.
1.2 Subject to change without notice
The information contained in this technical file comprises the technical specifications approved at the time of printing. Significant modifications will be included in a new edition of the technical file.
The document number and version number of this technical file are shown in
the footer.
1.3 Completeness
This technical file is incomplete without the supporting documentation.
1.4 Safekeeping
Keep this technical file and all supporting documents ready at hand and accessible for future use at all times.
1.5 Notation conventions
This section contains an overview of the symbols and textual emphasis
used.
Warnings in this technical file are displayed as follows.
1.5.1.1 Warning relating to section
Warnings relating to sections refer to entire chapters or sections, sub-sections or several paragraphs within this technical file. Warnings relating to
sections use the following format:
1 Introduction
WARNING
Type of danger!
Source of the danger and outcome.
► Action
► Action
1.5.1.2 Embedded warning information
Embedded warnings refer to a particular part within a section. These warnings apply to smaller units of information than the warnings relating to sections. Embedded warnings use the following format:
DANGER! Instruction for avoiding a dangerous situation.
1.5.1.3 Signal words and pictograms
The following signal words are used:
Signal wordMeaning
DANGERIndicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNINGIndicates a hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTIONIndicates a hazardous situation which, if not avoided, could result
in injury.
NOTICEIndicates measures to be taken to prevent damage to property.
The technical file contains detailed descriptions on the safe and proper installation, connection, commissioning and monitoring of the product.
▪ Read this technical file through carefully to familiarize yourself with the
product.
▪ Particular attention should be paid to the information given in this chapter.
2.2 Appropriate use
If used as intended and in compliance with the requirements and conditions
specified in this technical document as well as with the warnings in this technical document and attached to the product, then the product does not
present any danger to people, property or the environment. This applies
throughout the product's entire life, from delivery through installation and operation to disassembly and disposal.
The operational quality-assurance system ensures a consistently high quality standard, particularly in regard to the observance of health and safety requirements.
The following is considered appropriate use
▪ The product must be operated in accordance with this technical file and
the agreed delivery conditions and technical data
▪ The equipment and special tools supplied must be used solely for the in-
tended purpose and in accordance with the specifications of this technical
file
2.3 Inappropriate use
Use is considered to be inappropriate if the product is used other than as described in the Appropriate use section. Please also note the following:
▪ Risk of explosion and fire from highly flammable or explosive gases, va-
pors, or dusts. Do not operate product in areas at risk of explosion.
▪ Unauthorized or inappropriate changes to the product may lead to per-
sonal injury, material damage, and operational faults. Only modify product
following discussion with Maschinenfabrik Reinhausen GmbH.
2.4 Personnel qualification
The product is designed solely for use in electrical energy systems and facilities operated by appropriately trained staff. This staff comprises people who
are familiar with the installation, assembly, commissioning and operation of
such products.
To prevent accidents, disruptions and damage as well as unacceptable adverse effects on the environment, those responsible for transport, installation, operation, maintenance and disposal of the product or parts of the product must ensure the following:
▪ All warning and hazard notices are complied with.
▪ Personnel are instructed regularly in all relevant aspects of operational
safety, the operating instructions and particularly the safety instructions
contained therein.
▪ Regulations and operating instructions for safe working as well as the rel-
evant instructions for staff procedures in the case of accidents and fires
are kept on hand at all times and are displayed in the workplace where
applicable.
▪ The product is only used when in a sound operational condition and safety
equipment in particular is checked regularly for operational reliability.
▪ Only replacement parts, lubricants and auxiliary materials which are au-
thorized by the manufacturer are used.
▪ The specified operating conditions and requirements of the installation lo-
cation are complied with.
▪ All necessary devices and personal protective equipment for the specific
activity are made available.
▪ The prescribed maintenance intervals and the relevant regulations are
complied with.
▪ Installation, electrical connection and commissioning of the product may
only be carried out by qualified and trained personnel in accordance with
this technical file.
▪ The operator must ensure appropriate use of the product.
This chapter contains an overview of the design and function of the product.
4.1 Scope of delivery
The following components are included in the delivery:
▪ Voltage Regulator TAPCON® 230 basic
▪ Folder with all device documentation
▪ Quick reference guide (in the inside door of the device)
▪ Door key
▪ 3mm Allen key
▪ 2 countersunk head screws
▪ Control panel bracket pre-mounted on device's housing
Please note the following:
▪ Check the shipment for completeness on the basis of the shipping docu-
ments.
▪ Store the parts in a dry place until installation.
4.2 Function description of the voltage regulation
The TAPCON® serves to keep constant the output voltage of a transformer
with an on-load tap-changer.
The TAPCON® compares the transformer's measured voltage (U
defined reference voltage (U
). The difference between U
desired
actual
) with a
actual
and U
desired
is the control deviation (dU).
The TAPCON® parameters can be optimally adjusted to the line voltage response to achieve a balanced control response with a small number of tapchange operations.
The following diagram shows an overview of voltage regulation.
The device can be operated in the following operating modes:
Auto mode (AUTO)
In auto mode, the voltage is automatically controlled in accordance with the
set parameters. You cannot change further device settings in auto mode.
There is no active management by a higher level control system in this operating mode.
Manual mode (MANUAL)
In manual mode, there is no automatic control. The motor-drive unit can be
controlled via the device's operating panel. You can change the device settings.
Local mode (LOCAL)
There is no active management by a superordinate control system in this operating mode.
Remote mode (REMOTE)
In remote mode, you can perform commands using an external control level.
In this case, manual operation of the , , and keys is dis-
abled.
+ LOCAL + REMOTE + LOCAL + REMOTE
Automatic regulationYesYesNoNo
Tap-change operation using operating
controls
Tap-change operation using inputsNoNoNoYes
The device has 15 pushbuttons. The illustration below is an overview of all
the device's operating controls.
Figure8: Operating controls
RAISE key: Sends control command for raise tap-change to the motordrive unit in manual mode.
LOWER key: Sends control command for lower tap-change to the motordrive unit in manual mode.
REMOTE key: Activate/deactivate "Remote" operating mode. When you
deactivate this operating mode, the "Local" operating mode is automatically activated.
Current messages and events are displayed in the status line . You can
find more information about messages and events in the Messages chapter.
4.5.4 Serial interface
The parameters for the device can be set using a PC. The COM1 (RS232)
serial interface on the front panel is provided for this purpose. You can use
the connection cable supplied to establish a connection to your PC via the
RS232 or USB port (using the optional USB adapter).
TAPCON®-trol software is needed for parameterization via the serial interface. The software and the associated user guide can be downloaded from
www.reinhausen.com.
The packaging is designed to protect the packaged goods during transport,
loading and unloading as well as periods of storage in such a way that no
(detrimental) changes occur. The packaging must protect the goods against
permitted transport stresses such as vibration, knocks and moisture (rain,
snow, condensation).
The packaging also prevents the packaged goods from moving impermissibly within the packaging. The packaged goods must be prepared for shipment before actually being packed so that the goods can be transported
safely, economically and in accordance with regulations.
5.1.2 Suitability, structure and production
The goods are packaged in a sturdy cardboard box. This ensures that the
shipment is secure when in the intended transportation position and that
none of its parts touch the loading surface of the means of transport or touch
the ground after unloading.
The box is designed for a maximum load of 10kg.
Inlays inside the box stabilize the goods, preventing impermissible changes
of position, and protect them from vibration.
5.1.3 Markings
The packaging bears a signature with instructions for safe transport and correct storage. The following symbols apply to the shipment of non-hazardous
goods. Adherence to these symbols is mandatory.
Protect against
moisture
Table6: Shipping pictograms
TopFragileAttach lifting
gear here
Center of mass
5.2 Transportation, receipt and handling of shipments
In addition to oscillation stress, jolts must also be expected during transportation. In order to prevent possible damage, avoid dropping, tipping,
knocking over and colliding with the product.
If a crate tips over, falls from a certain height (e.g. when slings tear) or is
subject to an unbroken fall, damage must be expected regardless of the
weight.
Every delivered shipment must be checked for the following by the recipient
before acceptance (acknowledgment of receipt):
▪ Completeness based on the delivery slip
▪ External damage of any type
The checks must take place after unloading when the crate or transport container can be accessed from all sides.
Visible damage If external transport damage is detected on receipt of the shipment, proceed
as follows:
▪ Immediately record the transport damage found in the shipping docu-
ments and have this countersigned by the carrier.
▪ In the event of severe damage, total loss or high damage costs, immedi-
ately notify the sales department at Maschinenfabrik Reinhausen and the
relevant insurance company.
▪ After identifying damage, do not modify the condition of the shipment fur-
ther and retain the packaging material until an inspection decision has
been made by the transport company or the insurance company.
▪ Record the details of the damage immediately onsite together with the
carrier involved. This is essential for any claim for damages!
▪ If possible, photograph damage to packaging and packaged goods. This
also applies to signs of corrosion on the packaged goods due to moisture
inside the packaging (rain, snow, condensation).
▪ Be absolutely sure to also check the sealed packaging.
Hidden damage When damages are not determined until unpacking after receipt of the ship-
ment (hidden damage), proceed as follows:
▪ Make the party responsible for the damage liable as soon as possible by
telephone and in writing, and prepare a damage report.
▪ Observe the time periods applicable to such actions in the respective
country. Inquire about these in good time.
With hidden damage, it is very hard to make the transportation company (or
other responsible party) liable. Any insurance claims for such damages can
only be successful if relevant provisions are expressly included in the insurance terms and conditions.
When selecting and setting up the storage location, ensure the following:
▪ Protect stored goods against moisture (flooding, water from melting snow
and ice), dirt, pests such as rats, mice, termites and so on, and against
unauthorized access.
▪ Store the crates on timber beams and planks as a protection against ris-
ing damp and for better ventilation.
▪ Ensure sufficient carrying capacity of the ground.
▪ Keep entrance paths free.
▪ Check stored goods at regular intervals. Also take appropriate action after
This chapter describes how to correctly install and connect the device. Observe the connection diagrams provided.
DANGER
WARNING
NOTICE
Electric shock!
Risk of fatal injury due to electrical voltage. Always observe the following
safety regulations when working in or on electrical equipment.
► Disconnect the equipment.
► Lock the equipment to prevent an unintentional restart.
► Make sure all poles are de-energized.
► Ground and short-circuit.
► Cover or cordon off adjacent energized parts.
Electric shock!
Dangerous high voltages may occur when a current transformer is operated
with an open secondary circuit. This can lead to death, injuries and property
damage.
► Never operate a current transformer with an open secondary circuit;
short-circuit the current transformer to prevent this.
► Observe the information in the current transformer operating instructions.
Damage to the device!
Electrostatic discharge may cause damage to the device.
► Take precautionary measures to prevent the build-up of electrostatic
charges on work surfaces and personnel.
6.1 Preparation
The following tools are needed for mounting:
▪ Provided 3mm Allen key (included in delivery)
▪ Small screwdriver for connecting the signal lines and supply lines
Other tools may be needed depending on installation location.
6.2 Mounting device
You can mount the device in the following installation versions:
▪ Flush panel mounting
▪ Wall mounting
▪ Wall mounting with mounting brackets
▪ Rail mounting (optional)
Preparing for mounting
Before commencing mounting, the two mounting brackets back on the rear
of the device must be removed and the cable gland plate taken off. To do so,
proceed as follows:
1. Loosen the 4 Allen screws with attached Allen key to remove the mount-
ing brackets.
Figure13: Loosen mounting bracket
2. Loosen the 4 Allen screws with attached Allen key to remove the cable
gland plate.
Figure14: Loosen cable gland plate
ð The mounting brackets and the cable gland plate are removed.
The relevant installation versions are described in the following sections.
For flush panel mounting , the device is inserted through a cutout in the control panel and fixed to the control panel or control cabinet from behind using
the mounting brackets. The diagram below shows the dimensions required
for the control panel cutout.
Figure15: Dimensions for the cutout
A wall thickness of 2...5 mm (0.08...0.2in) is needed for secure device fixing.
To mount the device in the control panel or control cabinet, proceed as follows:
1. Close the device's door.
2. Insert the device through the cutout in the control panel or control cabinet
.
3. Screw both fixing brackets to the rear of the device with 2 hexagon socket
Proceed with wiring as shown in the connection diagram and as described in
the Connecting device [►Section 6.3, Page 34] section.
6.2.3 Cap rail mounting
As an option, the device can be fitted with a cap rail clip (aluminum extrusion
with wire spring integrated at center). This enables you to mount the device
on a cap rail.
When attaching the cap rail, sufficient space for the device must be planned
for. At least 5cm (1.97in) of space must be provided above and at least
35cm (13.78in) below the fixing screws of the cap rail for the device housing.
To mount the device using the cap rail, proceed as follows:
1. Lay the device carefully on the door.
2. Screw the cap rail clip into the two top holes on the rear with the M5
hexagon socket countersunk head screws provided .
3. Suspend the cap rail clip in the cap rail and push the underside carefully
towards the wall until the clip can be heard to click into place .
Figure19: Cap rail mounting
ð The device is mounted and can be wired up .
Proceed with wiring as shown in the connection diagram and as described in
the Connecting device [►Section 6.3, Page 34] section.
When the door is fitted, the device satisfies protection category IP54. The
door may be removed if the device is used solely in a dry atmosphere protected from environmental influences. The device then satisfies protection
category IP21.
Proceed as follows to remove the door:
1. Loosen the grounding strap on the door using an open-end wrench.
Figure22: Remove door
2. Unscrew the fixing bolt using a slotted screwdriver and lift the door out
of the upper mounting .
3. Hook the cover strip in the upper and lower suspension mount and
fasten it with the provided raised countersunk head screws.
Figure24: Fasten covering strip
ð The door is removed and the exposed attachment points for the door are
covered.
WARNING
6.3 Connecting device
The following section describes how to establish the electrical connection to
the device.
Electric shock!
Connection errors can lead to death, injury or property damage.
► Ground the device with a protective conductor using the grounding screw
on the housing.
► Note the phase difference of the secondary terminals for the current
transformer and voltage transformer.
► Connect the output relays correctly to the motor-drive unit.
Supply the voltage via separators and ensure that current paths can be
short circuited. Fit the separator, clearly labeled, close to the device's power
supply so that it is freely accessible. This ensures that the device can be replaced with ease in the event of a defect.
Wiring information
Note this procedure for the wiring:
ü To obtain a better overview when connecting cables, only use as many
leads as necessary.
ü Note the connection diagram.
ü Use only the specified cables for wiring. Note the cable recommendation
[►Section 6.3.1, Page 35].
ü Wire the leads to the system periphery [►Section 6.3.4, Page 39].
Please note the following recommendation from Maschinenfabrik Reinhausen when wiring the device.
Excessive line capacitance can prevent the relay contacts from breaking the
contact current. In control circuits operated with alternating current, take into
account the effect of the line capacitance of long control cables on the function of the relay contacts.
Table7: Cable recommendation for connection cable
X4Unshielded1.5 mm²-0.6 Nm
X1:5/6/9Unshielded4 mm²-1.5 Nm
X2:1/2Shielded1.5 mm²-0.6 Nm
Max. lengthMax. permissible
torque
*) Observe line capacitance, see note above.
Cable clips X1 to X4 are on the MIO card of the device.
6.3.2 Information about laying fiber-optic cable
To ensure the smooth transfer of data via the fiber-optic cable, you must ensure that mechanical loads are avoided when laying the fiber-optic cable and
later on during operation. Also observe the information from the manufacturer of the fiber-optic cable and the following instructions:
▪ Radii must not fall below the minimum permissible bend radii (do not bend
fiber-optic cable).
▪ The fiber-optic cables must not be over-stretched or crushed. Observe the
▪ Be aware of sharp edges because they can damage the fiber-optic cable's
coating during laying or can place mechanical loads on the coating later
on.
▪ Provide a sufficient cable reserve near distributor cabinets. Lay the re-
serve such that the fiber-optic cable is neither bent nor twisted when tightened.
6.3.3 Electromagnetic compatibility
The device has been developed in accordance with applicable EMC standards. The following points must be noted in order to maintain the EMC
standards.
6.3.3.1 Wiring requirement of installation site
Note the following when selecting the installation site:
▪ The system's overvoltage protection must be effective.
▪ The system's ground connection must comply with all technical regula-
tions.
▪ Separate system parts must be joined by a potential equalization.
▪ The device and its wiring must be at least 10m away from circuit-break-
ers, load disconnectors and busbars.
6 Mounting
6.3.3.2 Wiring requirement of operating site
Note the following when wiring the operating site:
▪ Route the connecting leads in grounded metal cable ducts.
▪ Do not route lines which cause interference (e.g. power lines) and lines
susceptible to interference (e.g. signal lines) in the same cable duct.
▪ Maintain a distance of more than 100 mm between lines which cause in-
terference and those which are susceptible to interference.
▪ Short-circuit and ground reserve lines.
▪ Never connect the device with a multi-wire collective pipe.
▪ For signal transmission, use shielded lines with individual conductors (out-
going conductor / return conductor) twisted in pairs.
▪ Connect full surface of shielding (360º) to device or to a nearby grounding
bar.
Using single conductors may limit the effectiveness of the shielding. Connect close-fitting shielding to cover all areas.
Figure26: Recommended connection of the shielding
6 Mounting
1 Connection of the shielding via a
single conductor
6.3.3.3 Wiring requirement in control cabinet
Note the following when wiring the control cabinet:
▪ The control cabinet where the device will be installed must be prepared in
accordance with EMC requirements:
– Functional division of control cabinet (physical separation)
– Constant potential equalization (all metal parts are joined)
– Line routing in accordance with EMC requirements (separation of lines
which cause interference and those susceptible to interference)
– Optimum shielding (metal housing)
– Overvoltage protection (lightning protection)
– Collective grounding (main grounding rail)
– Cable bushings in accordance with EMC requirements
– Any contactor coils present must be interconnected
▪ The device's connection cables must be laid in close contact with the
grounded metal housing or in metallic cable ducts with a ground connection.
▪ Signal lines and power lines/switching lines must be laid in separate cable
ducts.
▪ The device must be grounded at the screw provided, the protective
grounding connection, using a ground strap (cross-section min. 8 mm²).
To connect cables to the system periphery, proceed as follows:
ü Use only the specified cables for wiring. Note the cable recommendation.
► Connect the lines to be wired to the device to the system periphery as
shown in the connection diagrams supplied.
6.3.5 Supplying the voltage regulator using auxiliary voltage
The device is normally supplied by the voltage transformer. If the voltage
transformer does not provide the supply voltage and power (see "Technical
Data") needed for operation, the device must be supplied via a 88...265V
AC/DC, 50...60Hz auxiliary supply .
Proceed as follows to supply the device with auxiliary voltage:
1. NOTICE! Voltage transformer damage Connecting an auxiliary voltage
when bridges are present between the X2:1/3 and X2:2/4 terminals can
result in voltage transformer damage. Remove the bridges between the
terminals X2:1/3 and X2:2/4.
2. Connect the voltage transformer to terminals X2:1 and X2:2.
3. Connect the auxiliary voltage using the following terminals: X2:3 and X2:4.
6 Mounting
Figure29: Voltage transformer and auxiliary supply connections
6.3.6 Wiring device
To obtain a better overview when connecting cables, only use as many
leads as necessary.
To wire the device, proceed as follows:
ü Use only the specified cables for wiring. Note the cable recommendation
[►Section 6.3.1, Page 35].
ü Wire the lines to the system periphery [►Section 6.3.4, Page 39].
You need to set several parameters and perform function tests before commissioning the device. These are described in the following sections.
NOTICE
Damage to device and system periphery
An incorrectly connected device can lead to damages in the device and system periphery.
► Check the entire configuration before commissioning.
► Prior to commissioning, be sure to check the actual voltage and operating
voltage.
We recommend using a device for industrial instrumentation to record the
actual transformer voltage value in order to evaluate how the device is functioning.
7.1 Setting the display contrast
You can adjust the contrast in the display with the help of an adjustment
screw on the front of the device. To adjust the contrast, proceed as follows:
► Use a screwdriver to turn the adjustment screw on the front until the con-
trast is adjusted to the desired setting.
Figure30: Setting the display contrast
7.2 Setting parameters
To commission the device, you must set the following parameters. For more
detailed information about the parameters, refer to the respective sections.
Set further parameters to commission the device. You will find more detailed
information about the respective parameters in the "Operation" [►Section 8,
Page 49] chapter.
Setting transformer data
Set the transformer data and phase difference of the current transformer and
voltage transformer:
1. Set primary transformer voltage [►Section 8.7.1, Page 82].
2. Set secondary transformer voltage [►Section 8.7.2, Page 82].
3. Set primary transformer current [►Section 8.7.3, Page 83].
If you want to commission voltage regulation quickly, you can activate
NORMset mode. If you want to set the parameters yourself, continue with
the sections below.
► Activate NORMset and set the relevant parameters [►Section 8.3, Page
If you need line drop compensation, you must set all important parameters
for this:
1. Select the LDC compensation method [►Section 8.6.1, Page 76].
2. Set the line data for the ohmic voltage drop Ur [►Section 8.6.1.1, Page
78].
3. Set the line data for the inductive voltage drop Ux [►Section 8.6.1.2,
Page 79].
7.3 Function tests
Before switching from manual mode to auto mode, Maschinenfabrik Reinhausen recommends carrying out function tests. These function tests are described in the following sections. Note the following points for all function
tests:
▪ You must ensure that REMOTE mode is disabled before you can control
the on-load tap-changer manually in manual mode.
▪ You can only activate the on-load tap-changer manually in manual mode
using the and keys.
▪ During the function test, you must set the most important parameters. De-
tails on the parameters listed can be found in the Operation [►Section 8,
Page 49] chapter.
7.3.1 Checking control functions
This section describes how you can check the device's control functions:
ü Supply voltage must be present.
1. Press to select manual mode.
2. Set transmission ratio for voltage transformer, current transformer and
measuring set-up.
3. Measure actual voltage and compare with the measured value displayed
on the device's main screen.
4. Press key several times to display the operating values for current,
power and phase angle and compare them with values of service instruments.
5. Control the on-load tap-changer manually with the or keys until
the measured voltage (U
the next stage.
7. Set bandwidth depending on step voltage [►Section 8.4.3, Page 65].
8. Set delay time T1 to 20 seconds [►Section 8.4.4, Page 66].
9. Set control response T1 to linear [►Section 8.4.5, Page 67].
10. Press to raise the on-load tap-changer 1 step.
11. Press to select auto mode.
ð After 20 seconds, the device returns the on-load tap-changer to the
original operating position.
12. Press to select manual mode.
13. Press to lower the on-load tap-changer 1 step.
14. Press to select auto mode.
ð After 20 seconds, the device returns the on-load tap-changer to the
original operating position.
15. Press to select manual mode.
16. Set delay time T2 to 10 seconds [►Section , Page 68].
17. Activate delay time T2.
18. Press twice to raise the on-load tap-changer 2 steps.
19. Press to select auto mode.
ð After 20seconds, the device lowers the on-load tap-changer one step
and after another 10seconds another step.
20. Press to select manual mode.
21. Set delay time T1 [►Section 8.4.4, Page 66] and delay time T2 [►Section , Page 68] to the desired value.
We recommend a temporary setting of 100 seconds for delay time T1 when
commissioning the transformer. Depending on the operating conditions, you
can also specify the delay time following a longer observation period. In this
regard, it is useful to register how the actual voltage progresses and the
number of tap-change operations per day.
7.3.2 Checking additional functions
This section describes how you can check the following additional functions:
▪ Undervoltage blocking
▪ Overvoltage blocking
▪ Activation of desired values 2 and 3
▪ Line drop compensation
▪ Z compensation
3. Apply voltage L+ to terminal X4:17desired value2 (see connection diagram).
4. Press until the main screen is displayed.
ð Desired value2 is shown on the main screen.
5. Set desired value3 to the value you want.
6. Apply voltage L+ to terminal desired value3 (see connection diagram).
7. Press until the main screen is displayed.
ð Desired value3 is shown on the main screen.
ð The function test for desired value2 and desired value3 is complete.
Checking line drop compensation
If you want to use line drop compensation, you need to run this function test.
A load current of ≥10% of the nominal transformer current is needed for the
following function tests. Before the function test, ensure that all parameters
for line drop compensation and for Z compensation are set to 0.
1. Press to select manual mode.
2. Set the compensation method parameter to LDC.
3. Press until the main screen is displayed.
4. If necessary, press until the control deviation dU is shown.
ð The measured voltage must be within the bandwidth.
5. Set line drop compensation Ur parameter to 20.0V.
6. Press until the main screen is displayed.
7. If necessary, press until the control deviation dU is shown.
ð The value for control deviation dU must be negative.
8. Set line drop compensation Ur parameter to -20.0V.
9. Press until the main screen is displayed.
10. If necessary, press until the control deviation dU is shown.
ð The value for control deviation dU must be positive.
If the control deviation appears in the opposite direction, change the polarity
of the current transformer.
11. Set the line drop compensation Ur and line drop compensation Ux
parameters to the desired operating values.
ð The function test for line drop compensation is complete.
Checking Z compensation
If you want to use Z compensation, you need to run this function test. A load
current of ≥10% of the nominal transformer current is needed for the following function test .
1. Press to select manual mode.
2. Set all parameters for line drop compensation and Z compensation to 0.
3. Set the compensation method parameter to Z.
4. Press until the main screen is displayed.
5. If necessary, press until the control deviation dU is shown.
ð The measured voltage must be within the bandwidth.
6. Set the Z compensation parameter to 15.0V.
7. Press until the main screen is displayed.
8. If necessary, press until the control deviation dU is shown.
ð The control deviation dU must be negative.
If the control deviation appears in the opposite direction, change the polarity
of the current transformer.
9. Set the Z compensation and Z compensation limit value parameters to
the desired operating values.
ð The function test for Z compensation is complete.
This chapter describes all the functions and setting options for the device.
8.1 Key lock
The device is equipped with a key lock to prevent unintentional operation.
You can only set or change the parameters when the key lock is deactivated
in manual mode.
Activating key lock
To activate the key lock, proceed as follows:
► Press and at the same time.
ð A confirmation appears in the display for a brief period. The key lock is ac-
tivated. Parameters can no longer be entered.
Deactivating key lock
To deactivate the key lock, proceed as follows:
► Press and at the same time.
ð The key lock is deactivated. Parameters can be entered.
8.2 General
You can undertake general settings on the device in the General menu item.
▪ Language [►Section 7.2.1, Page 43]
▪ Regulator ID
▪ Baud rate (COM1 setting)
▪ Raise/Lower pulse duration
▪ Operations counter
▪ Display dimming
▪ Key lock
▪ Function monitoring
▪ Motor runtime
▪ Manual mode/auto mode
▪ Local/Remote
8.2.1 Setting device ID
You can use the device ID parameter to assign a 4-digit ID to the device.
This ID is used to uniquely identify the device in the TAPCON®-trol software.
1. > Configuration > General > Press until the desired pa-
rameter is displayed.
ð Baud rate.
2. Press or to select the required baud rate.
3. Press .
ð The baud rate is set.
8.2.3 Setting the switching pulse time
You can use this parameter to set the duration of the switching pulse for the
motor-drive unit.
If you set the switching pulse time to 0s, the motor-drive unit is activated
with a continuous signal. The signal then remains active for as long as the
If you set the switching pulse time to 1.5seconds for example, after the set
delay time T1 or delay time T2 there will be a switching pulse of 1.5sec-
onds .
The waiting time between 2 consecutive switching pulses corresponds to the
set delay time T1 or delay time T2.
Figure32: Switching pulse time in normal mode
1 Set delay time T1 or T22 Set switching pulse time (for exam-
ple 1.5seconds)
If the motor-drive unit does not start with the factory setting (1.5seconds),
you need to extend the raise switching pulse time / lower switching pulse
time.
If you set the raise switching pulse time or lower switching pulse time to
1.5seconds, for example, the next earliest switching pulse occurs in rapid
return control mode 1.5 seconds after the previous switching pulse
ended.
Figure33: Switching pulse in rapid return control mode
1 Start of first raise switching pulse/
lower switching pulse
2 Set switching pulse time (for exam-
ple 1.5seconds)
To set the pulse duration, proceed as follows:
1. > Configuration > General > Press until the desired pa-
rameter is displayed.
ð R/L pulse duration.
2. Press or to select the pulse duration you want.
3. Press .
ð The R/L pulse duration is now set.
8.2.4 Setting operations counter
The device's operations counter is automatically increased with every tapchange operation. You can use this parameter to set the number of tapchange operations for comparing with the operations counter of the motordrive unit, for example.
To ensure correct operation counter function, the Motor running signal of the
motor-drive unit must be connected with a configurable input (GPI 1...6) and
then the Motor running function assigned to this input.
3 Earliest time for the next raise
switching pulse/lower switching
pulse (for example 1.5seconds)
To set the operations counter, proceed as follows:
1. > Configuration > General > Press until the desired parameter is displayed.
ð Operations counter.
2. Press to highlight a digit.
ð The desired position is highlighted and the value can be changed.
3. Press to increase the value or to reduce it.
4. Press .
ð The operations counter is set.
8.2.5 Dimming display
You can use this parameter to activate or deactivate automatic display dimming. You can select the following options:
▪ On: The display is automatically dimmed if no key is pressed for 15min-
utes. The display returns to full brightness by pressing any key.
▪ Off: Automatic display dimming is deactivated.
Activating this function extends the display's service life.
To activate/deactivate automatic display dimming, proceed as follows:
1. Press > Configuration > General > until the desired parameter is displayed.
ð Display off.
2. Press or to activate/deactivate automatic dimming.
3. Press .
ð Automatic dimming is set.
8.2.6 Activating/deactivating the automatic key lock
Activating this function automatically activates the key lock if no keys are
pressed for 15minutes. You can also lock the keys manually. This function
can be deactivated as well.
To set the automatic key lock, proceed as follows:
1. > Configuration > General > Press until the desired parameter is displayed.
ð Key lock
2. Press or to select On or Off.
3. Press .
ð Automatic key lock is set.
8.2.7 "Function monitoring" message for monitoring messages <30 V
By default, the Function monitoring message is activated for measured voltages. This message is issued as soon as the measured voltage is under
30V for longer than the set signaling delay time.
Switched-off transformer You can suppress the message with this parameter to prevent the message
from being continuously issued when a transformer is shut off.
The device behaves as follows:
ParameterFunction
OnThe Function monitoring message is issued after the con-
figured delay time if the measured voltage is less than
30V.
OffThe Function monitoring message is suppressed if the
measured voltage is less than 30V.
Table8: Settings
Activate/deactivate
To activate/deactivate function monitoring, proceed as follows:
message
1. > Configuration > General > Press until the desired parameter is displayed.
ð Function monitoring
2. Press or to select On or Off.
3. Press .
ð The Function monitoring message for is activated/deactivated for mea-
sured voltages <30V.
Setting delay time You can configure the delay time after which the Function monitoring mes-
sage is to be issued. If you select 0, function monitoring is deactivated.
To set the delay time for the Function monitoring message, proceed as follows:
1. > Configuration > General > Press until the desired parameter is displayed.
ð Delay function monitoring
2. Press to increase the value or to reduce it.
3. Press .
ð The delay time for the Function monitoring message is set.
8.2.8 Setting motor runtime monitoring
You can use this motor runtime parameter to set the motor runtime. The motor-drive unit's runtime can also be monitored by the device. This function is
used to identify motor-drive unit malfunctions during the tap-change operation and to trigger any actions needed.
Behavior The motor-drive unit issues the Motor-drive unit running signal during the
Parameterizing control
input
tap-change operation. This signal is present until the tap-change operation is
complete. The device compares the duration of this signal with the set motor
runtime. If the set motor runtime is exceeded, the device triggers the following actions:
1. Motor runtime monitoring message is issued
2. Continuous signal via output relay Motor-drive unit runtime exceeded (optional)
3. Pulse signal via Trigger motor protective switch output relay (optional)
To use runtime monitoring, you need to correctly wire the corresponding
control input and parameterize to Motor running. The motor runtime must
also be set.
If you want to monitor the motor runtime, the device and motor-drive unit
must be connected and parameterized as shown below.
Figure35: Wiring for motor runtime monitoring
1 Motor running control input I/O3 Motor protective switch tripped
GPO output relay (optional)
2 Motor protective switch triggered
control input I/O (optional)
4 Motor runtime exceeded GPO out-
put relay (optional)
If you want to use the output relay, the feedback from the motor-drive unit
Motor protective switch triggered must be wired to a control input and parameterized. This message resets the Motor runtime exceeded output relay
when the motor protective switch is switched back on and activates the Mo-tor protective switch triggered message.
If the runtime monitoring is set to "0.0s", this equates to it being switched
off.
This parameter can be used to activate the Local or Remote operation
modes. This parameter has the same functions as the keys.
ParameterFunction
LocalYou can operate the device using the control panel.
RemoteYou can operate the device using an external con-
Table10: Adjustable parameters
To activate Manual or Automatic operating mode, proceed as follows:
1. > Configuration > General > Press until the desired parameter is displayed.
2. Local/Remote
8 Operation
trol level.
Manual operation is disabled.
3. Press or to select the operating mode you want.
4. Press .
ð The operating mode is set.
8.2.11 Setting the COM1 password
You can use this parameter to enter a password for the COM1 front interface. This enables you to protect the device against unauthorized access via
these interfaces. If a COM1 password is assigned, you must first enter the
correct password to establish a connection via the interfaces.
Note the following information:
▪ The password must be at least 1 character long and must not exceed 8
characters. If you enter an empty password (only an end marker), then the
COM1 password is deactivated.
▪ You can enter alphanumeric characters (A to Z, a to z, 0 to 9) and an end
marker (space).
▪ If you want to use a password with fewer than 8 characters, you must se-
lect the end marker after the last character of your password.
▪ Once you save the password, the display changes to xxxxxxxx. The
password is only displayed in plain text during text input.
1. > Configuration > General > Press until the desired parameter is displayed.
ð COM1 password.
2. Enter the current COM1 password. Press or to change a character and to select the next character.
3. Press .
ð The Parallel operation active LED flashes. You can establish a connec-
tion via the front interface or enter a new password.
4. Press or to change a character and to select the next character.
5. Press .
ð The COM1 password is set. The display changes to xxxxxxxx.
8.2.12 Setting the password duration
You can use this parameter to set the period for which the password is active once it has been entered. If the password is active, the Parallel opera-tion active LED flashes.
If you establish a connection via the COM1 front interface, the password remains active for as long as data is being transferred via the interface. The
set password duration expires the moment that no more data is transmitted.
To set the password duration, proceed as follows:
1. > Configuration > General > Press until the desired parameter is displayed.
ð Password duration.
2. Press or to increase or decrease the value.
3. Press .
ð The password duration is set.
8.3 NORMset
NORMset mode is used for quickly starting voltage regulation. In NORMset
mode, the bandwidth and delay time parameters are automatically adapted
to the requirements of the grid.
To start NORMset mode, you must set the following parameters:
▪ Normset activation
▪ Desired value 1
1. > NORMset > Press until the desired parameter is displayed.
ð Secondary voltage.
2. Press to increase the value or to reduce it.
3. Press .
ð The secondary voltage is set.
Setting desired value 1
With this parameter, you can set the desired value for automatic voltage regulation. You can enter the desired value in V or in kV. If you enter the desired value in V, the value relates to the voltage transformer's secondary
voltage. If you set the desired value in kV, the value relates to the voltage
transformer's primary voltage.
Settings in kV are only possible if you have previously entered the parameters for primary and secondary voltage.
To set the desired value, proceed as follows:
1. > NORMset > Press until the desired parameter is displayed.
ð Desired value 1.
2. Press to increase the value or to reduce it.
3. Press .
ð The desired value is set.
8.4 Control parameters
All of the required for the regulation function are described in this section.
For voltage regulation, you can set the following parameters:
▪ Desired values 1…3
▪ Bandwidth
▪ Delay time T1
▪ Control response T1
▪ Delay time T2
For voltage regulation, you can set delay time T1 and also delay time T2.
The following sections describe how the regulation function responds in both
cases:
commands are issued to the motor-drive unit for the tap-change operation.
Control commands will also not be issued to the motor-drive unit if the mea-
sured voltage returns to the tolerance bandwidth within the set delay time
T1 . However, if the measured voltage deviates from the set bandwidth for
a long period , a tap-change command occurs after expiration of the
set delay time T1. The on-load tap-changer carries out a tap-change in a
raise or lower direction to return to the tolerance bandwidth.
Figure38: Behavior of the regulation function with delay time T1
1 +B%: Upper limit4 Set delay time T1
2 U
: Desired value5 U
desired
: Measured voltage
actual
3 -B%: Lower limit6 B%: Tolerance bandwidth
A U
C U
is outside the bandwidth. De-
actual
lay time T1 starts.
is outside the bandwidth. De-
actual
lay time T1 starts.
B U
is within the bandwidth be-
actual
fore delay time T1 is complete.
D U
is still outside the bandwidth
actual
when delay time T1 is complete.
Tap-change operation is initiated.
Behavior with delay times T1 and T2
Delay time T2 can be used to correct major control deviations more quickly.
Ensure that you set a lower value in the "Delay time T2" parameter than in
the "Delay time T1" parameter.
If the measured voltage U
deviates from the set bandwidth for a long
actual
period , a control impulse is output to the motor-drive unit after the set delay time T1. If the measured voltage U
delay time T2 starts once delay time T1 is complete. Once delay time T2
is complete, a control impulse is again output to the motor-drive unit for the
tap change to return to the tolerance bandwidth.
Figure39: Behavior of the regulation function with delay times T1 and T2
1 +B%: Upper limit4 Set delay times T1 and T2.
2 U
: Desired value5 U
desired
3 -B%: Lower limit6 B%: Tolerance bandwidth
A U
is outside the bandwidth. De-
actual
lay time T1 starts.
C Delay time T2 complete. Tap
change triggered.
The following sections describe how to set the relevant control parameters.
8.4.1 Setting desired value 1...3
You can use this parameter to set up to 3 desired voltage values U
desired voltage value is specified as a fixed value. The desired value 1 is the
default desired value. Desired values 2 and 3 are activated if there is a continuous signal at factory-preset control inputs X4:17 or X4:18 provided you
have programmed these previously. If there is a signal at several control inputs at the same time, desired value 2 is activated.
The device provides the following ways of changing the desired voltage
value during operation:
▪ Using the control parameters menu item via the operating screen
▪ Using binary inputs
▪ Using control system protocols if a communication card is ready for opera-
tion
Desired values set in kV refer to the primary voltage of the voltage transformer. Desired values set in V refer to the secondary voltage of the voltage
transformer. The transformer data must be entered correctly for this display.
To set the desired value, proceed as follows:
1. > Control parameter > voltage regulator > Press until
the desired parameter is displayed.
2. If you have already entered the transformer data, press to select the
unit you want: "V" or "kV".
3. Press to highlight the position.
ð The desired position is highlighted and the value can be changed.
4. Press to increase the value or to reduce it.
5. Press .
ð The desired value is set.
8.4.2 Selecting a desired value
You can use this parameter to select the active desired value 1, 2 or 3.
If you select the desired value using appropriately configured GPIs, this parameter's setting is ignored. Refer to the Configuration [►Section 8.8, Page
88] section for more information about GPI configuration.
Proceed as follows to select a desired value:
1. > Control parameter > Voltage regulation > Press until
the desired parameter is displayed.
You can use this parameter to set the maximum permissible deviation in
measured voltage U
The following sections describe how you determine and set the bandwidth
required.
8.4.3.1 Determining bandwidth
In order to set the correct value, the transformer's step voltage and nominal
voltage must be known.
. The deviation relates to the activated desired value.
Act
Too small/large a
bandwidth
You have to set the bandwidth in such a way that the output voltage of the
transformer (U
) returns to within the specified tolerance bandwidth after
Act
the tap change. If too small a bandwidth is defined, the output voltage exceeds the bandwidth selected and the device immediately issues a tapchange command in the opposite direction. If a very large bandwidth is selected, this results in a major control deviation.
The following value is recommended for the bandwidth setting:
Figure41: Recommended bandwidth
U
U
U
Step voltage of tap position n-1
n-1
Step voltage of tap position n
n
Nominal voltage
nom
The following transformer values are used to determine the recommended
bandwidth:
Nominal voltage U
Step voltage in tap position 4 U
Step voltage in tap position 5 U
= 11,000V
nom
= 11,275V
Step4
= 11,000V
Step5
The following section describes how you can set the bandwidth.
To enter the determined bandwidth, proceed as follows:
1. > Parameter > Control parameter > Press until the desired parameter is displayed.
2. Press to highlight the position.
ð The desired position is highlighted and the value can be changed.
3. Press to increase the value or to reduce it.
4. Press .
ð The bandwidth is set.
8.4.3.3 Visual display
The deviation from the set bandwidth is shown visually in the device's display. The measured voltage highlighting shows whether the measured
voltage is above, within or below the set bandwidth . Progress of delay
time T1 is indicated by the gradual filling of the time bar . The seconds
display above this indicates the remaining delay time T1.
8 Operation
Figure42: Visual display of deviation from desired value
1 Bandwidth (upper and lower limit)4 Desired voltage value U
2 Time bar for delay time T15 Remaining delay time T1
3 Measured voltage U
8.4.4 Setting delay time T1
Use this parameter to set delay time T1. This function delays the issuing of a
tap-change command for a defined period. This prevents unnecessary tapchange operations if the tolerance bandwidth is exited.
1. > Parameter > Control parameter > Press until the desired parameter is displayed.
2. Press to highlight the position.
ð The desired position is highlighted and the value can be changed.
3. Press to increase the time or to reduce it.
4. Press .
ð The delay time T1 is set.
8.4.5 Setting control response T1
The control response T1 can be set to linear or integral.
Linear control response T1 With linear control response, the device responds with a constant delay time
regardless of the control deviation.
Integral control responseT1With integral control response, the device responds with a variable delay
time depending on the control deviation. The greater the control deviation
(ΔU) in relation to the set bandwidth (B), the shorter the delay time. The delay time can therefore be reduced down to 1 second. This means that the
device responds faster to large voltage changes in the grid. Regulation accuracy improves as a result but the frequency of tap-changes increases too.
Figure43: Diagram showing integral control response
ΔU/B Control deviation "ΔU" as % of desired value as ratio to the set bandwidth
To set the control response T1, proceed as follows:
1. > Parameter > Control parameter > Press until the desired parameter is displayed.
2. Press or to set the response you want.
3. Press .
ð The control response T1 is set.
8.4.6 Setting delay time T2
With this parameter, you can set delay time T2. Delay time T2 is used to
compensate for large control deviations faster.
The delay time T2 only takes effect if more than one tap-change operation is
required to return the voltage to within the set bandwidth. The first output
pulse occurs after the set delay time T1. After the set tap-change delay time
T2 has elapsed, additional pulses occur in order to correct the existing control deviation.
8 Operation
The following requirements must be noted to set delay time T2:
▪ The delay time T2 must be greater than the switching pulse time.
▪ The delay time T2 must be greater than the maximum operating time of
the motor-drive unit.
▪ The delay time T2 must be less than the value set for delay time T1.
To set the delay time T2, proceed as follows:
1. > Parameter > Control parameter > Press until the desired
parameter is displayed.
ð Delay time T2.
2. Press to increase the time or to reduce it.
3. Press .
ð The delay time T2 is set.
Activating/deactivating delay time T2
To activate/deactivate delay time T2 , proceed as follows:
1. > Parameter > Control parameter > Press until the desired parameter is displayed.
In the Limit values menu item, you can set all the parameters needed for
limit value monitoring as relative or absolute values. You can set three limit
values:
Limit value monitoring is used to reduce damage to the system periphery.
The following sections describe how you can set the parameters.
8.5.1 Setting undervoltage monitoring U<
You can use these parameters to set the limit values for an undervoltage.
Undervoltage monitoring prevents tap-change operations if there is a power
cut.
To set the limit value for undervoltage U< as %, proceed as follows:
1. > Control parameter > Limit values > Press until the
desired parameter is displayed.
ð U< Undervoltage (%)
2. Press to increase the value or to reduce it.
3. Press .
ð The limit value for undervoltage U< is set.
Setting signaling delay for undervoltage U<
You can use this parameter to set the delay time after which the Undervoltage relay is to activate and the event message appear on the display. This
can be used to prevent messages from being issued when the value briefly
falls below the limit value. The undervoltage LED always lights up immediately regardless.
To set the delay time for this message, proceed as follows:
1. > Control parameter > Limit values > Press until the
desired parameter is displayed.
ð U< Delay
2. Press to highlight the position.
ð The desired position is highlighted and the value can be changed.
3. Press to increase the time or to reduce it.
4. Press .
ð The signaling delay time for undervoltage U< is set.
Activating/deactivating undervoltage blocking
You can use this parameter to set how the device behaves if the voltage falls
below the undervoltage limit. You can select the following options:
SettingFunction
OnAutomatic regulation is blocked.
OffAutomatic regulation remains active.
To activate/deactivate the undervoltage blocking, proceed as follows:
1. > Control parameter > Limit values > Press until the
desired parameter is displayed.
ð U< blocking.
2. Press for On setting or for Off setting.
3. Press .
ð Undervoltage blocking is activated/deactivated.
Activating/deactivating message for voltages below 30V
You can use this parameter to set whether the Undervoltage message is to
be suppressed at a measured value of less than 30V. This setting is used to
ensure that no event message appears when the transformer is switched off.
You can select the following options:
SettingFunction
OnThe Undervoltage message is also displayed when
the measured value is less than 30V.
OffThe Undervoltage message is no longer displayed
when the measured value is less than 30V.
Table12: Response
To activate/deactivate the message, proceed as follows:
1. > Control parameter > Limit values > Press until the
desired parameter is displayed.
ð U< also under 30V.
2. Press for On setting or for Off setting.
3. Press .
ð The message is activated/deactivated.
8.5.2 Setting overvoltage monitoring U>
You can use these parameters to set the limit values for overvoltage monitoring. This overvoltage monitoring triggers tap-change operations to return
to the desired operating status. If the operating status can no longer be corrected, a message is triggered by the Function monitoring relay.
and associated signaling relay activate. The Overvoltage U> message appears in the display. At the same time, the high-speed return function is acti-
vated without delay time T1. Once the set switching pulse time has
passed, the tap position is lowered by activating the motor-drive unit until
the measured voltage U
again falls below the limit value . The Over-
actual
voltage U> message is reset.
Response to overvoltage
blocking
Figure45: Response to limit value being exceeded
1 Set limit value for overvoltage U>6 U
2 +B%: Upper limitA Value exceeds limit value
3 U
4 -B%: Lower limitC High-speed return is started (lower
5 Set switching pulse time
: Desired valueB Value falls below limit value
desired
: Measured voltage
actual
tap-change)
If you activated the overvoltage blocking, all switching pulses to the motordrive unit are blocked when a limit value is exceeded. At the same time, the
red LED U> lights up and the Overvoltage U> message is displayed. As
soon as the measured voltage U
has again fallen below the limit value,
actual
blocking and the message are reset.
The following sections describe how you can set the parameters for the
overvoltage U> limit value.
The limit value is entered as a relative value (%) of the set desired value. To
set the limit value, proceed as follows:
1. > Control parameter > Limit values > Press until the
desired parameter is displayed.
ð U> Overvoltage (%)
2. Press to increase the value or to reduce it.
3. Press .
ð The limit value is set.
Activating overvoltage blocking/high-speed return
You can use this parameter to set how the device responds to overvoltage.
The following settings are possible:
SettingBehavior
OnDuring overvoltage, the device blocks all switch pulses
to the motor-drive unit.
OffIn the event of overvoltage, a high-speed return is un-
dertaken until the value again falls below the limit value.
Table13: Possible settings
To set the device's response to overvoltage, proceed as follows:
1. > Control parameter > Limit values > Press until the
desired parameter is displayed.
ð Overvolt. blocking U>.
2. Press or to set the option you want.
3. Press .
ð The response is set.
8.5.3 Setting overcurrent monitoring I>
You can use this parameter to set the limit value for overcurrent to prevent
tap-change operations in the event of excess load currents.
If the measured current exceeds the set limit value, the red LED I> lights up.
The Overcurrent message appears in the display. The device's output pulses
are blocked at the same time.
To activate/deactivate undercurrent monitoring, proceed as follows:
1. > Control parameter > Limit values > Press until the
desired parameter is displayed.
ð Blocking undercurrent I>.
2. Press or to activate (ON)/deactivate (OFF) undercurrent blocking.
3. Press .
ð The I< undercurrent blocking is activated/deactivated.
8.5.5 Activate/deactivate active power monitoring
This parameter can be used to set active power monitoring. If blocking is activated, the control is blocked if a negative active power flow is detected.
However, this is only possible if the current transformer connection is connected and correctly set. When regulator blocking is deactivated, then the
sign of the active power does not affect the regulation.
8 Operation
To activate/deactivate regulator blocking, proceed as follows:
1. > control parameter > Compensation > Press until the
desired parameter is displayed.
ð Neg. active power block.
2. Press or to select the option you want.
3. Press .
ð Blocking the regulator with negative active power is activated/deactivated.
8.6 Compensation
You can use the "Compensation" function to compensate for the load-dependent voltage drop between the transformer and consumer. The device provides 2 methods of compensation for this purpose:
▪ R&X compensation (line drop compensation)
▪ Z compensation
8.6.1 Line drop compensation
R&X compensation (LDC) requires exact cable data. Line voltage drops can
be compensated very accurately using LDC.
To set R&X compensation correctly, you need to calculate the ohmic and inductive voltage drop in V with reference to the secondary side of the voltage
transformer. You also need to correctly set the transformer circuit used.
Figure46: Equivalent circuit
Figure47: Phasor diagram
You can calculate the ohmic and inductive voltage drop using the following
formulas. This voltage drop calculation relates to the relativized voltage on
the secondary side of the voltage transformer.
Formula for calculating the ohmic voltage drop:
Formula for calculating the inductive voltage drop:
U
r
U
x
I
N
Voltage drop in V due to ohmic line resistance
Voltage drop in V due to inductive line resistance
Nominal current (amps) of selected current-transformer con-
You can use this parameter to set the inductive voltage drop (inductive resistance load). The compensation effect can be rotated by 180° in the display
using a plus or minus sign.
If you do not want to use line drop compensation, you have to set the value
0.0V.
To set the inductive voltage drop Ux, proceed as follows:
ü Select the LDC compensation method.
1. > Parameter > Compensation > Press until the desired
parameter is displayed.
ð Ux line drop compensation.
2. Press to highlight the position.
ð The desired position is highlighted and the value can be changed.
3. Press to increase the value or to reduce it.
4. Press .
ð The inductive voltage drop Ux is set.
8.6.2 Z compensation
To keep the voltage constant for the consumer, you can use Z compensation
to activate a current-dependent increase in voltage. You can also define a
limit value to avoid excess voltage on the transformer.
To set the current dependent voltage increase, proceed as follows:
ü Select Z compensation.
1. > Parameter > Compensation > Press until the desired
parameter is displayed.
ð Z compensation.
2. Press to increase the value or to reduce it.
3. Press .
ð The current-dependent voltage increase is set.
8.6.2.2 Setting the Z compensation limit value
You can use this parameter to define the maximum permissible voltage increase to avoid excess voltage on the transformer.
If you do not want to use a limit value, you have to set the value 0.0%.
To set the limit value for the current-dependent voltage increase, proceed as
follows:
ü Select Z compensation.
ü Set the "Z compensation" parameter
1. > Parameter > Compensation > Press until the desired
parameter is displayed.
ð Z comp. limit value.
2. Press to increase the value or to reduce it.
3. Press .
ð The limit value is set.
8.7 Transformer data
The transformation ratios and measuring set-up for the voltage and current
transformers used in the system can be set with the following parameters.
The device uses this information to calculate the corresponding measured
values on the primary side of the current transformer (and therefore the
transformer) from the recorded measured values. These are then displayed.
The following parameters are available for this purpose:
▪ Primary voltage
▪ Secondary voltage
▪ Primary current
▪ Secondary current (current transformer connection)
▪ Transformer circuit
The measured values displayed for the device are influenced by the settings
for the above parameters. Note the table below.
Parameter setMeasured value display
Primary
voltage
-Yes--Secondary voltage
YesYes--Primary voltage
YesYesYes-Primary voltage
YesYes-YesPrimary voltage
YesYesYesYesPrimary voltage
Table14: Influence of transformer data on measured value display
Secondary
voltage
Primary cur-
rent
Trans-
former con-
nection
Voltage (main
screen)
[V]
[kV]
[kV]
[kV]
[kV]
Current (main
screen)
-Secondary current
[% of connection]
-Secondary current
[% of connection]
Primary current
[A]
-Secondary current
Primary current
[A]
Secondary current
[% of connection]
Secondary current
8 Operation
Current (info
screen)
[A]
[A]
8.7.1 Setting the primary transformer voltage
This parameter can be used to set the primary transformer voltage in kV.
When you are setting the primary transformer voltage, the device shows the
primary voltage rather than the secondary voltage in the main screen and
you can also set the control parameters in kV.
If a setting of 0kV is chosen, no primary transformer voltage is displayed.
To set the primary transformer voltage, proceed as follows:
This parameter can be used to set the current transformer connection. This
setting is needed for the device to display the correct secondary current in
the info screen.
If you select the "Unknown" option, the percentage of current (with reference
to the current transformer connection used) is displayed in the info screen.
▪ 1 A
▪ 5 A
Proceed as follows to set the current-transformer connection:
1. > Configuration > Transformer data > Press until the
desired parameter is displayed.
ð Current-transformer connection
2. Press or to select a current-transformer connection.
3. Press .
ð The current-transformer connection is set.
8 Operation
8.7.5 Setting the phase difference for the current transformer/voltage
transformer
You can use this parameter to set the phase difference of the current transformer and voltage transformer. You can set the common transformer circuits as follows:
▪ The voltage transformer VT is connected to the outer conductor and neu-
tral conductor.
▪ The current transformer CT is looped into the outer conductor.
▪ The voltage UL1 and current IL1 are in phase.
▪ The voltage drop on an outer conductor is determined by the current IL1.
Circuit B: 1-phase measurement in 3-phase grid
Figure53: Phase difference 0 3PHN
▪ The voltage transformer VT is connected to the outer conductors L1 and
neutral.
▪ The current transformer CT is looped into the outer conductor L1.
▪ The voltage U and current I are in phase.
▪ The voltage drop on an outer conductor is determined by the current IL1.
▪ The voltage transformer VT is connected to the outer conductors L1 and
L2.
▪ The current transformer CT1 is looped into the outer conductor L1 and
CT2 into the outer conductor L2.
▪ The current transformers CT1 and CT2 are connected crosswise in paral-
lel (total current = IL1+IL2).
▪ The total current IL1+IL2 and voltage UL1-UL2 are in phase.
▪ The voltage drop on an outer conductor is determined by the current:
(IL1+IL2)/√3.
Circuit D
Figure55: Phase difference 90 3PH
▪ The voltage transformer VT is connected to the outer conductors L1 and
L2.
▪ The current transformer CT is looped into the outer conductor L3.
▪ The current IL3 is ahead of voltage UL1-UL2 by 90°.
▪ The voltage drop on an outer conductor is determined by the current IL3.
▪ The voltage transformer VT is connected to the outer conductors L1 and
L2.
▪ The current transformer CT is looped into the outer conductor L2.
▪ The current IL2 is ahead of voltage UL2-UL1 by 30°.
▪ The voltage drop on an outer conductor is determined by the current IL2.
Circuit F
Figure57: Phase difference -30 3PH
▪ The voltage transformer VT is connected to the outer conductors L1 and
L2.
▪ The current transformer CT is looped into the outer conductor L1.
▪ The current IL1 lags behind UL1-UL2 by 30°. This corresponds to a phase
shift of -30°.
▪ The voltage drop on an outer conductor is determined by the current IL1.
To set the phase difference for the transformer circuit, proceed as follows:
1. > Configuration > Transformer data > Press until the
desired parameter is displayed.
ð Transformer circuit.
2. Press or to select the required phase difference.
3. Press .
ð The phase difference is set.
8.8 Configurable inputs and outputs
You can individually configure the digital inputs (GPI ) and outputs (GPO ).
The following digital inputs and outputs are available:
▪ 6 digital inputs (GPI1...6)
▪ 2 digital outputs (GPO1 and 2)
8 Operation
8.8.1 Linking inputs with functions
You can activate the inputs as follows :
▪ Statically using signal statuses
– The input signal must be continually present (status: high level).
▪ Dynamically using pulses
– A pulse (rising edge) is needed at the input. The input signal must
change its status from "Low" to "High". If you are using a pulsed input,
you can trigger the assigned function at the same time as the keys connected to the inputs also using the control system.
You can recognize pulsed inputs from the preceding "P:". The note "Warning: P = pulsed inputs" is displayed on the screen.
You can assign one of the following functions to each of the digital inputs
(GPI 1...6):
FunctionDescription
OffNo function selected
Remote/Loc.Define remote/local mode.
DVL 3Activate desired value level 3
Blk U raiseBlock tap-change operations (raise).
Blk U low.Block tap-change operations (lower).
P: DV 1Activate desired value 1
P: DV 2
P: DV 3
Table17: Functions for digital inputs (GPI 1...6)
Input for MPS tripped feedback.
Input for MD in progr. feedback.
Activate desired value level 2
Activate desired value 2
Activate desired value 3
If you assign the same functionality to two inputs, the device produces an
event message. This also applies if you assign the same functionality via a
static input and via a pulsed input.
Other examples of double assignment of functions are (n, m = 1...6):
▪ GPI n = master/follower and GPI m = P: DV 1
▪ GPI n = master/follower and GPI m = P: DV 2
To assign a function to a digital input or to deactivate it, proceed as follows:
1. > Configuration > User I/Os (press for further GPIs).
ð GPI
2. Press or until the desired function is displayed.
3. Press .
ð The function is set.
Functions can be assigned to all other GPIs as described above. You can
select the GPIs as follows:
You can assign one of the following functions to the digital outputs (GPO 1
and 2):
FunctionDescription
OffNo function selected
Local/Rem.Message: Local control/remote control
UndervoltageMessage: Undervoltage blocking
OvervoltageMessage: Overvoltage blocking
UndercurrentMessage: Undercurrent blocking
OvercurrentMessage: Overcurrent blocking
Desired value 1Message: Desired value 1
Desired value 2Message: Desired value 2
Desired value 3Message: Desired value 3
MPS triggeredMessage: Motor protective switch was
Motor runtime >Message: Motor runtime exceeded.
Motor runningMessage: "Motor running"
Bandwidth <Message: Value fallen below bandwidth
Bandwidth >Message: Bandwidth exceeded
GPI 1Message: GPI 1 active
GPI 2Message: GPI 2 active
GPI 3Message: GPI 3 active
GPI 4Message: GPI 4 active
GPI 5Message: GPI 5 active
GPI 6Message: GPI 6 active
Table19: Functions for digital outputs (GPOs 1 and 2)
8 Operation
tripped.
To assign a function to a digital output or to deactivate it, proceed as follows:
1. > Configuration > User I/Os > Press until the desired
parameter is displayed.
ð GPO.
2. Press or until the desired function is displayed.
3. Press .
ð The function is set.
Functions can be assigned to all other GPOs as described above. You can
select the GPOs as follows:
You can use this parameter to assign functions to the free LEDs which light
up when an event occurs. You can use labeling strips to label the LED.
Depending on your device configuration, the following parameters can be
used by MR for special functions. In this case, these parameters are pre-assigned. You may not be able to view or freely assign these parameters.
An overview of all possible functions which you can assign to the LEDs is
provided in the table below.
Functions available
OffLED deactivated
GPIxThere is a signal at control input GPIx (e.g. GPI1)
GPOxThe signaling relay at the GPOx (e.g. GPO 1) output has acti-
UndercurrentUndercurrent present
MPS triggeredMotor protective switch triggered
BlockingRegulation is blocked
AutomaticAuto mode active
Bandwidth<Value is below bandwidth
Bandwidth>Value is below bandwidth
Desired value1Desired value1 activated
Desired value2Desired value2 activated
Desired value3Desired value3 activated
Function monitor-
The info screen displays the following information:
Figure58: Info screen
1 Type designation4 Additional cards
2 Software version5 RAM memory
3 Serial number
To display the info screen, proceed as follows:
► > Info.
ð Info.
8.10.2 Displaying measured values
The current measured values are shown in this display. The values on the
right in rows , and are only displayed if the transformer data [►Section 8.7, Page 81] has been entered previously. In row , the value actually
measured can be seen on the left and the value converted to the transformer
circuit is on the right.
1 Voltage U in V or kV3 Frequency f in Hz
2 Current I in % or A4 Measurement performance PMeas
in % or MW
To display the measured values, proceed as follows:
► > Info > Press until the desired display appears.
ð Measured values.
8.10.3 Display calculated values
Calculated values are shown on this screen . The following values can be
displayed:
Figure60: Calculated values
1 I active (active share) in A4 Reactive power Q in Mvar
2 I reactive (reactive share) in A5 Power factor cos ϕ
3 Apparent power S in MVA6 Operation counter
The values in the rows on the right are only displayed if the transformer data
has been entered previously.
The status of the optocoupler inputs is shown in the "MIO card digital inputs"
display. As soon as a continuous signal is present at the input, status 1 is
displayed. 0 indicates no signal at the input.
Proceed as follows to display the status:
► > Info > Press until the desired display appears.
ð MIO card digital inputs
Digital outputs
The status of the relays is shown in the "MIO card digital outputs" display As
soon as a relay has activated, status 1 is displayed. If status 0 is displayed,
the relay has not activated.
Proceed as follows to display the status:
► > Info > Press until the desired display appears.
ð MIO card digital outputs
8.10.6 Resetting parameters
With this display you can reset your settings to the factory settings . It also
shows whether all parameters are saved correctly.
Resetting the parameters to the factory settings permanently deletes your
settings.
To reset all parameters, proceed as follows:
1. > Info > Press until the desired display appears.
ð Default parameter
2. Press and at the same time.
ð "Default parameter active" is displayed.
ð All parameters have been reset to the factory settings.
The memory overview can be used to display various database entries with
the relevant number of data records. The information is not relevant for operation. It is only needed for service checks. The following information is displayed:
Parameter errorReset parameters to factory settings.
Contrast incorrectly set.Set contrast [►Section 7.1, Page 42].
Voltage supply interrupted.Check voltage supply.
Fuse faulty.Contact Maschinenfabrik Reinhausen.
Customized LED parameteriza-
tion.
Input signal not constant.Check input signal.
Different baud rates set.Check baud rate set on device and PC.
Press to activate LOCAL mode.
Check parameters.
9.4 Incorrect measured values
Characteristics/detailCauseRemedy
Measured voltage
▪ No measured value.
Measured voltage
▪ Measured value too low.
Measured voltage
▪ Measured value fluctuates.
Measured current
▪ No measured value.
Connection has no contact in the
plug terminal.
Insulation trapped
Wire not inserted far enough.
Circuit breaker tripped.Check fuse.
Voltage drop on measuring lead.Check measured voltage at plug terminal X2:1/
Possible sources of fault:
▪ Leads laid in parallel.
▪ Tap-change operations.
Line to current transformer interrupted.
Short-circuiting jumper in current
transformer not removed.
Check wiring and plug terminal.
X2:2.
Check measured voltage at plug terminal X2:1/
X2:2.
Increase distance from source of interference.
Install filter if necessary.
Check wiring.