unless expressly permitted.
Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents,
utility models or designs.
The product may have been altered since this document was published.
We reserve the right to change the technical data, design and scope of supply.
Generally the information provided and agreements made when processing the individual quotations and orders
are binding.
The original operating instructions were written in German.
1.4.1Hazard communication system .............................................................................................................................8
1.4.3Instruction system ...............................................................................................................................................10
2.1Appropriate use ................................................................................................................................ 12
4.1Scope of delivery .............................................................................................................................. 21
4.5.2Central processing unit .......................................................................................................................................24
4.5.3Voltage measurement and current measurement...............................................................................................25
4.5.6Media converter with managed switch ................................................................................................................27
4.6Additional operating controls and display elements when using the MControl touch panel (optional) ..
28
5Packaging, transport and storage ..................................................................................30
5.1Packaging, transport and storage..................................................................................................... 30
5.1.1Suitability, structure and production ...................................................................................................................30
Maschinenfabrik Reinhausen GmbH 201835252433/02 ENECOTAP® VPD® CONTROL PRO
6.1.1Wiring requirement of installation site ................................................................................................................32
6.1.2Wiring requirement of operating site ..................................................................................................................33
6.1.3Wiring requirement in control cabinet..................................................................................................................34
6.1.4Information about shielding the CAN bus............................................................................................................34
6.4Mounting the device.......................................................................................................................... 36
6.4.1Mounting the device using the cap rail included in delivery ................................................................................37
6.4.2Mounting the device on an alternative cap rail....................................................................................................43
6.5.2Information about laying fiber-optic cable ...........................................................................................................51
6.5.3Mounting terminating resistor of CAN bus ..........................................................................................................51
6.5.4Connecting cables to the system periphery ........................................................................................................51
6.5.5Wiring the CPU I assembly .................................................................................................................................52
6.5.6Wiring the UI assembly .......................................................................................................................................54
6.5.7Wiring the MC 2-2/SW3-3 assembly ...................................................................................................................56
6.5.8Connecting the power supply..............................................................................................................................57
7.1.1Ground test .........................................................................................................................................................59
7.1.2Performing a dielectric test..................................................................................................................................60
7.2Establishing connection to visualization ........................................................................................... 61
7.3.2Setting the parameters manually ........................................................................................................................63
8.2.1Activating/deactivating automatic launch of commissioning wizard ....................................................................67
Maschinenfabrik Reinhausen GmbH 201845252433/02 ENECOTAP® VPD® CONTROL PRO
Page 5
Table of contents
8.2.2Setting measured value display ..........................................................................................................................67
8.2.5Activating/deactivating the USB interface ...........................................................................................................70
8.4.1Setting the desired value.....................................................................................................................................71
8.4.3Delay time T1 ......................................................................................................................................................76
8.4.4Delay time T2 ......................................................................................................................................................78
8.4.6Setting control variables......................................................................................................................................80
8.5Transformer data .............................................................................................................................. 81
8.5.1Setting the primary transformer voltage ..............................................................................................................81
8.5.2Setting the secondary transformer voltage .........................................................................................................81
8.5.3Setting primary transformer current ....................................................................................................................82
8.5.4Setting the secondary transformer current..........................................................................................................82
8.5.5Setting circuit for current transformer/voltage transformer and phase angle correction .....................................82
8.6.4Setting the display for the power factor...............................................................................................................93
8.7Line drop compensation ................................................................................................................... 93
8.10.7Tap position monitoring (optional).....................................................................................................................118
8.11.7Configure data points (optional) ........................................................................................................................135
8.12.1Activating time synchronization using SNTP.....................................................................................................143
8.12.2Entering the time server address ......................................................................................................................144
8.12.3Setting the time zone ........................................................................................................................................144
8.13.3Creating, editing and deleting users..................................................................................................................148
8.13.4Setting access rights to parameters and events ...............................................................................................149
8.14.1Displaying and acknowledging events ..............................................................................................................150
8.15.1Displaying current measured values .................................................................................................................154
8.15.2Displaying measured value recorder (optional).................................................................................................154
8.15.3Setting the average value interval.....................................................................................................................165
8.16Information about device ................................................................................................................ 166
8.17.1Exporting data ...................................................................................................................................................169
8.17.2Importing data (software version 3.44 and later)...............................................................................................170
Maschinenfabrik Reinhausen GmbH 201865252433/02 ENECOTAP® VPD® CONTROL PRO
Page 7
Table of contents
8.18Linking signals and events.............................................................................................................. 171
8.18.2Linking control system messages .....................................................................................................................173
9Maintenance and care .................................................................................................... 175
Further information on the product and copies of this technical file are available from this address if required.
1.2 Completeness
This technical file is incomplete without the further applicable documentation.
The following documents apply to this product:
▪ Operating instructions
▪ Connection diagrams
1.3 Safekeeping
Keep this technical file and all supporting documents ready at hand and accessible for future use at all times.
1.4 Notation conventions
This section contains an overview of the symbols and textual emphasis
used.
1.4.1 Hazard communication system
Warnings in this technical file are displayed as follows.
Maschinenfabrik Reinhausen GmbH 201885252433/02 ENECOTAP® VPD® CONTROL PRO
Page 9
1 Introduction
1.4.1.1 Warning relating to section
Warnings relating to sections refer to entire chapters or sections, sub-sections or several paragraphs within this technical file. Warnings relating to
sections use the following format:
WARNING
Type of danger!
Source of the danger and outcome.
► Action
► Action
1.4.1.2 Embedded warning information
Embedded warnings refer to a particular part within a section. These warnings apply to smaller units of information than the warnings relating to sections. Embedded warnings use the following format:
DANGER! Instruction for avoiding a dangerous situation.
1.4.1.3 Signal words and pictograms
The following signal words are used:
Signal wordDefinition
DANGERIndicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNINGIndicates a hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTIONIndicates a hazardous situation which, if not avoided, could result
in minor or moderate injury.
NOTICEIndicates measures to be taken to prevent damage to property.
Table1: Signal words in warning notices
Pictograms warn of dangers:
PictogramDefinition
Warning of a danger point
Warning of dangerous electrical voltage
Maschinenfabrik Reinhausen GmbH 201895252433/02 ENECOTAP® VPD® CONTROL PRO
Page 10
PictogramDefinition
Warning of combustible substances
Warning of danger of tipping
Warning of danger of crushing
Table2: Pictograms used in warning notices
1 Introduction
1.4.2 Information system
Information is designed to simplify and improve understanding of particular
procedures. In this technical file it is laid out as follows:
Important information.
1.4.3 Instruction system
This technical file contains single-step and multi-step instructions.
Single-step instructions
Instructions which consist of only a single process step are structured as follows:
Aim of action
ü Requirements (optional).
► Step 1 of 1.
ð Result of step (optional).
ð Result of action (optional).
Multi-step instructions
Instructions which consist of several process steps are structured as follows:
Maschinenfabrik Reinhausen GmbH 2018105252433/02 ENECOTAP® VPD® CONTROL PRO
Page 11
1 Introduction
Aim of action
ü Requirements (optional).
1. Step 1.
ð Result of step (optional).
2. Step 2.
ð Result of step (optional).
ð Result of action (optional).
1.4.4 Typographic conventions
The following typographic conventions are used in this technical file:
Maschinenfabrik Reinhausen GmbH 2018115252433/02 ENECOTAP® VPD® CONTROL PRO
Page 12
2 Safety
This technical file contains detailed descriptions on the safe and proper installation, connection, commissioning, operation, and monitoring of the product.
▪ Read this technical file through carefully to familiarize yourself with the
product.
▪ This technical file is part of the product.
▪ Read and observe the safety instructions provided in this chapter in partic-
ular.
▪ Observe the warnings in this technical file in order to avoid function-re-
lated dangers.
▪ The product is manufactured according to the state of the art. Risks to life
and limb of the user or impairment of the product and other material as-
sets may occur during use due to function-related dangers despite this.
2.1 Appropriate use
2 Safety
The ECOTAP VPD CONTROL PRO device expands automatic voltage regulation of the ECOTAP VPD CONTROL device by adding additional functions.
If used as intended, in compliance with the requirements and conditions
specified in this technical file and observing the warning notices in this technical file and attached to the product, the product does not pose a danger of
injury or damage to property or the environment. This applies across the entire service life of the product, from delivery to installation and operation
through to disassembly and disposal.
The following is considered appropriate use:
▪ You will find the standard valid for the product and the year of issue on the
nameplate.
▪ Operate the product in accordance with this technical file, the agreed-
upon delivery conditions and the technical data.
▪ Ensure that all necessary work is performed by qualified personnel only.
▪ Only use the equipment and special tools included in delivery for the in-
tended purpose and in accordance with the specifications of this technical
file.
▪ Only operate the product in industrial areas. Observe the notices in this
technical file regarding electromagnetic compatibility and the technical
data.
2.2 Fundamental Safety Instructions
To prevent accidents, disruptions and damage as well as unacceptable adverse effects on the environment, those responsible for transport, installation, operation, maintenance and disposal of the product or parts of the product must ensure the following:
Maschinenfabrik Reinhausen GmbH 2018125252433/02 ENECOTAP® VPD® CONTROL PRO
Page 13
2 Safety
Personal protective equipment
Loosely worn or unsuitable clothing increases the danger of becoming
trapped or caught up in rotating parts and the danger of getting caught on
protruding parts. This increases the danger to life and limb.
▪ All necessary devices and personal protective equipment required for the
specific task, such as a hard hat, safety footwear, etc. must be worn. Observe the section "Personal protective equipment" [►Section 2.4, Page
16].
▪ Never wear damaged personal protective equipment.
▪ Never wear rings, necklaces, or other jewelry.
▪ If you have long hair, wear a hairnet.
Work area
Untidy and poorly lit work areas can lead to accidents.
▪ Keep the work area clean and tidy.
▪ Make sure that the work area is well lit.
▪ Observe the applicable laws for accident prevention in the relevant coun-
try.
Working during operation
The product may be operated only in a sound, operational condition. Otherwise it poses a danger to life and limb.
▪ Regularly check the operational reliability of safety equipment.
▪ Comply with the inspection work, maintenance work and maintenance in-
tervals described in this technical file.
Invisible laser radiation
Looking directly into the beam or the reflected beam can cause eye damage.
The beam is emitted at the optical connections or at the end of the fiber-optic
cables connected to them on the assemblies. Read the chapter "Technical
Data" [►Section 12, Page 178] for further information.
▪ Never look directly into the beam or the reflected beam.
▪ Never look into the beam with the aid of optical instruments such as a
magnifying glass or a microscope.
▪ In the event that the laser beam strikes your eyes, close your eyes imme-
diately and move your head out of the path of the beam.
Maschinenfabrik Reinhausen GmbH 2018135252433/02 ENECOTAP® VPD® CONTROL PRO
Page 14
2 Safety
Working with current transformers
Dangerous high voltages may occur when a current transformer is operated
with an open secondary circuit. This can lead to injuries and property damage.
▪ Never operate a current transformer with an open secondary circuit; short-
circuit the current transformer to prevent this.
▪ Observe the information in the current transformer operating instructions.
Explosion protection
Highly flammable or explosive gases, vapors and dusts can cause serious
explosions and fire.
▪ Do not install or operate the product in areas where a risk of explosion is
present.
Safety markings
Warning signs and safety information plates are safety markings on the
product. They are an important aspect of the safety concept.
▪ Observe all safety markings on the product.
▪ Make sure all safety markings on the product remain intact and legible.
▪ Replace safety markings that are damaged or missing.
Ambient conditions
To ensure reliable and safe operation, the product must only be operated
under the ambient conditions specified in the technical data.
▪ Observe the specified operating conditions and requirements for the in-
stallation location.
Modifications and conversions
Unauthorized or inappropriate changes to the product may lead to personal
injury, material damage and operational faults.
▪ Only modify the product after consultation with the manufacturer.
Spare parts
Spare parts not approved by the manufacturer may lead to physical injury,
damage to the product and operational faults.
▪ Only use spare parts approved by the manufacturer.
▪ Contact the manufacturer.
Maschinenfabrik Reinhausen GmbH 2018145252433/02 ENECOTAP® VPD® CONTROL PRO
Page 15
2 Safety
2.3 Personnel qualification
The person responsible for assembly, commissioning, operation, maintenance and inspection must ensure that the personnel are sufficiently qualified.
Electrically skilled person
The electrically skilled person has a technical qualification and therefore has
the required knowledge and experience, and is also conversant with the applicable standards and regulations. The electrically skilled person is also proficient in the following:
▪ Can identify potential dangers independently and is able to avoid them.
▪ Is able to perform work on electrical systems.
▪ Is specially trained for the working environment in which (s)he works.
▪ Must satisfy the requirements of the applicable statutory regulations for
accident prevention.
Electrically trained persons
An electrically trained person receives instruction and guidance from an
electrically skilled person in relation to the tasks undertaken and the potential dangers in the event of inappropriate handling as well as the protective
devices and safety measures. The electrically trained person works exclusively under the guidance and supervision of an electrically skilled person.
Operator
The operator uses and operates the product in line with this technical file.
The operating company provides the operator with instruction and training
on the specific tasks and the associated potential dangers arising from improper handling.
Technical Service
We strongly recommend having maintenance, repairs and retrofitting carried
out by our Technical Service department. This ensures that all work is performed correctly. If maintenance is not carried out by our Technical Service
department, please ensure that the personnel who carry out the maintenance are trained and authorized by Maschinenfabrik Reinhausen GmbH to
carry out the work.
Authorized personnel
Authorized personnel are trained by Maschinenfabrik Reinhausen GmbH to
carry out special maintenance.
Maschinenfabrik Reinhausen GmbH 2018155252433/02 ENECOTAP® VPD® CONTROL PRO
Page 16
2.4 Personal protective equipment
Personal protective equipment must be worn during work to minimize risks to
health.
▪ Always wear the personal protective equipment required for the job at
hand.
▪ Never wear damaged personal protective equipment.
▪ Observe information about personal protective equipment provided in the
work area.
Personal protective equipment to be worn at all times
Protective clothing
Close-fitting work clothing with a low tearing
strength, with tight sleeves and with no protruding parts. It mainly serves to protect the wearer
against being caught by moving machine parts.
Safety shoes
To protect against falling heavy objects and slipping on slippery surfaces.
2 Safety
Special personal protective equipment for particular environments
Safety glasses
To protect the eyes from flying parts and splashing liquids.
Visor
To protect the face from flying parts and splashing liquids or other dangerous substances.
Hard hat
To protect from falling and flying parts and materials.
Maschinenfabrik Reinhausen GmbH 2018165252433/02 ENECOTAP® VPD® CONTROL PRO
Page 17
2 Safety
Hearing protection
To protect from hearing damage.
Protective gloves
To protect from mechanical, thermal, and electrical hazards.
Maschinenfabrik Reinhausen GmbH 2018175252433/02 ENECOTAP® VPD® CONTROL PRO
Page 18
3 IT security
3 IT security
Observe the following recommendations for secure operation of the product.
General
▪ Ensure that only authorized personnel have access to the device.
▪ Only use the device within an ESP (electronic security perimeter). Do not
connect the device to the Internet in an unprotected state.
▪ Ensure that the device is only operated by trained personnel who are fa-
miliar with IT security.
Commissioning
Observe the following recommendations for device commissioning:
▪ User IDs should be unique and attributable. Do not use a "Group account"
function or an "Auto login" function.
▪ Restrict the rights of the individual user groups as much as is feasible; this
helps avoid errors during operating actions. A user with the "Operator"
role, for example, should only perform operating actions and should not
be able to change any device settings.
▪ Delete or disable the default "admin" user ID. This requires first creating a
new user account with the "Administrator" role. You can then use it to
delete or disable the default "admin" account.
▪ Enable SSL/TLS encryption [►Section 8.2, Page 66]; access to the de-
vice is then only possible using the SSL/TLS protocol. In addition to en-
crypting communication, this protocol also checks the authenticity of the
server.
▪ Use TLS version 1.2 or higher wherever possible.
▪ Integrate the device into a public key infrastructure. Create your own SSL
certificate for this if necessary and then import it.
Operation
Observe the following recommendations during device operation:
▪ Change the password at regular intervals.
▪ Export the security log [►Section 8.17.1, Page 169] at regular intervals.
Interfaces
The device uses the following interfaces for communication:
Maschinenfabrik Reinhausen GmbH 2018185252433/02 ENECOTAP® VPD® CONTROL PRO
Page 19
3 IT security
Figure1: Interfaces of the CPU assembly
InterfaceProtocolPortDescription
CAN 1--Attachment of the DIO assembly
CAN 2--Communication with other ISM® devices
(e.g. parallel operation)
COM 1--Internal system interface
COM 2--Serial interface (SCADA)
USB--Import or export of data
ETH 1TCP102IEC 61850
ETH 1TCP502Modbus
ETH 1TCP20000DNP3
2)
2)
2)
ETH 1UDP67DHCP server
ETH 2.xTCP21FTP1) (only for MR service)
ETH 2.xTCP80HTTP for web-based visualization
ETH 2.xTCP443HTTPS for web-based visualization
1)
1)
ETH 2.xTCP990FTPS (only for MR service)
ETH2.xTCP8080HTTP for web-based visualization
ETH2.xTCP8081HTTPS for web-based visualization
Table4: Interfaces and open ports of the CPU assembly
1)
1)
1)
Port is closed if you activate the device's SSL encryption.
2)
Default setting; if you have modified the port for the control system proto-
col, only the set port is opened.
Maschinenfabrik Reinhausen GmbH 2018195252433/02 ENECOTAP® VPD® CONTROL PRO
Page 20
3 IT security
Encryption standards
The device supports the following TLS versions:
▪ TLS 1.0
▪ TLS 1.1
▪ TLS 1.2
The device uses the following cipher suites for a TLS-secured connection:
The device uses the SHA256 hash function to save passwords.
1)
1)
Maschinenfabrik Reinhausen GmbH 2018205252433/02 ENECOTAP® VPD® CONTROL PRO
Page 21
4 Product description
CONTROLCONTROL PRO
Motor-drive unit
SCADA
serialEthernet
ECOTAP VPD
4 Product description
This chapter contains an overview of the design and function of the product.
4.1 Scope of delivery
The following items are included in the delivery:
▪ ECOTAP VPD CONTROL PRO
▪ Connection cable for connecting to ECOTAP VPD MD&C
▪ Terminating resistor for CAN bus (optional)
▪ Technical files
▪ Additional nameplate
Please note the following:
▪ Check the shipment for completeness on the basis of the shipping docu-
ments.
▪ Store the parts in a dry place until installation.
4.2 Function description
The ECOTAP VPD CONTROL PRO device expands automatic voltage regulation of the ECOTAP VPD CONTROL device by adding additional functions.
For this purpose, the two devices are connected via serial connection.
Figure2: Operating principle
Maschinenfabrik Reinhausen GmbH 2018215252433/02 ENECOTAP® VPD® CONTROL PRO
Page 22
4.3 Performance features
The device offers the following functions:
▪ Automatic voltage regulation AVR pro
– Measurement of voltage and current
– Desired value in accordance with order (1, 3 or 5 desired values,
TDSC, analog desired value specification, incremental desired value
specification, desired value via BCD)
– Automatic voltage regulation with linear or integral delay time T1 and
with delay time T2
– Parallel operation
– Line drop compensation
– Status of the motor-drive unit (motor protective switch, motor is running)
– Bandwidth monitoring
– Function monitoring
You can operate the device in the operating modes listed below. You can
select the operating mode using the keys on the connected ECOTAP VPD
CONTROL control unit.
Auto mode (AVR AUTO)
In auto mode, the ECOTAP VPD CONTROL control unit regulates voltage
automatically in accordance with the set parameters. It is not possible to perform manual tap-change operations using operating controls, inputs or a
control system.
Manual mode (AVR MANUAL)
In manual mode, you can perform manual tap-change operations to increase
or decrease the voltage using the keys on the ECOTAP VPD CONTROL
control unit. There is no automatic voltage regulation.
Maschinenfabrik Reinhausen GmbH 2018225252433/02 ENECOTAP® VPD® CONTROL PRO
Page 23
4 Product description
External control (EXTERNAL CONTROL)
In the external control operating mode, the ECOTAP VPD CONTROL control
unit performs the raise/lower switching commands issued by the CONTROL
PRO controller.
Operating modeVPD CONTROLCONTROL PRO
Operating
VPD CONTROL automatic
AVR AUTOLocal (= 0)-
regulation
Tap-change operation us-
AVR MANing VPD CONTROL operating controls
CONTROL PRO automatic
regulation
CONTROL PRO automatic
regulation
Tap-change operation via
SCADA
Table6: Overview of operating modes
2)
EXTERNAL
CONTROL
EXTERNAL
CONTROL
EXTERNAL
CONTROL
mode
UAL
Local/RemoteOperating mode
Remote (= 1)-
Local-
Remote-
LocalAuto
RemoteAuto
RemoteManual
3)
3)
1)
Can be set via parameter P9 in VPD MD&C
2)
Optional when connecting the CONTROL PRO control unit to a control sys-
tem (SCADA).
3)
You can switch the operating mode using a SCADA command.
4.5 Design
The device consists of various assemblies that are pre-installed and wired
on a cap rail:
▪ G1 power supply
▪ CPU (central processing unit) I
▪ UI 3 voltage measurement and current measurement
▪ VD001 voltage divider
▪ Optional: MC 2-2 media converter or media converter with SW 3-3 man-
aged switch
Maschinenfabrik Reinhausen GmbH 2018235252433/02 ENECOTAP® VPD® CONTROL PRO
Page 24
Figure3: Overview
The individual device assemblies are described in the following section.
4.5.1 Power supply
The G1 PULS DIMENSION QS3.241 assembly supplies power to the device.
4 Product description
Figure4: G1 PULS DIMENSION QS3.241 assembly
4.5.2 Central processing unit
The CPU I assembly is the central computing unit for the device. It contains
the following interfaces:
▪ Internal system interface RS232 (COM1)
▪ Serial interface RS232/485 (COM2)
▪ 3x Ethernet (ETH1, ETH 2.1, ETH 2.2)
▪ USB (USB 2.0)
▪ 2x CAN bus (CAN 1, CAN 2)
Maschinenfabrik Reinhausen GmbH 2018245252433/02 ENECOTAP® VPD® CONTROL PRO
Page 25
4 Product description
Figure5: CPU I assembly
4.5.3 Voltage measurement and current measurement
The UI 3 assembly is used for measuring 3-phase voltage and current.
Figure6: UI 3 assembly
Maschinenfabrik Reinhausen GmbH 2018255252433/02 ENECOTAP® VPD® CONTROL PRO
Page 26
4.5.4 Voltage divider
The assembly VD001 is a voltage divider. The voltage divider reduces the
voltage of a three-phase measuring system to the permissible range of the
measuring assembly.
4 Product description
Figure7: Voltage divider VD001
4.5.5 Media converter
The MC 2-2 assembly is a media converter, which converts 2 electrical connections (RJ45) to one fiber-optic cable connection each. Each is converted
independently of the other. The following interfaces are available:
The following redundancy functions are available to you according to your
order:
▪ PRP (standard setting)
▪ RSTP
Maschinenfabrik Reinhausen GmbH 2018275252433/02 ENECOTAP® VPD® CONTROL PRO
Page 28
Figure9: SW 3-3 assembly
4 Product description
4.6 Additional operating controls and display elements when
using the MControl touch panel (optional)
If you are using the device with the optionally available MControl touch
panel, additional operating controls and display elements are displayed on
the left edge of the screen
Figure10: Additional display elements and operating controls
StatusLED statusStatus display
REMOTE keySelect the operating mode:
1)
▪ On: REMOTE
▪ Off: LOCAL
AVR AUTO keyActivate auto mode.
Maschinenfabrik Reinhausen GmbH 2018285252433/02 ENECOTAP® VPD® CONTROL PRO
Page 29
4 Product description
RAISE keySend a control command to the motor-drive
unit to increase the voltage. Only possible in
manual mode.
AVR Manual keyActivate manual mode.
LOWER keySend a control command to the motor-drive
unit to reduce the voltage. Only possible in
manual mode.
1)
Not available if local/remote is toggled using a digital input.
Maschinenfabrik Reinhausen GmbH 2018295252433/02 ENECOTAP® VPD® CONTROL PRO
Page 30
5 Packaging, transport and storage
5 Packaging, transport and storage
5.1 Packaging, transport and storage
5.1.1 Suitability, structure and production
The goods are packaged in a sturdy cardboard box. This ensures that the
shipment is secure when in the intended transportation position and that
none of its parts touch the loading surface of the means of transport or touch
the ground after unloading.
The box is designed for a maximum load of 10kg.
Inlays inside the box stabilize the goods, preventing impermissible changes
of position, and protect them from vibration.
5.1.2 Markings
The packaging bears a signature with instructions for safe transport and correct storage. The following symbols apply to the shipment of non-hazardous
goods. Adherence to these symbols is mandatory.
Protect against
moisture
Table7: Shipping pictograms
TopFragileAttach lifting
gear here
Center of mass
5.2 Transportation, receipt and handling of shipments
In addition to oscillation stress, jolts must also be expected during transportation. In order to prevent possible damage, avoid dropping, tipping,
knocking over and colliding with the product.
If a crate tips over, falls from a certain height (e.g. when slings tear) or is
subject to an unbroken fall, damage must be expected regardless of the
weight.
Every delivered shipment must be checked for the following by the recipient
before acceptance (acknowledgment of receipt):
▪ Completeness based on the delivery slip
▪ External damage of any type
The checks must take place after unloading when the crate or transport container can be accessed from all sides.
Maschinenfabrik Reinhausen GmbH 2018305252433/02 ENECOTAP® VPD® CONTROL PRO
Page 31
5 Packaging, transport and storage
Visible damage If external transport damage is detected on receipt of the shipment, proceed
as follows:
▪ Immediately record the transport damage found in the shipping docu-
ments and have this countersigned by the carrier.
▪ In the event of severe damage, total loss or high damage costs, immedi-
ately notify the sales department at Maschinenfabrik Reinhausen and the
relevant insurance company.
▪ After identifying damage, do not modify the condition of the shipment fur-
ther and retain the packaging material until an inspection decision has
been made by the transport company or the insurance company.
▪ Record the details of the damage immediately onsite together with the
carrier involved. This is essential for any claim for damages!
▪ If possible, photograph damage to packaging and packaged goods. This
also applies to signs of corrosion on the packaged goods due to moisture
inside the packaging (rain, snow, condensation).
▪ Be absolutely sure to also check the sealed packaging.
Hidden damage When damages are not determined until unpacking after receipt of the ship-
ment (hidden damage), proceed as follows:
▪ Make the party responsible for the damage liable as soon as possible by
telephone and in writing, and prepare a damage report.
▪ Observe the time periods applicable to such actions in the respective
country. Inquire about these in good time.
With hidden damage, it is very hard to make the transportation company (or
other responsible party) liable. Any insurance claims for such damages can
only be successful if relevant provisions are expressly included in the insurance terms and conditions.
5.3 Storage of shipments
When selecting and setting up the storage location, ensure the following:
▪ Protect stored goods against moisture (flooding, water from melting snow
and ice), dirt, pests such as rats, mice, termites and so on, and against
unauthorized access.
▪ Store the crates on timber beams and planks as a protection against ris-
ing damp and for better ventilation.
▪ Ensure sufficient carrying capacity of the ground.
▪ Keep entrance paths free.
▪ Check stored goods at regular intervals. Also take appropriate action after
storms, heavy rain or snow and so on.
Maschinenfabrik Reinhausen GmbH 2018315252433/02 ENECOTAP® VPD® CONTROL PRO
Page 32
6 Mounting
6 Mounting
The following description does not apply if you have ordered the device version with control cabinet. If that is the case, follow the description in the
ECOTAP VPD MD&C operating instructions.
This chapter describes how to correctly install and connect the device. Observe the connection diagrams provided.
DANGER
WARNING
NOTICE
Electric shock!
Risk of fatal injury due to electrical voltage. Always observe the following
safety regulations when working in or on electrical equipment.
► Disconnect the equipment.
► Lock the equipment to prevent an unintentional restart.
► Make sure all poles are de-energized.
► Ground and short-circuit.
► Cover or cordon off adjacent energized parts.
Electric shock!
Dangerous high voltages may occur when a current transformer is operated
with an open secondary circuit. This can lead to death, injuries and property
damage.
► Never operate a current transformer with an open secondary circuit;
short-circuit the current transformer to prevent this.
► Observe the information in the current transformer operating instructions.
Damage to the device!
Electrostatic discharge may cause damage to the device.
► Take precautionary measures to prevent the build-up of electrostatic
charges on work surfaces and personnel.
6.1 Electromagnetic compatibility
The device has been developed in accordance with applicable EMC standards. The following points must be noted in order to maintain the EMC
standards.
6.1.1 Wiring requirement of installation site
Note the following when selecting the installation site:
▪ The system's overvoltage protection must be effective.
▪ The system's ground connection must comply with all technical regula-
tions.
Maschinenfabrik Reinhausen GmbH 2018325252433/02 ENECOTAP® VPD® CONTROL PRO
Page 33
6 Mounting
▪ Separate system parts must be joined by a potential equalization.
▪ The device and its wiring must be at least 10m away from circuit-break-
ers, load disconnectors and busbars.
6.1.2 Wiring requirement of operating site
Note the following when wiring the operating site:
▪ Route the connecting leads in grounded metal cable ducts.
▪ Do not route lines which cause interference (e.g. power lines) and lines
susceptible to interference (e.g. signal lines) in the same cable duct.
▪ Maintain a distance of more than 100 mm between lines which cause in-
terference and those which are susceptible to interference.
Figure11: Recommended wiring
1 Cable duct for lines causing inter-
ference
2 Line causing interference (e.g.
power line)
3 Cable duct for lines susceptible to
interference
4 Line susceptible to interference
(e.g. signal line)
▪ Short-circuit and ground reserve lines.
▪ Never connect the device with a multi-wire collective pipe.
▪ For signal transmission, use shielded lines with individual conductors (out-
going conductor / return conductor) twisted in pairs.
▪ Connect full surface of shielding (360º) to device or to a nearby grounding
bar.
Using single conductors may limit the effectiveness of the shielding. Connect close-fitting shielding to cover all areas.
Maschinenfabrik Reinhausen GmbH 2018335252433/02 ENECOTAP® VPD® CONTROL PRO
Page 34
Figure12: Recommended connection of the shielding
6 Mounting
1 Connection of the shielding via a
single conductor
2 Full-surface connection of the
6.1.3 Wiring requirement in control cabinet
Note the following when wiring the control cabinet:
▪ The control cabinet where the device will be installed must be prepared in
accordance with EMC requirements:
– Functional division of control cabinet (physical separation)
– Constant potential equalization (all metal parts are joined)
– Line routing in accordance with EMC requirements (separation of lines
which cause interference and those susceptible to interference)
– Optimum shielding (metal housing)
– Overvoltage protection (lightning protection)
– Collective grounding (main grounding rail)
– Cable bushings in accordance with EMC requirements
– Any contactor coils present must be interconnected
▪ The device's connection cables must be laid in close contact with the
grounded metal housing or in metallic cable ducts with a ground connection.
▪ Signal lines and power lines/switching lines must be laid in separate cable
ducts.
shielding
6.1.4 Information about shielding the CAN bus
In order for the CAN bus to operate faultlessly, you have to connect the
shielding using one of the following variants. If you are not able to use any of
the variants detailed below, we recommend using fiber-optic cables. Fiberoptic cables decouple the devices and are not sensitive to electromagnetic
interference (surge and burst).
Maschinenfabrik Reinhausen GmbH 2018345252433/02 ENECOTAP® VPD® CONTROL PRO
Page 35
6 Mounting
NOTICE
Damage to the device!
If you connect the CAN bus cable to devices with different potentials, current may flow across the shielding. This current may damage the device.
► Connect the devices to a potential equalization rail to equalize the poten-
tial.
► If both devices have different potentials, only connect the CAN bus cable
shielding to one device.
Variant 1: The connected devices share the same potential
If the devices to be connected share the same potential, proceed as follows:
1. Connect all devices to a potential equalization rail to equalize the poten-
tial.
2. Connect the CAN bus cable shielding to all connected devices.
Variant 2: The connected devices have different potentials
Note that the shielding is less effective with this variant.
If the devices to be connected have different potentials, proceed as follows:
► Connect the CAN bus cable shielding to just one device.
NOTICE
Connecting shielding
Connect the shielding for the CAN bus cable to the 9-pin D-sub connector:
Figure13: Connection of CAN bus cable shielding to the 9-pin D-sub connector
6.2 Minimum distances
Damage to the device!
Insufficient circulation of ambient air can result in damage to the device due
to overheating.
► Keep the ventilation slots clear.
► Ensure sufficient distance to neighboring components.
► Only mount device in horizontal position (ventilation slots are at the top
and bottom).
Maschinenfabrik Reinhausen GmbH 2018355252433/02 ENECOTAP® VPD® CONTROL PRO
Page 36
6 Mounting
Reliable operation of the device in the permitted temperature range requires
that you maintain the following minimum distances to the control cabinet and
to neighboring components:
Minimum distance
To the floor of the control cabinet88.9 mm (3.5 in)
To the roof of the control cabinet
Between assemblies on the bus bar and assem-
blies on the remote cap rail
Table8: Minimum distances in the control cabinet
Corresponds to 2 RU
Figure14: Example depiction of the minimum distances in a control cabinet
For other installation types, contact Maschinenfabrik Reinhausen GmbH.
6.3 Mounting location
In order to ensure safe operation of the device, the device must be mounted
in an enclosure or control cabinet that has the following properties:
▪ Protection against mechanical influences
▪ Assurance of permissible ambient conditions (see Technical data [►Sec-
tion 12, Page 178] section)
6.4 Mounting the device
You can mount the device in one of the variants described below:
▪ Mounting the device using the cap rail included in delivery
▪ Mounting the device on an alternative cap rail
Observe the following sections when doing so.
Maschinenfabrik Reinhausen GmbH 2018365252433/02 ENECOTAP® VPD® CONTROL PRO
Page 37
6 Mounting
6.4.1 Mounting the device using the cap rail included in delivery
The cap rail included in delivery has 3 mounting drill holes, which you can
use to fasten the cap rail to the rear panel of the switch cabinet. Before you
can begin mounting, you have to remove a part of the device.
Figure15: Overview of the partial removal of assemblies
Preparing the device for mounting
To prepare the device for mounting, proceed as follows:
1. Remove the plug for voltage measurement from the UI assembly.
Figure16: Removing the plug for voltage measurement
Maschinenfabrik Reinhausen GmbH 2018375252433/02 ENECOTAP® VPD® CONTROL PRO
Page 38
2. Remove the "24V DC" plug from the CPU assembly.
6 Mounting
Figure17: Removing the plug (voltage supply)
3. If the device is equipped with the SW3-3 or MC2-2 assembly: Remove the
"24V DC" plug from the SW3-3 or MC2-2 assembly.
Figure18: Removing the plug (voltage supply)
Maschinenfabrik Reinhausen GmbH 2018385252433/02 ENECOTAP® VPD® CONTROL PRO
Page 39
6 Mounting
4. If the device is equipped with the SW3-3 or MC2-2 assembly: Unhook the
SW3-3 or MC2-2 assembly.
Figure19: Unhooking the MC2-2 / SW3-3 assembly
5. Unhook the bus rail.
Figure20: Unhooking the bus rail
Maschinenfabrik Reinhausen GmbH 2018395252433/02 ENECOTAP® VPD® CONTROL PRO
Page 40
6 Mounting
Mounting the cap rail
To mount the cap rail, proceed as follows:
► Fasten the cap rail to the rear panel of the switch cabinet using screws
and contact washers or lock washers.
Figure21: Fastening the cap rail
Maschinenfabrik Reinhausen GmbH 2018405252433/02 ENECOTAP® VPD® CONTROL PRO
Page 41
6 Mounting
Mounting the device assemblies
To mount the device assemblies that had been previously removed, proceed
as follows:
1.WARNING! Mount the bus rail on the cap rail, ensuring that the bus
rail engages correctly. Otherwise, it can result in electric shock due to a
faulty connection to the protective ground.
Figure22: Hooking the bus rail into position
2.WARNING! Hook the optional SW3-3 or MC2-2 assembly into position
on the cap rail at the specified location, ensuring that the assembly engages correctly. Otherwise, it can result in electric shock due to a faulty
connection to the protective ground.
Maschinenfabrik Reinhausen GmbH 2018415252433/02 ENECOTAP® VPD® CONTROL PRO
Page 42
6 Mounting
3. If the device is equipped with the SW3-3 or MC2-2 assembly: Plug the
plug into the corresponding "24V DC" slot and screw it into place.
Figure23: Fastening the 24V DC plug
4. Connect the connection cable for connecting to ECOTAP VPD MD&C to
connection COM 2 on the CPU assembly.
5. Plug in the "24V DC" plug of the CPU assembly and screw it into place.
Figure24: Fastening the 24V DC plug
Maschinenfabrik Reinhausen GmbH 2018425252433/02 ENECOTAP® VPD® CONTROL PRO
Page 43
6 Mounting
6. Plug the UI assembly plugs into the corresponding slots and engage
them.
Figure25: Engaging the plug
6.4.2 Mounting the device on an alternative cap rail
As an alternative, you can mount the device onto a cap rail other than that
included in delivery. When doing so, note the following instructions.
6.4.2.1 Removing assemblies
If you would like to mount the device on an alternative cap rail, you must remove the individual assemblies from the cap rail included in delivery. When
doing so, observe the schematic in the connection diagram included in delivery.
Figure26: Overview of assembly removal
Maschinenfabrik Reinhausen GmbH 2018435252433/02 ENECOTAP® VPD® CONTROL PRO
Page 44
6 Mounting
Proceed as follows to remove the assemblies:
1. G1 QS3.241 assembly: Open the lever and remove the neutral conductor (N), phase conductor (L) and protective conductor .
Figure27: Removing the neutral conductor, phase conductor and protective conductor
Maschinenfabrik Reinhausen GmbH 2018445252433/02 ENECOTAP® VPD® CONTROL PRO
Page 45
6 Mounting
2. G1 QS3.241 assembly: Open the lever and remove the wiring .
Figure28: Removing the wiring
3. UI assembly: Remove the plug for voltage measurement.
Figure29: Voltage measurement
Maschinenfabrik Reinhausen GmbH 2018455252433/02 ENECOTAP® VPD® CONTROL PRO
Page 46
4. CPU assembly: Remove the "24V DC" plug.
6 Mounting
Figure30: Removing the plug (voltage supply)
5. CPU assembly: Remove the Ethernet cable.
Figure31: Removing the Ethernet cable
Maschinenfabrik Reinhausen GmbH 2018465252433/02 ENECOTAP® VPD® CONTROL PRO
Page 47
6 Mounting
6. CPU assembly: If necessary, remove the data cable (D-Sub 9-pole).
Figure32: Removing the data cable
7. SW3-3 assembly: Remove the "24V DC" plug.
Figure33: Removing the plug (voltage supply)
8. Unhook terminal X5 from the cap rail.
9. Unhook the G1 QS3.241 assembly from the cap rail.
10. Optional: Unhook the SW3-3 assembly from the cap rail.
11. Unhook the bus rail with the CPU I and UI 3 assemblies from the cap
rail.
Maschinenfabrik Reinhausen GmbH 2018475252433/02 ENECOTAP® VPD® CONTROL PRO
Page 48
12. Unhook the voltage divider VD001 from the cap rail.
13. Unhook terminals X1 and X10 from the cap rail.
6.4.2.2 Fastening the cap rail
The cap rail is required to mount a bus bar or a device's remote assemblies
in a control cabinet. Only use the following types of cap rails in accordance
with EN 60715:
▪ TH 35-7.5
▪ TH 35-15
The cap rail may not be painted or lacquered.
6 Mounting
WARNING
Electric shock!
Risk of fatal injury due to electrical voltage if the cap rail is not connected to
the protective ground.
► Connect the cap rail to the protective ground securely (e.g. with a protec-
tive conductor line-up terminal).
► Ensure that the cap rail is connected securely to the protective ground via
a ground test after installation.
► Fasten the cap rail to the rear panel of the switch cabinet using screws
and contact washers or lock washers. The distance between the screws
may be no more than 10 cm (3.94 in).
Figure34: Fastening the cap rail
Maschinenfabrik Reinhausen GmbH 2018485252433/02 ENECOTAP® VPD® CONTROL PRO
Page 49
6 Mounting
6.4.2.3 Mounting the assemblies
To mount the assemblies on the cap rail, proceed as follows:
1.WARNING! Mount the bus rail with the CPU and UI assemblies on the
cap rail, ensuring that the bus rail engages correctly. Otherwise, it can result in electric shock due to a faulty connection to the protective ground.
WARNING
Figure35: Hooking the bus rail into position
2. Optional: Hook the SW3-3 assembly into place on the cap rail.
3. Hook the G1 QS3.241 assembly into place on the cap rail.
4. Hook terminal X5 into place on the cap rail.
5. Hook the voltage divider VD001 into place on the cap rail.
6. Hook terminals X1 and X10 into place on the cap rail.
6.5 Connecting device
The following section describes how to establish the electrical connection to
the device.
Electric shock!
Connection errors can lead to death, injury or property damage.
► Ground the device with a protective conductor using the grounding screw
on the housing.
► Note the phase difference of the secondary terminals for the current
transformer and voltage transformer.
► Connect the output relays correctly to the motor-drive unit.
Maschinenfabrik Reinhausen GmbH 2018495252433/02 ENECOTAP® VPD® CONTROL PRO
Page 50
6 Mounting
Supply the voltage via separators and ensure that current paths can be
short circuited. Fit the separator, clearly labeled, close to the device's power
supply so that it is freely accessible. This ensures that the device can be replaced with ease in the event of a defect.
Wiring information
Note this procedure for the wiring:
ü To obtain a better overview when connecting cables, only use as many
leads as necessary.
ü Note the connection diagram.
ü Use only the specified cables for wiring. Note the cable recommendation.
ü Wire the leads to the system periphery [►Section 6.5.4, Page 51].
1. Strip insulation from leads and wires.
2. Crimp stranded wires with wire end sleeves.
6.5.1 Cable recommendation
Please note the following Maschinenfabrik Reinhausen recommendation
when wiring the device.
If you want to route Ethernet connections from a control cabinet or building,
we recommend the use of fiber-optic cables (in accordance with the IEC
61850-90-4 recommendation).
CableAssemblyCable typeConductor cross-sec-
tion
Power supply (external)X1Unshielded1.5 mm²Power supply (internal, 24
VDC)
Voltage measurementX10Shielded2.5 mm²Current measurementUI 3Unshielded4 mm²RS485 SUB-DCPU I COM2Shielded, pin assign-
CAN busCPU I CAN2Shielded0.75 mm²2,000 m (total CAN bus)
Ethernet RJ45CPU IMin. CAT5, shielded
Ethernet FOMC2-2, SW3-3 Duplex LC
Table9: Recommendation for connection cables
CPU I, MC2-2,
SW3-3
Unshielded1.5mm²-
0.25 mm
ment 1:1
-100 m
S/FTP
-2000 m
Multimode, OM3,
1310 nm
2
Max. length
140 m
Maschinenfabrik Reinhausen GmbH 2018505252433/02 ENECOTAP® VPD® CONTROL PRO
Page 51
6 Mounting
6.5.2 Information about laying fiber-optic cable
To ensure the smooth transfer of data via the fiber-optic cable, you must ensure that mechanical loads are avoided when laying the fiber-optic cable and
later on during operation. Also observe the information from the manufacturer of the fiber-optic cable and the following instructions:
▪ Radii must not fall below the minimum permissible bend radii (do not bend
fiber-optic cable).
▪ The fiber-optic cables must not be over-stretched or crushed. Observe the
permissible load values.
▪ The fiber-optic cables must not be twisted.
▪ Be aware of sharp edges because they can damage the fiber-optic cable's
coating during laying or can place mechanical loads on the coating later
on.
▪ Provide a sufficient cable reserve near distributor cabinets. Lay the re-
serve such that the fiber-optic cable is neither bent nor twisted when tight-
ened.
6.5.3 Mounting terminating resistor of CAN bus
If you want to operate the device in parallel operation, you need to mount a
120 Ω terminating resistor at both ends of the CAN bus. Use the plug connector with terminating resistor provided as an option.
Figure36: Terminating resistor of CAN bus
6.5.4 Connecting cables to the system periphery
To obtain a better overview when connecting cables, only use as many
leads as necessary.
Maschinenfabrik Reinhausen GmbH 2018515252433/02 ENECOTAP® VPD® CONTROL PRO
Page 52
To connect cables to the system periphery, proceed as follows:
ü Use only the specified cables for wiring. Note the cable recommendation.
► Connect the lines to be wired to the device to the system periphery as
shown in the connection diagrams supplied.
6.5.5 Wiring the CPU I assembly
6 Mounting
NOTICE
Damage to the device
Assigning the connection cable pins for the COM 2 interface incorrectly can
result in the device being damaged.
► Use the connection cable provided.
► Alternative: Use a connection cable in accordance with the cable recom-
mendation [►Section 6.5.1, Page 50].
1. Connect the COM 2 interface (D-Sub 9-pole) to the ECOTAP VPD CONTROL in accordance with the connection diagram.
Figure37: ECOTAP VPD CONTROL connection via COM 2 interface
Maschinenfabrik Reinhausen GmbH 2018525252433/02 ENECOTAP® VPD® CONTROL PRO
Page 53
6 Mounting
2. Connect the ETH 2.2 interface to a PC for accessing the web-based visualization.
Figure38: Connection to a computer via Ethernet interface
Maschinenfabrik Reinhausen GmbH 2018535252433/02 ENECOTAP® VPD® CONTROL PRO
Page 54
6 Mounting
3. Optional: Connect the ETH 1 interface to the control system (SCADA) in
accordance with the connection diagram.
NOTICE
Figure39: SCADA connection
6.5.6 Wiring the UI assembly
Damage to the device due to incorrect current transformer connection
Connecting a grounded current transformer can lead to inadmissibly high
EMC loads, causing damage to the UI assembly.
► Do not ground the current transformer.
Maschinenfabrik Reinhausen GmbH 2018545252433/02 ENECOTAP® VPD® CONTROL PRO
Page 55
6 Mounting
To wire the UI assembly, proceed as follows:
1. Insert the leads into the respective current measurement plug terminals
and fasten using a screwdriver.
Figure40: Example: Current measurement plug
2. Plug the plug into the corresponding slot and engage the plug.
3. Connect the voltage measurement leads to terminal X10.
Maschinenfabrik Reinhausen GmbH 2018555252433/02 ENECOTAP® VPD® CONTROL PRO
Page 56
6.5.7 Wiring the MC 2-2/SW3-3 assembly
1. Insert the supplied SFP module into the corresponding Ethernet interface
in accordance with the connection diagram and fold the clasp down.
6 Mounting
Figure41: Engaging the SFP module
2. Remove the SFP module dust plug.
Figure42: Removing the dust plug
Maschinenfabrik Reinhausen GmbH 2018565252433/02 ENECOTAP® VPD® CONTROL PRO
Page 57
6 Mounting
3. Insert the fiber-optic cable into the SFP module.
Figure43: Inserting the fiber-optic cable
4. Insert the network cable.
Figure44: Inserting the network cable
6.5.8 Connecting the power supply
You may only connect the device to circuits with an external overcurrent protection device and an all-pole isolating device, enabling the equipment to be
fully de-energized if required (service, maintenance etc.).
Maschinenfabrik Reinhausen GmbH 2018575252433/02 ENECOTAP® VPD® CONTROL PRO
Page 58
6 Mounting
Suitable equipment includes isolating devices in accordance with IEC
60947-1 and IEC 60947-3 (e.g. circuit breaker). Note the properties of the
relevant circuits (voltage, maximum currents) when selecting the circuit
breaker type. In addition, observe the following:
▪ It must be easy for the operator to access the isolating device
▪ The isolating device must be labeled for the device and circuits to be iso-
lated
▪ The isolating device may not be a part of the power line
▪ The isolating device may not interrupt the main protective conductor
Miniature circuit breaker You must fuse the power supply circuit with a miniature circuit breaker. The
miniature circuit breaker must have the following properties:
▪ Rated current: 6 to 20 A
▪ Triggering characteristic: B or C
Conductor cross-section For the power supply circuit, use a conductor cross-section suitable for the
miniature circuit breaker that you have selected, but at least 1.5mm2 (AWG
15).
Connecting the voltage supply
To connect the voltage supply, proceed as follows:
► Connect the voltage supply in accordance with the connection diagram
provided.
Maschinenfabrik Reinhausen GmbH 2018585252433/02 ENECOTAP® VPD® CONTROL PRO
Page 59
7 Commissioning
7 Commissioning
This chapter describes how to commission the device.
NOTICE
Damage to device and system periphery
An incorrectly connected device can lead to damages in the device and system periphery.
► Check the entire configuration before commissioning.
► Prior to commissioning, be sure to check the actual voltage and operating
voltage.
7.1 Performing tests
The following description does not apply if you have ordered the device version with control cabinet. If that is the case, follow the description in the
ECOTAP VPD MD&C operating instructions.
Please contact Maschinenfabrik Reinhausen GmbH (MR) if any aspect of
the tests is not clear.
7.1.1 Ground test
For commissioning, carry out a ground test (check of the protective bonding
impedance) in accordance with IEC 61010-1. Observe the following information when testing:
▪ Test current: 2 times the rated current of the overcurrent protection device
in the supply line.
▪ Test duration: 1 minute for each measurement point.
▪ The measured voltage between the measurement point and the protective
conductor must be less than 10V.
To carry out the ground test, proceed as follows:
► Apply the test current at the grounding terminal of the G1 PULS DIMEN-
SION QS3.241 assembly using a constant current source and measure
the voltage between the measurement point and the protective conductor.
ð The measured voltage must remain less than 10V for a period of 1
minute.
Maschinenfabrik Reinhausen GmbH 2018595252433/02 ENECOTAP® VPD® CONTROL PRO
Page 60
7 Commissioning
Figure45: Perform a ground test on the G1 PULS DIMENSION QS3.241 assembly
7.1.2 Performing a dielectric test
The device is tested before delivery. Note the following points if you would
like to perform a dielectric test:
NOTICE
AssemblyInterfacesTest parameters
UI 3N, L1, L2, L3
k1, l1, k2, l2, k3, l32.2 kV AC2 s5s
G1 (PULS)N, L> 4 mA
Table10: Permitted interfaces and test parameters for the dielectric test
Damage to the device!
A dielectric test with a test voltage that is greater than the maximum permitted test voltage can lead to the device being damaged.
► Perform the dielectric test with a test voltage that is less than or equal to
the maximum permitted test voltage.
► Perform the dielectric test using the permitted interfaces only.
Depending on the device configuration, you may only test the assemblies
listed below. You may not test any other assemblies.
Max. test voltageMax. test dura-
tion
RampBreaking current
threshold
> 4 mA
Maschinenfabrik Reinhausen GmbH 2018605252433/02 ENECOTAP® VPD® CONTROL PRO
Page 61
7 Commissioning
Sample dielectric test set-up
Figure46: Sample dielectric test set-up for a device designed with the G1 (PULS) power supply
7.2 Establishing connection to visualization
The device is supplied with the IP address 192.0.1.230 at the factory.
Maschinenfabrik Reinhausen GmbH 2018615252433/02 ENECOTAP® VPD® CONTROL PRO
Page 62
7 Commissioning
To connect via the ETH2.2 interface on the CPU assembly, proceed as follows:
1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the
ETH2.2 interface.
Figure47: Establishing a connection via the ETH2.2 interface
2. Assign a unique IP address to the PC in the same subnet as the device
(e.g. 192.0.1.100).
3. Enter the visualization's IP address (e.g. http://192.0.1.230, if SSL
encryption is active enter https://192.0.1.230) on the PC in the
browser.
ð The visualization has been accessed.
7.3 Setting parameters
Commissioning the device requires setting some parameters. There are 2
options available for this:
▪ Commissioning wizard
▪ Setting the parameters manually
7.3.1 Commissioning wizard
If you want the device to help when setting the relevant parameters, you can
use the commissioning wizard. The commissioning wizard provides a selection of parameters that you can configure in order.
A detailed description of each of the parameters can be found in the Operation [►Section 8, Page 66] chapter.
Maschinenfabrik Reinhausen GmbH 2018625252433/02 ENECOTAP® VPD® CONTROL PRO
Page 63
7 Commissioning
To call up the commissioning wizard, you will need the necessary access
rights [►Section 8.13, Page 145].
When in delivery status, you can log in as the administrator as follows:
▪ User name: admin
▪ Password: admin
To set the parameters with the help of the commissioning wizard, proceed
as follows:
1. Log in as a user with the necessary access rights.
2. Go to Settings > Commissioning wizard.
Figure48: Calling up the commissioning wizard
3. Press the Next button to launch the commissioning wizard.
4. Follow the on-screen instructions.
Once you have entered all of the parameters relevant to commissioning,
continue with the function test.
7.3.2 Setting the parameters manually
To commission the device, you must set the following parameters. You will
find more detailed information about these parameters in the respective sections.
To set the parameters, you need the necessary access rights [►Section
8.13, Page 145].
Maschinenfabrik Reinhausen GmbH 2018635252433/02 ENECOTAP® VPD® CONTROL PRO
Page 64
When in delivery status, you can log in as the administrator as follows:
▪ User name: admin
▪ Password: admin
7.3.2.1 Setting the language
You can use this parameter to set the display language for the device. The
device comes with a maximum of 4 languages. The following languages are
available:
2. Select the language you want from the list box.
3. Press the Accept button to save the modified parameter.
ð The "Restart device" dialog appears.
4. Restart the device to apply the changed language setting.
7.3.2.2 Setting date and time
You can set the date and time in the following ways:
▪ Manually
▪ Time synchronization via control system (SCADA)
▪ Time synchronization via SNTP time server
If you are using a control system, the device automatically synchronizes the
date and time with the control system. If you would like to use an SNTP time
server, you must set the required parameters. When doing so, observe the
information provided in the Time synchronization [►Section 8.12, Page 142]
section.
If you would like to set the date and time manually, you must enter the values in the following formats:
DateTime
DD.MM.YYYYHH:MM
Table11: Formats
Maschinenfabrik Reinhausen GmbH 2018645252433/02 ENECOTAP® VPD® CONTROL PRO
Page 65
7 Commissioning
The time does not switch from daylight saving time to standard time and
back automatically.
Proceed as follows to set the date and time manually:
1. Go to Settings > Time.
Figure50: Setting date and time
2. Enter date and time.
3. Press the Accept button to save the modified parameter.
7.3.2.3 Setting further parameters
Set further parameters to commission the device. You will find more detailed
information about the respective parameters in the Operation [►Section 8,
Page 66] chapter.
1. Activate ECOTAP VPD communication [►Section 8.3, Page 70].
2. Set transformer data [►Section 8.5, Page 81].
3. Set control parameters [►Section 8.4, Page 71].
4. Set control system protocol (optional) [►Section 8.11, Page 119].
Maschinenfabrik Reinhausen GmbH 2018655252433/02 ENECOTAP® VPD® CONTROL PRO
Page 66
8 Operation
This chapter describes all the functions and setting options for the device.
8.1 Establishing connection to visualization
The device is supplied with the IP address 192.0.1.230 at the factory.
To connect via the ETH2.2 interface on the CPU assembly, proceed as follows:
1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the
ETH2.2 interface.
8 Operation
Figure51: Establishing a connection via the ETH2.2 interface
2. Assign a unique IP address to the PC in the same subnet as the device
(e.g. 192.0.1.100).
3. Enter the visualization's IP address (e.g. http://192.0.1.230, if SSL
encryption is active enter https://192.0.1.230) on the PC in the
browser.
ð The visualization has been accessed.
8.2 General
You can set general parameters in this menu item:
Maschinenfabrik Reinhausen GmbH 2018665252433/02 ENECOTAP® VPD® CONTROL PRO
Page 67
8 Operation
General settings
▪ Display language for the device
– Can also be set via the status bar [►Section 7.3.2.1, Page 64]
▪ Activate/deactivate launching the commissioning wizard after the device is
restarted
▪ Measured value display
▪ Transformer name
▪ Remote behavior
8.2.1 Activating/deactivating automatic launch of commissioning
wizard
You can use this parameter to set whether the commissioning wizard
[►Section 7.3.1, Page 62] is to launch automatically when the device is
restarted.
1. Go to Settings > Parameters > General > Commissioning wizard.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
8.2.2 Setting measured value display
This parameter lets you set whether the displayed measured values and
control parameters are to refer to the primary side or secondary side.
Maschinenfabrik Reinhausen GmbH 2018675252433/02 ENECOTAP® VPD® CONTROL PRO
Page 68
To set the measurement transformer display, proceed as follows:
1. Go to Settings > Parameters > General > Measured value display.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
8.2.3 Remote behavior
You can use this parameter to select the behavior of the device in remote
operating mode. You can select the following options:
OptionDescription
Hardware onlyNo function.
SCADA onlyThe device accepts commands via SCADA.
Hardware and SCADAThe device accepts commands via SCADA.
Table12: Selecting Remote behavior
To set the Remote behavior, proceed as follows:
1. Go to Settings > Parameters > General > Remote behavior.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
8 Operation
8.2.4 Visualization
The device is equipped with a web-based visualization. This allows you to
configure the device with a computer and to display measured values.
You can establish a link to the visualization via the ETH2.2 interface on the
CPU assembly (for access via remote display, control center etc.).
System requirements
To access the web-based visualization, you need a PC with an HTML5-capable browser. The display is optimized for the following browsers:
▪ Microsoft® Internet Explorer 10 or higher
▪ Google Chrome™
To establish a connection to the visualization, please observe the following
sections.
8.2.4.1 Configuring visualization
You can use the following parameters to configure the interface for the visualization. The following parameters are available:
▪ IP address
▪ Subnet mask
Maschinenfabrik Reinhausen GmbH 2018685252433/02 ENECOTAP® VPD® CONTROL PRO
Page 69
8 Operation
▪ Gateway address
▪ SSL encryption
IP address, subnet mask and gateway address
You can use these parameters to undertake the network configuration for
the visualization. These settings apply to access via the ETH2.2 interface on
the CPU module.
Assign IP addresses to both web-based visualization and SCADA (optional)
in different subnets. Otherwise you will not be able to establish a connection.
1. Go to Settings > Parameters > General > IP address, Subnet mask or
Gateway.
2. Enter the desired value.
3. Press the Accept button to save the modified parameter.
Activating SSL/TLS encryption
You can use this parameter to set whether access to the visualization should
take place over an SSL-encrypted connection.
To activate SSL encryption, proceed as follows:
1. Go to Settings > Parameters > General > SSL/TLS encryption.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
Setting the TLS version
You can use this parameter to set the accepted TLS versions. If you would
like to establish an encrypted connection to the visualization, you must use
an accepted TLS version. You can select the following options:
OptionAccepted TLS versions
>= 1.0▪ 1.0
▪ 1.1
▪ 1.2
>= 1.1▪ 1.1
▪ 1.2
1)
>= 1.2
Table13: TLS version
▪ 1.2
1)
This option can be selected only if the TLS versions are supported by the
connected peripheral equipment.
To set the TLS version, proceed as follows:
1. Go to Settings > Parameters > General > TLS version.
Maschinenfabrik Reinhausen GmbH 2018695252433/02 ENECOTAP® VPD® CONTROL PRO
Page 70
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
8.2.4.2 Accessing online help
The web-based visualization has an online help section. To call up the online
help, proceed as follows:
1. Call up the web-based visualization with the PC.
2. Select the MR logo in the status line.
ð The online help appears.
8.2.5 Activating/deactivating the USB interface
This parameter lets you deactivate the USB interface. You can select the following options:
▪ On: USB interface is activated
▪ Off: USB interface is deactivated
8 Operation
Proceed as follows to activate/deactivate the USB interface:
1. Go to Settings > Parameters > General > USB interface.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
8.3 Unlocking ECOTAP VPD communication
With an ECOTAP Pro, you can unlock communication to an ECOTAP VPD
Control a maximum of three times. The number of remaining unlocking actions is displayed in the dialog window.
Figure53: Unlocking ECOTAP VPD communication
Maschinenfabrik Reinhausen GmbH 2018705252433/02 ENECOTAP® VPD® CONTROL PRO
Page 71
8 Operation
Proceed as follows to unlock communication between the ECOTAP VPD
Control and ECOTAP Pro:
ü There is a connection between the ECOTAP VPD Control and ECOTAP
Pro.
1. Go to Settings > ECOTAP VPD Comm..
2. Press the Continue button to unlock communication with the connected
ECOTAP VPD Control.
8.4 Control
All of the parameters required for the regulation function are described in this
section.
Figure54: Setting the control parameters (example)
8.4.1 Setting the desired value
In accordance with the order, the device is equipped with one of the following variants for setting the desired value:
8.4.1.1 Desired value 1
You have to set the parameters for both winding 1 (W1) and winding 2
(W2).
To set the desired value, proceed as follows:
1. Go to Settings > Parameters > Control > Desired value.
2. Enter desired value.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 2018715252433/02 ENECOTAP® VPD® CONTROL PRO
Page 72
8 Operation
8.4.1.2 Active power-dependent adjustment of desired voltage value
The TAPCON® Dynamic Setpoint Control (TDSC) function is used to adapt
the desired voltage value depending on the measured active power. This allows you to compensate for a voltage drop during increased load or a voltage increase due to a decentralized feed-in.
Depending on whether positive or negative active power is measured, the
desired value calculation is based on 2 linear equations (see example in diagram below).
ParameterFunctionSettings (see diagram
below)
U
: Maximum desired valueMaximum set desired value is activated when P
max
exceeded.
U
: Minimum desired valueMinimum set desired value is activated when value falls
min
U0: Desired value at 0 active
power
P
: Active power at max. de-
max
sired value
P
: Active power at min. desired
min
value
Table14: Parameters to be set for active power-dependent adjustment of desired voltage value
below P
min
.
Set desired value is activated when measured active
power is 0MW.
Set maximum active power value above which the
power-dependent desired value is to attain the maximum value U
max
.
Set minimum active power value below which the
power-dependent desired value is to attain the minimum value U
min
.
max
is
103.0 V
99.0 V
100.00 V
20.0 MW
-20.0 MW
Figure55: Active power-dependent adjustment of desired voltage value
U
ref
P
meas
Desired valueU
Measured active powerU
min
max
Minimum desired value
Maximum desired value
Maschinenfabrik Reinhausen GmbH 2018725252433/02 ENECOTAP® VPD® CONTROL PRO
Page 73
8 Operation
P
min
P
max
Active power at minimum desired value
Active power at maximum de-
U
0
Set desired value when measured active power = 0
sired value
Response to active power P
If the measured active power P
U
is adopted as the desired value.
max
being exceeded
max
exceeds the set parameter P
meas
Response to value falling below active power P
If the measured active power P
value U
is adopted as the desired value.
min
Response to a measured active power P
falls below the set parameter P
meas
= 0 MW:
meas
min
, the value
max
, the
min
If the measured active power P
= 0, the set parameter U0 is adopted.
meas
Linear dependency with negative active power:
If the measured active power P
min
≤ P
≤ 0, the desired value is calculated
meas
using the following formula:
Linear dependency with positive active power:
If the measured active power 0 ≤ P
meas
≤ P
, the desired value is calculated
max
using the following formula:
Maschinenfabrik Reinhausen GmbH 2018735252433/02 ENECOTAP® VPD® CONTROL PRO
Page 74
8 Operation
To activate the active power-dependent adjustment of the desired voltage
value, you need to set the following parameters:
You have to set the parameters for both winding 1 (W1) and winding 2
(W2).
Activating TDSC
The TDSC function is only active when the device can calculate the active
power (correct current measurement and voltage measurement) and the required parameters are set. If this is not the case, voltage regulation is in accordance with the set desired value [►Section 8.4.1.1, Page 71]. You can
activate or deactivate the power-dependent adjustment of the desired voltage value as follows:
▪ Parameters
▪ Control system command (optional)
If you activate TDSC, the line drop compensation (R&X compensation or Z
compensation) function is deactivated.
To activate/deactivate TDSC using parameters, proceed as follows:
1. Go to Settings > Parameters > Control > Activate TDSC.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
TDSC Umax/Umin
You can use these parameters to set the maximum and minimum desired
value. The maximum or minimum desired value is activated when the measured active power reaches the set minimum or maximum active power.
1. Go to Settings > Parameters > Control > TDSC Umax/Umin.
2. Enter maximum/minimum desired value.
3. Press the Accept button to save the modified parameter.
TDSC U0
You can use this parameter to set the desired value which is to be used
when the measured active power is 0.
1. Go to Settings > Parameter > Control > TDSC U0.
2. Enter desired value at active power 0.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 2018745252433/02 ENECOTAP® VPD® CONTROL PRO
Page 75
8 Operation
TDSC Pmax/Pmin
You can use these parameters to set the maximum and minimum active
power value at which the maximum and minimum active power-dependent
desired value is to be used for regulation.
1. Go to Settings > Parameters > Control > TDSC Pmax/Pmin.
2. Enter active power for maximum/minimum desired value.
3. Press the Accept button to save the modified parameter.
8.4.2 Bandwidth
You can use this parameter to set the maximum permissible deviation in
measured voltage U
describes how you determine and set the bandwidth.
Determining bandwidth
In order to set the correct value, the transformer's step voltage and nominal
voltage must be known. Note that a large bandwidth will result in a large
control deviation.
from the desired value U
actual
. The following section
desired
The bandwidth must always be greater than the following value:
Figure56: Calculation of minimum bandwidth
U
n-1
U
n
U
nom
Step voltage of tap position n-1
Step voltage of tap position n
Nominal voltage
The following transformer values are used to determine the minimum bandwidth:
Nominal voltage U
Step voltage in tap position 4 U
Step voltage in tap position 5 U
= 11,000 V
nom
= 11,275 V
Step4
= 11,000 V
Step5
Maschinenfabrik Reinhausen GmbH 2018755252433/02 ENECOTAP® VPD® CONTROL PRO
Page 76
Setting the bandwidth
To set the bandwidth, proceed as follows:
1. Go to Settings > Parameters > Control > Bandwidth.
2. Enter bandwidth.
3. Press the Accept button to save the modified parameter.
8.4.3 Delay time T1
Delay time T1 delays the issuing of a tap-change command for a defined period. This prevents unnecessary tap-change operations if the tolerance
bandwidth is exited briefly.
Behavior only with delay time T1
8 Operation
If the measured voltage U
is within the set bandwidth , no control
actual
commands are issued to the motor-drive unit for the tap-change operation.
Control commands will also not be issued to the motor-drive unit if the mea-
sured voltage returns to the tolerance bandwidth within the set delay time
T1 . However, if the measured voltage deviates from the set bandwidth for
a long period , a tap-change command occurs after expiration of the
set delay time T1. The on-load tap-changer carries out a tap-change in a
raise or lower direction to return to the tolerance bandwidth.
Figure57: Behavior of the regulation function with delay time T1
1 +B%: Upper limit4 Set delay time T1
2 U
3 -B%: Lower limit6 B%: Tolerance bandwidth
: Desired value5 U
desired
: Measured voltage
actual
Maschinenfabrik Reinhausen GmbH 2018765252433/02 ENECOTAP® VPD® CONTROL PRO
Page 77
8 Operation
A U
C U
is outside the bandwidth. De-
actual
lay time T1 starts.
is outside the bandwidth. De-
actual
lay time T1 starts.
B U
is within the bandwidth be-
actual
fore delay time T1 is complete.
D U
is still outside the bandwidth
actual
when delay time T1 is complete.
Tap-change operation is initiated.
Setting delay time T1
To set the delay time T1, proceed as follows:
1. Go to Settings > Parameters > Control > Delay time T1.
2. Enter delay time T1.
3. Press the Accept button to save the modified parameter.
Selecting time response T1
You can use this parameter to set the time response for delay time T1. You
can select the following options:
▪ Linear time response
▪ Integral time response
Linear time response With linear time response, the device responds with a constant delay time
regardless of the control deviation.
Maschinenfabrik Reinhausen GmbH 2018775252433/02 ENECOTAP® VPD® CONTROL PRO
Page 78
8 Operation
Integral time response With integral time response, the device responds with a variable delay time
depending on the control deviation. The greater the control deviation (ΔU) in
relation to the set bandwidth (B), the shorter the delay time. This means that
the device responds faster to large voltage changes in the grid. Regulation
accuracy improves as a result but the frequency of tap-changes increases
too.
Figure58: Diagram for integral time response
ΔU/B Control deviation "ΔU" as % of desired value in relation to the set band-
width "B" as % of desired value
1 "Delay time T1" parameter
To set the time response T1, proceed as follows:
1. Go to Settings > Parameters > Control > Time response T1.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
8.4.4 Delay time T2
You can use this parameter to set the delay time T2. Delay time T2 is used
to compensate for large control deviations faster.
The delay time T2 only takes effect if more than one tap-change operation is
required to correct the control deviation. The first output pulse occurs after
the set delay time T1. After the set tap-change delay time T2 has elapsed,
additional pulses occur in order to correct the existing control deviation.
The following requirements must be noted to set delay time T2:
▪ The delay time T2 must be greater than the switching pulse time.
▪ The delay time T2 must be greater than the maximum operating time of
the motor-drive unit.
▪ The delay time T2 must be less than the value set for delay time T1.
Maschinenfabrik Reinhausen GmbH 2018785252433/02 ENECOTAP® VPD® CONTROL PRO
Page 79
8 Operation
Behavior with delay times T1 and T2
Delay time T2 can be used to correct major control deviations more quickly.
Ensure that you set a lower value in the "Delay time T2" parameter than in
the "Delay time T1" parameter.
If the measured voltage U
deviates from the set bandwidth for a long
actual
period , a control impulse is output to the motor-drive unit after the set delay time T1. If the measured voltage U
is still outside the bandwidth,
actual
delay time T2 starts once delay time T1 is complete. Once delay time T2
is complete, a control impulse is again output to the motor-drive unit for the
tap change to return to the tolerance bandwidth.
Figure59: Behavior of the regulation function with delay times T1 and T2
1 +B%: Upper limit4 Set delay times T1 and T2.
2 U
: Desired value5 U
desired
: Measured voltage
actual
3 -B%: Lower limit6 B%: Tolerance bandwidth
A U
is outside the bandwidth. De-
actual
lay time T1 starts.
B Delay time T1 complete. Tap
change triggered.
C Delay time T2 complete. Tap
change triggered.
Setting delay time T2
To set the delay time T2 proceed as follows:
1. Go to Settings > Parameters > Control > Delay time T2.
2. Set delay time T2.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 2018795252433/02 ENECOTAP® VPD® CONTROL PRO
Page 80
Activating delay time T2
To activate delay time T2, proceed as follows:
1. Go to Settings > Parameters > Control > Activate delay T2.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
8.4.5 Setting regulation mode
If you are measuring the voltage and current with the 3-phase UI 3 measuring module, you can use this parameter to set whether you want 1-phase
voltage regulation or voltage regulation to the average value of the 3 phases.
You can select the following options:
▪ Single-phase: Voltage is automatically regulated to one selected phase.
Limit value monitoring, line drop compensation, and parallel operation
also take place on the selected phase using the circulating reactive current minimization method.
▪ Average value regulation: Voltage is automatically regulated to the aver-
age of the 3 phases. Limit value monitoring, line drop compensation, and
parallel operation also take place using the circulating reactive current
minimization method to the average of the 3 phases.
8 Operation
If you activate the average value regulation option, automatic voltage regulation is blocked should the voltage or current measurement of one of the 3
phases fail.
To set the regulation mode, proceed as follows:
1. Go to Settings > Parameters > Measurement.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
8.4.6 Setting control variables
If you are measuring the voltage and current with the 3-phase UI 3 measuring module and using the "single-phase" regulation mode, this parameter
can be used to select the phase used for voltage regulation. You can select
the following options:
▪ L1/N or L1/L2
▪ L2/N or L2/L3
▪ L3/N or L3/L1
To set the control variable, proceed as follows:
1. Go to Settings > Parameters > Measurement.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 2018805252433/02 ENECOTAP® VPD® CONTROL PRO
Page 81
8 Operation
8.5 Transformer data
The transformation ratios and measuring set-up for the voltage and current
transformers used in the system can be set with the following parameters.
The device uses this information to calculate the corresponding measured
values on the primary side of the current transformer (and therefore the
transformer) from the recorded measured values. These are then displayed.
Figure60: Setting transformer data (example)
8.5.1 Setting the primary transformer voltage
With this parameter, you can set the primary voltage of the voltage transformer in kV.
To set the primary transformer voltage, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Primary trans-
former voltage.
2. Enter the primary transformer voltage.
3. Press the Accept button to save the modified parameter.
8.5.2 Setting the secondary transformer voltage
With this parameter, you can set the secondary voltage of the voltage transformer in V.
To set the secondary transformer voltage, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Secondary trans-
former voltage.
2. Enter the secondary transformer voltage.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 2018815252433/02 ENECOTAP® VPD® CONTROL PRO
Page 82
8.5.3 Setting primary transformer current
You can use this parameter to set the primary current of the current transformer.
To set the primary transformer current, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Primary trans-former current.
2. Enter the primary transformer current.
3. Press the Accept button to save the modified parameter.
8.5.4 Setting the secondary transformer current
You can use this parameter to set the secondary current of the current transformer. You can select the following options:
▪ 0.2 A
▪ 1 A
▪ 5 A
8 Operation
To set the secondary transformer current, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Secondary trans-former current.
2. Select the secondary transformer current.
3. Press the Accept button to save the modified parameter.
8.5.5 Setting circuit for current transformer/voltage transformer and
phase angle correction
To configure the circuit for the current transformer and voltage transformer,
you must set the following parameters:
Table15: Setting configuration of current transformer and voltage transformer (UI 3 measuring
module)
*) According to setting of UI measuring channels [►Section 8.6.1, Page 91]
parameter.
Note the following examples of common transformer circuits:
Maschinenfabrik Reinhausen GmbH 2018825252433/02 ENECOTAP® VPD® CONTROL PRO
Page 83
8 Operation
Circuit A
▪ The voltage transformer VT is connected to the phase conductor and neu-
tral conductor.
▪ The current transformer CT is looped into the phase conductor.
▪ The voltage UL1 and current IL1 are in phase.
▪ The voltage drop on a phase conductor is determined by the current IL1.
If you use this circuit, set the device as follows:
ParameterOption
Voltage-transformer circuit1 Ph phase voltage
Current-transformer circuit1 Ph phase current
Phase angle correction0°
Table16: Circuit A
Circuit B
▪ The voltage transformer VT is connected to the phase conductor L1 and
the neutral conductor.
▪ The current transformer CT is looped into the phase conductor L1.
▪ The voltage U and current I are in phase.
▪ The voltage drop on a phase conductor is determined by the current IL1.
Maschinenfabrik Reinhausen GmbH 2018835252433/02 ENECOTAP® VPD® CONTROL PRO
Page 84
If you use this circuit, set the device as follows:
ParameterOption
Voltage-transformer circuit3 Ph phase voltage
Current-transformer circuit3 Ph phase current
Phase angle correction0°
Table17: Circuit B
Circuit C
8 Operation
▪ The voltage transformer VT is connected to the phase conductors L1 and
L2.
▪ The current transformer CT1 is looped into the phase conductor L1 and
CT2 into the phase conductor L2.
▪ The current transformers CT1 and CT2 are connected crosswise in paral-
lel (total current = IL1 + IL2).
▪ The total current IL1 + IL2 and voltage UL1-UL2 are in phase.
▪ The voltage drop on a phase conductor is determined by the current: (IL1 +
IL2) / √3.
If you use this circuit, set the device as follows:
ParameterOption
Voltage-transformer circuit3 Ph differential voltage
Current-transformer circuit3 Ph total current
Phase angle correction0°
Table18: Circuit C
Maschinenfabrik Reinhausen GmbH 2018845252433/02 ENECOTAP® VPD® CONTROL PRO
Page 85
8 Operation
Circuit D
▪ The voltage transformer VT is connected to the phase conductors L1 and
L2.
▪ The current transformer CT is looped into the phase conductor L3.
▪ The current IL3 is ahead of voltage UL1-VL2 by 90°. This corresponds to a
phase shift of -90°.
▪ The voltage drop on a phase conductor is determined by the current IL3.
If you use this circuit, set the device as follows:
ParameterOption
Voltage-transformer circuit3 Ph differential voltage
Current-transformer circuit3 Ph phase current
Phase angle correction90°
Table19: Circuit D
Circuit E
▪ The voltage transformer VT is connected to the phase conductors L1 and
L2.
▪ The current transformer CT is looped into the phase conductor L2.
▪ The current IL2 is ahead of voltage UL2-UL1 by 30°. This corresponds to a
phase shift of -30°.
▪ The voltage drop on a phase conductor is determined by the current IL2.
Maschinenfabrik Reinhausen GmbH 2018855252433/02 ENECOTAP® VPD® CONTROL PRO
Page 86
If you use this circuit, set the device as follows:
ParameterOption
Voltage-transformer circuit3 Ph differential voltage
Current-transformer circuit3 Ph phase current
Phase angle correction30°
Table20: Circuit E
Circuit F
8 Operation
▪ The voltage transformer VT is connected to the phase conductors L1 and
L2.
▪ The current transformer CT is looped into the phase conductor L1.
▪ The current IL1 lags behind UL1-UL2 by 30°. This corresponds to a phase
shift of +30° and a correction value of -30°.
▪ The voltage drop on a phase conductor is determined by the current IL1.
If you use this circuit, set the device as follows:
ParameterOption
Voltage-transformer circuit3 Ph differential voltage
Current-transformer circuit3 Ph phase current
Phase angle correction-30°
Table21: Circuit F
Maschinenfabrik Reinhausen GmbH 2018865252433/02 ENECOTAP® VPD® CONTROL PRO
Page 87
8 Operation
Circuit G
▪ Three-phase measurement.
▪ The voltage transformers are connected between the phases.
▪ The current lags behind the voltage by 30°.
If you use this circuit, set the device as follows:
Only use the circuits I, J and K on symmetrical grids. Otherwise the device
will calculate incorrect performance values.
Circuit I
▪ Three-phase voltage measurement, single-phase current measurement.
▪ The voltage transformers are connected between the phases.
▪ The current transformer is connected to phase L1.
If you use this circuit, set the device as follows:
Maschinenfabrik Reinhausen GmbH 2018885252433/02 ENECOTAP® VPD® CONTROL PRO
Page 89
8 Operation
Circuit J
▪ Three-phase voltage measurement, single-phase current measurement.
▪ The voltage transformers are connected between the phases.
▪ The current transformer is connected to phase L2.
▪ Three-phase voltage measurement, single-phase current measurement.
▪ The voltage transformers are connected between the phases.
▪ The current transformer is connected to phase L3.
Maschinenfabrik Reinhausen GmbH 2018895252433/02 ENECOTAP® VPD® CONTROL PRO
Page 90
8 Operation
ParameterOption
UI measuring channels3-ph. voltage, 1-ph. current
Measurement modePhase-phase
Table26: Circuit K
Setting voltage-transformer circuit
You can use this parameter to set your voltage transformer's circuit. You can
select the following options:
OptionDescription
1 Ph phase voltageMeasurement in 1-phase grid between
the conductor and neutral conductor.
3 Ph differential voltageMeasurement in 3-phase grid between 2
conductors
3 Ph phase voltageMeasurement in 3-phase grid between
conductor and neutral conductor
Table27: Voltage-transformer circuit
To set the voltage-transformer circuit, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Voltage-trans-
former circuit.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
Setting current-transformer circuit
You can use this parameter to set the circuit for your current transformer.
You can select the following options:
OptionDescription
1 Ph phase currentMeasurement of phase current in 1-phase
grid.
3 Ph total currentMeasurement of differential current in 3-
phase grid.
3 Ph phase currentMeasurement of phase current in 3-phase
grid.
Table28: Current-transformer circuit
To set the current-transformer circuit, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Current-trans-
former circuit.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 2018905252433/02 ENECOTAP® VPD® CONTROL PRO
Page 91
8 Operation
Setting phase angle correction
You can use this parameter to set the phase angle correction for your transformer circuit. To do so, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Phase angle cor-rection.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
Setting measurement mode
If you are measuring the voltage and current with the 3-phase UI 3 measuring module, you can use this parameter to set whether you have connected
the voltage transformer between 2 phases or between a phase and neutral.
To set the measuring mode, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Measuring mode.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
Also refer to
2 Setting UI measuring channels [►91]
8.6 Measurement
8.6.1 Setting UI measuring channels
If you are measuring the voltage and current with the 3-phase UI 3 measuring module, you can use this parameter to set the measurement channels in
use:
OptionDescription
1-ph. measurement: Channel 1The device uses 1 channel each for measure-
ment of voltage and current.
3-ph. measurement: Channel 1,
2, 3
3-ph. voltage, 1-ph. currentThe device uses 3 channels for voltage measure-
Table29: UI measuring channels
To set the UI measuring channels, proceed as follows:
1. Go to Settings > Parameters > Measurement > UI measuring chan-nels.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
The device uses 3 channels each for measurement of voltage and current.
ment and 1 channel for current measurement.
Maschinenfabrik Reinhausen GmbH 2018915252433/02 ENECOTAP® VPD® CONTROL PRO
Page 92
8.6.2 Control variable
If you are measuring the voltage and current with the 3-phase UI 3 measuring module and using the "single-phase" regulation mode, this parameter
can be used to select the phase used for voltage regulation. You can select
the following options:
▪ L1/N or L1/L2
▪ L2/N or L2/L3
▪ L3/N or L3/L1
To set the control variable, proceed as follows:
1. Go to Settings > Parameters > Measurement > Control variable.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
8.6.3 Regulation mode
If you are measuring the voltage and current with the 3-phase UI 3 measuring module, you can use this parameter to set whether you want 1-phase
voltage regulation or voltage regulation to the average value of the 3 phases.
You can select the following options:
▪ Single-phase: Voltage is automatically regulated to one selected phase.
Limit value monitoring, line drop compensation, and parallel operation
also take place on the selected phase using the circulating reactive current minimization method.
▪ Average value regulation: Voltage is automatically regulated to the aver-
age of the 3 phases. Limit value monitoring, line drop compensation, and
parallel operation also take place using the circulating reactive current
minimization method to the average of the 3 phases.
8 Operation
If you activate the average value regulation option, automatic voltage regulation is blocked should the voltage or current measurement of one of the 3
phases fail.
To set the regulation mode, proceed as follows:
1. Go to Settings > Parameters > Measurement > Regulation mode.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 2018925252433/02 ENECOTAP® VPD® CONTROL PRO
Page 93
8 Operation
8.6.4 Setting the display for the power factor
This parameter lets you set whether the device is to display a negative
power factor. You can select the following options:
OptionDescription
OffThe power factor is always shown as positive.
P > 0The power factor is shown as negative if the active power is
positive.
P < 0The power factor is shown as negative if the active power is
negative.
Q > 0The power factor is shown as negative if the reactive power is
positive.
Q < 0The power factor is shown as negative if the reactive power is
negative.
Table30: Setting the display for the power factor
To set the power factor display, proceed as follows:
1. Go to Settings > Parameters > Measurement > Negative power factordisplay.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
8.7 Line drop compensation
You can use the compensation function to compensate for the load-dependent voltage drop between the transformer and consumer. The device provides 2 methods of compensation for this purpose:
▪ R&X compensation
▪ Z compensation
Figure61: Setting line drop compensation
Maschinenfabrik Reinhausen GmbH 2018935252433/02 ENECOTAP® VPD® CONTROL PRO
Page 94
Note the description below for configuration of line drop compensation.
8.7.1 R&X compensation
R&X compensation can compensate for voltage losses on the lines and
therefore ensure correct voltage on the consumer. This requires precise line
data. After you have entered all of the line data, the device automatically calculates the ohmic and inductive voltage drop and takes this into account for
automatic voltage regulation.
8 Operation
Figure62: Equivalent circuit of R&X compensation
Figure63: Phasor diagram of R&X compensation
To use R&X compensation, you have to enter the following line data:
▪ Ohmic resistance load in mΩ/m
▪ Inductive resistance load in mΩ/m
▪ Length of line in km
Selecting R&X compensation
To select R&X compensation, proceed as follows:
1. Go to Settings > Parameters > Compensation > Compensationmethod.
2. Select R&X compensation option.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 2018945252433/02 ENECOTAP® VPD® CONTROL PRO
Page 95
8 Operation
Setting ohmic resistance load
To enter the value for ohmic resistance load, proceed as follows:
1. Go to Settings > Parameters > Compensation > Ohmic resistanceload.
2. Enter ohmic resistance load.
3. Press the Accept button to save the modified parameter.
Setting inductive resistance load
To enter the value for inductive resistance load, proceed as follows:
1. Go to Settings > Parameters > Compensation > Inductive resistanceload.
2. Enter inductive resistance load.
3. Press the Accept button to save the modified parameter.
Entering length of line
To enter the length of line, proceed as follows:
1. Go to Settings > Parameters > Compensation > Length of line.
2. Enter length of line.
3. Press the Accept button to save the modified parameter.
8.7.2 Z compensation
To keep the voltage constant for the consumer, you can use Z compensation
to activate a current-dependent increase in voltage. You can also define a
limit value to avoid excess voltage on the transformer.
Figure64: Z compensation
Maschinenfabrik Reinhausen GmbH 2018955252433/02 ENECOTAP® VPD® CONTROL PRO
Page 96
8 Operation
To use Z compensation, you need to calculate the increase in voltage (ΔU)
taking the current into account. Use the following formula for this purpose:
∆UVoltage increaseILoad current in A
U
U
Transformer voltage at current I I
Tr
Voltage on line end at current I
Load
and on-load tap-changer in
same operating position
N
k
Nominal current of current-transformer connection in A
Transmission ratio of current
CT
transformer
Sample calculation: UTr = 100.1 V, U
= 100.0 V, IN = 5 A kCT = 200 A/5 A,
Load
I = 100 A
Produces a voltage increase ∆U of 0.2%
The following sections describe how you can set the parameters you need
for Z compensation.
Selecting Z compensation
To select Z compensation, proceed as follows:
1. Go to Settings > Parameters > Compensation > Compensationmethod.
2. Select the Z compensation option.
3. Press the Accept button to save the modified parameter.
Setting the current-dependent voltage increase
You can use this parameter to set the voltage increase ∆U.
To set the limit value for voltage increase ΔU, proceed as follows:
1. Go to Settings > Parameters > Compensation > Voltage increase.
2. Enter voltage increase.
3. Press the Accept button to save the modified parameter.
Setting voltage limit value
You can use this parameter to define the maximum permissible voltage increase to avoid excess voltage on the transformer.
To set the voltage limit value, proceed as follows:
1. Go to Settings > Parameters > Compensation > Voltage limit value.
2. Enter voltage limit value.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 2018965252433/02 ENECOTAP® VPD® CONTROL PRO
Page 97
8 Operation
MasterFollower
Tap position
CAN bus
MAVRMAVR
T1T2
8.8 Tap position capture
The current tap position of the on-load tap-changer is transmitted from the
ECOTAP VPD MD&C controller to the CONTROL PRO controller. No further
settings are necessary for this.
8.9 Parallel operation (optional)
Parallel transformer operation is used to increase the throughput capacity or
short-circuit capacity at one location. The device provides you with specific
functions for regulating transformers.
Conditions for parallel
operation
8.9.1 Parallel operation methods
8.9.1.1 Tap synchronization
Compliance with the following general conditions is required for operating
transformers in parallel:
▪ Identical rated voltages
▪ Transformer power ratio (<3:1)
▪ Maximum deviation of short-circuit voltages (UK) for transformers con-
nected in parallel <10%
▪ Same number of switching groups
▪ For parallel operation with CAN communication: Current transformers with
the same rated values must be used for all devices operating in parallel
You can undertake parallel operation with various parallel operation methods.
With the tap synchronization parallel operation method, one voltage regulator works as the master and all others as followers.
Figure65: Tap synchronization
Maschinenfabrik Reinhausen GmbH 2018975252433/02 ENECOTAP® VPD® CONTROL PRO
Page 98
8 Operation
The master handles voltage regulation and transmits its current tap positions
to all followers via the CAN bus. The followers compare the tap position received with their own tap position. If the tap position is not the same, the followers switch to the tap position received from the master. This ensures that
the transformers operating in parallel are always in the same tap position.
You can set whether the master transfers the change in tap position to the
followers before or after its own tap-change operation. The devices then either change position sequentially (first the master, then the followers) or in
synch (master and followers at the same time).
If there is a tap difference between the master and followers, the master refrains from issuing any control commands to the motor-drive unit until all of
the followers have reached the same tap position. If the tap difference persists for longer than the set delay time for parallel operation error messages,
the master triggers the Step difference to follower event.
You can explicitly designate the voltage regulators as master and followers,
or set automatic designation using the CAN bus address.
For the tap synchronization parallel operation method, you have to set the
following parameters:
ParameterAutoMasterFollower
Activate parallel operationYes
Parallel operation methodAuto. tap syn-
chronization
CAN bus addressYes
Circul. reactive current
blocking limit
Master/follower current
blocking
Master/follower switching
characteristics
Maximum tap differenceYes (if follower)NoYes
Error if no communication
present
Behavior if no communi-
cation present
Parallel operation error
delay time
Table31: Parameter
ParameterAutoMasterFollower
Activate parallel operationYes
Parallel operation methodAuto. tap syn-
CAN bus addressYes
Optional, if master/follower current blocking is active
chronization
MasterFollower
Yes
Yes
Yes
Yes
Yes
MasterFollower
Maschinenfabrik Reinhausen GmbH 2018985252433/02 ENECOTAP® VPD® CONTROL PRO
Page 99
8 Operation
U, I, cosφ
CAN bus
MAVRMAVR
T1T2
ParameterAutoMasterFollower
Master/follower switching
characteristics
Maximum tap differenceYes (if follower)NoYes
Error if no communication
present
Behavior if no communi-
cation present
Parallel operation error
delay time
Table32: Parameter
Yes
Yes
Yes
Yes
8.9.1.2 Circulating reactive current minimization with CAN bus communication
With the circulating reactive current parallel operation method, parallel operation is carried out using the circulating reactive current minimization
method.
Figure66: Circulating reactive current minimization with CAN bus communication
The circulating reactive current is calculated from the transformer currents
and their phase angles. The voltage regulators in the parallel operation
group share this information via CAN bus. An extra control deviation proportional to circulating reactive current is added to the independently regulating
voltage regulators as a correction for the control deviation determined on the
basis of the measurement voltage. You can use the circulating reactive current sensitivity parameter to decrease or increase this extra control deviation.
The circulating reactive current method is suited to transformers connected
in parallel with a similar nominal output and short-circuit voltage UK and to
vector groups with the same and different step voltages. This does not require any information about the tap position.
Maschinenfabrik Reinhausen GmbH 2018995252433/02 ENECOTAP® VPD® CONTROL PRO
Page 100
8 Operation
Desired cosφ
Desired cosφ
U, I, (cosφ)
T1: U, I, (cosφ)
T2: U, I, (cosφ)
MAVRMAVR
T1T2
Note that the following prerequisites must be met for the "circulating reactive
current minimization" parallel operation method:
▪ You have to use current transformers with the same rated values for all
transformers in parallel operation.
▪ If you wish to operate in parallel operation with existing devices, you have
to activate the Retrofit TAPCON® 2xx parameter.
For the circulating reactive current minimization parallel operation method
with CAN communication, you have to set the following parameters:
▪ Activate parallel operation
▪ Parallel operation method: Circulating reactive current
▪ CAN bus address
▪ Circulating reactive current sensitivity
▪ Circul. reactive current blocking limit
▪ Error if no communication present
▪ Behavior if no communication present
▪ Parallel operation error delay time
8.9.1.3 Circulating reactive current minimization without CAN bus
communication
With this method, you can operate several voltage regulators without a communication connection (CAN bus) in parallel with circulating reactive current
minimization.
Figure67: Circulating reactive current minimization without CAN bus communication
The circulating reactive current is calculated using the desired power factor
parameter, the desired load stress type parameter, and the measured transformer current. An extra control deviation proportional to circulating reactive
current is added to the independently regulating voltage regulators as a correction for the control deviation determined on the basis of the measurement
voltage. This extra control deviation depends on how much the measured
power factor deviates from the desired power factor.
Maschinenfabrik Reinhausen GmbH 20181005252433/02 ENECOTAP® VPD® CONTROL PRO
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.