MR ECOTAP VPD CONTROL PRO Operating Instructions Manual

Page 1
Voltage Regulator ECOTAP® VPD® CONTROL PRO
Operating Instructions
5252433/02 EN
Page 2
© All rights reserved by Maschinenfabrik Reinhausen Dissemination and reproduction of this document and use and disclosure of its content are strictly prohibited
unless expressly permitted. Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents,
utility models or designs. The product may have been altered since this document was published. We reserve the right to change the technical data, design and scope of supply. Generally the information provided and agreements made when processing the individual quotations and orders
are binding. The original operating instructions were written in German.
Page 3

Table of contents

Table of contents
1 Introduction......................................................................................................................... 8
1.1 Manufacturer....................................................................................................................................... 8
1.2 Completeness..................................................................................................................................... 8
1.3 Safekeeping........................................................................................................................................ 8
1.4 Notation conventions .......................................................................................................................... 8
1.4.1 Hazard communication system .............................................................................................................................8
1.4.2 Information system..............................................................................................................................................10
1.4.3 Instruction system ...............................................................................................................................................10
1.4.4 Typographic conventions ....................................................................................................................................11
2 Safety................................................................................................................................. 12
2.1 Appropriate use ................................................................................................................................ 12
2.2 Fundamental Safety Instructions ...................................................................................................... 12
2.3 Personnel qualification...................................................................................................................... 15
2.4 Personal protective equipment ......................................................................................................... 16
3 IT security.......................................................................................................................... 18
4 Product description.......................................................................................................... 21
4.1 Scope of delivery .............................................................................................................................. 21
4.2 Function description.......................................................................................................................... 21
4.3 Performance features ....................................................................................................................... 22
4.4 Operating modes .............................................................................................................................. 22
4.5 Design............................................................................................................................................... 23
4.5.1 Power supply.......................................................................................................................................................24
4.5.2 Central processing unit .......................................................................................................................................24
4.5.3 Voltage measurement and current measurement...............................................................................................25
4.5.4 Voltage divider ....................................................................................................................................................26
4.5.5 Media converter ..................................................................................................................................................26
4.5.6 Media converter with managed switch ................................................................................................................27
4.6 Additional operating controls and display elements when using the MControl touch panel (optional) .. 28
5 Packaging, transport and storage ..................................................................................30
5.1 Packaging, transport and storage..................................................................................................... 30
5.1.1 Suitability, structure and production ...................................................................................................................30
Maschinenfabrik Reinhausen GmbH 2018 35252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 4
Table of contents
5.1.2 Markings..............................................................................................................................................................30
5.2 Transportation, receipt and handling of shipments........................................................................... 30
5.3 Storage of shipments........................................................................................................................ 31
6 Mounting ...........................................................................................................................32
6.1 Electromagnetic compatibility ........................................................................................................... 32
6.1.1 Wiring requirement of installation site ................................................................................................................32
6.1.2 Wiring requirement of operating site ..................................................................................................................33
6.1.3 Wiring requirement in control cabinet..................................................................................................................34
6.1.4 Information about shielding the CAN bus............................................................................................................34
6.2 Minimum distances........................................................................................................................... 35
6.3 Mounting location.............................................................................................................................. 36
6.4 Mounting the device.......................................................................................................................... 36
6.4.1 Mounting the device using the cap rail included in delivery ................................................................................37
6.4.2 Mounting the device on an alternative cap rail....................................................................................................43
6.5 Connecting device ............................................................................................................................ 49
6.5.1 Cable recommendation .......................................................................................................................................50
6.5.2 Information about laying fiber-optic cable ...........................................................................................................51
6.5.3 Mounting terminating resistor of CAN bus ..........................................................................................................51
6.5.4 Connecting cables to the system periphery ........................................................................................................51
6.5.5 Wiring the CPU I assembly .................................................................................................................................52
6.5.6 Wiring the UI assembly .......................................................................................................................................54
6.5.7 Wiring the MC 2-2/SW3-3 assembly ...................................................................................................................56
6.5.8 Connecting the power supply..............................................................................................................................57
7 Commissioning................................................................................................................. 59
7.1 Performing tests................................................................................................................................ 59
7.1.1 Ground test .........................................................................................................................................................59
7.1.2 Performing a dielectric test..................................................................................................................................60
7.2 Establishing connection to visualization ........................................................................................... 61
7.3 Setting parameters ........................................................................................................................... 62
7.3.1 Commissioning wizard ........................................................................................................................................62
7.3.2 Setting the parameters manually ........................................................................................................................63
8 Operation........................................................................................................................... 66
8.1 Establishing connection to visualization ........................................................................................... 66
8.2 General............................................................................................................................................. 66
8.2.1 Activating/deactivating automatic launch of commissioning wizard ....................................................................67
Maschinenfabrik Reinhausen GmbH 20184 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 5
Table of contents
8.2.2 Setting measured value display ..........................................................................................................................67
8.2.3 Remote behavior.................................................................................................................................................68
8.2.4 Visualization ........................................................................................................................................................68
8.2.5 Activating/deactivating the USB interface ...........................................................................................................70
8.3 Unlocking ECOTAP VPD communication......................................................................................... 70
8.4 Control .............................................................................................................................................. 71
8.4.1 Setting the desired value.....................................................................................................................................71
8.4.2 Bandwidth ...........................................................................................................................................................75
8.4.3 Delay time T1 ......................................................................................................................................................76
8.4.4 Delay time T2 ......................................................................................................................................................78
8.4.5 Setting regulation mode ......................................................................................................................................80
8.4.6 Setting control variables......................................................................................................................................80
8.5 Transformer data .............................................................................................................................. 81
8.5.1 Setting the primary transformer voltage ..............................................................................................................81
8.5.2 Setting the secondary transformer voltage .........................................................................................................81
8.5.3 Setting primary transformer current ....................................................................................................................82
8.5.4 Setting the secondary transformer current..........................................................................................................82
8.5.5 Setting circuit for current transformer/voltage transformer and phase angle correction .....................................82
8.6 Measurement.................................................................................................................................... 91
8.6.1 Setting UI measuring channels ...........................................................................................................................91
8.6.2 Control variable ...................................................................................................................................................92
8.6.3 Regulation mode .................................................................................................................................................92
8.6.4 Setting the display for the power factor...............................................................................................................93
8.7 Line drop compensation ................................................................................................................... 93
8.7.1 R&X compensation .............................................................................................................................................94
8.7.2 Z compensation...................................................................................................................................................95
8.8 Tap position capture ......................................................................................................................... 97
8.9 Parallel operation (optional).............................................................................................................. 97
8.9.1 Parallel operation methods .................................................................................................................................97
8.9.2 Configuring parallel operation ...........................................................................................................................101
8.10 Monitoring functions........................................................................................................................ 107
8.10.1 Voltage monitoring ............................................................................................................................................107
8.10.2 Current monitoring ............................................................................................................................................109
8.10.3 Power monitoring ..............................................................................................................................................112
8.10.4 Power flow monitoring.......................................................................................................................................113
8.10.5 Bandwidth monitoring........................................................................................................................................115
Maschinenfabrik Reinhausen GmbH 2018 55252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 6
Table of contents
8.10.6 Phase symmetry monitoring..............................................................................................................................117
8.10.7 Tap position monitoring (optional).....................................................................................................................118
8.11 SCADA ........................................................................................................................................... 119
8.11.1 Configuring IEC 61850 (optional)......................................................................................................................119
8.11.2 Displaying IEC 61850 log (optional)..................................................................................................................122
8.11.3 Configuring IEC 60870-5-104 (optional) ...........................................................................................................122
8.11.4 Configuring Modbus (optional) ..........................................................................................................................124
8.11.5 Configuring DNP3 (optional) .............................................................................................................................126
8.11.6 Configuring GOOSE (optional)..........................................................................................................................129
8.11.7 Configure data points (optional) ........................................................................................................................135
8.12 Time synchronization...................................................................................................................... 142
8.12.1 Activating time synchronization using SNTP.....................................................................................................143
8.12.2 Entering the time server address ......................................................................................................................144
8.12.3 Setting the time zone ........................................................................................................................................144
8.12.4 Setting synchronization interval ........................................................................................................................145
8.12.5 Reference time..................................................................................................................................................145
8.13 User administration......................................................................................................................... 145
8.13.1 User roles..........................................................................................................................................................145
8.13.2 Changing password ..........................................................................................................................................147
8.13.3 Creating, editing and deleting users..................................................................................................................148
8.13.4 Setting access rights to parameters and events ...............................................................................................149
8.14 Event management......................................................................................................................... 150
8.14.1 Displaying and acknowledging events ..............................................................................................................150
8.14.2 Configuring events ............................................................................................................................................151
8.14.3 Displaying event memory..................................................................................................................................152
8.15 Measured values ............................................................................................................................ 153
8.15.1 Displaying current measured values .................................................................................................................154
8.15.2 Displaying measured value recorder (optional).................................................................................................154
8.15.3 Setting the average value interval.....................................................................................................................165
8.16 Information about device ................................................................................................................ 166
8.16.1 Hardware...........................................................................................................................................................166
8.16.2 Software ............................................................................................................................................................167
8.16.3 Parallel operation ..............................................................................................................................................167
8.17 Import/export manager ................................................................................................................... 168
8.17.1 Exporting data ...................................................................................................................................................169
8.17.2 Importing data (software version 3.44 and later)...............................................................................................170
Maschinenfabrik Reinhausen GmbH 20186 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 7
Table of contents
8.18 Linking signals and events.............................................................................................................. 171
8.18.1 Linking functions ...............................................................................................................................................171
8.18.2 Linking control system messages .....................................................................................................................173
9 Maintenance and care .................................................................................................... 175
10 Fault elimination .............................................................................................................176
10.1 General faults ................................................................................................................................. 176
10.2 Human-machine interface............................................................................................................... 176
10.3 Other faults ..................................................................................................................................... 176
11 Disposal........................................................................................................................... 177
12 Technical data................................................................................................................. 178
12.1 Voltage supply ................................................................................................................................ 178
12.2 Voltage measurement and current measurement .......................................................................... 178
12.3 Voltage divider ................................................................................................................................ 179
12.4 Central processing unit ................................................................................................................... 179
12.5 System networking ......................................................................................................................... 181
12.6 Dimensions and weight................................................................................................................... 183
12.7 Ambient conditions ......................................................................................................................... 183
12.8 Standards and directives ................................................................................................................ 183
13 Appendix ......................................................................................................................... 186
13.1 Check list for commissioning .......................................................................................................... 186
Glossary .......................................................................................................................... 187
List of key words ............................................................................................................ 188
Maschinenfabrik Reinhausen GmbH 2018 75252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 8

1 Introduction

1 Introduction
This technical file contains detailed descriptions on the safe and proper in­stallation, connection, commissioning and monitoring of the product.
It also includes safety instructions and general information about the prod­uct.
This technical file is intended solely for specially trained and authorized per­sonnel.
1.1 Manufacturer
The product is manufactured by:
Maschinenfabrik Reinhausen GmbH
Falkensteinstraße 8 93059 Regensburg, Germany Tel.: (+49) 9 41/40 90-0 Fax: (+49) 9 41/40 90-7001 E-mail: sales@reinhausen.com
Further information on the product and copies of this technical file are avail­able from this address if required.
1.2 Completeness
This technical file is incomplete without the further applicable documentation.
The following documents apply to this product: ▪ Operating instructions ▪ Connection diagrams
1.3 Safekeeping
Keep this technical file and all supporting documents ready at hand and ac­cessible for future use at all times.
1.4 Notation conventions
This section contains an overview of the symbols and textual emphasis used.
1.4.1 Hazard communication system
Warnings in this technical file are displayed as follows.
Maschinenfabrik Reinhausen GmbH 20188 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 9
1 Introduction
1.4.1.1 Warning relating to section
Warnings relating to sections refer to entire chapters or sections, sub-sec­tions or several paragraphs within this technical file. Warnings relating to sections use the following format:
WARNING
Type of danger!
Source of the danger and outcome. ► Action ► Action
1.4.1.2 Embedded warning information
Embedded warnings refer to a particular part within a section. These warn­ings apply to smaller units of information than the warnings relating to sec­tions. Embedded warnings use the following format:
DANGER! Instruction for avoiding a dangerous situation.
1.4.1.3 Signal words and pictograms
The following signal words are used:
Signal word Definition
DANGER Indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING Indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION Indicates a hazardous situation which, if not avoided, could result
in minor or moderate injury.
NOTICE Indicates measures to be taken to prevent damage to property.
Table1: Signal words in warning notices
Pictograms warn of dangers:
Pictogram Definition
Warning of a danger point
Warning of dangerous electrical voltage
Maschinenfabrik Reinhausen GmbH 2018 95252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 10
Pictogram Definition
Warning of combustible substances
Warning of danger of tipping
Warning of danger of crushing
Table2: Pictograms used in warning notices
1 Introduction
1.4.2 Information system
Information is designed to simplify and improve understanding of particular procedures. In this technical file it is laid out as follows:
Important information.
1.4.3 Instruction system
This technical file contains single-step and multi-step instructions.
Single-step instructions
Instructions which consist of only a single process step are structured as fol­lows:
Aim of action ü Requirements (optional). ► Step 1 of 1.
ð Result of step (optional).
ð Result of action (optional).
Multi-step instructions
Instructions which consist of several process steps are structured as follows:
Maschinenfabrik Reinhausen GmbH 201810 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 11
1 Introduction
Aim of action ü Requirements (optional).
1. Step 1. ð Result of step (optional).
2. Step 2.
ð Result of step (optional).
ð Result of action (optional).
1.4.4 Typographic conventions
The following typographic conventions are used in this technical file:
Typographic convention Purpose Example
UPPERCASE Operating controls, switches ON/OFF [Brackets] PC keyboard [Ctrl] + [Alt] Bold Software operating controls Press Continue button …>…>… Menu paths Parameter > Control parameter Italics System messages, error messages,
signals
[► Number of pages]. Cross reference [► 41].
Table3: Typographic conventions
Function monitoring alarm triggered
Maschinenfabrik Reinhausen GmbH 2018 115252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 12

2 Safety

This technical file contains detailed descriptions on the safe and proper in­stallation, connection, commissioning, operation, and monitoring of the prod­uct.
▪ Read this technical file through carefully to familiarize yourself with the
product. ▪ This technical file is part of the product. ▪ Read and observe the safety instructions provided in this chapter in partic-
ular. ▪ Observe the warnings in this technical file in order to avoid function-re-
lated dangers. ▪ The product is manufactured according to the state of the art. Risks to life
and limb of the user or impairment of the product and other material as-
sets may occur during use due to function-related dangers despite this.
2.1 Appropriate use
2 Safety
The ECOTAP VPD CONTROL PRO device expands automatic voltage regu­lation of the ECOTAP VPD CONTROL device by adding additional functions.
If used as intended, in compliance with the requirements and conditions specified in this technical file and observing the warning notices in this tech­nical file and attached to the product, the product does not pose a danger of injury or damage to property or the environment. This applies across the en­tire service life of the product, from delivery to installation and operation through to disassembly and disposal.
The following is considered appropriate use: ▪ You will find the standard valid for the product and the year of issue on the
nameplate. ▪ Operate the product in accordance with this technical file, the agreed-
upon delivery conditions and the technical data. ▪ Ensure that all necessary work is performed by qualified personnel only. ▪ Only use the equipment and special tools included in delivery for the in-
tended purpose and in accordance with the specifications of this technical
file. ▪ Only operate the product in industrial areas. Observe the notices in this
technical file regarding electromagnetic compatibility and the technical
data.
2.2 Fundamental Safety Instructions
To prevent accidents, disruptions and damage as well as unacceptable ad­verse effects on the environment, those responsible for transport, installa­tion, operation, maintenance and disposal of the product or parts of the prod­uct must ensure the following:
Maschinenfabrik Reinhausen GmbH 201812 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 13
2 Safety
Personal protective equipment
Loosely worn or unsuitable clothing increases the danger of becoming trapped or caught up in rotating parts and the danger of getting caught on protruding parts. This increases the danger to life and limb.
▪ All necessary devices and personal protective equipment required for the
specific task, such as a hard hat, safety footwear, etc. must be worn. Ob­serve the section "Personal protective equipment" [Section 2.4, Page
16]. ▪ Never wear damaged personal protective equipment. ▪ Never wear rings, necklaces, or other jewelry. ▪ If you have long hair, wear a hairnet.
Work area
Untidy and poorly lit work areas can lead to accidents. ▪ Keep the work area clean and tidy. ▪ Make sure that the work area is well lit. ▪ Observe the applicable laws for accident prevention in the relevant coun-
try.
Working during operation
The product may be operated only in a sound, operational condition. Other­wise it poses a danger to life and limb.
▪ Regularly check the operational reliability of safety equipment. ▪ Comply with the inspection work, maintenance work and maintenance in-
tervals described in this technical file.
Invisible laser radiation
Looking directly into the beam or the reflected beam can cause eye damage. The beam is emitted at the optical connections or at the end of the fiber-optic cables connected to them on the assemblies. Read the chapter "Technical Data" [Section 12, Page 178] for further information.
▪ Never look directly into the beam or the reflected beam. ▪ Never look into the beam with the aid of optical instruments such as a
magnifying glass or a microscope. ▪ In the event that the laser beam strikes your eyes, close your eyes imme-
diately and move your head out of the path of the beam.
Maschinenfabrik Reinhausen GmbH 2018 135252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 14
2 Safety
Working with current transformers
Dangerous high voltages may occur when a current transformer is operated with an open secondary circuit. This can lead to injuries and property dam­age.
▪ Never operate a current transformer with an open secondary circuit; short-
circuit the current transformer to prevent this.
▪ Observe the information in the current transformer operating instructions.
Explosion protection
Highly flammable or explosive gases, vapors and dusts can cause serious explosions and fire.
▪ Do not install or operate the product in areas where a risk of explosion is
present.
Safety markings
Warning signs and safety information plates are safety markings on the product. They are an important aspect of the safety concept.
▪ Observe all safety markings on the product. ▪ Make sure all safety markings on the product remain intact and legible. ▪ Replace safety markings that are damaged or missing.
Ambient conditions
To ensure reliable and safe operation, the product must only be operated under the ambient conditions specified in the technical data.
▪ Observe the specified operating conditions and requirements for the in-
stallation location.
Modifications and conversions
Unauthorized or inappropriate changes to the product may lead to personal injury, material damage and operational faults.
▪ Only modify the product after consultation with the manufacturer.
Spare parts
Spare parts not approved by the manufacturer may lead to physical injury, damage to the product and operational faults.
▪ Only use spare parts approved by the manufacturer. ▪ Contact the manufacturer.
Maschinenfabrik Reinhausen GmbH 201814 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 15
2 Safety
2.3 Personnel qualification
The person responsible for assembly, commissioning, operation, mainte­nance and inspection must ensure that the personnel are sufficiently quali­fied.
Electrically skilled person
The electrically skilled person has a technical qualification and therefore has the required knowledge and experience, and is also conversant with the ap­plicable standards and regulations. The electrically skilled person is also pro­ficient in the following:
▪ Can identify potential dangers independently and is able to avoid them. ▪ Is able to perform work on electrical systems. ▪ Is specially trained for the working environment in which (s)he works. ▪ Must satisfy the requirements of the applicable statutory regulations for
accident prevention.
Electrically trained persons
An electrically trained person receives instruction and guidance from an electrically skilled person in relation to the tasks undertaken and the poten­tial dangers in the event of inappropriate handling as well as the protective devices and safety measures. The electrically trained person works exclu­sively under the guidance and supervision of an electrically skilled person.
Operator
The operator uses and operates the product in line with this technical file. The operating company provides the operator with instruction and training on the specific tasks and the associated potential dangers arising from im­proper handling.
Technical Service
We strongly recommend having maintenance, repairs and retrofitting carried out by our Technical Service department. This ensures that all work is per­formed correctly. If maintenance is not carried out by our Technical Service department, please ensure that the personnel who carry out the mainte­nance are trained and authorized by Maschinenfabrik Reinhausen GmbH to carry out the work.
Authorized personnel
Authorized personnel are trained by Maschinenfabrik Reinhausen GmbH to carry out special maintenance.
Maschinenfabrik Reinhausen GmbH 2018 155252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 16
2.4 Personal protective equipment
Personal protective equipment must be worn during work to minimize risks to health.
▪ Always wear the personal protective equipment required for the job at
hand. ▪ Never wear damaged personal protective equipment. ▪ Observe information about personal protective equipment provided in the
work area.
Personal protective equipment to be worn at all times
Protective clothing
Close-fitting work clothing with a low tearing strength, with tight sleeves and with no protrud­ing parts. It mainly serves to protect the wearer against being caught by moving machine parts.
Safety shoes
To protect against falling heavy objects and slip­ping on slippery surfaces.
2 Safety
Special personal protective equipment for particular environments
Safety glasses
To protect the eyes from flying parts and splash­ing liquids.
Visor
To protect the face from flying parts and splash­ing liquids or other dangerous substances.
Hard hat
To protect from falling and flying parts and mate­rials.
Maschinenfabrik Reinhausen GmbH 201816 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 17
2 Safety
Hearing protection
To protect from hearing damage.
Protective gloves
To protect from mechanical, thermal, and electri­cal hazards.
Maschinenfabrik Reinhausen GmbH 2018 175252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 18

3 IT security

3 IT security
Observe the following recommendations for secure operation of the product.
General
▪ Ensure that only authorized personnel have access to the device. ▪ Only use the device within an ESP (electronic security perimeter). Do not
connect the device to the Internet in an unprotected state. ▪ Ensure that the device is only operated by trained personnel who are fa-
miliar with IT security.
Commissioning
Observe the following recommendations for device commissioning: ▪ User IDs should be unique and attributable. Do not use a "Group account"
function or an "Auto login" function. ▪ Restrict the rights of the individual user groups as much as is feasible; this
helps avoid errors during operating actions. A user with the "Operator"
role, for example, should only perform operating actions and should not
be able to change any device settings. ▪ Delete or disable the default "admin" user ID. This requires first creating a
new user account with the "Administrator" role. You can then use it to
delete or disable the default "admin" account. ▪ Enable SSL/TLS encryption [Section 8.2, Page 66]; access to the de-
vice is then only possible using the SSL/TLS protocol. In addition to en-
crypting communication, this protocol also checks the authenticity of the
server. ▪ Use TLS version 1.2 or higher wherever possible. ▪ Integrate the device into a public key infrastructure. Create your own SSL
certificate for this if necessary and then import it.
Operation
Observe the following recommendations during device operation: ▪ Change the password at regular intervals. ▪ Export the security log [Section 8.17.1, Page 169] at regular intervals.
Interfaces
The device uses the following interfaces for communication:
Maschinenfabrik Reinhausen GmbH 201818 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 19
3 IT security
Figure1: Interfaces of the CPU assembly
Interface Protocol Port Description
CAN 1 - - Attachment of the DIO assembly CAN 2 - - Communication with other ISM® devices
(e.g. parallel operation) COM 1 - - Internal system interface COM 2 - - Serial interface (SCADA) USB - - Import or export of data ETH 1 TCP 102 IEC 61850 ETH 1 TCP 502 Modbus ETH 1 TCP 20000 DNP3
2)
2)
2)
ETH 1 UDP 67 DHCP server ETH 2.x TCP 21 FTP1) (only for MR service) ETH 2.x TCP 80 HTTP for web-based visualization ETH 2.x TCP 443 HTTPS for web-based visualization
1)
1)
ETH 2.x TCP 990 FTPS (only for MR service) ETH2.x TCP 8080 HTTP for web-based visualization ETH2.x TCP 8081 HTTPS for web-based visualization
Table4: Interfaces and open ports of the CPU assembly
1)
1)
1)
Port is closed if you activate the device's SSL encryption.
2)
Default setting; if you have modified the port for the control system proto-
col, only the set port is opened.
Maschinenfabrik Reinhausen GmbH 2018 195252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 20
3 IT security
Encryption standards
The device supports the following TLS versions: ▪ TLS 1.0 ▪ TLS 1.1 ▪ TLS 1.2
The device uses the following cipher suites for a TLS-secured connection:
Key exchange Authentication Encryption Key length Operating
mode
Hash func-
tion
TLS ECDHE RSA WITH AES 128 CBC SHA
DHE SHA265
ECDHE ECDSA GCM SHA256
ECDH 256 CBC SHA
1)
RSA
SHA256
GCM SHA384
Table5: Cipher suite
1)
Not available with TLS version >= 1.2
The device uses the SHA256 hash function to save passwords.
1)
1)
Maschinenfabrik Reinhausen GmbH 201820 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 21

4 Product description

CONTROL CONTROL PRO
Motor-drive unit
SCADA
serial Ethernet
ECOTAP VPD
4 Product description
This chapter contains an overview of the design and function of the product.
4.1 Scope of delivery
The following items are included in the delivery: ▪ ECOTAP VPD CONTROL PRO ▪ Connection cable for connecting to ECOTAP VPD MD&C ▪ Terminating resistor for CAN bus (optional) ▪ Technical files ▪ Additional nameplate
Please note the following: ▪ Check the shipment for completeness on the basis of the shipping docu-
ments.
▪ Store the parts in a dry place until installation.
4.2 Function description
The ECOTAP VPD CONTROL PRO device expands automatic voltage regu­lation of the ECOTAP VPD CONTROL device by adding additional functions. For this purpose, the two devices are connected via serial connection.
Figure2: Operating principle
Maschinenfabrik Reinhausen GmbH 2018 215252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 22
4.3 Performance features
The device offers the following functions: ▪ Automatic voltage regulation AVR pro
– Measurement of voltage and current – Desired value in accordance with order (1, 3 or 5 desired values,
TDSC, analog desired value specification, incremental desired value specification, desired value via BCD)
– Automatic voltage regulation with linear or integral delay time T1 and
with delay time T2 – Parallel operation – Line drop compensation – Status of the motor-drive unit (motor protective switch, motor is running) – Bandwidth monitoring – Function monitoring
▪ Web-based visualization ▪ SCADA
– IEC 60870-5-104 – IEC 61850 (edition 1 and edition 2) – Modbus (TCP) – DNP3 (TCP)
4 Product description
4.4 Operating modes
You can operate the device in the operating modes listed below. You can select the operating mode using the keys on the connected ECOTAP VPD CONTROL control unit.
Auto mode (AVR AUTO)
In auto mode, the ECOTAP VPD CONTROL control unit regulates voltage automatically in accordance with the set parameters. It is not possible to per­form manual tap-change operations using operating controls, inputs or a control system.
Manual mode (AVR MANUAL)
In manual mode, you can perform manual tap-change operations to increase or decrease the voltage using the keys on the ECOTAP VPD CONTROL control unit. There is no automatic voltage regulation.
Maschinenfabrik Reinhausen GmbH 201822 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 23
4 Product description
External control (EXTERNAL CONTROL)
In the external control operating mode, the ECOTAP VPD CONTROL control
unit performs the raise/lower switching commands issued by the CONTROL
PRO controller.
Operating mode VPD CONTROL CONTROL PRO
Operating
VPD CONTROL automatic
AVR AUTO Local (= 0) -
regulation
Tap-change operation us-
AVR MAN­ing VPD CONTROL oper­ating controls
CONTROL PRO automatic regulation
CONTROL PRO automatic regulation
Tap-change operation via SCADA
Table6: Overview of operating modes
2)
EXTERNAL
CONTROL
EXTERNAL
CONTROL
EXTERNAL
CONTROL
mode
UAL
Local/Remote Operating mode
Remote (= 1) -
Local -
Remote -
Local Auto
Remote Auto
Remote Manual
3)
3)
1)
Can be set via parameter P9 in VPD MD&C
2)
Optional when connecting the CONTROL PRO control unit to a control sys-
tem (SCADA).
3)
You can switch the operating mode using a SCADA command.
4.5 Design
The device consists of various assemblies that are pre-installed and wired on a cap rail:
▪ G1 power supply ▪ CPU (central processing unit) I ▪ UI 3 voltage measurement and current measurement ▪ VD001 voltage divider ▪ Optional: MC 2-2 media converter or media converter with SW 3-3 man-
aged switch
Maschinenfabrik Reinhausen GmbH 2018 235252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 24
Figure3: Overview
The individual device assemblies are described in the following section.
4.5.1 Power supply
The G1 PULS DIMENSION QS3.241 assembly supplies power to the de­vice.
4 Product description
Figure4: G1 PULS DIMENSION QS3.241 assembly
4.5.2 Central processing unit
The CPU I assembly is the central computing unit for the device. It contains the following interfaces:
▪ Internal system interface RS232 (COM1) ▪ Serial interface RS232/485 (COM2) ▪ 3x Ethernet (ETH1, ETH 2.1, ETH 2.2) ▪ USB (USB 2.0) ▪ 2x CAN bus (CAN 1, CAN 2)
Maschinenfabrik Reinhausen GmbH 201824 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 25
4 Product description
Figure5: CPU I assembly
4.5.3 Voltage measurement and current measurement
The UI 3 assembly is used for measuring 3-phase voltage and current.
Figure6: UI 3 assembly
Maschinenfabrik Reinhausen GmbH 2018 255252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 26
4.5.4 Voltage divider
The assembly VD001 is a voltage divider. The voltage divider reduces the voltage of a three-phase measuring system to the permissible range of the measuring assembly.
4 Product description
Figure7: Voltage divider VD001
4.5.5 Media converter
The MC 2-2 assembly is a media converter, which converts 2 electrical con­nections (RJ45) to one fiber-optic cable connection each. Each is converted independently of the other. The following interfaces are available:
▪ 2x RJ45 (ETH12, ETH22) ▪ 2x Duplex-LC (SFP module) (ETH11, ETH21)
The media converter is designed to be transparent for the network and does not have its own IP address.
Maschinenfabrik Reinhausen GmbH 201826 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 27
4 Product description
Figure8: MC 2-2 assembly
4.5.6 Media converter with managed switch
The assembly SW 3-3 is a media converter with managed switch. It com­bines two independent functions and provides you with the following inter­faces:
▪ A media converter converts an electric connection (RJ45) into a fiber-optic
cable connection – RJ45 (ETH12) – Duplex-LC (SFP module) (ETH11)
▪ Managed switch with redundancy function (PRP or RSTP)
– 2x RJ45 (ETH23, ETH24), device-internal connection – 2x Duplex-LC (SFP module) (ETH21, ETH22), redundancy connection
The following redundancy functions are available to you according to your order:
▪ PRP (standard setting) ▪ RSTP
Maschinenfabrik Reinhausen GmbH 2018 275252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 28
Figure9: SW 3-3 assembly
4 Product description
4.6 Additional operating controls and display elements when using the MControl touch panel (optional)
If you are using the device with the optionally available MControl touch panel, additional operating controls and display elements are displayed on the left edge of the screen
Figure10: Additional display elements and operating controls
Status LED status Status display
REMOTE key Select the operating mode:
1)
▪ On: REMOTE ▪ Off: LOCAL
AVR AUTO key Activate auto mode.
Maschinenfabrik Reinhausen GmbH 201828 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 29
4 Product description
RAISE key Send a control command to the motor-drive
unit to increase the voltage. Only possible in manual mode.
AVR Manual key Activate manual mode.
LOWER key Send a control command to the motor-drive
unit to reduce the voltage. Only possible in manual mode.
1)
Not available if local/remote is toggled using a digital input.
Maschinenfabrik Reinhausen GmbH 2018 295252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 30

5 Packaging, transport and storage

5 Packaging, transport and storage
5.1 Packaging, transport and storage
5.1.1 Suitability, structure and production
The goods are packaged in a sturdy cardboard box. This ensures that the shipment is secure when in the intended transportation position and that none of its parts touch the loading surface of the means of transport or touch the ground after unloading.
The box is designed for a maximum load of 10kg.
Inlays inside the box stabilize the goods, preventing impermissible changes of position, and protect them from vibration.
5.1.2 Markings
The packaging bears a signature with instructions for safe transport and cor­rect storage. The following symbols apply to the shipment of non-hazardous goods. Adherence to these symbols is mandatory.
Protect against
moisture
Table7: Shipping pictograms
Top Fragile Attach lifting
gear here
Center of mass
5.2 Transportation, receipt and handling of shipments
In addition to oscillation stress, jolts must also be expected during trans­portation. In order to prevent possible damage, avoid dropping, tipping, knocking over and colliding with the product.
If a crate tips over, falls from a certain height (e.g. when slings tear) or is subject to an unbroken fall, damage must be expected regardless of the weight.
Every delivered shipment must be checked for the following by the recipient before acceptance (acknowledgment of receipt):
▪ Completeness based on the delivery slip ▪ External damage of any type
The checks must take place after unloading when the crate or transport con­tainer can be accessed from all sides.
Maschinenfabrik Reinhausen GmbH 201830 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 31
5 Packaging, transport and storage
Visible damage If external transport damage is detected on receipt of the shipment, proceed
as follows: ▪ Immediately record the transport damage found in the shipping docu-
ments and have this countersigned by the carrier.
▪ In the event of severe damage, total loss or high damage costs, immedi-
ately notify the sales department at Maschinenfabrik Reinhausen and the relevant insurance company.
▪ After identifying damage, do not modify the condition of the shipment fur-
ther and retain the packaging material until an inspection decision has been made by the transport company or the insurance company.
▪ Record the details of the damage immediately onsite together with the
carrier involved. This is essential for any claim for damages!
▪ If possible, photograph damage to packaging and packaged goods. This
also applies to signs of corrosion on the packaged goods due to moisture inside the packaging (rain, snow, condensation).
▪ Be absolutely sure to also check the sealed packaging.
Hidden damage When damages are not determined until unpacking after receipt of the ship-
ment (hidden damage), proceed as follows: ▪ Make the party responsible for the damage liable as soon as possible by
telephone and in writing, and prepare a damage report.
▪ Observe the time periods applicable to such actions in the respective
country. Inquire about these in good time.
With hidden damage, it is very hard to make the transportation company (or other responsible party) liable. Any insurance claims for such damages can only be successful if relevant provisions are expressly included in the insur­ance terms and conditions.
5.3 Storage of shipments
When selecting and setting up the storage location, ensure the following: ▪ Protect stored goods against moisture (flooding, water from melting snow
and ice), dirt, pests such as rats, mice, termites and so on, and against unauthorized access.
▪ Store the crates on timber beams and planks as a protection against ris-
ing damp and for better ventilation. ▪ Ensure sufficient carrying capacity of the ground. ▪ Keep entrance paths free. ▪ Check stored goods at regular intervals. Also take appropriate action after
storms, heavy rain or snow and so on.
Maschinenfabrik Reinhausen GmbH 2018 315252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 32

6 Mounting

6 Mounting
The following description does not apply if you have ordered the device ver­sion with control cabinet. If that is the case, follow the description in the ECOTAP VPD MD&C operating instructions.
This chapter describes how to correctly install and connect the device. Ob­serve the connection diagrams provided.
DANGER
WARNING
NOTICE
Electric shock!
Risk of fatal injury due to electrical voltage. Always observe the following safety regulations when working in or on electrical equipment.
► Disconnect the equipment. ► Lock the equipment to prevent an unintentional restart. ► Make sure all poles are de-energized. ► Ground and short-circuit. ► Cover or cordon off adjacent energized parts.
Electric shock!
Dangerous high voltages may occur when a current transformer is operated with an open secondary circuit. This can lead to death, injuries and property damage.
► Never operate a current transformer with an open secondary circuit;
short-circuit the current transformer to prevent this.
► Observe the information in the current transformer operating instructions.
Damage to the device!
Electrostatic discharge may cause damage to the device. ► Take precautionary measures to prevent the build-up of electrostatic
charges on work surfaces and personnel.
6.1 Electromagnetic compatibility
The device has been developed in accordance with applicable EMC stan­dards. The following points must be noted in order to maintain the EMC standards.
6.1.1 Wiring requirement of installation site
Note the following when selecting the installation site: ▪ The system's overvoltage protection must be effective. ▪ The system's ground connection must comply with all technical regula-
tions.
Maschinenfabrik Reinhausen GmbH 201832 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 33
6 Mounting
▪ Separate system parts must be joined by a potential equalization. ▪ The device and its wiring must be at least 10m away from circuit-break-
ers, load disconnectors and busbars.
6.1.2 Wiring requirement of operating site
Note the following when wiring the operating site: ▪ Route the connecting leads in grounded metal cable ducts. ▪ Do not route lines which cause interference (e.g. power lines) and lines
susceptible to interference (e.g. signal lines) in the same cable duct. ▪ Maintain a distance of more than 100 mm between lines which cause in-
terference and those which are susceptible to interference.
Figure11: Recommended wiring
1 Cable duct for lines causing inter-
ference
2 Line causing interference (e.g.
power line)
3 Cable duct for lines susceptible to
interference
4 Line susceptible to interference
(e.g. signal line)
▪ Short-circuit and ground reserve lines. ▪ Never connect the device with a multi-wire collective pipe. ▪ For signal transmission, use shielded lines with individual conductors (out-
going conductor / return conductor) twisted in pairs. ▪ Connect full surface of shielding (360º) to device or to a nearby grounding
bar.
Using single conductors may limit the effectiveness of the shielding. Con­nect close-fitting shielding to cover all areas.
Maschinenfabrik Reinhausen GmbH 2018 335252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 34
Figure12: Recommended connection of the shielding
6 Mounting
1 Connection of the shielding via a
single conductor
2 Full-surface connection of the
6.1.3 Wiring requirement in control cabinet
Note the following when wiring the control cabinet: ▪ The control cabinet where the device will be installed must be prepared in
accordance with EMC requirements: – Functional division of control cabinet (physical separation) – Constant potential equalization (all metal parts are joined) – Line routing in accordance with EMC requirements (separation of lines
which cause interference and those susceptible to interference)
– Optimum shielding (metal housing) – Overvoltage protection (lightning protection) – Collective grounding (main grounding rail) – Cable bushings in accordance with EMC requirements – Any contactor coils present must be interconnected
▪ The device's connection cables must be laid in close contact with the
grounded metal housing or in metallic cable ducts with a ground connec­tion.
▪ Signal lines and power lines/switching lines must be laid in separate cable
ducts.
shielding
6.1.4 Information about shielding the CAN bus
In order for the CAN bus to operate faultlessly, you have to connect the shielding using one of the following variants. If you are not able to use any of the variants detailed below, we recommend using fiber-optic cables. Fiber­optic cables decouple the devices and are not sensitive to electromagnetic interference (surge and burst).
Maschinenfabrik Reinhausen GmbH 201834 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 35
6 Mounting
NOTICE
Damage to the device!
If you connect the CAN bus cable to devices with different potentials, cur­rent may flow across the shielding. This current may damage the device.
► Connect the devices to a potential equalization rail to equalize the poten-
tial.
► If both devices have different potentials, only connect the CAN bus cable
shielding to one device.
Variant 1: The connected devices share the same potential
If the devices to be connected share the same potential, proceed as follows:
1. Connect all devices to a potential equalization rail to equalize the poten-
tial.
2. Connect the CAN bus cable shielding to all connected devices.
Variant 2: The connected devices have different potentials
Note that the shielding is less effective with this variant.
If the devices to be connected have different potentials, proceed as follows: ► Connect the CAN bus cable shielding to just one device.
NOTICE
Connecting shielding
Connect the shielding for the CAN bus cable to the 9-pin D-sub connector:
Figure13: Connection of CAN bus cable shielding to the 9-pin D-sub connector
6.2 Minimum distances
Damage to the device!
Insufficient circulation of ambient air can result in damage to the device due to overheating.
► Keep the ventilation slots clear. ► Ensure sufficient distance to neighboring components. ► Only mount device in horizontal position (ventilation slots are at the top
and bottom).
Maschinenfabrik Reinhausen GmbH 2018 355252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 36
6 Mounting
Reliable operation of the device in the permitted temperature range requires that you maintain the following minimum distances to the control cabinet and to neighboring components:
Minimum distance
To the floor of the control cabinet 88.9 mm (3.5 in) To the roof of the control cabinet Between assemblies on the bus bar and assem-
blies on the remote cap rail
Table8: Minimum distances in the control cabinet
Corresponds to 2 RU
Figure14: Example depiction of the minimum distances in a control cabinet
For other installation types, contact Maschinenfabrik Reinhausen GmbH.
6.3 Mounting location
In order to ensure safe operation of the device, the device must be mounted in an enclosure or control cabinet that has the following properties:
▪ Protection against mechanical influences ▪ Assurance of permissible ambient conditions (see Technical data [Sec-
tion 12, Page 178] section)
6.4 Mounting the device
You can mount the device in one of the variants described below: ▪ Mounting the device using the cap rail included in delivery ▪ Mounting the device on an alternative cap rail
Observe the following sections when doing so.
Maschinenfabrik Reinhausen GmbH 201836 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 37
6 Mounting
6.4.1 Mounting the device using the cap rail included in delivery
The cap rail included in delivery has 3 mounting drill holes, which you can use to fasten the cap rail to the rear panel of the switch cabinet. Before you can begin mounting, you have to remove a part of the device.
Figure15: Overview of the partial removal of assemblies
Preparing the device for mounting
To prepare the device for mounting, proceed as follows:
1. Remove the plug for voltage measurement from the UI assembly.
Figure16: Removing the plug for voltage measurement
Maschinenfabrik Reinhausen GmbH 2018 375252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 38
2. Remove the "24V DC" plug from the CPU assembly.
6 Mounting
Figure17: Removing the plug (voltage supply)
3. If the device is equipped with the SW3-3 or MC2-2 assembly: Remove the "24V DC" plug from the SW3-3 or MC2-2 assembly.
Figure18: Removing the plug (voltage supply)
Maschinenfabrik Reinhausen GmbH 201838 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 39
6 Mounting
4. If the device is equipped with the SW3-3 or MC2-2 assembly: Unhook the SW3-3 or MC2-2 assembly.
Figure19: Unhooking the MC2-2 / SW3-3 assembly
5. Unhook the bus rail.
Figure20: Unhooking the bus rail
Maschinenfabrik Reinhausen GmbH 2018 395252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 40
6 Mounting
Mounting the cap rail
To mount the cap rail, proceed as follows: ► Fasten the cap rail to the rear panel of the switch cabinet using screws
and contact washers or lock washers.
Figure21: Fastening the cap rail
Maschinenfabrik Reinhausen GmbH 201840 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 41
6 Mounting
Mounting the device assemblies
To mount the device assemblies that had been previously removed, proceed as follows:
1. WARNING! Mount the bus rail on the cap rail, ensuring that the bus rail engages correctly. Otherwise, it can result in electric shock due to a faulty connection to the protective ground.
Figure22: Hooking the bus rail into position
2. WARNING! Hook the optional SW3-3 or MC2-2 assembly into position on the cap rail at the specified location, ensuring that the assembly en­gages correctly. Otherwise, it can result in electric shock due to a faulty connection to the protective ground.
Maschinenfabrik Reinhausen GmbH 2018 415252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 42
6 Mounting
3. If the device is equipped with the SW3-3 or MC2-2 assembly: Plug the plug into the corresponding "24V DC" slot and screw it into place.
Figure23: Fastening the 24V DC plug
4. Connect the connection cable for connecting to ECOTAP VPD MD&C to connection COM 2 on the CPU assembly.
5. Plug in the "24V DC" plug of the CPU assembly and screw it into place.
Figure24: Fastening the 24V DC plug
Maschinenfabrik Reinhausen GmbH 201842 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 43
6 Mounting
6. Plug the UI assembly plugs into the corresponding slots and engage them.
Figure25: Engaging the plug
6.4.2 Mounting the device on an alternative cap rail
As an alternative, you can mount the device onto a cap rail other than that included in delivery. When doing so, note the following instructions.
6.4.2.1 Removing assemblies
If you would like to mount the device on an alternative cap rail, you must re­move the individual assemblies from the cap rail included in delivery. When doing so, observe the schematic in the connection diagram included in deliv­ery.
Figure26: Overview of assembly removal
Maschinenfabrik Reinhausen GmbH 2018 435252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 44
6 Mounting
Proceed as follows to remove the assemblies:
1. G1 QS3.241 assembly: Open the lever and remove the neutral con­ductor (N), phase conductor (L) and protective conductor .
Figure27: Removing the neutral conductor, phase conductor and protective conductor
Maschinenfabrik Reinhausen GmbH 201844 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 45
6 Mounting
2. G1 QS3.241 assembly: Open the lever and remove the wiring .
Figure28: Removing the wiring
3. UI assembly: Remove the plug for voltage measurement.
Figure29: Voltage measurement
Maschinenfabrik Reinhausen GmbH 2018 455252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 46
4. CPU assembly: Remove the "24V DC" plug.
6 Mounting
Figure30: Removing the plug (voltage supply)
5. CPU assembly: Remove the Ethernet cable.
Figure31: Removing the Ethernet cable
Maschinenfabrik Reinhausen GmbH 201846 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 47
6 Mounting
6. CPU assembly: If necessary, remove the data cable (D-Sub 9-pole).
Figure32: Removing the data cable
7. SW3-3 assembly: Remove the "24V DC" plug.
Figure33: Removing the plug (voltage supply)
8. Unhook terminal X5 from the cap rail.
9. Unhook the G1 QS3.241 assembly from the cap rail.
10. Optional: Unhook the SW3-3 assembly from the cap rail.
11. Unhook the bus rail with the CPU I and UI 3 assemblies from the cap rail.
Maschinenfabrik Reinhausen GmbH 2018 475252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 48
12. Unhook the voltage divider VD001 from the cap rail.
13. Unhook terminals X1 and X10 from the cap rail.
6.4.2.2 Fastening the cap rail
The cap rail is required to mount a bus bar or a device's remote assemblies in a control cabinet. Only use the following types of cap rails in accordance with EN 60715:
▪ TH 35-7.5 ▪ TH 35-15
The cap rail may not be painted or lacquered.
6 Mounting
WARNING
Electric shock!
Risk of fatal injury due to electrical voltage if the cap rail is not connected to the protective ground.
► Connect the cap rail to the protective ground securely (e.g. with a protec-
tive conductor line-up terminal).
► Ensure that the cap rail is connected securely to the protective ground via
a ground test after installation.
► Fasten the cap rail to the rear panel of the switch cabinet using screws
and contact washers or lock washers. The distance between the screws may be no more than 10 cm (3.94 in).
Figure34: Fastening the cap rail
Maschinenfabrik Reinhausen GmbH 201848 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 49
6 Mounting
6.4.2.3 Mounting the assemblies
To mount the assemblies on the cap rail, proceed as follows:
1. WARNING! Mount the bus rail with the CPU and UI assemblies on the
cap rail, ensuring that the bus rail engages correctly. Otherwise, it can re­sult in electric shock due to a faulty connection to the protective ground.
WARNING
Figure35: Hooking the bus rail into position
2. Optional: Hook the SW3-3 assembly into place on the cap rail.
3. Hook the G1 QS3.241 assembly into place on the cap rail.
4. Hook terminal X5 into place on the cap rail.
5. Hook the voltage divider VD001 into place on the cap rail.
6. Hook terminals X1 and X10 into place on the cap rail.
6.5 Connecting device
The following section describes how to establish the electrical connection to the device.
Electric shock!
Connection errors can lead to death, injury or property damage. ► Ground the device with a protective conductor using the grounding screw
on the housing.
► Note the phase difference of the secondary terminals for the current
transformer and voltage transformer.
► Connect the output relays correctly to the motor-drive unit.
Maschinenfabrik Reinhausen GmbH 2018 495252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 50
6 Mounting
Supply the voltage via separators and ensure that current paths can be short circuited. Fit the separator, clearly labeled, close to the device's power supply so that it is freely accessible. This ensures that the device can be re­placed with ease in the event of a defect.
Wiring information
Note this procedure for the wiring: ü To obtain a better overview when connecting cables, only use as many
leads as necessary.
ü Note the connection diagram. ü Use only the specified cables for wiring. Note the cable recommendation. ü Wire the leads to the system periphery [Section 6.5.4, Page 51].
1. Strip insulation from leads and wires.
2. Crimp stranded wires with wire end sleeves.
6.5.1 Cable recommendation
Please note the following Maschinenfabrik Reinhausen recommendation when wiring the device.
If you want to route Ethernet connections from a control cabinet or building, we recommend the use of fiber-optic cables (in accordance with the IEC 61850-90-4 recommendation).
Cable Assembly Cable type Conductor cross-sec-
tion
Power supply (external) X1 Unshielded 1.5 mm² ­Power supply (internal, 24
VDC) Voltage measurement X10 Shielded 2.5 mm² ­Current measurement UI 3 Unshielded 4 mm² ­RS485 SUB-D CPU I COM2 Shielded, pin assign-
CAN bus CPU I CAN2 Shielded 0.75 mm² 2,000 m (total CAN bus) Ethernet RJ45 CPU I Min. CAT5, shielded
Ethernet FO MC2-2, SW3-3 Duplex LC
Table9: Recommendation for connection cables
CPU I, MC2-2, SW3-3
Unshielded 1.5mm² -
0.25 mm
ment 1:1
- 100 m
S/FTP
- 2000 m
Multimode, OM3, 1310 nm
2
Max. length
140 m
Maschinenfabrik Reinhausen GmbH 201850 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 51
6 Mounting
6.5.2 Information about laying fiber-optic cable
To ensure the smooth transfer of data via the fiber-optic cable, you must en­sure that mechanical loads are avoided when laying the fiber-optic cable and later on during operation. Also observe the information from the manufac­turer of the fiber-optic cable and the following instructions:
▪ Radii must not fall below the minimum permissible bend radii (do not bend
fiber-optic cable).
▪ The fiber-optic cables must not be over-stretched or crushed. Observe the
permissible load values. ▪ The fiber-optic cables must not be twisted. ▪ Be aware of sharp edges because they can damage the fiber-optic cable's
coating during laying or can place mechanical loads on the coating later
on. ▪ Provide a sufficient cable reserve near distributor cabinets. Lay the re-
serve such that the fiber-optic cable is neither bent nor twisted when tight-
ened.
6.5.3 Mounting terminating resistor of CAN bus
If you want to operate the device in parallel operation, you need to mount a 120 Ω terminating resistor at both ends of the CAN bus. Use the plug con­nector with terminating resistor provided as an option.
Figure36: Terminating resistor of CAN bus
6.5.4 Connecting cables to the system periphery
To obtain a better overview when connecting cables, only use as many leads as necessary.
Maschinenfabrik Reinhausen GmbH 2018 515252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 52
To connect cables to the system periphery, proceed as follows: ü Use only the specified cables for wiring. Note the cable recommendation. ► Connect the lines to be wired to the device to the system periphery as
shown in the connection diagrams supplied.
6.5.5 Wiring the CPU I assembly
6 Mounting
NOTICE
Damage to the device
Assigning the connection cable pins for the COM 2 interface incorrectly can result in the device being damaged.
► Use the connection cable provided. ► Alternative: Use a connection cable in accordance with the cable recom-
mendation [Section 6.5.1, Page 50].
1. Connect the COM 2 interface (D-Sub 9-pole) to the ECOTAP VPD CON­TROL in accordance with the connection diagram.
Figure37: ECOTAP VPD CONTROL connection via COM 2 interface
Maschinenfabrik Reinhausen GmbH 201852 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 53
6 Mounting
2. Connect the ETH 2.2 interface to a PC for accessing the web-based visu­alization.
Figure38: Connection to a computer via Ethernet interface
Maschinenfabrik Reinhausen GmbH 2018 535252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 54
6 Mounting
3. Optional: Connect the ETH 1 interface to the control system (SCADA) in accordance with the connection diagram.
NOTICE
Figure39: SCADA connection
6.5.6 Wiring the UI assembly
Damage to the device due to incorrect current transformer con­nection
Connecting a grounded current transformer can lead to inadmissibly high EMC loads, causing damage to the UI assembly.
► Do not ground the current transformer.
Maschinenfabrik Reinhausen GmbH 201854 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 55
6 Mounting
To wire the UI assembly, proceed as follows:
1. Insert the leads into the respective current measurement plug terminals and fasten using a screwdriver.
Figure40: Example: Current measurement plug
2. Plug the plug into the corresponding slot and engage the plug.
3. Connect the voltage measurement leads to terminal X10.
Maschinenfabrik Reinhausen GmbH 2018 555252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 56
6.5.7 Wiring the MC 2-2/SW3-3 assembly
1. Insert the supplied SFP module into the corresponding Ethernet interface in accordance with the connection diagram and fold the clasp down.
6 Mounting
Figure41: Engaging the SFP module
2. Remove the SFP module dust plug.
Figure42: Removing the dust plug
Maschinenfabrik Reinhausen GmbH 201856 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 57
6 Mounting
3. Insert the fiber-optic cable into the SFP module.
Figure43: Inserting the fiber-optic cable
4. Insert the network cable.
Figure44: Inserting the network cable
6.5.8 Connecting the power supply
You may only connect the device to circuits with an external overcurrent pro­tection device and an all-pole isolating device, enabling the equipment to be fully de-energized if required (service, maintenance etc.).
Maschinenfabrik Reinhausen GmbH 2018 575252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 58
6 Mounting
Suitable equipment includes isolating devices in accordance with IEC 60947-1 and IEC 60947-3 (e.g. circuit breaker). Note the properties of the relevant circuits (voltage, maximum currents) when selecting the circuit breaker type. In addition, observe the following:
▪ It must be easy for the operator to access the isolating device ▪ The isolating device must be labeled for the device and circuits to be iso-
lated ▪ The isolating device may not be a part of the power line ▪ The isolating device may not interrupt the main protective conductor
Miniature circuit breaker You must fuse the power supply circuit with a miniature circuit breaker. The
miniature circuit breaker must have the following properties: ▪ Rated current: 6 to 20 A ▪ Triggering characteristic: B or C
Conductor cross-section For the power supply circuit, use a conductor cross-section suitable for the
miniature circuit breaker that you have selected, but at least 1.5mm2 (AWG
15).
Connecting the voltage supply
To connect the voltage supply, proceed as follows: ► Connect the voltage supply in accordance with the connection diagram
provided.
Maschinenfabrik Reinhausen GmbH 201858 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 59

7 Commissioning

7 Commissioning
This chapter describes how to commission the device.
NOTICE
Damage to device and system periphery
An incorrectly connected device can lead to damages in the device and sys­tem periphery.
► Check the entire configuration before commissioning. ► Prior to commissioning, be sure to check the actual voltage and operating
voltage.
7.1 Performing tests
The following description does not apply if you have ordered the device ver­sion with control cabinet. If that is the case, follow the description in the ECOTAP VPD MD&C operating instructions.
Please contact Maschinenfabrik Reinhausen GmbH (MR) if any aspect of the tests is not clear.
7.1.1 Ground test
For commissioning, carry out a ground test (check of the protective bonding impedance) in accordance with IEC 61010-1. Observe the following informa­tion when testing:
▪ Test current: 2 times the rated current of the overcurrent protection device
in the supply line. ▪ Test duration: 1 minute for each measurement point. ▪ The measured voltage between the measurement point and the protective
conductor must be less than 10V.
To carry out the ground test, proceed as follows: ► Apply the test current at the grounding terminal of the G1 PULS DIMEN-
SION QS3.241 assembly using a constant current source and measure
the voltage between the measurement point and the protective conductor. ð The measured voltage must remain less than 10V for a period of 1
minute.
Maschinenfabrik Reinhausen GmbH 2018 595252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 60
7 Commissioning
Figure45: Perform a ground test on the G1 PULS DIMENSION QS3.241 assembly
7.1.2 Performing a dielectric test
The device is tested before delivery. Note the following points if you would like to perform a dielectric test:
NOTICE
Assembly Interfaces Test parameters
UI 3 N, L1, L2, L3
k1, l1, k2, l2, k3, l3 2.2 kV AC 2 s 5s
G1 (PULS) N, L > 4 mA
Table10: Permitted interfaces and test parameters for the dielectric test
Damage to the device!
A dielectric test with a test voltage that is greater than the maximum permit­ted test voltage can lead to the device being damaged.
► Perform the dielectric test with a test voltage that is less than or equal to
the maximum permitted test voltage.
► Perform the dielectric test using the permitted interfaces only.
Depending on the device configuration, you may only test the assemblies listed below. You may not test any other assemblies.
Max. test voltage Max. test dura-
tion
Ramp Breaking current
threshold
> 4 mA
Maschinenfabrik Reinhausen GmbH 201860 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 61
7 Commissioning
Sample dielectric test set-up
Figure46: Sample dielectric test set-up for a device designed with the G1 (PULS) power supply
7.2 Establishing connection to visualization
The device is supplied with the IP address 192.0.1.230 at the factory.
Maschinenfabrik Reinhausen GmbH 2018 615252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 62
7 Commissioning
To connect via the ETH2.2 interface on the CPU assembly, proceed as fol­lows:
1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the ETH2.2 interface.
Figure47: Establishing a connection via the ETH2.2 interface
2. Assign a unique IP address to the PC in the same subnet as the device (e.g. 192.0.1.100).
3. Enter the visualization's IP address (e.g. http://192.0.1.230, if SSL encryption is active enter https://192.0.1.230) on the PC in the browser.
ð The visualization has been accessed.
7.3 Setting parameters
Commissioning the device requires setting some parameters. There are 2 options available for this:
▪ Commissioning wizard ▪ Setting the parameters manually
7.3.1 Commissioning wizard
If you want the device to help when setting the relevant parameters, you can use the commissioning wizard. The commissioning wizard provides a selec­tion of parameters that you can configure in order.
A detailed description of each of the parameters can be found in the Opera­tion [Section 8, Page 66] chapter.
Maschinenfabrik Reinhausen GmbH 201862 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 63
7 Commissioning
To call up the commissioning wizard, you will need the necessary access rights [Section 8.13, Page 145].
When in delivery status, you can log in as the administrator as follows: ▪ User name: admin ▪ Password: admin
To set the parameters with the help of the commissioning wizard, proceed as follows:
1. Log in as a user with the necessary access rights.
2. Go to Settings > Commissioning wizard.
Figure48: Calling up the commissioning wizard
3. Press the Next button to launch the commissioning wizard.
4. Follow the on-screen instructions.
Once you have entered all of the parameters relevant to commissioning, continue with the function test.
7.3.2 Setting the parameters manually
To commission the device, you must set the following parameters. You will find more detailed information about these parameters in the respective sec­tions.
To set the parameters, you need the necessary access rights [Section
8.13, Page 145].
Maschinenfabrik Reinhausen GmbH 2018 635252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 64
When in delivery status, you can log in as the administrator as follows: ▪ User name: admin ▪ Password: admin
7.3.2.1 Setting the language
You can use this parameter to set the display language for the device. The device comes with a maximum of 4 languages. The following languages are available:
English Italian* German Portuguese* French* Russian* Spanish* Chinese* Korean* -
*) Language is available as an option
7 Commissioning
To set the language, proceed as follows:
1. Press the Language button in the status bar.
Figure49: Setting the language
2. Select the language you want from the list box.
3. Press the Accept button to save the modified parameter. ð The "Restart device" dialog appears.
4. Restart the device to apply the changed language setting.
7.3.2.2 Setting date and time
You can set the date and time in the following ways: ▪ Manually ▪ Time synchronization via control system (SCADA) ▪ Time synchronization via SNTP time server
If you are using a control system, the device automatically synchronizes the date and time with the control system. If you would like to use an SNTP time server, you must set the required parameters. When doing so, observe the information provided in the Time synchronization [Section 8.12, Page 142] section.
If you would like to set the date and time manually, you must enter the val­ues in the following formats:
Date Time
DD.MM.YYYY HH:MM
Table11: Formats
Maschinenfabrik Reinhausen GmbH 201864 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 65
7 Commissioning
The time does not switch from daylight saving time to standard time and back automatically.
Proceed as follows to set the date and time manually:
1. Go to Settings > Time.
Figure50: Setting date and time
2. Enter date and time.
3. Press the Accept button to save the modified parameter.
7.3.2.3 Setting further parameters
Set further parameters to commission the device. You will find more detailed information about the respective parameters in the Operation [Section 8, Page 66] chapter.
1. Activate ECOTAP VPD communication [Section 8.3, Page 70].
2. Set transformer data [Section 8.5, Page 81].
3. Set control parameters [Section 8.4, Page 71].
4. Set control system protocol (optional) [Section 8.11, Page 119].
Maschinenfabrik Reinhausen GmbH 2018 655252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 66

8 Operation

This chapter describes all the functions and setting options for the device.
8.1 Establishing connection to visualization
The device is supplied with the IP address 192.0.1.230 at the factory.
To connect via the ETH2.2 interface on the CPU assembly, proceed as fol­lows:
1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the ETH2.2 interface.
8 Operation
Figure51: Establishing a connection via the ETH2.2 interface
2. Assign a unique IP address to the PC in the same subnet as the device (e.g. 192.0.1.100).
3. Enter the visualization's IP address (e.g. http://192.0.1.230, if SSL encryption is active enter https://192.0.1.230) on the PC in the browser.
ð The visualization has been accessed.
8.2 General
You can set general parameters in this menu item:
Maschinenfabrik Reinhausen GmbH 201866 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 67
8 Operation
General settings
▪ Display language for the device
– Can also be set via the status bar [Section 7.3.2.1, Page 64]
▪ Activate/deactivate launching the commissioning wizard after the device is
restarted ▪ Measured value display ▪ Transformer name ▪ Remote behavior
Settings for web-based visualization
▪ IP address ▪ Subnet mask ▪ Gateway address ▪ SSL encryption
Figure52: General
8.2.1 Activating/deactivating automatic launch of commissioning wizard
You can use this parameter to set whether the commissioning wizard [Section 7.3.1, Page 62] is to launch automatically when the device is restarted.
1. Go to Settings > Parameters > General > Commissioning wizard.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
8.2.2 Setting measured value display
This parameter lets you set whether the displayed measured values and control parameters are to refer to the primary side or secondary side.
Maschinenfabrik Reinhausen GmbH 2018 675252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 68
To set the measurement transformer display, proceed as follows:
1. Go to Settings > Parameters > General > Measured value display.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
8.2.3 Remote behavior
You can use this parameter to select the behavior of the device in remote operating mode. You can select the following options:
Option Description
Hardware only No function. SCADA only The device accepts commands via SCADA. Hardware and SCADA The device accepts commands via SCADA.
Table12: Selecting Remote behavior
To set the Remote behavior, proceed as follows:
1. Go to Settings > Parameters > General > Remote behavior.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
8 Operation
8.2.4 Visualization
The device is equipped with a web-based visualization. This allows you to configure the device with a computer and to display measured values.
You can establish a link to the visualization via the ETH2.2 interface on the CPU assembly (for access via remote display, control center etc.).
System requirements
To access the web-based visualization, you need a PC with an HTML5-ca­pable browser. The display is optimized for the following browsers:
▪ Microsoft® Internet Explorer 10 or higher ▪ Google Chrome™
To establish a connection to the visualization, please observe the following sections.
8.2.4.1 Configuring visualization
You can use the following parameters to configure the interface for the visu­alization. The following parameters are available:
▪ IP address ▪ Subnet mask
Maschinenfabrik Reinhausen GmbH 201868 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 69
8 Operation
▪ Gateway address ▪ SSL encryption
IP address, subnet mask and gateway address
You can use these parameters to undertake the network configuration for the visualization. These settings apply to access via the ETH2.2 interface on the CPU module.
Assign IP addresses to both web-based visualization and SCADA (optional) in different subnets. Otherwise you will not be able to establish a connec­tion.
1. Go to Settings > Parameters > General > IP address, Subnet mask or
Gateway.
2. Enter the desired value.
3. Press the Accept button to save the modified parameter.
Activating SSL/TLS encryption
You can use this parameter to set whether access to the visualization should take place over an SSL-encrypted connection.
To activate SSL encryption, proceed as follows:
1. Go to Settings > Parameters > General > SSL/TLS encryption.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
Setting the TLS version
You can use this parameter to set the accepted TLS versions. If you would like to establish an encrypted connection to the visualization, you must use an accepted TLS version. You can select the following options:
Option Accepted TLS versions
>= 1.0 ▪ 1.0
▪ 1.1 ▪ 1.2
>= 1.1 ▪ 1.1
▪ 1.2
1)
>= 1.2
Table13: TLS version
▪ 1.2
1)
This option can be selected only if the TLS versions are supported by the
connected peripheral equipment.
To set the TLS version, proceed as follows:
1. Go to Settings > Parameters > General > TLS version.
Maschinenfabrik Reinhausen GmbH 2018 695252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 70
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
8.2.4.2 Accessing online help
The web-based visualization has an online help section. To call up the online help, proceed as follows:
1. Call up the web-based visualization with the PC.
2. Select the MR logo in the status line. ð The online help appears.
8.2.5 Activating/deactivating the USB interface
This parameter lets you deactivate the USB interface. You can select the fol­lowing options:
▪ On: USB interface is activated ▪ Off: USB interface is deactivated
8 Operation
Proceed as follows to activate/deactivate the USB interface:
1. Go to Settings > Parameters > General > USB interface.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
8.3 Unlocking ECOTAP VPD communication
With an ECOTAP Pro, you can unlock communication to an ECOTAP VPD Control a maximum of three times. The number of remaining unlocking ac­tions is displayed in the dialog window.
Figure53: Unlocking ECOTAP VPD communication
Maschinenfabrik Reinhausen GmbH 201870 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 71
8 Operation
Proceed as follows to unlock communication between the ECOTAP VPD Control and ECOTAP Pro:
ü There is a connection between the ECOTAP VPD Control and ECOTAP
Pro.
1. Go to Settings > ECOTAP VPD Comm..
2. Press the Continue button to unlock communication with the connected
ECOTAP VPD Control.
8.4 Control
All of the parameters required for the regulation function are described in this section.
Figure54: Setting the control parameters (example)
8.4.1 Setting the desired value
In accordance with the order, the device is equipped with one of the follow­ing variants for setting the desired value:
8.4.1.1 Desired value 1
You have to set the parameters for both winding 1 (W1) and winding 2 (W2).
To set the desired value, proceed as follows:
1. Go to Settings > Parameters > Control > Desired value.
2. Enter desired value.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 2018 715252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 72
8 Operation
8.4.1.2 Active power-dependent adjustment of desired voltage value
The TAPCON® Dynamic Setpoint Control (TDSC) function is used to adapt the desired voltage value depending on the measured active power. This al­lows you to compensate for a voltage drop during increased load or a volt­age increase due to a decentralized feed-in.
Depending on whether positive or negative active power is measured, the desired value calculation is based on 2 linear equations (see example in dia­gram below).
Parameter Function Settings (see diagram
below)
U
: Maximum desired value Maximum set desired value is activated when P
max
exceeded.
U
: Minimum desired value Minimum set desired value is activated when value falls
min
U0: Desired value at 0 active power
P
: Active power at max. de-
max
sired value
P
: Active power at min. desired
min
value
Table14: Parameters to be set for active power-dependent adjustment of desired voltage value
below P
min
.
Set desired value is activated when measured active power is 0MW.
Set maximum active power value above which the power-dependent desired value is to attain the maxi­mum value U
max
.
Set minimum active power value below which the power-dependent desired value is to attain the mini­mum value U
min
.
max
is
103.0 V
99.0 V
100.00 V
20.0 MW
-20.0 MW
Figure55: Active power-dependent adjustment of desired voltage value
U
ref
P
meas
Desired value U Measured active power U
min
max
Minimum desired value Maximum desired value
Maschinenfabrik Reinhausen GmbH 201872 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 73
8 Operation
P
min
P
max
Active power at minimum de­sired value
Active power at maximum de-
U
0
Set desired value when mea­sured active power = 0
sired value
Response to active power P
If the measured active power P U
is adopted as the desired value.
max
being exceeded
max
exceeds the set parameter P
meas
Response to value falling below active power P
If the measured active power P value U
is adopted as the desired value.
min
Response to a measured active power P
falls below the set parameter P
meas
= 0 MW:
meas
min
, the value
max
, the
min
If the measured active power P
= 0, the set parameter U0 is adopted.
meas
Linear dependency with negative active power:
If the measured active power P
min
≤ P
≤ 0, the desired value is calculated
meas
using the following formula:
Linear dependency with positive active power:
If the measured active power 0 ≤ P
meas
≤ P
, the desired value is calculated
max
using the following formula:
Maschinenfabrik Reinhausen GmbH 2018 735252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 74
8 Operation
To activate the active power-dependent adjustment of the desired voltage value, you need to set the following parameters:
You have to set the parameters for both winding 1 (W1) and winding 2 (W2).
Activating TDSC
The TDSC function is only active when the device can calculate the active power (correct current measurement and voltage measurement) and the re­quired parameters are set. If this is not the case, voltage regulation is in ac­cordance with the set desired value [Section 8.4.1.1, Page 71]. You can activate or deactivate the power-dependent adjustment of the desired volt­age value as follows:
▪ Parameters ▪ Control system command (optional)
If you activate TDSC, the line drop compensation (R&X compensation or Z compensation) function is deactivated.
To activate/deactivate TDSC using parameters, proceed as follows:
1. Go to Settings > Parameters > Control > Activate TDSC.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
TDSC Umax/Umin
You can use these parameters to set the maximum and minimum desired value. The maximum or minimum desired value is activated when the mea­sured active power reaches the set minimum or maximum active power.
1. Go to Settings > Parameters > Control > TDSC Umax/Umin.
2. Enter maximum/minimum desired value.
3. Press the Accept button to save the modified parameter.
TDSC U0
You can use this parameter to set the desired value which is to be used when the measured active power is 0.
1. Go to Settings > Parameter > Control > TDSC U0.
2. Enter desired value at active power 0.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 201874 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 75
8 Operation
TDSC Pmax/Pmin
You can use these parameters to set the maximum and minimum active power value at which the maximum and minimum active power-dependent desired value is to be used for regulation.
1. Go to Settings > Parameters > Control > TDSC Pmax/Pmin.
2. Enter active power for maximum/minimum desired value.
3. Press the Accept button to save the modified parameter.
8.4.2 Bandwidth
You can use this parameter to set the maximum permissible deviation in measured voltage U describes how you determine and set the bandwidth.
Determining bandwidth
In order to set the correct value, the transformer's step voltage and nominal voltage must be known. Note that a large bandwidth will result in a large control deviation.
from the desired value U
actual
. The following section
desired
The bandwidth must always be greater than the following value:
Figure56: Calculation of minimum bandwidth
U
n-1
U
n
U
nom
Step voltage of tap position n-1 Step voltage of tap position n Nominal voltage
The following transformer values are used to determine the minimum band­width:
Nominal voltage U
Step voltage in tap position 4 U
Step voltage in tap position 5 U
= 11,000 V
nom
= 11,275 V
Step4
= 11,000 V
Step5
Maschinenfabrik Reinhausen GmbH 2018 755252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 76
Setting the bandwidth
To set the bandwidth, proceed as follows:
1. Go to Settings > Parameters > Control > Bandwidth.
2. Enter bandwidth.
3. Press the Accept button to save the modified parameter.
8.4.3 Delay time T1
Delay time T1 delays the issuing of a tap-change command for a defined pe­riod. This prevents unnecessary tap-change operations if the tolerance bandwidth is exited briefly.
Behavior only with delay time T1
8 Operation
If the measured voltage U
is within the set bandwidth , no control
actual
commands are issued to the motor-drive unit for the tap-change operation. Control commands will also not be issued to the motor-drive unit if the mea-
sured voltage returns to the tolerance bandwidth within the set delay time T1 . However, if the measured voltage deviates from the set bandwidth for a long period , a tap-change command occurs after expiration of the
set delay time T1. The on-load tap-changer carries out a tap-change in a raise or lower direction to return to the tolerance bandwidth.
Figure57: Behavior of the regulation function with delay time T1
1 +B%: Upper limit 4 Set delay time T1 2 U 3 -B%: Lower limit 6 B%: Tolerance bandwidth
: Desired value 5 U
desired
: Measured voltage
actual
Maschinenfabrik Reinhausen GmbH 201876 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 77
8 Operation
A U
C U
is outside the bandwidth. De-
actual
lay time T1 starts.
is outside the bandwidth. De-
actual
lay time T1 starts.
B U
is within the bandwidth be-
actual
fore delay time T1 is complete.
D U
is still outside the bandwidth
actual
when delay time T1 is complete. Tap-change operation is initiated.
Setting delay time T1
To set the delay time T1, proceed as follows:
1. Go to Settings > Parameters > Control > Delay time T1.
2. Enter delay time T1.
3. Press the Accept button to save the modified parameter.
Selecting time response T1
You can use this parameter to set the time response for delay time T1. You can select the following options:
▪ Linear time response ▪ Integral time response
Linear time response With linear time response, the device responds with a constant delay time
regardless of the control deviation.
Maschinenfabrik Reinhausen GmbH 2018 775252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 78
8 Operation
Integral time response With integral time response, the device responds with a variable delay time
depending on the control deviation. The greater the control deviation (ΔU) in relation to the set bandwidth (B), the shorter the delay time. This means that the device responds faster to large voltage changes in the grid. Regulation accuracy improves as a result but the frequency of tap-changes increases too.
Figure58: Diagram for integral time response
ΔU/B Control deviation "ΔU" as % of desired value in relation to the set band-
width "B" as % of desired value
1 "Delay time T1" parameter
To set the time response T1, proceed as follows:
1. Go to Settings > Parameters > Control > Time response T1.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
8.4.4 Delay time T2
You can use this parameter to set the delay time T2. Delay time T2 is used to compensate for large control deviations faster.
The delay time T2 only takes effect if more than one tap-change operation is required to correct the control deviation. The first output pulse occurs after the set delay time T1. After the set tap-change delay time T2 has elapsed, additional pulses occur in order to correct the existing control deviation.
The following requirements must be noted to set delay time T2: ▪ The delay time T2 must be greater than the switching pulse time. ▪ The delay time T2 must be greater than the maximum operating time of
the motor-drive unit.
▪ The delay time T2 must be less than the value set for delay time T1.
Maschinenfabrik Reinhausen GmbH 201878 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 79
8 Operation
Behavior with delay times T1 and T2
Delay time T2 can be used to correct major control deviations more quickly. Ensure that you set a lower value in the "Delay time T2" parameter than in the "Delay time T1" parameter.
If the measured voltage U
deviates from the set bandwidth for a long
actual
period , a control impulse is output to the motor-drive unit after the set de­lay time T1 . If the measured voltage U
is still outside the bandwidth,
actual
delay time T2 starts once delay time T1 is complete. Once delay time T2 is complete, a control impulse is again output to the motor-drive unit for the
tap change to return to the tolerance bandwidth.
Figure59: Behavior of the regulation function with delay times T1 and T2
1 +B%: Upper limit 4 Set delay times T1 and T2. 2 U
: Desired value 5 U
desired
: Measured voltage
actual
3 -B%: Lower limit 6 B%: Tolerance bandwidth
A U
is outside the bandwidth. De-
actual
lay time T1 starts.
B Delay time T1 complete. Tap
change triggered.
C Delay time T2 complete. Tap
change triggered.
Setting delay time T2
To set the delay time T2 proceed as follows:
1. Go to Settings > Parameters > Control > Delay time T2.
2. Set delay time T2.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 2018 795252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 80
Activating delay time T2
To activate delay time T2, proceed as follows:
1. Go to Settings > Parameters > Control > Activate delay T2.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
8.4.5 Setting regulation mode
If you are measuring the voltage and current with the 3-phase UI 3 measur­ing module, you can use this parameter to set whether you want 1-phase voltage regulation or voltage regulation to the average value of the 3 phases. You can select the following options:
▪ Single-phase: Voltage is automatically regulated to one selected phase.
Limit value monitoring, line drop compensation, and parallel operation also take place on the selected phase using the circulating reactive cur­rent minimization method.
▪ Average value regulation: Voltage is automatically regulated to the aver-
age of the 3 phases. Limit value monitoring, line drop compensation, and parallel operation also take place using the circulating reactive current minimization method to the average of the 3 phases.
8 Operation
If you activate the average value regulation option, automatic voltage regu­lation is blocked should the voltage or current measurement of one of the 3 phases fail.
To set the regulation mode, proceed as follows:
1. Go to Settings > Parameters > Measurement.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
8.4.6 Setting control variables
If you are measuring the voltage and current with the 3-phase UI 3 measur­ing module and using the "single-phase" regulation mode, this parameter can be used to select the phase used for voltage regulation. You can select the following options:
▪ L1/N or L1/L2 ▪ L2/N or L2/L3 ▪ L3/N or L3/L1
To set the control variable, proceed as follows:
1. Go to Settings > Parameters > Measurement.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 201880 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 81
8 Operation
8.5 Transformer data
The transformation ratios and measuring set-up for the voltage and current transformers used in the system can be set with the following parameters. The device uses this information to calculate the corresponding measured values on the primary side of the current transformer (and therefore the transformer) from the recorded measured values. These are then displayed.
Figure60: Setting transformer data (example)
8.5.1 Setting the primary transformer voltage
With this parameter, you can set the primary voltage of the voltage trans­former in kV.
To set the primary transformer voltage, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Primary trans-
former voltage.
2. Enter the primary transformer voltage.
3. Press the Accept button to save the modified parameter.
8.5.2 Setting the secondary transformer voltage
With this parameter, you can set the secondary voltage of the voltage trans­former in V.
To set the secondary transformer voltage, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Secondary trans-
former voltage.
2. Enter the secondary transformer voltage.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 2018 815252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 82
8.5.3 Setting primary transformer current
You can use this parameter to set the primary current of the current trans­former.
To set the primary transformer current, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Primary trans- former current.
2. Enter the primary transformer current.
3. Press the Accept button to save the modified parameter.
8.5.4 Setting the secondary transformer current
You can use this parameter to set the secondary current of the current trans­former. You can select the following options:
▪ 0.2 A ▪ 1 A ▪ 5 A
8 Operation
To set the secondary transformer current, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Secondary trans- former current.
2. Select the secondary transformer current.
3. Press the Accept button to save the modified parameter.
8.5.5 Setting circuit for current transformer/voltage transformer and phase angle correction
To configure the circuit for the current transformer and voltage transformer, you must set the following parameters:
Parameter UI 3 measuring module
1-channel* 3-channel*
Voltage-transformer circuit Yes No Current-transformer circuit Yes No Phase angle correction Yes No Measurement mode No Yes
Table15: Setting configuration of current transformer and voltage transformer (UI 3 measuring module)
*) According to setting of UI measuring channels [Section 8.6.1, Page 91] parameter.
Note the following examples of common transformer circuits:
Maschinenfabrik Reinhausen GmbH 201882 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 83
8 Operation
Circuit A
▪ The voltage transformer VT is connected to the phase conductor and neu-
tral conductor. ▪ The current transformer CT is looped into the phase conductor. ▪ The voltage UL1 and current IL1 are in phase. ▪ The voltage drop on a phase conductor is determined by the current IL1.
If you use this circuit, set the device as follows:
Parameter Option
Voltage-transformer circuit 1 Ph phase voltage Current-transformer circuit 1 Ph phase current Phase angle correction
Table16: Circuit A
Circuit B
▪ The voltage transformer VT is connected to the phase conductor L1 and
the neutral conductor. ▪ The current transformer CT is looped into the phase conductor L1. ▪ The voltage U and current I are in phase. ▪ The voltage drop on a phase conductor is determined by the current IL1.
Maschinenfabrik Reinhausen GmbH 2018 835252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 84
If you use this circuit, set the device as follows:
Parameter Option
Voltage-transformer circuit 3 Ph phase voltage Current-transformer circuit 3 Ph phase current Phase angle correction
Table17: Circuit B
Circuit C
8 Operation
▪ The voltage transformer VT is connected to the phase conductors L1 and
L2.
▪ The current transformer CT1 is looped into the phase conductor L1 and
CT2 into the phase conductor L2.
▪ The current transformers CT1 and CT2 are connected crosswise in paral-
lel (total current = IL1 + IL2). ▪ The total current IL1 + IL2 and voltage UL1-UL2 are in phase. ▪ The voltage drop on a phase conductor is determined by the current: (IL1 +
IL2) / √3.
If you use this circuit, set the device as follows:
Parameter Option
Voltage-transformer circuit 3 Ph differential voltage Current-transformer circuit 3 Ph total current Phase angle correction
Table18: Circuit C
Maschinenfabrik Reinhausen GmbH 201884 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 85
8 Operation
Circuit D
▪ The voltage transformer VT is connected to the phase conductors L1 and
L2. ▪ The current transformer CT is looped into the phase conductor L3. ▪ The current IL3 is ahead of voltage UL1-VL2 by 90°. This corresponds to a
phase shift of -90°. ▪ The voltage drop on a phase conductor is determined by the current IL3.
If you use this circuit, set the device as follows:
Parameter Option
Voltage-transformer circuit 3 Ph differential voltage Current-transformer circuit 3 Ph phase current Phase angle correction 90°
Table19: Circuit D
Circuit E
▪ The voltage transformer VT is connected to the phase conductors L1 and
L2. ▪ The current transformer CT is looped into the phase conductor L2. ▪ The current IL2 is ahead of voltage UL2-UL1 by 30°. This corresponds to a
phase shift of -30°. ▪ The voltage drop on a phase conductor is determined by the current IL2.
Maschinenfabrik Reinhausen GmbH 2018 855252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 86
If you use this circuit, set the device as follows:
Parameter Option
Voltage-transformer circuit 3 Ph differential voltage Current-transformer circuit 3 Ph phase current Phase angle correction 30°
Table20: Circuit E
Circuit F
8 Operation
▪ The voltage transformer VT is connected to the phase conductors L1 and
L2. ▪ The current transformer CT is looped into the phase conductor L1. ▪ The current IL1 lags behind UL1-UL2 by 30°. This corresponds to a phase
shift of +30° and a correction value of -30°. ▪ The voltage drop on a phase conductor is determined by the current IL1.
If you use this circuit, set the device as follows:
Parameter Option
Voltage-transformer circuit 3 Ph differential voltage Current-transformer circuit 3 Ph phase current Phase angle correction -30°
Table21: Circuit F
Maschinenfabrik Reinhausen GmbH 201886 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 87
8 Operation
Circuit G
▪ Three-phase measurement. ▪ The voltage transformers are connected between the phases. ▪ The current lags behind the voltage by 30°.
If you use this circuit, set the device as follows:
Parameter Option
Voltage-transformer circuit ­Current-transformer circuit ­Phase angle correction 0° UI measuring channels 3-phase measurement (channels 1, 2, 3) Measurement mode Phase-phase
Table22: Circuit G
Circuit H
▪ Three-phase measurement. ▪ The voltage transformers are connected between the phase and neutral
conductor.
Parameter Option
Voltage-transformer circuit ­Current-transformer circuit -
Maschinenfabrik Reinhausen GmbH 2018 875252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 88
8 Operation
Parameter Option
Phase angle correction 0° UI measuring channels 3-phase measurement (channels 1, 2, 3) Measurement mode Phase-neutral
Table23: Circuit H
Only use the circuits I, J and K on symmetrical grids. Otherwise the device will calculate incorrect performance values.
Circuit I
▪ Three-phase voltage measurement, single-phase current measurement. ▪ The voltage transformers are connected between the phases. ▪ The current transformer is connected to phase L1.
If you use this circuit, set the device as follows:
Parameter Option
Voltage-transformer circuit ­Current-transformer circuit ­Phase angle correction -30° UI measuring channels 3-ph. voltage, 1-ph. current Measurement mode Phase-phase
Table24: Circuit I
Maschinenfabrik Reinhausen GmbH 201888 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 89
8 Operation
Circuit J
▪ Three-phase voltage measurement, single-phase current measurement. ▪ The voltage transformers are connected between the phases. ▪ The current transformer is connected to phase L2.
Parameter Option
Voltage-transformer circuit ­Current-transformer circuit ­Phase angle correction -150° UI measuring channels 3-ph. voltage, 1-ph. current Measurement mode Phase-phase
Table25: Circuit J
Circuit K
▪ Three-phase voltage measurement, single-phase current measurement. ▪ The voltage transformers are connected between the phases. ▪ The current transformer is connected to phase L3.
Parameter Option
Voltage-transformer circuit ­Current-transformer circuit ­Phase angle correction 90°
Maschinenfabrik Reinhausen GmbH 2018 895252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 90
8 Operation
Parameter Option
UI measuring channels 3-ph. voltage, 1-ph. current Measurement mode Phase-phase
Table26: Circuit K
Setting voltage-transformer circuit
You can use this parameter to set your voltage transformer's circuit. You can select the following options:
Option Description
1 Ph phase voltage Measurement in 1-phase grid between
the conductor and neutral conductor.
3 Ph differential voltage Measurement in 3-phase grid between 2
conductors
3 Ph phase voltage Measurement in 3-phase grid between
conductor and neutral conductor
Table27: Voltage-transformer circuit
To set the voltage-transformer circuit, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Voltage-trans-
former circuit.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
Setting current-transformer circuit
You can use this parameter to set the circuit for your current transformer. You can select the following options:
Option Description
1 Ph phase current Measurement of phase current in 1-phase
grid.
3 Ph total current Measurement of differential current in 3-
phase grid.
3 Ph phase current Measurement of phase current in 3-phase
grid.
Table28: Current-transformer circuit
To set the current-transformer circuit, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Current-trans-
former circuit.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 201890 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 91
8 Operation
Setting phase angle correction
You can use this parameter to set the phase angle correction for your trans­former circuit. To do so, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Phase angle cor- rection.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
Setting measurement mode
If you are measuring the voltage and current with the 3-phase UI 3 measur­ing module, you can use this parameter to set whether you have connected the voltage transformer between 2 phases or between a phase and neutral.
To set the measuring mode, proceed as follows:
1. Go to Settings > Parameters > Transformer data > Measuring mode.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
Also refer to
2 Setting UI measuring channels [91]
8.6 Measurement
8.6.1 Setting UI measuring channels
If you are measuring the voltage and current with the 3-phase UI 3 measur­ing module, you can use this parameter to set the measurement channels in use:
Option Description
1-ph. measurement: Channel 1 The device uses 1 channel each for measure-
ment of voltage and current.
3-ph. measurement: Channel 1, 2, 3
3-ph. voltage, 1-ph. current The device uses 3 channels for voltage measure-
Table29: UI measuring channels
To set the UI measuring channels, proceed as follows:
1. Go to Settings > Parameters > Measurement > UI measuring chan- nels.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
The device uses 3 channels each for measure­ment of voltage and current.
ment and 1 channel for current measurement.
Maschinenfabrik Reinhausen GmbH 2018 915252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 92
8.6.2 Control variable
If you are measuring the voltage and current with the 3-phase UI 3 measur­ing module and using the "single-phase" regulation mode, this parameter can be used to select the phase used for voltage regulation. You can select the following options:
▪ L1/N or L1/L2 ▪ L2/N or L2/L3 ▪ L3/N or L3/L1
To set the control variable, proceed as follows:
1. Go to Settings > Parameters > Measurement > Control variable.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
8.6.3 Regulation mode
If you are measuring the voltage and current with the 3-phase UI 3 measur­ing module, you can use this parameter to set whether you want 1-phase voltage regulation or voltage regulation to the average value of the 3 phases. You can select the following options:
▪ Single-phase: Voltage is automatically regulated to one selected phase.
Limit value monitoring, line drop compensation, and parallel operation also take place on the selected phase using the circulating reactive cur­rent minimization method.
▪ Average value regulation: Voltage is automatically regulated to the aver-
age of the 3 phases. Limit value monitoring, line drop compensation, and parallel operation also take place using the circulating reactive current minimization method to the average of the 3 phases.
8 Operation
If you activate the average value regulation option, automatic voltage regu­lation is blocked should the voltage or current measurement of one of the 3 phases fail.
To set the regulation mode, proceed as follows:
1. Go to Settings > Parameters > Measurement > Regulation mode.
2. Select the option you want.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 201892 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 93
8 Operation
8.6.4 Setting the display for the power factor
This parameter lets you set whether the device is to display a negative power factor. You can select the following options:
Option Description
Off The power factor is always shown as positive. P > 0 The power factor is shown as negative if the active power is
positive.
P < 0 The power factor is shown as negative if the active power is
negative.
Q > 0 The power factor is shown as negative if the reactive power is
positive.
Q < 0 The power factor is shown as negative if the reactive power is
negative.
Table30: Setting the display for the power factor
To set the power factor display, proceed as follows:
1. Go to Settings > Parameters > Measurement > Negative power factor display.
2. Select the desired option.
3. Press the Accept button to save the modified parameter.
8.7 Line drop compensation
You can use the compensation function to compensate for the load-depen­dent voltage drop between the transformer and consumer. The device pro­vides 2 methods of compensation for this purpose:
▪ R&X compensation ▪ Z compensation
Figure61: Setting line drop compensation
Maschinenfabrik Reinhausen GmbH 2018 935252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 94
Note the description below for configuration of line drop compensation.
8.7.1 R&X compensation
R&X compensation can compensate for voltage losses on the lines and therefore ensure correct voltage on the consumer. This requires precise line data. After you have entered all of the line data, the device automatically cal­culates the ohmic and inductive voltage drop and takes this into account for automatic voltage regulation.
8 Operation
Figure62: Equivalent circuit of R&X compensation
Figure63: Phasor diagram of R&X compensation
To use R&X compensation, you have to enter the following line data: ▪ Ohmic resistance load in mΩ/m ▪ Inductive resistance load in mΩ/m ▪ Length of line in km
Selecting R&X compensation
To select R&X compensation, proceed as follows:
1. Go to Settings > Parameters > Compensation > Compensation method.

2. Select R&X compensation option.

3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 201894 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 95
8 Operation
Setting ohmic resistance load
To enter the value for ohmic resistance load, proceed as follows:
1. Go to Settings > Parameters > Compensation > Ohmic resistance load.
2. Enter ohmic resistance load.
3. Press the Accept button to save the modified parameter.
Setting inductive resistance load
To enter the value for inductive resistance load, proceed as follows:
1. Go to Settings > Parameters > Compensation > Inductive resistance load.
2. Enter inductive resistance load.
3. Press the Accept button to save the modified parameter.
Entering length of line
To enter the length of line, proceed as follows:
1. Go to Settings > Parameters > Compensation > Length of line.
2. Enter length of line.
3. Press the Accept button to save the modified parameter.
8.7.2 Z compensation
To keep the voltage constant for the consumer, you can use Z compensation to activate a current-dependent increase in voltage. You can also define a limit value to avoid excess voltage on the transformer.
Figure64: Z compensation
Maschinenfabrik Reinhausen GmbH 2018 955252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 96
8 Operation
To use Z compensation, you need to calculate the increase in voltage (ΔU) taking the current into account. Use the following formula for this purpose:
∆U Voltage increase I Load current in A U
U
Transformer voltage at current I I
Tr
Voltage on line end at current I
Load
and on-load tap-changer in same operating position
N
k
Nominal current of current-trans­former connection in A
Transmission ratio of current
CT
transformer
Sample calculation: UTr = 100.1 V, U
= 100.0 V, IN = 5 A kCT = 200 A/5 A,
Load
I = 100 A Produces a voltage increase ∆U of 0.2%
The following sections describe how you can set the parameters you need for Z compensation.
Selecting Z compensation
To select Z compensation, proceed as follows:
1. Go to Settings > Parameters > Compensation > Compensation method.
2. Select the Z compensation option.
3. Press the Accept button to save the modified parameter.
Setting the current-dependent voltage increase
You can use this parameter to set the voltage increase ∆U.
To set the limit value for voltage increase ΔU, proceed as follows:
1. Go to Settings > Parameters > Compensation > Voltage increase.
2. Enter voltage increase.
3. Press the Accept button to save the modified parameter.
Setting voltage limit value
You can use this parameter to define the maximum permissible voltage in­crease to avoid excess voltage on the transformer.
To set the voltage limit value, proceed as follows:
1. Go to Settings > Parameters > Compensation > Voltage limit value.
2. Enter voltage limit value.
3. Press the Accept button to save the modified parameter.
Maschinenfabrik Reinhausen GmbH 201896 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 97
8 Operation
Master Follower
Tap position
CAN bus
M AVR MAVR
T1 T2
8.8 Tap position capture
The current tap position of the on-load tap-changer is transmitted from the ECOTAP VPD MD&C controller to the CONTROL PRO controller. No further settings are necessary for this.
8.9 Parallel operation (optional)
Parallel transformer operation is used to increase the throughput capacity or short-circuit capacity at one location. The device provides you with specific functions for regulating transformers.
Conditions for parallel
operation
8.9.1 Parallel operation methods
8.9.1.1 Tap synchronization
Compliance with the following general conditions is required for operating transformers in parallel:
▪ Identical rated voltages ▪ Transformer power ratio (<3:1) ▪ Maximum deviation of short-circuit voltages (UK) for transformers con-
nected in parallel <10% ▪ Same number of switching groups ▪ For parallel operation with CAN communication: Current transformers with
the same rated values must be used for all devices operating in parallel
You can undertake parallel operation with various parallel operation meth­ods.
With the tap synchronization parallel operation method, one voltage regu­lator works as the master and all others as followers.
Figure65: Tap synchronization
Maschinenfabrik Reinhausen GmbH 2018 975252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 98
8 Operation
The master handles voltage regulation and transmits its current tap positions to all followers via the CAN bus. The followers compare the tap position re­ceived with their own tap position. If the tap position is not the same, the fol­lowers switch to the tap position received from the master. This ensures that the transformers operating in parallel are always in the same tap position.
You can set whether the master transfers the change in tap position to the followers before or after its own tap-change operation. The devices then ei­ther change position sequentially (first the master, then the followers) or in synch (master and followers at the same time).
If there is a tap difference between the master and followers, the master re­frains from issuing any control commands to the motor-drive unit until all of the followers have reached the same tap position. If the tap difference per­sists for longer than the set delay time for parallel operation error messages, the master triggers the Step difference to follower event.
You can explicitly designate the voltage regulators as master and followers, or set automatic designation using the CAN bus address.
For the tap synchronization parallel operation method, you have to set the following parameters:
Parameter Auto Master Follower
Activate parallel operation Yes Parallel operation method Auto. tap syn-
chronization CAN bus address Yes Circul. reactive current
blocking limit Master/follower current
blocking Master/follower switching
characteristics Maximum tap difference Yes (if follower) No Yes Error if no communication
present Behavior if no communi-
cation present Parallel operation error
delay time
Table31: Parameter
Parameter Auto Master Follower
Activate parallel operation Yes Parallel operation method Auto. tap syn-
CAN bus address Yes
Optional, if master/follower current blocking is active
chronization
Master Follower
Yes
Yes
Yes
Yes
Yes
Master Follower
Maschinenfabrik Reinhausen GmbH 201898 5252433/02 ENECOTAP® VPD® CONTROL PRO
Page 99
8 Operation
U, I, cosφ
CAN bus
M AVR MAVR
T1 T2
Parameter Auto Master Follower
Master/follower switching characteristics
Maximum tap difference Yes (if follower) No Yes Error if no communication
present Behavior if no communi-
cation present Parallel operation error
delay time
Table32: Parameter
Yes
Yes
Yes
Yes
8.9.1.2 Circulating reactive current minimization with CAN bus communication
With the circulating reactive current parallel operation method, parallel op­eration is carried out using the circulating reactive current minimization method.
Figure66: Circulating reactive current minimization with CAN bus communication
The circulating reactive current is calculated from the transformer currents and their phase angles. The voltage regulators in the parallel operation group share this information via CAN bus. An extra control deviation propor­tional to circulating reactive current is added to the independently regulating voltage regulators as a correction for the control deviation determined on the basis of the measurement voltage. You can use the circulating reactive cur­rent sensitivity parameter to decrease or increase this extra control devia­tion.
The circulating reactive current method is suited to transformers connected in parallel with a similar nominal output and short-circuit voltage UK and to vector groups with the same and different step voltages. This does not re­quire any information about the tap position.
Maschinenfabrik Reinhausen GmbH 2018 995252433/02 EN ECOTAP® VPD® CONTROL PRO
Page 100
8 Operation
Desired cosφ
Desired cosφ
U, I, (cosφ)
T1: U, I, (cosφ)
T2: U, I, (cosφ)
M AVR MAVR
T1 T2
Note that the following prerequisites must be met for the "circulating reactive current minimization" parallel operation method:
▪ You have to use current transformers with the same rated values for all
transformers in parallel operation.
▪ If you wish to operate in parallel operation with existing devices, you have
to activate the Retrofit TAPCON® 2xx parameter.
For the circulating reactive current minimization parallel operation method with CAN communication, you have to set the following parameters:
▪ Activate parallel operation ▪ Parallel operation method: Circulating reactive current ▪ CAN bus address ▪ Circulating reactive current sensitivity ▪ Circul. reactive current blocking limit ▪ Error if no communication present ▪ Behavior if no communication present ▪ Parallel operation error delay time
8.9.1.3 Circulating reactive current minimization without CAN bus communication
With this method, you can operate several voltage regulators without a com­munication connection (CAN bus) in parallel with circulating reactive current minimization.
Figure67: Circulating reactive current minimization without CAN bus communication
The circulating reactive current is calculated using the desired power factor parameter, the desired load stress type parameter, and the measured trans­former current. An extra control deviation proportional to circulating reactive current is added to the independently regulating voltage regulators as a cor­rection for the control deviation determined on the basis of the measurement voltage. This extra control deviation depends on how much the measured power factor deviates from the desired power factor.
Maschinenfabrik Reinhausen GmbH 2018100 5252433/02 ENECOTAP® VPD® CONTROL PRO
Loading...